CLIENT: ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERSATLANTIC COUNTY
IMPROVEMENT AUTHORITY1333 ATLANTIC AVE SUITE 700
ATLANTIC CITY, NJ 08203PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
ISSUED FOR BID
HORNET ROADLOWER TOWNSHIP NJ 08242CAPE MAY COUNTY
MULTI-TENANT UAS BLDG12.28.2018
PROJECT NO.: 01-01-14807
ABVAP
ACSACT
ADADD
ADDLADHADJ
ADJTAFF
AGGAC
ALTALUM
ABANOD
APPROXARCHASPHAUTO
AVG
BBDBP
BSMTBM
BELBMKBETBYDBIT
BLKBLKG
BLSBDBS
BOTBOCBOFBOS
BOWBRCGBRKT
BRKBC
BRZBLDG
CABCPT
CBCK
CLGCEM
CTRCLCT
CHBDCHAM
CCO
CLRCLOCW
COLCOMBCOMP
COMPRCONC
CMUCONDCNDTCONN
CONSTCONT
CONTRCJT
COORDCPR
CORRCNTR
CFLCS
CRSCVRCFTCYDCUS
DPRDMPF
DLDEMODEPTDEPR
DETDTLDIA
DIFFDIM
DISPDIVDR
DBLDWL
DNDS
DDWR
DWG
EAE
ELASELEC
EPEWCELEV
ELEMER
ENCENTEPXEQ
EQPESTEXCEXHEXG
EDEPS
EBEJT
EXP JTEXPEXT
EXTR
FABFBFO
FOBFOCFOMFOS
FOWFCUFDVFNDFNVFBDFGLFINFFLFFEFGD
FFFA
FECFRCFRTFPFFXDFLG
FLXFLRFD
FLUORFT
FTGFDN
FRFS
FBOFOIC
FURNFURFUT
GAGAL
GALVGSM
GSTLGL
GFRGGLZGBR
GDGRNGNDGWP
GTGWB
HNRLHDW
HDWDHDRHTRHTG
HVAC
HTHEX
HPHM
HMDRFHK
HORIZHW
HWHHR
HYD
ININCL
ID
INSULINTINV
JANJT
JTF
KPL
LBLLADLAMLAV
LCCPRL
LHLNG
LTLTGLW
LMSLINLTL
LLLKGLVR
LP
MACHMH
MFRMRBMASMO
MARLMAX
MECHMED
MEMBMTLMM
MWKMINMIR
MISCMOD
MLDGMR
MRTMT
MOVMUL
NAT
NEONOM
NNIC
NTSNUM
OCOPQ
OPNGOPP
OPPFOPPHOPPS
OZO TO O
ODOVHD
OA
PPNT
PRPNLPTDPTR
PARAPARPBDPTN
PVMTPERFPERI
PERPPLASPLAM
PLPNT
PLYWDPWDPSFPSIPIP
PFBPFNPFMPMFPRT
PROJ
QTQTR
RADREC
RECTREF
RPRFL
REFRREG
REINFRLF
RMVREQRESRTN
RAREV
RHR
RDRFGRMRO
RNDRBR
SFGLSCHD
SCNSNTSECSSK
SBSHTH
SHTSHL
SHRGSIMSLVSP
SSPKSPL
SPECSFPSQSF
STAGSSTSTDSTL
STORSTRUCT
SURSUSP
SWSYMSYN
SYSTKBD
TELTEMP
TCTHER
THRSHLDTHKTLT
T>O
TOCTOFTOS
TOWTD
TRANSTR
TYP
UCTUL
UNFUON
URTHU/S
UTIL
VBVNR
VENTVIF
VERTVCBVCTVSBVOL
WSCTWCWRWS
WPFWT
WWFW
WFWDW
WMW/
W/O
aboveaccess panelacousticalacoustical ceiling tilearea drainaddendumadditionaladhesiveadjacentadjustableabove floor finishaggregateair conditioningalternatealuminumanchor boltanodizedapproximatearchitect, -uralasphaltautomaticaverage
base boardbase platebasementbeambelowbench markbetweenbeyondbituminousblockblockingbluestoneboardboth sidesbottombottom of concretebottom of footingbottom of steelbottom of wallbracingbracketbrickbrick coursebronzebuilding
cabinetcarpetcatch basincaulkceilingcement
ABBREVATIONS:centercenter lineceramic tilechalkboardchamferchannelclean outclear, clearanceclosetcold watercolumncombinationcomputercompress, -ed, -ion, -ibleconcreteconcrete masonry unitcondition, -alconduitconnect, -or, -ionconstructioncontinuouscontract, -orcontrol jointcoordinatecoppercorrugatedcountercounterflashingcountersunkcourse, -scovercubic footcubic yardcustom
damperdampproofingdead loaddemolish, demolitiondepartmentdepress, -eddetaildetaildiameterdiffusedimensiondispenserdivisiondoordoubledoweldowndown spoutdraindrawer
drawing
eacheastelastomericelectric, -alelectrical panelelectrical water coolerelevationelevatoremergencyenclosureentranceepoxyequalequipmentestimateexcavator, excavationexhaustexisting, existentexisting dimensionexpanded polystyreneexpansion boltexpansion jointexpansion jointexpose, -dexteriorextrusion
fabricate, fabricatorface brickface offace of buildingface of concreteface of masonryface of studface of wallfan coil unitfire department valvefeminine napkin disposalfeminine napkin vendorfiberboardfiberglassfinishfinish floorfinish floor elevationfinish gradefinished facefire alarmfire extinguisher cabinetfire-resistant coatingfire-retardantfireproof, -ingfixedflashing
flexiblefloorfloor drainfluorescentfoot, feetfootingfoundationframe, -d, -ingfull sizefurnish by othersfurnished by owner,installed by contractorfurnish, -edfurred, -ingfuture
gaugegallongalvanize, -dgalvanized sheet metalgalvanized steelglassglass fiber reinforced gypsumglaze, -d, -inggrab bargrade, -inggranitegroundgrounded waterproof outletgroutgrypsum wall board
handrailhardwarehardwoodheaderheaterheatingheating, ventilating, & air conditioningheighthexagonalhigh pointhollow metalhollow metal door framehookhorizontalhot waterhot water heaterhourhydrant
inchinclude, -d,- inginside diameter
insulate, -d, -inginteriorinvert
janitorjointjoint filler
kick plate
labelladderlaminate, -dlavatorylead coated copperleftleft handlength, longlightlightinglightweightlimestonelinoleumlintellive loadlookinglouverlow point
machinemanholemanufacturermarblemasonrymasonry openingmaterialmaximummechanicalmediummembranemetal, -icmillimetermillworkminimummirrormiscellaneousmodularmoldingmop receptaclemortarmount, -edmovablemullion
natural
neoprenenominalnorthnot in contractnot to scalenumber
on centeropaqueopeningoppositeopposite faceopposite handopposite sideounceout to outoutside diameteroverheadoverall
pagepaintpairpanelpaintedpaper towel receptacleparagraphparallelparticle boardpartitionpavementperforate, -dperimeterperpendicularplasterplastic laminateplatepaint, -edplywoodplywoodpounds per square footpounds per square inchpoured in placeprefabricatedprefinishedpreformedpremolded fillerpressure treatedproject
quarry tilequarter
radiusrecessed
rectangularreferencereference pointreflect, -edrefrigeratorregletreinforcing, -mentreliefremove, -ablerequire, -dresilientreturnreturn airrevise, -d, -ionright handriserroof drainroofingroomrough openingroundrubber
safety glassschedulescreensealantsectionservice sinksetting bedsheathingsheetshelf, shelvingshoringsimilarsleevesoundproof, -ingsouthspeakerspecialspecification, -sspray fireproofingsquaresquare footstaggeredstainless steelstandardsteelstoragestructure, -alsurfacesuspendedswitchsymmetricalsynthetic
systemtackboardtelephonetemperatireterra cotta tilethermostatthresholdthick, -nesstoilettongue and groovetop oftop of concretetop of footingtop of steeltop of walltowel dispensertransparenttreadtypical
undercutunderwriter's laboratoryunfinishedunless otherwise notedurethaneundersideutility
vapor barrierveneerventilatingverify in fieldverticalvinyl cove basevinyl composite tilevinyl straight basevolume
wainscotwater closetwater repellentwater stopwaterproof, -ingweightwelded wire fabricwestwide flangewindowwire meshwithwithout
ALL WORK AND MATERIALS SHALL MEET THE REQUIREMENTS OF LOCAL AND STATE CODES AND THE SPEC'S OF THE NATIONAL BOARD OF FIRE UNDERWRITERS. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OF THE TOWNSHIP AND/OR APPROPRIATE AUTHORITY HAVING JURISDICTION OVER CONSTRUCTION WHERE THE PROJECT IS LOCATED. CONTRACTOR SHALL CHECK AND VERIFY ALL PLAN DIMENSIONS AND CONDITIONS BEFORE PROCEEDING WITH CONSTRUCTION AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT FOR CORRECTION PRIOR TO BEGINNING ANY WORK. DO NOT SCALE DRAWINGS. ALL WRITTEN DIMENSIONS GOVERN.
THE GENERAL CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR, WHETHER IMPLIED BY, OR DIRECTLY STATED ON THESES DRAWINGS, IN ORDER TO COMPLETE THE WORK AS INDICATED HEREIN.
THE ARCHITECT IS NOT RESPONSIBLE FOR ANY DEVIATIONS FROM THE PLANS AND SPECIFICATION INFORMATION.
THE ARCHITECT SHALL NOT HAVE CONTROL OR CHARGE OF AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, FOR SAFETY PRE-CAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, OR THE ACTS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS, OR ANY OTHER PERSONS PERFORMING ANY WORK, OR FOR FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS.
ANY WORK SHOWN OR REFERRED TO ON ANY PORTION OF THE DOCUMENTS SHALL BE PROVIDED AS THOUGH SHOWN ON ALL DOCUMENTS, WHERE DISCREPANCIES OCCUR IN THE DOCUMENTS, GC SHALL OBTAIN CLARIFICATION IN WRITING PRIOR TO SUBMITTING HIS BID. OTHERWISE, IT WILL BE ASSUMED THE HIGHER COST ITEM WAS BID ON. IN ORDER TO ENSURE COORDINATION, PARTIAL SETS OF DRAWINGS SHALL NOT BE ISSUED TO ANY CONTRACTOR, SUB-CONTRACTOR, OR VENDOR. ONLY COMPLETE SETS OF DOCUMENTS ARE TO BE ISSUED.
THE FOLLOWING SET OF DRAWINGS IS AN INSTRUMENT OF PROFESSIONAL SERVICE AND SHALL REMAIN THE PROPERTY OF STOKES ARCHITECTURE, WHETHER THE PROJECT IS EXECUTED OR NOT. NO CHANGES, ALTERATIONS, OR DELETIONS MAY BE MAKE HERETO EXCEPT BY THE ARCHITECT.
ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED BY THE CONTRACTOR AT THE SITE.
HOLD INDICATED DIMENSIONS. DO NOT SCALE DRAWINGS. RESOLVE ANY DISCREPANCIES BEFORE BEGINNING WORK.
ALL EXISTING CONSTRUCTION AND LANDSCAPE FEATURES THAT ARE TO REMAIN AS PART OF THE PROJECT SHALL BE PROTECTED FROM DAMAGE THROUGHOUT THE PERIOD OF CONSTRUCTION WORK. ANY DAMAGED CONSTRUCTION OR FEATURES SHALL BE REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE SATISFACTION
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND ALL SUBCONTRACTORS TO VERIFY ALL DIMENSIONS AND INSPECT CONDITIONS OF PRIOR WORK OF OTHER TRADES BEFORE PROCEEDING WITH ANY WORK. UNACCEPTABLE OR INCORRECT PRIOR WORK SHALL BE REPAIRED OR REPLACED BEFORE STARTING WORK. PROCEEDING WITH THE WORK SHALL CONSTITUTE ACCEPTANCE OF PRIOR WORK.
REFER TO SPECIFICATION AND/OR SCHEDULES.
ALL CONTRACTORS SHALL VISIT THE SITE AND THOROUGHLY ACQUAINT THEMSELVES WITH THE CONDITIONS IN THE FIELD AND THE NATURE AND THE EXTENT OF THE WORK TO BE PERFORMED.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS IN CONNECTION WITH THE WORK. THE CONTRACTOR SHALL GIVE NOTICES AND COMPLY WITH ALL APPLICABLE LAWS, ORDINANCES, RULES, REGULATIONS AND ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE SAFETY OF PERSONS AND PROPERTY, AND THEIR PROTECTION FROM DAMAGE, INJURY AND LOSS. THE CONTRACTOR SHALL INSURE THAT THE JOB SITE IS MAINTAINED AT ALL TIMES IN SUCH A WAY AS TO PREVENT INJURY OR DAMAGE TO ALL PERSONS WORKING ON OR VISITING THE PREMISES AND TO PERSONAL PROPERTY.
THE CONTRACTOR REPRESENTS THAT HE HAS THOROUGHLY REVIEWED THE DRAWINGS, SPECIFICATIONS AND CONTRACT DOCUMENTS AND THAT THEY ARE SUITABLE FOR SUBMITTING A VALID BID. CONTRACTOR SHALL SUBMIT A WRITTEN DESCRIPTION OF ALL DEFICIENCIES AND AMBIGUITIES IN THE CONTRACT DOCUMENTS TO THE OWNER WITHIN 30 DAYS OF SIGNING THE CONTRACT. CHANGE ORDERS FOR DESIGN DEFICIENCIES OR AMBIGUITIES NOT INCLUDED IN CONTRACTORS DESCRIPTION WILL NOT BE AUTHORIZED
1.
2.
3.
4.
5.
6.
7.
8.
9.
10
11.
12.
13.
14.
GENERAL NOTES: SYMBOLS KEY:
?
1
A101
2A2A
2A2A
101-
1
___________________1
A101
F-01
25
25
STAIR24" 36"
EXISTING EXIT SIGN
PROPOSED EXIT SIGN
EMERGENCY LIGHT
OCCUPANT LOAD
COMBINED OCCUPANT LOAD
DIRECTIONALILLUMINATION
EGRESS COMPONENT WIDTH
EXIT DISCHARGE
PROPOSED WIDTHCODE REQ. WIDTH
BUILDING SECTION
BUILDING ELEVATION
DETAIL
LEVEL MARKER
SPOT ELEVATION
INTERIOR ELEVATION MARKER
REVISION TAG
PARTITION TAG
DOOR TAG
WINDOW TAG
LIGHTING FIXTURE TAG
FINISH TAG
10'-0"
DRAWING NUMBERSHEET NUMBER
DOOR NUMBERROOM NUMBER
W-2
EXIT SIGN WITH EMERGENCY LIGHT COMBO
PROPOSED EXIT SIGN
E
FE PORTABLE FIRE EXTINGUISHER
ROOM TAG101ROOM NAME
ROOM NUMBERROOM NAME
W1
1A
CR CARD READER
1A101
_________
DRAWING NUMBERSHEET NUMBER
A1011
SIM
A1011
DRAWING NUMBERSHEET NUMBER
DRAWING NUMBERSHEET NUMBER
INDIVISUAL ELEVATION MARKERDRAWING NUMBERSHEET NUMBER
FIRST FLOOR0'-0"
LEVELELEVATION
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
12" = 1'-0"
CS-2
DRAWING LIST, NOTES,ABBREVIATIONS, &
SYMBOLS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
CD REVIEW11/9/2018
ISSUED FOR BID12/28/2018
COVER SHEETCS-1 COVER SHEET • •CS-2 DRAWING LIST, NOTES, ABBREVIATIONS, & SYMBOLS • •
CIVILLG-1 GENERAL NOTES AND LEGEND • •
T-1 SURVEY TIES • •CP-1 CONSTRUCTION PLAN • •CP-2 CONSTRUCTION PLAN • •GD-1 GRADING AND DRAINAGE PLAN • •GD-2 GRADING AND DRAINAGE PLAN • •XS-1 METHOD OF CROSS SECTIONS • •XS-2 CROSS SECTIONS • •XS-3 CROSS SECTIONS • •XS-4 CROSS SECTIONS • •XS-5 CROSS SECTIONS • •SS-1 SIGNING AND STRIPING PLAN • •
U-1 UTILITY PLAN • •U-2 UTILITY PLAN • •U-3 UTILITY PLAN • •
LP-1 LIGHTING PLAN • •LP-2 LIGHTING PLAN • •LP-3 LIGHTING PLAN • •SE-1 SOIL EROSION AND SEDIMENT CONTROL PLAN • •SE-2 SOIL EROSION AND SEDIMENT CONTROL NOTES • •SE-3 SOIL EROSION AND SEDIMENT CONTROL NOTES • •CD-1 CONSTRUCTION DETAILS • •CD-2 CONSTRUCTION DETAILS • •CD-3 CONSTRUCTION DETAILS • •CD-4 CONSTRUCTION DETAILS • •CD-5 CONSTRUCTION DETAILS • •CD-6 CONSTRUCTION DETAILS • •CD-7 CONSTRUCTION DETAILS • •CD-8 CONSTRUCTION DETAILS • •CD-9 CURB RAMP LAYOUT DETAIL • •
CD-10 CONSTRUCTION DETAILS • •CD-11 CONSTRUCTION DETAILS • •CD-12 CONSTRUCTION DETAILS • •CD-13 CONSTRUCTION DETAILS • •
DRAWING LIST:
ARCHITECTURALLIFE SAFETYLS101 CODE REVIEW • •LS102 LIFE SAFETY & BUILDING AREA DIAGRAMS • •LS103 TYPICAL CLEARANCES & MOUNTING ELEVATIONS • •3D VIEWS
A001 AXONOMETRIC VIEW • •PLANS & RCPS
A101 FIRST FLOOR PLAN • •A102 SECOND FLOOR PLAN • •A103 ROOF PLAN • •A111 FIRST FLOOR TENANT FITOUT • •A112 SECOND FLOOR TENANT FITOUT • •A121 FIRST FLOOR REFLECTED CEILING PLAN • •A122 SECOND FLOOR REFLECTED CEILING PLAN • •
ELEVATIONSA201 BUILDING ELEVATIONS • •A202 BUILDING ELEVATIONS • •A203 BUILDING ELEVATIONS • •
BUILDING SECTIONS & WALL SECTIONSA301 BUILDING SECTIONS • •A302 WALL SECTIONS • •A303 WALL SECTIONS • •
EXTERIOR DETAILSA400 EXTERIOR WALL AND ROOF ASSEMBLIES • •A401 EXTERIOR DETAILS • •A402 EXTERIOR DETAILS • •A404 SIGNAGE •A411 ROOF DETAILS • •
ENLARGED PLANS AND DETAILSA501 STAIR PLANS, SECTIONS & DETAILS • •A503 KITCHENETTE PLANS ELEVATIONS AND DETAILS • •A511 ENLARGED TOILET ROOM PLANS • •A512 RESTROOM ELEVATIONS • •
SPECS, SCHEDULES, DIAGRAMSA601 PARTITION TYPES SCHEDULE • •A602 DOOR SCHEDULE • •A603 DOOR DETAILS • •A604 FINISH SCHEDULES • •A605 WINDOW SCHEDULE • •
INTERIOR ELEVATIONSA701 INTERIOR ELEVATIONS • •A702 INTERIOR ELEVATIONS TENANT 1 • •
INTERIOR DETAILSA801 INTERIOR DETAILS • •
CD REVIEW11/9/2018
ISSUED FOR BID12/28/2018
STRUCTURALS001 COVER SHEET • •S101 FOUNDATION PLAN • •S102 SECOND FLOOR & LOW ROOF FRAMING PLAN • •S103 ROOF FRAMING PLAN • •S201 GENERAL NOTES & SCHEDULES • •S202 SPECIAL INSPECTIONS • •S301 FOUNDATION DETAILS • •S401 TYPICAL FRAMING DETAILS • •S402 FRAMING SECTIONS • •
MEP NOTESN001 GENERAL NOTES • •N002 GENERAL NOTES • •N003 GENERAL NOTES • •N004 GENERAL NOTES • •
MECHANICALM001 HVAC SPECS, SYMBOLS & GENERAL INFORMATION • •M101 HVAC PLAN FIRST FLOOR • •M102 HVAC PLAN SECOND FLOOR • •M501 HVAC SCHEDULES • •M701 HVAC DETAILS • •M702 HVAC DETAILS • •
ELECTRICALE001 SPECS, SYMBOLS & GENERAL INFORMATION • •E101 ELECTRICAL POWER PLAN FIRST FLOOR • •E102 ELECTRICAL POWER PLAN SECOND FLOOR • •E103 ELECTRICAL HVAC POWER PLAN • •E201 ELECTRICAL LIGHTING PLAN FIRST FLOOR • •E202 ELECTRICAL LIGHTING PLAN SECOND FLOOR • •E203 ELECTRICAL LIGHTING CONTROLS PLAN • •E501 ELECTRICAL SCHEDULES • •E502 ELECTRICAL SCHEDULES • •E503 ELECTRICAL SCHEDULES • •E601 ELECTRICAL RISERS • •
PLUMBINGP001 SPECS, SYMBOLS & GENERAL INFORMATION • •P101 PLUMBING PLAN FIRST FLOOR • •P102 PLUMBING PLAN GAS PIPING • •P401 PLUMBING LARGE SCALE PLAN • •P501 PLUMBING SCHEDULES • •P601 PLUMBING RISERS • •P701 PLUMBING DETAILS • •
FIRE PROTECTIONSP101 SPRINKLER PLAN • •
A ISSUED FOR BID 12/28/2018
CHAPTER 5: GENERAL BUILDING HEIGHTS AND AREAS
504.3 BUILDING HEIGHT ABOVE GRADE 60 FT
ALLOWABLE AREA PER STORYTABULAR AREA (At)FRONTAGE (NS x If)TOTAL: (At + (NS x If)
25,500 SF+ 6,375 SF
= 31,875 SF
A BBUILDING ELEMENT
3 2PRIMARY STRUCTURAL FRAME
BEARING WALLS:EXTERIORINTERIOR
33
22
NONBEARING WALLS & PARTITIONS - EXTERIOR
NONBEARING WALLS & PARTITIONS - INTERIOR 0 0
FLOOR CONSTRUCTION & SECONDARY MEMBERS 2 2
ROOF CONSTRUCTION & SECONDARY MEMBERS 11/2 1
TABL
E 60
1FI
RE R
ESIS
TANC
E RA
TING
REQ
UIRE
MENT
S FO
R BU
ILDI
NG E
LEME
NTS
(HOU
RS)
TYPE II TYPE III TYPE IV TYPE VA B
1 0
11
00
0 0
1 0
1 0
A B
1 0
11
00
0 0
1 0
1 0
A B
1 0
21
20
0 0
1 0
1 0
HT
HT
21/HT
SEE SECTION
602.4.6
HT
HT
SEE TABLE 602
CHAPTER 8: INTERIOR FINISHES
803.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS
INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84 OR UL 723. SUCH INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEXES.
CLASS A: FLAME SPREAD INDEX 0-25SMOKE-DEVELOPED INDEX 0-450
CLASS B: FLAME SPREAD INDEX 26-75SMOKE-DEVELOPED INDEX 0-450
CLASS C: FLAME SPREAD INDEX 76-200SMOKE-DEVELOPED INDEX 0-450
TABL
E 80
3.11
INTE
RIOR
WAL
L AN
D CE
ILIN
G FI
NISH
REQ
UIRM
ENTS
BY
OCCU
PANC
Y
GROUP
BF
SPRINKLEREDINTERIOR EXIT STAIRWAYS,
INTERIOR EXIT RAMPS AND EXIT PASSAGEWAYS
CORRIDORS AND ENCLOSURE FOR
EXIT ACCESS STAIRWAYS AND
EXIT ACCESS RAMPS
ROOMS AND ENCLOSED
SPACES
BC
CC
CC
CHAPTER 9: FIRE PROTECTION SYSTEMS
903.3.1.1 NFPA 13 SPRINKLER SYSTEMS WHERE THE PROVISIONS OF THIS CODE REQUIRE THAT A BUILDING OR PORTION THEROF BE EQUIPPED THROUGHOUT WIHT AN AUTOMATIC SPRINKLER SYTEM IN ACCORDANCE WITH THIS SECTION, SPRINKLERS SHALL BE INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.
TABL
E 90
6.3(1
)FI
RE E
XTIN
GUIS
HERS
FOR
CL
ASS
A FI
RE H
AZAR
DS
LIGHT (LOW) HAZARD
MINIMUM RATED SINGLE EXTINGUISHER 2-A
ORDINARY (MODERATE)
HAZARD
EXTRA (HIGH) HAZARD
MAXIMUM FLOOR AREA PER UNIT OF A
MAXIMUM FLOOR AREA FOR EXTINGUISHER
MAX TRAVEL DISTANCE TO EXTINGUISHER
3,000 SF
11,250 SF
75 FT
2-A
1,500 SF
11,250 SF
75 FT
4-A
1,000 SF
11,250 SF
75 FT
CHAPTER 10: MEANS OF EGRESS
TABL
E 10
04.1.
2MA
XIMU
M FL
OOR
AREA
AL
LOW
ANCE
S PE
R OC
CUPA
NT
FUNCTION OF SPACE
BUSINESS AREAS
INDUSTRIAL AREAS
100 GROSS
OCCUPANT LOAD FACTOR (FLOOR AREA IN SF PER OCCUPANT)
100 GROSS
1005.3.1 STAIRWAYS THE CAPACITY, IN INCHES, OF MEANS OF EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH STAIRWAYS BY A MEANS OF EGRESS CAPACITY FACTOR OF 0.3 INCH PER OCCUPANT
TYPE V: STRUCTURAL ELEMENTS, EXTERIOR WALLS AND INTERIOR WALLS ARE OF ANY MATERIALS PERMITTED BY THIS CODE.
CHAPTER 3: USE AND OCCUPANCY CLASSIFICATION
304.1
304.1
B-BUSINESS
F-1 MOD HAZARD INDUSTRIAL
OFFICES; RESEARCH & DEVELOPMENT
LIGHT MANUFACTURING
CHAPTER 4: SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
416
416.3 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE. WHERE SUCH SPACES ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS
international building code 2015 nj ed.
416.3.1 SURFACES THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE SMOOTH AND CONTINUOUS WITHOUT EDGES; SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE WASHING AND CLEANING; AND SHALL BE DESIGNED TO CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM SHALL NOT BE USED.
307.1.1 USES OTHER THAN GROUP H AN OCCUPANCY THAT STORES, USES, OR HANDLES HAZARDOUS MATERIALS AS DESCRIBED IN ONE OR MORE OF THE FOLLOWING ITEMS SHALL NOT BE CLASSIFIED AS GROUP H, BUT SHALL BE CLASSIFIED AS THE OCCUPANCY THAT IT MOST NEARLY RESEMBLES.
1.) BUILDINGS AND STRUCTURES OCCUPIED FOR THE APPLICATION OF FLAMMABLE FINISHES, PROVIDED THAT SUCH BUILDINGS OR AREAS CONFORM TO THE REQUIREMENTS OF SECTION 416 AND THE INTERNATIONAL FIRE CODE.
APPLICATION OF FLAMMABLE FINISHES
SPRAYING SPACES
416.5 AN AUTOMATIC SPRINKLER SYSTEM OR FIRE EXINGUISHING SYSTEM SHALL BE PROVIDED IN ALL SPRAY, DIP AND IMMERSING SPACES AND STORAGE ROOMS AND SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 9.
FIRE PROTECTION
NOTES:•CONSTRUCTION TYPE: 5B•FULLY SPRINKLERED PER NFPA 13•MOST STRINGENT USE WAS USED TO CALCULATE ALLOWABLE BUILDING HEIGHTS AND AREAS.
ALLOWED PROPOSED
28 FT
NO. OF STORIES (Sa) 2 2
20,600 SF 1ST FL. 6,000 SF 2ND FL.
TOTAL ALLOWABLE BUILDING AREA (Aa = [At + (NS x If)] x Sa)
63,750 SF 26,600 SF
504.4
506.2
CAPE MAY COUNTY MULTI-TENANT UAS BLDGPROJECT DESCRIPTION:
NEW TWO STORY BUILDING WITH MULTIPLE TENANTS.
APPLICABLE CODES & REGULATORY AGENCIES:NEW JERSEY ADMINISTRATIVE CODE § 5:23-3INTERNATIONAL BUILDING CODE 2015 NJ ed.NATIONAL STANDARD PLUMBING CODE 2015NFPA 70 NATIONAL ELECTRIC CODE 2014ENERGY SUBCODE ASHRAE 90.1-2013INTERNATIONAL MECHANICAL CODE 2015INTERNATIONAL FIRE CODE 2015 NJ ed.ICC/ANSI A117.1-2009
CODE REVIEW
CHAPTER 7: PLUMBING FIXTURES
NATIONAL STANDARD PLUMBING CODE 2015
TABL
E 72
1.1MI
NIMU
M NU
MBER
OF
REQU
IRED
PLU
MBIN
G FI
XTUR
ES
WATER CLOSET
B-BUSINESS1
add 1add 1
LAVATORYNO. OF PERSONS OF EACH SEX
SHOWER DRINKING FOUNTAIN
(2)
OCCU
PANC
Y
1add 1add 1
1add 0add 1
M F
1add 0add 1
NR
OTHER
1 per 100 1 service sink per floor
M F
F-1 INDUSTRIAL1
add 1add 1add 1
1 emergency shower per 10
people exposed to skin contamination
1 per 100
1 service sink per floor
1add 1add 1add 1
1add 1add 1add 1
1add 1add 1add 1
PROP
OSED
FI
XTUR
ES
WATER CLOSET(5)
TENANT #12
LAVATORYNO. OF PERSONS OF EACH SEX
SHOWER DRINKING FOUNTAIN
(2)
OCCU
PANC
Y
2 1
M F
1 0
OTHER
01 SERVICE
SINK
M F
73 OCCS.
1-2526-5051-100ea. add'l 100
1-1516-50ea. add'l 50
TENANT #21 1 1 1 0 0
1 SERVICE SINK21 OCCS.
TENANT #3
TENANT #4
TENANT #5
2 2 1 1 0 01 SERVICE
SINK73 OCCS.
1 1 1 1 0 01 SERVICE
SINK24 OCCS.
2 2 1 1 0 01 SERVICE
SINK73 OCCS.
TABL
E 50
6.2TA
BULA
R AL
LOW
ABLE
AR
EA F
ACTO
R (A
t)
TYPE OF CONSTRUCTIONTYPE I TYPE II TYPE III TYPE VTYPE IV
A B A B A B A BHTTABLE 504.3 ALLOWABLE BUILDING HEIGHT ABOVE GRADE PLANE (FT)US
E GR
OUP
NSSB; F-1 UL
UL160180
6585
5575
6585
5575
5070
4060
6585
NSSB UL
UL78
56
34
45
34
34
23
56
F-1 NSS
ULUL
67
45
23
34
23
23
12
45
TABLE 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
NSS(M)B UL
UL37,500
112,50023,00069,000
28,50085,500
19,00057,000
18,00054,000
9,00027,000
36,000108,000
F-1 NSS(M)
ULUL
25,00075,000
15,50046,500
19,00057,000
12,00036,000
14,00042,000
8,50025,500
33,500100,500
TABLE 506.2 TABULAR ALLOWABLE AREA (SF)ULUL
ULUL
506.3 FRONTAGE INCREASEIf = [ F/P - 0.25 ] W/30
F = 660; P = 660; W = 30
If = [ 660/660 - 0.25 ] 30/30 = 0.75
CHAPTER 6: TYPES OF CONSTRUCTION
TYPE I
602.5
906.1 PORTABLE FIRE EXTINGUISHERSWHERE REQUIRED:
1. GROUPS: B, F3. IN AREAS WHERE FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE STORED, USED OR DISPENSED5. WHERE REQUIRED BY THE INTERNATIONAL FIRE CODE SECTIONS INDICATED IN TABLE 906.1
CHAPTER 24: FLAMMABLE FINISHES
2404.3.3 SPRAYING SPACES SPRAYING SPACES SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, AND SECTION 2404.3.3.1 AND SECTIONS 2404.4 THROUGH 2404.8 OF THIS CODE
2404.3.3.1 FLOOR COMBUSTIBLE FLOOR CONSTRUCTION IN SPRAYING SPACES SHALL BE COVERED BY APPROVED NONCOMBUSTIBLE NON SPARKING MATERIAL.
INTERNATIONAL FIRE CODE 2015
2404.4.1 FIRE EXTINGUISHERS PORTABLE FIRE EXINGUISHERS COMPLYING WITH SECTION 906 SHALL BE PROVIDED FOR IN SPRAYING AREAS IN ACCORDANCE WITH THE REQUIREMENTS FOR A EXTRA (HIGH) HAZARD OCCUPANCY.
TABL
E 90
6.3(2
)FI
RE E
XTIN
GUIS
HERS
FOR
CL
ASS
B FI
RE H
AZAR
DS
BASIC MINIMUM EXTINGUISHER RATING
LIGHT (LOW) HAZARD 5-B10-B
MAXIMUM DISTANCE OF TRAVEL TO
EXTINGUISHERS
ORDINARY (MODERATE)
TYPE OF HAZARD
EXTRA (HIGH)
3050
10-B20-B
3050
40-B80-B
3050
1004.1.2 AREAS WITHOUT FIXED SEATING THE NUMBER OF OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT PER UNIT OF AREA AS PRESCIBED IN TABLE 1004.1.2
AREA FLOOR AREA LOAD FACTOR(SF PER OCC.)
OCCUPANT LOAD
TENANT #1FIRST FLOORSECOND FLOOR
5,204 SF1,978 SF
100 GROSS100 GROSS
5320
TENANT #2FIRST FLOOR 2,093 SF 100 GROSS 21
TENANT #3FIRST FLOORSECOND FLOOR
5,214 SF1,978 SF
100 GROSS100 GROSS
5320
TENANT #4FIRST FLOOR 2,341 SF 100 GROSS 24
TENANT #1FIRST FLOORSECOND FLOOR
5,203 SF1,978 SF
100 GROSS100 GROSS
5320
CHAPTER 11: ACCESSIBILITY
1104.4 MULTILEVEL NON-RESIDENTIAL BUILDINGS AND MULTILEVEL BUILDING OF GROUP R-1
1104.4.2 LARGE BUILDINGS LARGE BUILDINGS, DEFINED AS THOSE WITH A TOTAL GROSS ENCLOSED FLOOR AREA OF 10,000 SQUARE FEET OR MORE, SHALL PROVIDE THE ACCESSIBLE BUILDING FEATURES REQUIRED OF SMALL BUILDINGS IN 1104.4.1. IN ADDITION, LARGE BUILDINGS SHALL BE REQUIRED TO HAVE AN ELEVATOR TO PROVIDE A VERTICAL ACCESSIBLE ROUTE BETWEEN FLOORS; HOWEVER, IN SUCH BUILDINGS, FLOORS THAT ARE LESS THAN 3,000 SQUARE FEET OR FLOORS WITH 0NLY MECHANICAL EQUIPMENT SHALL NOT BE REQUIRED TO BE SERVED BY AN ELEVATOR.
1005.3.2 OTHER EGRESS COMPONENTS THE CAPACITY, IN INCHES, OF MEANS OF EGRESS COMPONENTS OTHER THAN STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF EGRESS CAPACITY FACTOR OF 0.2 INCH PER OCCUPANT
NOTE: INDIVIDUAL TENANT SPACE ON SECOND FLOOR LESS THAN 3,000 SF. NO ELEVATOR REQURIED.
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
12" = 1'-0"
LS101
CODE REVIEW
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A ISSUED FOR BID 12/28/2018
5,204 SF5,204 SFTENANT 1TENANT 1
2,093 SF2,093 SFTENANT 2TENANT 2
5,214 SF5,214 SFTENANT 3TENANT 3
2,341 SF2,341 SFTENANT 4TENANT 4
5,203 SF5,203 SFTENANT 5TENANT 5
131 SF131 SFMECHMECH
206 SF206 SFMECHMECH
DOOR8" 36"
20
52
21
(GROSS)
(GROSS)
11
11
11
1(GROSS)
0FT (COMMON PATH)
90FT (TRAVEL DIST. )
32FT
(COM
MON
PATH
)
118F
T (T
RAVE
L DI
ST. )
36
7236
3636
24
12
12
12
(GROSS)
1
20
36
72
3636
52
DOOR8" 36"
DOOR8" 72"
DOOR3" 36"
DOOR3" 36"
DOOR8" 36"
DOOR3" 36"
DOOR8" 36"
20
(GROSS)
52
72
3636
36
36
DOOR8" 36"
36
35FT
(COM
MON
PATH
)
122F
T (T
RAVE
L DI
ST. )0F
T (C
OMMO
N PA
TH)
56FT
(TRA
VEL
DIST
. )
0FT
(COM
MON
PATH
)
56FT
(TRA
VEL
DIST
. )
DOOR3" 36"
OCCUPANCY TYPE
Accessory - Stor, Mech, Equip
Business Areas
FE
FE
FE
FE
FE
FE
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
STAIR6" 36"
20
74FT
(COM
MON
PATH
)
126F
T (T
RAVE
L DI
ST. )
MECHANICAL ROOFTOP
AREA
MECHANICAL ROOFTOP
AREASTAIR6" 36"
20
74FT
(COM
MON
PATH
)
134F
T (T
RAVE
L DI
ST. )
STAIR6" 36"
20
74FT
(COM
MON
PATH
)
134F
T (T
RAVE
L DI
ST. )
(GROSS)
(GROSS)(GROSS)
20
20
20
1,978 SF1,978 SFTENANT 1TENANT 1
1,978 SF1,978 SFTENANT 3TENANT 3
1,978 SF1,978 SFTENANT 5TENANT 5
FE FE
FE
FE
FE
LEGEND
25
25
PROPOSED EXIT SIGN
EMERGENCY LIGHT
OCCUPANT LOAD
COMBINED OCCUPANT LOAD
DIRECTIONALILLUMINATION
EGRESS WIDTH
EGRESS
PROPOSED
CODE REQ. WIDTHSTAIR WIDTH = 0.3 PER OCCUPANTDOOR WIDTH = 0.2 PER OCCUPANT
EGRESS
FE PORTABLE FIRE EXTINGUISHER
21,199 SF21,199 SFFIRST FLOORFIRST FLOOR
BUILDING AREA TYPE
Gross Building Area
2,084 SF2,084 SFSECOND FLOORSECOND FLOOR
2,092 SF2,092 SFSECOND FLOORSECOND FLOOR
2,092 SF2,092 SFSECOND FLOORSECOND FLOOR
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
4,901 SF4,901 SFTENANT #1TENANT #1
1,831 SF1,831 SFTENANT #2TENANT #2
4,900 SF4,900 SFTENANT #3TENANT #3
2,124 SF2,124 SFTENANT #4TENANT #4
4,900 SF4,900 SFTENANT #5TENANT #5
306 SF306 SF
118 SF118 SF
287 SF287 SF TENANT LEGEND
COMMON AREA
TENANT #1
TENANT #2
TENANT #3
TENANT #4
TENANT #5
316 SF316 SF
325 SF325 SF
113 SF113 SF305 SF305 SF
1,978 SF1,978 SFTENANT #1TENANT #1
1,978 SF1,978 SFTENANT #3TENANT #3 1,978 SF1,978 SF
TENANT #5TENANT #5
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
LS102
LIFE SAFETY & BUILDINGAREA DIAGRAMS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
LS102 1/16" = 1'-0"1 FIRST FLOOR EGRESS PLAN
LS102 1/16" = 1'-0"2 SECOND FLOOR OCCUPANCY PLAN
FIRST FLOOR 21,199 SF
SECOND FLOOR 6,269 SFTOTAL AREA: 27,467 SF
BUILDING AREA SCHEDULE
2ND FLOORTENANT 1 1,978 SF Business Areas 100 Gross 20TENANT 3 1,978 SF Business Areas 100 Gross 20TENANT 5 1,978 SF Business Areas 100 Gross 20TOTAL: 60
AREA NAME AREA (SF)OCCUPANCY TYPE
(PER TABLE 1004.1.1)
FLOOR AREAPER OCCUPANT OCCUPANT
LOAD COMMENTS(SF) TYPE
1ST FLOORMECH 131 SF Accessory - Stor, Mech, Equip 300 Gross 1MECH 206 SF Accessory - Stor, Mech, Equip 300 Gross 1TENANT 1 5,204 SF Business Areas 100 Gross 53TENANT 2 2,093 SF Business Areas 100 Gross 21TENANT 3 5,214 SF Business Areas 100 Gross 53TENANT 4 2,341 SF Business Areas 100 Gross 24TENANT 5 5,203 SF Business Areas 100 Gross 53TOTAL: 206
OCCUPANT LOAD SCHEDULE
TENANT #11ST FL. 4,900.7 SF1ST FL. BATHROOMS 306.0 SF2ND FL. 1,978.0 SF
7,184.7 SF
TENANT #21ST FL. 1,831.3 SF1ST FL. BATHROOMS 118.4 SF
1,949.8 SF
TENANT #31ST FL. 4,899.7 SF1ST FL. BATHROOMS 315.6 SF2ND FL. 1,978.4 SF
7,193.7 SF
TENANT #41ST FL. 2,123.5 SF1ST FL. BATHROOMS 112.6 SF
2,236.1 SF
TENANT #51ST FL. 4,899.7 SF1ST FL. BATHROOMS 305.2 SF2ND FL. 1,978.4 SF
7,183.3 SFTOTAL USABLE AREA 25,747.6 SF
TENANT RENTABLE AREA SCHEDULE
26,359.2 SFTOTAL RENTABLE AREA:
COMMON AREAUTILITY AREA B 286.9 SFUTILITY AREA D 324.7 SF
611.6 SFTOTAL COMMON AREA 611.6 SF
LS102 1" = 30'-0"3 FIRST FLOOR GROSS BUILDING AREA
LS102 1" = 30'-0"4 SECOND FLOOR GROSS BUILDING AREA
LS102 1" = 30'-0"5 FIRST FLOOR RENTABLE AREA PLAN
LS102 1" = 30'-0"6 SECOND FLOOR RENTABLE AREA PLAN
A ISSUED FOR BID 12/28/2018
11"-1
7"
12"MIN
24" MIN
33"-3
6"39
"-41"
18"
MIN
18"
MIN
24" MIN
42"
7"-9"
15"MIN
17"
MA
44"
15"MIN
17"
MA
44"
27" M
IN 34"
15"MIN
40"
15"
48"
48"
27" M
IN 48"
40"
48"
22"
MA
48"
40"-4
8"
11"-1
7" 33"-3
6"54" MIN 39
"-41"
18"
MIN
39"-41"
12" MAX
42" MIN
18"
MIN
17"
MA 17"
MA
27" M
IN34"
9" MIN
8"MIN
11" MIN
17"MIN
40" 48
"
48"
27" M
IN 48"
40"
48"
22"
MA
48"
40"-4
8"
1'-6"5'
5' 5'
12"MIN
24"MIN
12"
MAX
42" M
IN 39"-4
1"
1'-3"
4'
2'-6"
1'-3"4'
2'-6"
1'-3" 1'-3"
4'2'-6"
4'
2'-6" 2'-6"
4'
2'-6"
4'
2'-6"
4'
2'-6"
4'
2'-6"
4'
PER ICC A117.1.606.6 (2009):WATER SUPPLY AND DRAINPIPES UNDER LAVATORIES AND
SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TOPROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
ABRASIVE SURFACES UNDER LAVATORIES & SINKS.
FLOOR MOUNTED TOILET -NO TANK
GRAB BARS TOILET PAPER DISPENSER URINAL URINAL WALL MOUNTED SINK SOAP DISPENSER PAPER TOWELDISPENSER/TRASH COMBO
DIAPER CHANGING STATION SANITARY NAPKIN/TAMPONDISPENSER
MIRROR AUTOMATIC HAND DRYER WALL MOUNTED SANITARYTRASH
TOILET PAPER DISPENSER COAT/ROBE HOOK
FLOOR MOUNTED TOILET -NO TANK
GRAB BARS TOILET PAPER DISPENSER URINAL URINAL WALL MOUNTED SINK SOAP DISPENSER PAPER TOWELDISPENSER/TRASH COMBO
DIAPER CHANGING STATION SANITARY NAPKIN/TAMPONDISPENSER
MIRROR AUTOMATIC HAND DRYER WALL MOUNTED SANITARYTRASH
TOILET PAPER DISPENSER COAT/ROBE HOOK
FLOOR MOUNTED TOILET - NO TANK GRAB BARS TOILET PAPER DISPENSER URINAL URINAL WALL MOUNTED SINK SOAP DISPENSER PAPER TOWELDISPENSER/TRASH COMBO
DIAPER CHANGING STATION SANITARY NAPKIN/TAMPONDISPENSER
MIRROR AUTOMATIC HAND DRYER WALL MOUNTED SANITARYTRASH
TOILET PAPER DISPENSER COAT/ROBE HOOK
18"
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/4" = 1'-0"
LS103
TYPICAL CLEARANCES &MOUNTING ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
1/4" = 1'-0"BATHROOM MOUNTING HEIGHTS
A ISSUED FOR BID 12/28/2018
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
A001
AXONOMETRIC VIEW
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A ISSUED FOR BID 12/28/2018
UP
UP UP
A
B
C
D
E
F
1 1.2 1.8 2
1A301
_________ 1A301
_________
2.6
1A302
_________
2A301
_________3A301
_________
A2011
A2012
A201 3
A20143 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
A.5
1-101-2
1-103MENS
1-10
2-1
1-10
3-1
2-104-2 2-105-1
2-10
2-1
2-10
3-1
2-10
4-1 3-
102-
13-
103-
1
2-10
1-1
3-101-2
3-10
1-3
4-105-14-104-2
4-10
4-1
4-10
3-1
4-10
2-1 5-
102-
1
5-101-2
5-10
1-3
4-10
1-1
2A302
_________
3A302
_________4A302
_________
5A302
_________
6A302
_________
___________________9
A402
A2022
A202 3
A2024
A202 1
1-102WOMENS
1-101TENANT #1
2-101TENANT #2
3-102WOMENS
3-103MENS
2-105MECHANICAL CLOSET
2-103WC2-102
WC
2-104CORRIDOR
3-101TENANT #3
4-101TENANT #4
4-103WC
4-102WC
4-105MECHANICAL CLOSET
4-104CORRIDOR
5-102WOMENS
5-103MENS
5-101TENANT #5
+0"
1A303
_________
1-104J.C.
3-104J.C.
2-106J.C.
5-104J.C.
4-106J.C.
___________________1
A501
___________________3
A511
2B 2B2B
2B
___________________1
A511
5-101-13-101-11-101-1
2A303
_________
3A303
_________
4-10
6-1
5-104-1
2-10
6-1
3-104-1
1-104-1
FLOOR QUADDRUPLEX RECEPTACLE OUTLET, REFER TO ELECTRICAL DRAWINGS FOR DETAILS. COORDINATE EXACT LOCATIONS WITH TENANT ON SITE TYPICAL OF (14)
___________________3
A402
___________________9
A501
___________________9
A501
TRASH ENCLOSURE(8'-0" x 10'-0")
2'-0" 5'-0" 5'-0" 2'-0" 4'-0" 5'-0" 3'-0"
2'-0"
13'-0
"3'-
0"5'-
0"2'-
0"3'-
0"7'-
0"5'-
0"2'-
0"3'-
0"3'-
0"2'-
0"
3'-0"3'-0" 4'-0"3'-0" 5'-0"3'-0"7'-8"
16'-8" 16'-0" 16'-8" 22'-4" 18'-4" 16'-8" 16'-0" 16'-8" 18'-4" 22'-4" 16'-8" 16'-0" 16'-8"4'-0" 4'-0"
20'-0
"20
'-0"
20'-0
"20
'-0"
10'-0
"10
'-0"
APPROXIMATE EXTENT OF SUB-SLAB ELECTRICAL TRENCH, COORDINATE EXACT LOCATION WITH OWNER/ARCHITECT ON SITE, TYPICAL.
MEZZANINE ABOVE
MEZZANINE ABOVE MEZZANINE ABOVE
SKYLIGHT ABOVE, TYP.
CANOPY ABOVE CANOPY ABOVE
6'-0"
TRASH ENCLOSURE(8'-0" x 10'-0")
PAINTED EXPOSED STEEL COLUMN, TYP.
___________________4
A503
___________________6
A503
4'-6"
7'-6"
8'-4"
7'-6"
4'-6"
2'-2"2'-3" 8'-2"
3'-10
"
3'-10
"
3'-10
"
___________________4
A503
___________________8
A5035-10
3-1
CR
CR
CR
CR
CR
CR CR CR
CRCR
TYP. @COL LINE 1
___________________9
A402TYP. @
COL LINE 6
___________________12
A402
___________________6
A203 ___________________6
A203
(VER
IFY)
7'-0"
(VER
IFY)
36'-6
"
EQ EQ
(VER
IFY)
26'-6
"
(VER
IFY)
18'-0
"
FLOOR QUADDRUPLEX RECEPTACLE OUTLET
SUB-SLAB ELECTRICAL TRENCH
EQ EQ
(VER
IFY)
18'-0
"
(VER
IFY)
16'-6
"
EQ EQ
FLOOR QUADDRUPLEX RECEPTACLE OUTLET
SUB-SLAB ELECTRICAL TRENCH
Sim3
A303_________
Sim3
A303_________
Sim3
A303_________
TYP. @ COL LINES 2, 3, 4 & 5
TYP.
PROVIDE MULTICOMPONENT, NON-SAG, TRAFFIC-GRADE, POLYURETHANE-BASEDJOINT SEALANT IN JOINTS IN INTERIOR CONCRETE FLOORS SUCH AS BUT NOT LIMITEDTO INTERIOR CONTROL JOINTS AND INTERIOR EXPANSION JOINTS, TYPICAL.
CONTRACTOR SHALL CONTACT THE ARCHITECT 2 WEEKS PRIOR TO TRENCH INSTALLATION TO VERIFY TOTAL TRENCH LENGTHS, TRENCH LOCATIONS, AND RECEPTABLE LOCATIONS TO FACILITATE COORDINATION WITH EACH TENANT'S REQUIREMENTS.
1.
2.
FLOOR PLAN GENERAL NOTES:
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A101
FIRST FLOOR PLAN
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A101 1/8" = 1'-0"1 FIRST FLOOR PLAN
N
A ISSUED FOR BID 12/28/2018
DN
DN DN
A
B
C
D
E
F
1 1.2 1.8 2
1A301
_________ 1A301
_________
2.6
1A302
_________
2A301
_________3A301
_________
A2011
A2012
A201 3
A2014
3 3.2 3.4 4 4.4 5 5.4 5.6 6
12'-8" 24'-0" 12'-8" 22'-4" 18'-4" 16'-8" 16'-0" 16'-8" 18'-4" 22'-4" 16'-8" 16'-0" 16'-8"
1.4 1.6
A.5
1-201-1
2A302
_________
3A302
_________4A302
_________
5A302
_________
6A302
_________
A2022
A202 3
A2024
A202 1
1A303
_________
A5018
14'-0
"
2A303
_________
3A303
_________ 3A303
_________
GUARDRAIL, SEE DTLS
5-201-1
OPEN TO BELOW
OPEN TO BELOW OPEN TO BELOW
EQUIPMENT PLATFORM
GUARDRAIL, SEE DTLS GUARDRAIL, SEE DTLS
SEE ROOF PLAN
SEE ROOF PLAN
___________________1
A501
___________________9
A501___________________
9A501
SEE SIGNAGE SHEET
SKYLIGHT ABOVE, TYP.
MECHANICAL UNIT, SEE ROOF PLAN TYP.
1-201-1TENANT 1 MEZZANINE
5-201-1TENANT 5 MEZZANINE
3A
3A
3A
HOLD PARTITIONS TIGHT TO DUCTWORK
± 10
'-6"
± 3'-0"
± 4'-4"
± 21
'-0"
HOLD PARTITIONS TIGHT TO DUCTWORK
3A
3A
3A
± 4'-4"
± 19
'-6"
3A
3A
3A
HOLD PARTITIONS TIGHT TO DUCTWORK
3-201-1TENANT 3 MEZZANINE
RTU-3B
RTU-3C
RTU-5C
RTU-5B
RTU-5A
RTU-3A
RTU-4
RTU-1D
RTU-1A
RTU-2
RTU-1C
RTU-1B
SEE SIGNAGE SHEET
PROVIDE MULTICOMPONENT, NON-SAG, TRAFFIC-GRADE, POLYURETHANE-BASEDJOINT SEALANT IN JOINTS IN INTERIOR CONCRETE FLOORS SUCH AS BUT NOT LIMITEDTO INTERIOR CONTROL JOINTS AND INTERIOR EXPANSION JOINTS, TYPICAL.
CONTRACTOR SHALL CONTACT THE ARCHITECT 2 WEEKS PRIOR TO TRENCH INSTALLATION TO VERIFY TOTAL TRENCH LENGTHS, TRENCH LOCATIONS, AND RECEPTABLE LOCATIONS TO FACILITATE COORDINATION WITH EACH TENANT'S REQUIREMENTS.
1.
2.
FLOOR PLAN GENERAL NOTES:
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A102
SECOND FLOOR PLAN
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A102 1/8" = 1'-0"1 SECOND FLOOR PLAN
N
A ISSUED FOR BID 12/28/2018
A
B
C
D
E
F
1 1.2 1.8 2
1A301
_________ 1A301
_________
2.6
1A302
_________
2A301
_________
2A301
_________
3A301
_________
3A301
_________
A2011
A2012
A201 3
A20143 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
A.5
2A302
_________
3A302
_________4A302
_________
5A302
_________
6A302
_________
3A411
_________
A2022
A202 3
A2024
A202 1
1A303
_________
2A303
_________
3A303
_________
ROOF ASSEMBLY 1 ROOF ASSEMBLY 1 ROOF ASSEMBLY 1
ROOF ASSEMBLY 2
ROOF ASSEMBLY 2
ROOF ASSEMBLY 3
3'-8"
4A411
_________
2'-0"
EQUIPMENT PLATFORM
W01 W01
W01 W01
W01 W01
W01 W01
W01 W01
W01 W01
W01 W01
W01 W01
W01 W01
SKYLIGHT, TYP.
1'-0"
6" X 6" WIND RESISTANT GUTTER
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT
METAL STAIR
GUARDRAIL
5A411
_________
6" X 6" WIND RESISTANT GUTTER
6" X 6" WIND RESISTANT GUTTER
6" X 6" WIND RESISTANT GUTTER
6" X 6" WIND RESISTANT GUTTER
6" X 6" WIND RESISTANT GUTTER
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT TO SPLASH PAD
2" DIA. DOWNSPOUT(CANOPY)
2" DIA. DOWNSPOUT(CANOPY)
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT TO
SPLASH PAD
2" DIA. DOWNSPOUT(CANOPY)
2" DIA. DOWNSPOUT(CANOPY)
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT TO SPLASH PAD
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT TO
SPLASH PAD
4" X 4" DOWNSPOUT
4" X 4" DOWNSPOUT
ROOF SLOPE
ROOF CRICKET, TYP.
1'-4"
1'-4"
ROOF SLOPE
ROOF CRICKET, TYP.
ROOF DRAIN, TYP. ROOF DRAIN, TYP.
WALKWAY PAD
5'-0"
10'-0
"10
'-0"
10'-0
"10
'-0"
10'-0
"10
'-0"
2'-0" 12'-0" 2'-0"
WALKWAY PAD
5'-0"
8'-0"
CANOPY ROOF CANOPY ROOF
1'-4"
1'-4"
OVERFLOW SCUPPER
9A411
_________OVERFLOW SCUPPER
OVERFLOWSCUPPER
OVERFLOWSCUPPER
OVERFLOW SCUPPER
OVERFLOW SCUPPER
OVERFLOWSCUPPER
9A411
_________
9'-10" 5'-10"
9'-10" 5'-10" 5'-10" 9'-10"
5'-10" 9'-10"
EQEQ
RTU-3B
RTU-3C
RTU-5C
RTU-5B
RTU-5A
RTU-4
RTU-1D
RTU-1A
RTU-2
RTU-1C
RTU-1B
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A103
ROOF PLAN
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A103 1/8" = 1'-0"1 ROOF PLAN
N
A ISSUED FOR BID 12/28/2018
UP
UP UP
A
B
C
D
E
F
1 1.2 1.8 2
A2011
A2012
2.6 3 3.2 3.4 4 4.4 5 5.4 5.6 6
1-100AVESTIBULE
1-100LOBBY
1-101OPEN OFFICE AREA
1-121CONFERENCE
1-106OFFICE
1-107OFFICE
1-108OFFICE
1-109OFFICE
1-110OFFICE
1-111OFFICE
1-112OFFICE
1-113OFFICE
1-114ASTORAGE
1-118OFFICE
1-119OFFICE
1-102WOMENS
1-103MENS
LOADING AREA
1-105OFFICE
1-120OFFICE
1-117OFFICE
1-116IT CLOSET
1-115KITCHEN
A201 3
A20141.4 1.6
1-114SHIPPING
A.5
1-114-1
1-101OPEN OFFICE AREA
1-101ALOUNGE
1-100-1
1-11
6-1
2-104CORRIDOR
2-105MECHANICAL CLOSET
3-103MENS
3-102WOMENS
2-102WC
2-103WC
2-101TENANT #2
3-101TENANT #3
4-101TENANT #4
5-107ACORR.
4-105MECHANICAL CLOSET 4-104
CORRIDOR
5-105SHOWROOM
5-106SHOWROOM
5-101D-TECH
5-107OFFICES
5-108VESTIBULE
2-106J.C.
1-104J.C.
3-104J.C.
4-102WC
4-103WC 5-102
WOMENS
5-103MENS
5-104J.C.
4-106J.C.
1A
1A
1A
1A
1A
1A
1A
1A
1A
1A
1A
1A1B1B
1B1B
1B
1B
1B
1B1E 1E
1B
1B
1B1B
1B1A
1A
1B
1B
A7023
A702 4
A7016
A7022
A7011
A7012
1-111-1
1-110-1
1-109-1
1-108-1
1-107-1
1-105-1
1-117-1
1-118-1
1-119-1
1-120-1
1-113-11-112-1
1-106-1
A605 1
___________________1
A503
A605
3 5-10
8-1
5-10
7A-1
5-10
7A-2
5-10
5-1
5-10
6-1
(TRASH ENCLOSURE)
EQ.
EQ.
EQ.
EQ.
EQ.
EQ.
7'-9"
11'-1
0"
ALIG
N
3'-0"
15'-0" 13'-5" V.I.F.
6'-2"
2'-5" 4'-0"
12'-0
"
7'-0"
12'-7"
7'-11
"9'-
7 1/
4"9'-
7 1/
4"11
'-7 1
/2"
8'-1"
135.0°
ALIG
N
8'-6 3/4"
12'-7"
5'-1"
OUTLINE OF MEZZANINE ABOVE
___________________3
A511
___________________1
A511
___________________1
A501
___________________9
A501___________________
9A501
2'-4"
(TRASH ENCLOSURE)
___________________4
A503
___________________4
A503
___________________6
A503
___________________8
A503
2
1-12
1-1
CR CR
CR
CR
CR
CR
CR
CR
CR
CR
A7014
2B
TYP. 4'-5 7/8"
4 5/
8"4
5/8"
5'-11"5'-4"
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A111
FIRST FLOOR TENANTFITOUT
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A111 1/8" = 1'-0"1 FIRST FLOOR TENANT FITOUT PLAN
N
A ISSUED FOR BID 12/28/2018
DN
UP
DN DN
A
B
C
D
E
F
1 1.2 1.8 2 2.6 3 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
1-201MEZZANINE
1-202FABRICATION
1-203FABRICATION
1-204STAGING
A.5
1-20
2-1
1-20
4-1
WALLS BELOW
SKYLIGHT ABOVE
5-204OFFICE
5-203OFFICE
5-202OFFICE
5-201MEZZANINE
3-201TENANT #3 MEZZANINE
EQUIPMENT PLATFORM
1C1C
1C
1C
1C 1C
A7013
5-20
3-1
5-204-1 5-202-1
6A801
_________
OPEN TO BELOW
OPEN TO BELOW OPEN TO BELOW
15'-11"15'-11" 16'-0" MIN.
20'-1
1/4
"
20'-3
"
WALKWAY PAD
EXHAUST HOOD
WALKWAY PAD
A7021
3A801
_________
2
6'-4"
1-20
3-1
8'-0"
A7015
2A
CENTER WALL ON COL LINE
EQ EQ
4 1/
2"
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A112
SECOND FLOOR TENANTFITOUT
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A112 1/8" = 1'-0"1 SECOND FLOOR TENANT FITOUT PLAN
N
A ISSUED FOR BID 12/28/2018
A
B
C
D
E
F
1 1.2 1.8 2 2.6 3 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
A.5
EQEQ
EQ EQLA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
UNISTUT FRAMING SPANNING WALL-TO-WALL (COORD. LOCATIONS W/ LIGHT FIXTURE)
PENDANT LIGHT SUSPENDED FROM UNISTRUT
EQ
10'-0
"5'-
0"
EQ
LA-03 LA-03
LA-03LA-03
LA-03 LA-03
LA-03LA-03
10'-0
"10
'-0"
LA-03
LA-03
EQEQ
1-100AVESTIBULE
1-100LOBBY
1-101OPEN OFFICE AREA
1-121CONFERENCE
1-106OFFICE
1-107OFFICE
1-108OFFICE
1-109OFFICE
1-110OFFICE
1-111OFFICE
1-112OFFICE
1-113OFFICE
1-114ASTORAGE
1-118OFFICE
1-119OFFICE
1-102WOMENS
1-103MENS
1-105OFFICE
1-120OFFICE
1-117OFFICE
1-116IT CLOSET
1-115KITCHEN
LA-05
EQ EQ
EQ EQ
4'-0"
8'-0"
EQ EQ
EQ EQ
LA-01
LA-01 LA-01
LA-01
9'-7"
3'-5 3/4"3'-6 1/4"
LA-05
LA-05
LA-05
LA-05
4'-8"
8'-8"
8'-0" 8'-0"
LA-04
LA-04 LA-04
LA-06
LA-06
LA-06LA-06
EQEQ
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
SITE LIGHT, TYP.
LE-01.1 LE-01.1 LE-01.1 LE-01.1
EQEQ
7'-6"
LE-02 LE-02 LE-02 LE-02 LE-02
CANOPY LIGHTS, TYP.
10'-6" 10'-6"
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01 LA-01
LA-01
LA-01
LA-01
LA-01
LA-06 LA-06
LA-06
LA-06
LA-06
LA-08
2'-8" 5'-4" 8'-0" 8'-0" 8'-0"
8'-0"
LA-02
LA-01 LA-01 LA-01 LA-01 LA-01
10'-0
"
8'-0" 2'-8" 2'-8" 8'-0"
LA-01 LA-01 LA-01 LA-01
LE-03
LE-03
LE-03
LA-01LA-01 LA-01 LA-01
8'-0" 8'-0" 8'-0" 8'-0"
LA-01
LA-01 LA-01 LA-01 LA-03.1LA-01
LA-06
LA-06 LA-06
LA-06
4'-8" 6'-0 1/4"(GWB)
C.H.9'-8"
(GWB)C.H.8'-0" 4'-
0"3'-
9"
LA-01
(GWB)C.H.8'-0"
(GWB)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
(GWB)C.H.8'-0"
(2X2 ACT)C.H.7'-11"
(2X2 ACT)C.H.7'-6"
(2X2 ACT)C.H.7'-6"
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
EXPOSED STRUCTURE
EXPOSED STRUCTURE
(GWB)C.H.8'-0"
LA-05LA-08
8'-0" 8'-0" 8'-0" 8'-0"
10'-0
"10
'-0"
20'-0
"
8'-0" 8'-0" 8'-0" 8'-0"
10'-0
"10
'-0"
20'-0
"
LA-03.1 LA-03.1 LA-03.1
LA-03.1LA-03.1LA-03.1
LA-03.1 LA-03.1 LA-03.1 LA-03.1 LA-03.1 LA-03.1
LA-03.1LA-03.1LA-03.1
LA-03.1 LA-03.1 LA-03.1
1-114SHIPPING
1-101ALOUNGE
2-102WC
2-103WC
2-104CORRIDOR
2-105MECHANICAL CLOSET
3-103MENS
3-102WOMENS
3-101TENANT #3
4-105MECHANICAL CLOSET
4-102WC
4-103WC
4-104CORRIDOR
5-103MENS
5-102WOMENS
4-101TENANT #4
5-107ACORR.
2-101TENANT #2
B.O. FIXTURE @ 8'-0" AFF, TYP.
B.O. FIXTURE @ 16'-8" AFF, TYP.
B.O. FIXTURE @ 16'-8" AFF, TYP.
B.O. FIXTURE @ 16'-8" AFF, TYP.
9'-0" B.O. FIXTURE AFF, TYP.
9'-0" B.O. FIXTURE AFF, TYP.
B.O. FIXTURE @ 8'-6" AFF, TYP.
B.O. FIXTURE @ 8'-0" AFF, TYP.
B.O. FIXTURE @ 8'-0" AFF, TYP.
LA-01
LA-01
LA-01
LA-01
LA-01 LA-01
LA-01
LA-01
LA-01
LA-01
B.O. FIXTURE @ 8'-6" AFF, TYP.
LA-01 LA-01
10'-6" 10'-6"
LA-09LA-09
LA-06LA-06
LA-06
LA-06
LA-06
LA-06
LA-08
LA-06
LA-06
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.8'-0"
(2X2 ACT)C.H.7'-6"
(2X2 ACT)C.H.7'-6"
(2X2 ACT)C.H.8'-0"
EXPOSED STRUCTURE
EXPOSED STRUCTURE
EXPOSED STRUCTURE
(2X2 ACT)C.H.8'-0"
EXPOSED STRUCTURE
EXPOSED STRUCTURE
EXPOSED STRUCTURE
3'-11
1/2
"
7'-6"
LE-02 LE-02 LE-02 LE-02 LE-02
CANOPY LIGHTS, TYP.
SITE LIGHT, TYP. LE-01.1 LE-01.1 LE-01.1 LE-01.1SITE LIGHT, TYP. LE-01.1 LE-01.1 LE-01.1 LE-01.1SITE LIGHT, TYP.
LE-03
LE-03
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
LE-01
10'-8"
LINEAR LIGHT - SEE CANOPY DETAILS
LL-01
LINEAR LIGHT - SEE CANOPY DETAILS
LL-01
EM-01
EM-01 EM-01
LA-05
LA-09LA-09
C.H.9'-3 13/16"
LA-05
LA-08
LA-08
EX-0
2
EX-02
EX-0
2
EX-0
1
EX-01
EX-01
EX-0
1
EX-01
EX-0
2
EX-02
EX-01 EX-01
EX-01
EX-01
EX-01
EX-0
1
LA-07
LA-07 LA-07
LA-07LA-07
LA-07
LA-07
LA-07LA-07
LA-07 LA-07
LA-07LA-07LA-07
LA-07 LA-07
LA-07 LA-07LA-07
LA-07LA-07
LA-07
LA-05
(GWB)C.H.8'-0"
EQEQ
EQ EQ
(GWB)C.H.7'-0"
(GWB)C.H.7'-0"
(GWB)C.H.7'-6"
(GWB)C.H.7'-6"
(GWB)C.H.7'-6"
(GWB)C.H.7'-6"
(GWB)C.H.7'-6"
(GWB)C.H.7'-6"
MECH. DIFFUSER, TYP.
MECH. DIFFUSER, TYP.
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A121
FIRST FLOOR REFLECTEDCEILING PLAN
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A121 1/8" = 1'-0"1 FIRST FLOOR REFLECTED CEILING PLAN
TAG TYPE MANUFACTURER PART COLOR WATTS VOLTS LAMP REMARKS
EM-01 LED OUTDOOR EGRESS EMERGENCY LIGHT MULE LIGHTING, INC. EAE-BB-10-A-T ALUM. 10 120 LEDEX-01 EXIT SIGN WITH EMERGENCY LIGHT WALL MOUNTED MULE LIGHTING, INC. AL-1-R-WW WHITE 3.9 120 LEDEX-01.1 EXIT SIGN WITH EMERGENCY LIGHT CEILING MOUNTED MULE LIGHTING INC. AL-1-R-WW WHITE 3.9 120 LEDEX-02 EXIT SIGN WITH EMERGENCY LIGHT AND DUAL REMOTE HEADS MULE LIGHTING INC. AL-U-R-WW-REM WHITE 3.9 120 LED RLEDC-2-WP REMOTE HEADSLA-01 LINEAR PENDANT - 8'-0" LITHONIA LIGHTING TZL1N-L96-6000LM-FST-120-30K-80-CS93W-MB BLACK 48 120 3000K LED ZACVH AIRCRAFT CABLE MOUNTING, PENDANT SYSTEMS "J BOX" W/ "MGR-1-40-20" AND
"NON-FEED J-BOX MOUNT BE"LA-02 LINEAR PENDANT - 4'-0" LITHONIA LIGHTING ZL1N-L48-3000LM-FST-120-30K-80-CS93W-MB BLACK 25 120 3000K LED ZACVH AIRCRAFT CABLE MOUNTING, PENDANT SYSTEMS "J BOX" W/ "MGR-1-40-20" AND
"NON-FEED J-BOX MOUNT BE"LA-03 PENDANT DELRAY LIGHTING INC. IL7304-W30-1-STANDARD DIMMING - 42 120 3000K LED AIRCRAFT CABLE MOUNTINGLA-03.1 PENDANT DELRAY LIGHTING INC. IL7306-W30-1-STANDARD DIMMING - 84 120 3000K LED AIRCRAFT CABLE MOUNTINGLA-04 TRACK LIGHTING WAC LIGHTING MO-1035-F-830-BK/BK BLACK 35 120 3000K LED 4 PER TYPE MARK; TRACK: WAC LIGHTING H TRACKLA-05 SURFACE-MTD CEILING LIGHT WAC LIGHTING FM-11RN-930-WT WHITE 20 120 3000K LEDLA-06 2X2 LED TROFFER COLUMBIA LIGHTING LJT-22-30-ML-G-FA-A12125 WHITE 18 120 LEDLA-07 WALL SCONCE BARN LIGHT USA BLE-W-CGG-100-NA-CGG-100-RIB-NA-LED16.8-3000K BLACK 16 120 3000K LEDLA-08 WALL-MOUNT LED LIGHT (J.C.) LITHONIA LIGHTING WL2-08L-EZ1-LP830 WHITE 7.5 120 3000K LEDLA-09 INDUSTRIAL CEILING-MOUNTED LINEAR LITHONIA LIGHTING FEM-L48-8000LM-LPPCL-MD-120-GZ10-3000K-80CRI WHITE 23 120 3000K LEDLE-01 EXTERIOR ADJUSTABLE FLOOD LIGHT (MEDIUM SPOT) LITHONIA LIGHTING DSXF1 LED-P1-30K-MSP-120-IS-DBLXD / DSXF1UBV DDBXD U
(VISOR)BLACK 21 120 3000K LED PROVIDE 6" DIA. X 24" CONCRETE MOUNT @ EACH FIXTURE
LE-01.1 EXTERIOR ADJUSTABLE FLOOD LIGHT (NARROW SPOT) LITHONIA LIGHTING DSXF1 LED-P1-30K-NSP-120-IS-DBLXD / DSXF1UBV DDBXD U(VISOR)
BLACK 21 120 3000K LED
LE-02 EXTERIOR RECESSED DOWNLIGHT WAC LIGHTING R4RD1T-F-830-BK / R4RNT-25 (HOUSING) BLACK 25 120 3000K LEDLE-03 LED WALL LIGHT LITHONIA LIGHTING KAXWLED-P1-30K-R3-120-DBLXD BLACK 29 120 3000K LEDLL-01 LED STRIP LIGHT LUMINII LL30WET-31K-SL-NC / PSV-96-24-U2ND-D (POWER SUPPLY) /
SLW15 (CHANNEL MOUNTING)ALUM. 2.5/FT 24 3100K LED 40'-0" LENGTH, MOUNT POWER SUPPLY @ INTERIOR CEILING
LIGHT FIXTURE
PRODUCTS INDICATED ARE THE BASIS OF DESIGN. SUBJECT TO COMPLIANCE WITH THE REQUIREMENTS, PROVIDE SPECIFIED PRODUCTS OR APPROVED EQUAL.
N
A ISSUED FOR BID 12/28/2018
A
B
C
D
E
F
1 1.2 1.8 2 2.6 3 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
A.5
10'-0
"5'-
0"
EQEQ
12'-0"12'-0"
LA-03
LA-03
LA-03
LA-03 LA-03
LA-03
LA-03
LA-03
EQ EQ
6'-0"
6'-0"
LA-02
LA-01 LA-01
LA-02
LA-01
LA-01
SKYLIGHT, TYP.
ROOF PURLIN, TYP.
GLULAM BEAM, TYP.
LA-03.1
LA-03.1
LA-03.1
LA-03.1
LA-03.1
LA-03.1
LA-03.1 LA-03.1 LA-03.1
10'-0
"8'-0" 8'-0" 8'-0" 8'-0"
10'-0
"8'-0" 8'-0" 8'-0" 8'-0"
SEE FIRST FLOOR RCP SEE FIRST FLOOR RCP
SEE FIRST FLOOR RCP
1-202FABRICATION
1-203FABRICATION
1-204STAGING
1-201MEZZANINE
B.O. FIXTURE @ 8'-0" AFF, TYP.
B.O. FIXTURE @ 8'-0" AFF, TYP.
B.O. FIXTURE @ 8'-0" AFF, TYP. B.O. FIXTURE @ 8'-0"
AFF, TYP.
LE-03EX-01.1
EX-01.1EX-01.1
LA-01
LA-01
LA-01
LA-01
LA-01
LA-01
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A122
SECOND FLOORREFLECTED CEILING PLAN
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A122 1/8" = 1'-0"1 SECOND FLOOR REFLECTED CEILING PLAN
N
A ISSUED FOR BID 12/28/2018
1ST FLOOR0"
2ND FLOOR11'-8"
1 1.2 1.8 2 2.6
2A301
_________3A301
_________
3 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
2A302
_________ 3A302
_________4A302
_________ 1A303
_________
___________________4
A203
___________________3
A203
SKYLIGHT, SEE ROOF PLAN, TYP.
EXTERIOR WALLASSEMBLY 3
EXTRIOR WALLASSEMBLY 2
EXTRIOR WALLASSEMBLY 2
EXTERIOR WALLASSEMBLY 3
12'-8" 4'-0" 16'-0" 4'-0" 12'-8" 22'-4" 18'-4" 16'-8" 16'-0" 16'-8" 18'-4" 22'-4" 16'-8" 16'-0" 16'-8"
5 3/4"5 3/4"5 3/4"5 3/4"
ALUMINUMSTOREFRONTSYSTEM
ALUMINUMSTOREFRONTSYSTEM
2-101-1 4-101-1
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 4A
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 4A
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 4A
CONTINIOUS RADIUS ALUMINUM COPING
CONTINIOUS RADIUS ALUMINUM CURTAINWALL
5 3/4"5 3/4"
SEE SIGNAGE SHEET (TYP. OF 3)
SEE SIGNAGE SHEET (TYP. OF 2)
SIGN SIGN SIGN SIGN
OVERFLOW SCUPPER, TYP.
OVERFLOW SCUPPER, TYP.
ALUM. CURTAINWALL SYSTEM
ALUM. CURTAINWALL SYSTEM
ALUM. CURTAINWALL SYSTEM
___________________3
A404
___________________5
A404
___________________7
A404
TYP.
SEE SIGNAGE SHEET (TYP. OF 2)
SEE SIGNAGE SHEET (TYP. OF 4)
1ST FLOOR0"
2ND FLOOR11'-8"
A B C D E F
1A301
_________ 1A302
_________
A.5
SKYLIGHT, SEE ROOF PLAN, TYP.
1'-3 1/2" 10'-0" 10'-0" 20'-0" 20'-0" 20'-0" 20'-0"
EXTERIOR WALLASSEMBLY 1
WP-3
WP-1
WP-2
1ST FLOOR0"
2ND FLOOR11'-8"
11.21.822.6
2A301
_________
3A301
_________
33.23.444.455.45.66 1.41.6
6A302
_________ 2A303
_________
W03W03W03W03
W02 W02 W02
W03 W03
W02
W03 W03 W03
W02 W02
W03 W03
W02
W03
W02 W02W02
W03W03
W02 W02 W02 W02
W03W03
2-104-22-105-14-104-2 4-105-1
TRASH ENCLOSURE - SEE DETAIL ELEVATIONS
SKYLIGHT, SEE ROOF PLAN, TYP.
EXTERIOR WALLASSEMBLY 1
EXTRIOR WALLASSEMBLY 2
EXTERIOR WALLASSEMBLY 1
EXTRIOR WALLASSEMBLY 2
EXTERIOR WALLASSEMBLY 1
APPROXIMATE LOCATION OF ELEC. DISTRIBUTION PANEL (SIZE TO BE CONFIRMED) - INSTALL 3/4" PLYWOOD OVER NAILERS BETWEEN STUDS; SEE MEP & CIVL FOR DETAILS
16'-8" 16'-0" 16'-8" 22'-4" 18'-4" 16'-8" 16'-0" 16'-8" 18'-4" 22'-4" 12'-8" 4'-0" 16'-0" 4'-0" 12'-8"
5 3/4"
5A411
_________
5 3/4"5 3/4"5 3/4"5 3/4"5 3/4"
APPROXIMATE LOCATION OF GAS METER BANK, SEE MEP & CIVL FOR DETAILS
OVERFLOWSCUPPER, TYP.
OVERFLOWSCUPPER, TYP.
TRASH ENCLOSURE -SEE DETAIL ELEVATIONS
EXHAUST VENT
EXHAUST VENT
GUARDRAIL
CR CR
WP-3
WP-2
WP-1
1ST FLOOR0"
2ND FLOOR11'-8"
ABCDEF
1A301
_________
WP-1
WP-3
A.5
5A302
_________
3A402
_________
2A402
_________
___________________1
A203
3A411
_________
WP-2
W03
W02 W02 W02
W03 W03
W02 W02
W03
W02
W03 W03W03
W02 W02W02
W03W03
W02 W02 W02
W03 W03
SKYLIGHT, SEE ROOF PLAN, TYP.
EXTERIOR WALLASSEMBLY 1
20'-0" 20'-0" 20'-0" 20'-0" 10'-0" 10'-0" 1'-3 1/2"
4" X 4" DOWNSPOUT 4" X 4" DOWNSPOUT
6" X 6" GUTTER
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A201
BUILDING ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A201 1/8" = 1'-0"1 EAST BUILDING ELEVATION
A201 1/8" = 1'-0"2 NORTH BUILDING ELEVATION
A201 1/8" = 1'-0"4 WEST BUILDING ELEVATION
A201 1/8" = 1'-0"3 SOUTH BUILDING ELEVATION
A ISSUED FOR BID 12/28/2018
1ST FLOOR0"
2ND FLOOR11'-8"
A B C D E F1
A301_________
A.5
___________________3
A302
3A411
_________
1-101-2
3A303
_________
1-101-1
1-201-1
SKYLIGHT, SEE ROOF PLAN, TYP.
ROOFTOP HVACE EQUIPMENT, TYP. - SEE MEP FOR DETAILS
EXTERIOR WALLASSEMBLY 1
WP-2
WP-1
WP-3
WP-310A411
_________7A411
_________
TRASH ENCLOSURE -SEE DETAIL ELEVATIONS
ROOF ASSEMBLY 1 GUTTER & DOWNSPOUT, TYP.
EXTERIOR WALLASSEMBLY 1EXTERIOR WALLASSEMBLY 3
EXHAUST VENTS -SEE MECH.
1ST FLOOR0"
2ND FLOOR11'-8"
A B C D E F1
A301_________
A.5
SKYLIGHT, SEE ROOF PLAN, TYP.
ROOFTOP HVACE EQUIPMENT, TYP. -SEE MEP FOR DETAILS
Sim3
A303_________
WP-2
WP-3EXTERIOR WALLASSEMBLY 1
7A411
_________
TRASH ENCLOSURE - SEE DETAIL ELEVATIONS
ROOF ASSEMBLY 1GUTTER & DOWNSPOUT, TYP.
WP-1
WP-3
1ST FLOOR0"
2ND FLOOR11'-8"
ABCDEF1
A301_________
A.5
3-101-33-101-2 3-101-1
SKYLIGHT, SEE ROOF PLAN, TYP.
Sim3
A303_________
WP-3EXTERIOR WALLASSEMBLY 1
WP-2
WP-1
WP-37
A411_________
ROOF ASSEMBLY 1GUTTER & DOWNSPOUT, TYP.
___________________5
A411 EXTERIOR WALLASSEMBLY 1
EXTERIOR WALLASSEMBLY 3
2'-0"
1ST FLOOR0"
2ND FLOOR11'-8"
ABCDEF1
A301_________
A.5
5-101-35-101-2 5-101-1
5-201-1
ROOFTOP HVACE EQUIPMENT, TYP. - SEE MEP FOR DETAILS
Sim3
A303_________
SKYLIGHT, SEE ROOF PLAN, TYP.
WP-2
WP-1
EXTERIOR WALLASSEMBLY 1
WP-3
WP-37
A411_________
ROOF ASSEMBLY 1 GUTTER & DOWNSPOUT, TYP.
EXTERIOR WALLASSEMBLY 1EXTERIOR WALLASSEMBLY 3
2'-0"
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A202
BUILDING ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A202 1/8" = 1'-0"2 BUILDING ELEV. - HANGER 1 - NORTH
A202 1/8" = 1'-0"4 BUILDING ELEV. - HANGER 2 - NORTH
A202 1/8" = 1'-0"3 BUILDING ELEV. - HANGER 2 - SOUTH
A202 1/8" = 1'-0"1 BUILDING ELEV. - HANGER 3 - SOUTH
A ISSUED FOR BID 12/28/2018
1ST FLOOR0"
2ND FLOOR11'-8"
13A401
_________
14A401
_________
6A402
_________
5A402
_________
1/2"
PANE
L
3'-11
1/2
"1/
2"
PANE
L
3'-11
1/2
"1/
2"
5 3/
4"1'-
0"1'-
0"1'-
0"5
3/4"
1'-0"
1'-0"
1'-0"
5 3/
4"
6'-5"
1/2"
1/2"
1'-6
1/2"
1'-0"
1/2"
PANE
L
7'-6
1/2"
1/2"
1'-6
1/2"
11A401
_________
7A402
_________
12A401
_________
1A401
_________
TYP.
1'-0"
5 3/
4"3/
4"3/
4"
3/4" TYP.
5 3/
4"
NOM. 1X4 PT WD FURRING, 24" O.C., TYP.2'-0" 2'-0" 2'-0"
MASONRY BASE
FIBER CEMENT PANEL, TYP.
1/2" VERTICAL REVEAL @ 2'-0" O.C.
STOREFRONT WINDOW
5 1/
4"1'-
0"
STOREFRONT WINDOW
3A401
_________
W03
W02
POWDER-COATED SHEET METAL
6" X 6" GUTTER
FIBER CEMENT PANEL W/ 1/2" VERTICAL JT. @ 8' O.C.
TYP.3/4"
1/2" HORIZONTAL JT.
FIBER CEMENT PANEL, TYP.
EXPOSED FASTENER, TYP.
1'-6"
METAL SILL FLASHING/COPING
1/2" HORIZONTAL JT.
IGU-2, TYP.
IGU-2TYP.
IGU-2TYP.
1ST FLOOR0"
2ND FLOOR11'-8"
1 1.2 1.8 21.4 1.6
2A302
_________
3A402
_________
2A402
_________
1A402
_________
1'-6"
5A401
_________ 8A401
_________ @ TENANT 3 & 5
6A401
_________
4A401
_________
3A402
_________
2A402
_________
STEEL BEAM BEYOND (SEE STRUCT.)
STEEL TIE-RODS BEYOND (SEE STRUCT.)
2 1/2" WIDE MULLION
5" WIDE MULLION
Sim1
A303_________ @ TENANT
3 & 5
IGU-3
SEE SIGNAGE SHEET
CONTINIOUS RADIUS ALUMINUM COPING
CONTINIOUS RADIUS HEADER
12'-8"4'-0"16'-0"4'-0"12'-8"
11'-8
"
2'-0"
8'-2"
± 6'-
9 1/
4"
2'-8"
4"4"15'-4" 15'-4" 15'-4"
± 12
'-6"
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALLASSEMBLY 4A
ACM PANEL JT., TYP.
3'-3"
3'-4"
3'-3"
3'-4
1/4"
3'-3"
___________________1
A404
TYP.
1ST FLOOR0"
4.4
22'-4"
9'-2"
9'-8"
EXTRIOR WALLASSEMBLY 2
EXTERIOR WALLASSEMBLY 3
8"3'-
8"3'-
10"
4-101-1
Sim3
A302_________
9'-8" 3'-0" 9'-8"
7'-0"
7A401
_________
IGU-1
4A402
_________
11A402
_________
3'-3" 3'-2" 3'-3" 3'-3"3'-2"3'-3"
8'-2"
CARD READER - MT. TO MULLION W/ CONCEALED WIRING
TYP.
10'-0"
6'-0" GATE
STEEL TUBE POSTS W/ CONCRETE FOUNDATION
GALVANIZED STEEL FIXED LOUVER INFILL PANEL
DOUBLE SWING GATE W/ PADLOCK
FRONT ELEVATION
EQ EQ
6'-0"
4"
10'-0
"
8'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
A2032
A2035
A2032
STEEL TUBE POSTS W/ CONCRETE FOUNDATION
4 1/2" DIA. X 42" HIGH CONCRETE-FILLED STEEL SAFETY BOLLARD W/ BASE PLATE AND DOMED TOP (BASIS-OF-DESIGN: ULINE H-2119F); BOLT TO SLAB PER MFR'S INSTRUCTIONS
DOUB
LE S
WI N
G G
ATE
W/ P
ADLO
CK
6'-0"
6"
8'-0"
SIDE ELEVATION
EQ EQALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR.
THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A203
BUILDING ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A203 3/4" = 1'-0"1 DETAIL ELEVATION @ FIBER CEMENT PANEL WALL
A203 1/4" = 1'-0"4 DETAIL ELEVATION @ CURTAINWALL
A203 3/8" = 1'-0"3 ENTRY STOREFRONT
A203 1/2" = 1'-0"5 DETAIL ELEVATION @ TRASH ENCLOSURE - FRONT
A ISSUED FOR BID 12/28/2018
A203 1/2" = 1'-0"6 DETAIL PLAN @ TRASH ENCLOSURE
A203 1/2" = 1'-0"2 DETAIL ELEVATION @ TRASH ENCLOSURE - SIDE
1ST FLOOR0"
2ND FLOOR11'-8"
1 1.2 1.8 2 2.6
2A301
_________3A301
_________
3 3.2 3.4 4 4.4 5 5.4 5.6 61.4 1.6
5A501
_________
2-102-1 2-103-1 2-104-1 2-106-1 4-102-1 4-103-1 4-104-1 4-106-15-101
TENANT #54-101
TENANT #43-101
TENANT #32-101
TENANT #21-101
TENANT #1
SKYLIGHT
ROOF ASSEMBLY 2
ROOF ASSEMBLY 1
ROOF ASSEMBLY 3
ROOF ASSEMBLY 1
ROOF ASSEMBLY 2
ROOF ASSEMBLY 1
GUARDRAIL GUARDRAIL GUARDRAIL
___________________3
A411
TIE RODTIE ROD TIE ROD
1ST FLOOR0"
2ND FLOOR11'-8"
A B C D E F
1A301
_________
A.5
5-101TENANT #5
5-201-1
5-104-1 5-101-25-101-3
___________________1
A303___________________
2A303
SIM./OPH
16'-8
"
8'-0"
A B C D E F
1A301
_________
A.5
3A411
_________ 3A303
_________
1-101-1 1-101-2
2-101TENANT #2
1-201-1
2-101TENANT #2
SKYLIGHT, TYP. -SEE ROOF PLAN ROOF ASSEMBLY 1
TRASH ENCLOSURE
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/8" = 1'-0"
A301
BUILDING SECTIONS
1729.rvtJCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A301 1/8" = 1'-0"1 BUILDING SECTION
A301 1/8" = 1'-0"2 BUILDING SECTION
A301 1/8" = 1'-0"3 BUILDING SECTION
A ISSUED FOR BID 12/28/2018
1ST FLOOR0"
2ND FLOOR11'-8"
6
___________________3
A401
MASONRY BASE
EXTERIOR WALLASSEMBLY 1
___________________14
A401SIM.
ROOF ASSEMBLY 1
F.O. STUD4 1/2"
___________________1
A401
1ST FLOOR0"
2ND FLOOR11'-8"
A
___________________4
A401
___________________5
A401
___________________6
A401
MASONRY BASE
CURTAIN WALLSYSTEM
2'-0"
8'-2"
1'-6"
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 4A
CURTAIN WALLSYSTEM
ROOF ASSEMBLY 1
1'-0 1/4"
___________________2
A404
1ST FLOOR0"
2ND FLOOR11'-8"
A.5___________________
11A402
___________________7
A401
ALUMINUMSTOREFRONTSYSTEM
EXTRIOR WALLASSEMBLY 2
F.O. STUD1'-1 1/4"
ROOF ASSEMBLY 2
CANOPY ROOF
1'-1 3/4"
LL-01 LIGHT FIXTURE -COORD. LOCATION W/ ARCHITECT
1ST FLOOR0"
2ND FLOOR11'-8"
A.5
___________________11
A402SIM.
___________________10
A401
___________________10
A402
EXTERIOR WALLASSEMBLY 3
EXTRIOR WALLASSEMBLY 2
F.O. STUD1'-1 1/4"
CANOPY ROOF ROOF ASSEMBLY 28'-
2"
1ST FLOOR0"
2ND FLOOR11'-8"
1
___________________1
A401
___________________12
A401
___________________11
A401
WDW6'-5"
11'-8
"
___________________3
A401 OPHW
03
EXTERIOR WALLASSEMBLY 1
MASONRY BASE
F.O. STUD4 1/2"
ROOF ASSEMBLY 1
1ST FLOOR0"
2ND FLOOR11'-8"
E
___________________11
A402SIM. (NO CANOPY)
EXTRIOR WALLASSEMBLY 2
___________________1
A401
MASONRY BASE
F.O. STUD1'-1 1/4"
ROOF ASSEMBLY 2
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/2" = 1'-0"
A302
WALL SECTIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A302 1/2" = 1'-0"1 WALL SECTION
A302 1/2" = 1'-0"2 WALL SECTION
A302 1/2" = 1'-0"3 WALL SECTION
A302 1/2" = 1'-0"4 WALL SECTION
A302 1/2" = 1'-0"5 WALL SECTION
A302 1/2" = 1'-0"6 WALL SECTION
A ISSUED FOR BID 12/28/2018
1ST FLOOR0"
2ND FLOOR11'-8"
A
___________________4
A401
___________________8
A401
___________________6
A401
CURTAIN WALLSYSTEM
CURTAIN WALLSYSTEM
MASONRY BASE
EXTERIOR WALLASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 4A
ROOF ASSEMBLY 1
F.O. CW1'-0 1/4"
1ST FLOOR0"
2ND FLOOR11'-8"
F
___________________15
A401
EXTERIOR WALLASSEMBLY 1
EXTERIOR WALLASSEMBLY 1
W03
___________________12
A401
___________________1
A401
___________________2
A401
MASONRY BASE
WDW6'-5"
F.O. STUD1'-0"
ROOF ASSEMBLY 1
1ST FLOOR0"
2ND FLOOR11'-8"
2
___________________8
A402
___________________3
A401
2B
EXTERIOR WALLASSEMBLY 1
___________________7
A411
EXTEND ROOF MEMBRANE UP WALL PER ELEVATIONS
F.O. STUD4 1/2"
ROOF ASSEMBLY 1
1-101TENANT #1
2-101TENANT #2
GWB EXPANSION JT., TYP. SEE DETAIL
ACOUSTICALLY SEAL PARTITION TO SLAB
___________________6
A601
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/2" = 1'-0"
A303
WALL SECTIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A303 1/2" = 1'-0"1 WALL SECTION
A303 1/2" = 1'-0"2 WALL SECTION
A303 1/2" = 1'-0"3 BUILDING SECTION
A ISSUED FOR BID 12/28/2018
roof ASSEMBLY 1DESCRIPTION: TPO OVER COVERBOARD OVER
RIGID INSULATION OVER WOOD DECKING (CURVED ASSEMBLY)
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-30 MIN.
TPO MEMBRANE ROOF (FULLY ADHERED)
roof ASSEMBLY 2DESCRIPTION: TPO ROOFING MEMBRANE
OVER GYPSUM ROOF BOARDOVER RIGID INSULATIONOVER T&G WOOD DECKING
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-30 MIN.
TPO MEMBRANE ROOF(FULLY ADHERED)
1/2" GYPSUM ROOF BOARD
RIGID INSULATION
T&G WOOD STRUCTURAL DECKING, EXPOSED.SEE STRUCT. DWGS
roof ASSEMBLY 3DESCRIPTION: CONCRETE PAVER AND
PEDESTAL SYSTEMOVER ROOF ASSEMBLY 2
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-30 MIN.
24" X 24" X 2" PRECAST CONCRETE PAVERS
ADJUSTABLE PEDESTAL SYSTEM @ 24" O.C. GRID
DESCRIPTION: ACM PANEL OVERSTEEL STUD BACKUP
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-13 + R-7.5ci MIN.
GLULAM BEAMSEE STRUCT.
CONTRACTOR SHALL ENSURE ROOFING FASTENERS DO NOT PENETRATE THROUGH EXPOSED WOOD DECKING
OPEN WEB WOOD JOISTSSEE STRUCT.
SEE
ROO
F AS
SEM
BLY
2
EXT. WALL ASSEMBLY 1DESCRIPTION: FIBER CEMENT PANEL OVER
WOOD STUD BACKUP
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-20 MIN.
EXT. WALL ASSEMBLY 2DESCRIPTION: FIBER CEMENT
HORIZONTAL SIDING OVERWOOD STUD BACKUP
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-20 MIN.
EXT. WALL ASSEMBLY 3DESCRIPTION: ACM PANEL OVER
WOOD STUD BACKUP
FIRE RATING: N/ASOUND RATING: N/AR-VALUE: R-20 MIN.
WP-1
WP-2
WP-3
= WALL PANEL COLOR 1
= WALL PANEL COLOR 2
= WALL PANEL COLOR 3
ROOFING FASTENERS SHALL NOT PENETRATE THROUGH EXPOSED WOOD DECK6"
2"1/
2"
VARI
ES
PURLINS, BEYOND
T&G WOOD STRUCTURAL DECKING, EXPOSED.SEE STRUCT. DWGS
ROOFING FASTENERS SHALL NOT PENETRATE THROUGH EXPOSED WOOD DECK
RIGID INSULATION
1/2" GYPSUM ROOF BOARD
1 1/
2"6"
1/2"
NOTE: CURVED ROOFROOFING MATERIAL SHALL CONFORM TO CURVED PROFILE OF ROOF
7/16" FIBER CEMENT BOARD W/ EXPOSED FASTENERS
NOMINAL 1X4 P.T. WD FURRING
AIR BARRIER MEMBRANE
1/2" GYPSUM SHEATHING
NOM. 2X8 WD STUDS @ 24" O.C.ALIGN STUDS WITH FURRING BASED ON EXTERIOR PANEL LAYOUT
R20 BATT INSULATION
5/8" GWB, PTD.
FIBER CEMENT HORIZONTAL SIDING
5/8" 7 1/4" 1/2" 3/4"
AIR BARRIER MEMBRANE
1/2" GYPSUM SHEATHING
NOM. 2X8 WD STUDS @ 24" O.C.
R20 BATT INSULATION
5/8" GWB, PTD.
ACM EXPOSED FASTENER SYSTEM
PREFINISHED EXTRUDED ALUMINUM VERTICAL FURRING BY PANEL MFR.
1/2" GYPSUM SHEATHING
NOM. 2X8 WD STUDS @ 24" O.C.
AIR BARRIER MEMBRANE
R20 BATT INSULATION
5/8" GWB, PTD.
EXT. WALL ASSEMBLY 4A/4B
ACM EXPOSED FASTENER SYSTEM
PREFINISHED EXTRUDED ALUMINUM VERTICAL FURRING BY PANEL MFR.
1/2" GYPSUM SHEATHING
STEEL STUDS @ 16" O.C.6" DP @ TYPE 4A8" DP @ TYPE 4B
GALVANIZED Z- FURRING CHANNELS
AIR BARRIER MEMBRANE
1 1/2" RIGID INSULATION (R-7.5 MIN)
± 11 3/4" @ TYPE 4A
± 9 3/4" @ TYPE 4A ± 9 5/8"± 9"
5/8" 7 1/4" 1/2"
± 9 1/2"
5/8" 7 1/4" 1/2"5/8" 6" 1/2" 1 1/2"
R13 BATT INSULATION
5/8" GWB, PTD.
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3" = 1'-0"
A400
EXTERIOR WALL ANDROOF ASSEMBLIES
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A ISSUED FOR BID 12/28/2018
6
8"
ROOF ASSEMBLY 1
1.5" T&G WOOD DECKING
6" X 6" WIND RESISTANTGUTTER (BOX PROFILE)
ROOF MEMBRANE FLASHING OVER COPING
METAL DRIP EDGE COPING
4"X 4" SQUARE DOWNSPOUT BEYOND
EXTERIOR WALL ASSEMBLY 1
7/16" FIBER CEMENT BD W/EXPOSED FASTENERSSTEEL TUBE COLUMN (PTD),
SEE STUCT.
5/8" GWB, PTD
SEALANT
4"
WOOD TRIM
'L' CASING BEAD
1ST FLOOR0"
A
RESILIENT WALL BASE
CMU FOUNDATION (SEE STRUCT.); COORD. BRICK LEDGE W/ GRADING
SILL FLASHING (SLOPE TOP) -FORM AROUND CONT. CLEATAND EXTEND BLW WDW;PROVIDE CONCEALED SPLICEPLATES AT JOINTS
CMU GROUTED SOLID TO FOUNDATION BELOW FLASHING
1'-10
"
1'-0 1/4"
1'-0 3/4"
MORTAR NET
SEALANT
CURTAINWALL SILL (CAULKFRAME TO AIR BARRIER)
1" AIR SPACE
SLAB ON GRADE
BACKER ROD & SEALANT
5/8" GWB, PTD
FINISH GRADE (VARIES)
3" RIGID INSULATION (EXTEND24" BELOW SLAB LEVEL)
SLAB VAPOR BARRIER
2" RIGID INSULATION
3/4" SOLID SURFACE SILL
2 1/2" STL STUD FRAMING
CLEAT ATTACHED TO F.O. BLOCKING
2 1/
2"
1/2"
'L' CASING BEAD
4" NOM. GROUND FACE CMU
SILL FLASHING (SLOPE TOP) -FORM AROUND CONT. CLEATAND EXTEND BLW WDW;PROVIDE CONCEALED SPLICEPLATES AT JOINTS
2ND FLOOR11'-8"
A1'-0 1/4"
2'-0"
1/2"
CURTAINWALL SILL (CAULKFRAME TO AIR BARRIER)
CURTAINWALL HEAD (CAULKFRAME TO FLASHING)
SEALANT
STEEL TUBE COLUMN (PTD),SEE STUCT.
5/8" GWB, PTD
R-20 BATT INSULATION
BACKER ROD & SEALANT
BACKER ROD & SEALANT
AIR BARRIER MEMBRANE1/2" GYPSUM SHEATHING
SEALANT
1 1/2" DEEP GWB L-BEAD
4 1/4"
SEALANT
PT RD BLOCKING AS REQ'D
STEEL ANGLE, SEE STRUCT.
ACM EXPOSED FASTENERSYSTEM
1 1/2" RIGID INSULATION
SLOPED SILL FLASHING (MATCH ACM) W/ CONT. CLEAT AND CONCEALED SPLICE PLATES
EXTERIOR WALL ASSEMBLY 4A
6" STEEL STUD FRAMING
'L' CASING BEAD'L' CASING BEAD
'L' CASING BEAD
'L' CASING BEAD
(1/4", TYP.)
A
T&G WOOD DECKING
GLULAM PURLIN BEAM BEYOND
SEALANTCONTINUOUS, ARCHEDCURTAINWALL HEAD (CAULKFRAME TO FLASHING)
BACKER ROD & SEALANT
AIR BARRIER MEMBRANE
METAL DRIP-EDGE COPING(CONTINUOUS RADIUS)
1'-0 1/4"
8"
CURVED HSS BEAM (PTD),SEE STRUCT.SEALANT
5/8" GWB, PTD
ROOF ASSEMBLY 1
EXTERIOR WALL ASSEMBLY 4B
8" STEEL STUD FRAMING
PT WD BLOCKING AS REQ'D
ROOF FLASHING OVER COPING
STEEL FLASHING TO MATCH ACM
INSECT SCREEN
FLASHING TAPE 1'-0 1/4"
'L' CASING BEAD
1ST FLOOR0"
A.51'-1 3/4"
1'-0"
3" RIGID INSULATION (EXTEND24" BELOW SLAB LEVEL)
SLAB VAPOR BARRIER
SLAB ON GRADE
SLAB VAPOR BARRIER
CAST-IN-PLACE CONCRETE CURB
CMU FOUNDATION (SEESTRUCT.)
3" RIGID INSULATION (EXTEND24" BELOW SLAB LEVEL)
RESILIENT WALL BASE
STOREFRONT WINDOW (CAULKFRAME TO SILL FLASHING) 3/4" SOLID SURFACE SILL
SILL PAN/FLASHING W/ CONT. CLEAT AND CONCEALED SPLICE PLATES
1"
SEALANT
± 1'-
1 1/
4"
PT WD BLOCKING AS REQ'D
1/2" 'L' CASING BEAD
PROVIDE WATERSTOP IF CONCRETE IS NOT MONOLITHIC POUR
1ST FLOOR0"
A.5
1"7"
ACM EXPOSED FASTENERSYSTEM
EXTERIOR WALL ASSEMBLY 3
SLAB VAPOR BARRIER
SLAB ON GRADE
5/8" GWB, PTD
NOM. 2X8 WD FRAMING @ 24"O.C.
SLAB VAPOR BARRIER
CAST-IN-PLACE CONCRETE CURB
CMU FOUNDATION (SEESTRUCT.)
3" RIGID INSULATION (EXTEND24" BELOW SLAB LEVEL)
INSECT SCREEN @ B.O. ACM FURRING
RESILIENT WALL BASE7"
(TIE-IN TO AIR BARRIER)
AIR BARRIER MEMBRANE
PROVIDE WATERSTOP IF CONCRETE IS NOT MONOLITHIC POUR
2ND FLOOR11'-8"
1
AIR BARRIER MEMBRANE1/2" GYPSUM SHEATHING
5/8" GWB, PTD
NOM. 2X8 WD FRAMING @ 24"O.C.
BATT INSULATION
5 3/4"
STOREFRONT WINDOW (CAULKFRAME TO SILL FLASHING)
SILL FLASHING
STEEL TUBE COLUMN (PTD),SEE STUCT.
DEFLECTION CLIP
SOLID WOOD SILL
POWDER-COATED 16 GAUGE SHEET MTL, EXTEND BEHIND DRIP CAP ABOVE TO CONCEAL FASTENERS AND FORM AROUND CLEAT BLW; PROVIDE CONCEALED SPLICE PLATE AT JOINTS
FLASHING TO RECIEVE SHEET METAL ABOVE
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
'L' CASING BEAD'L' CASING BEAD
'L' CASING BEAD
1
5 3/4"
EXTERIOR WALL ASSEMBLY 1
DRIP CAP TRIM
FLASHING TAPE
STOREFRONT HEAD (CAULKFRAME TO AIR BARRIER)
5/8" GWB, PTD
NOM. 2X8 WD FRAMING @ 24"O.C.
AIR BARRIER MEMBRANE
'L' CASING BEAD
2ND FLOOR11'-8"
1
1/2"
1'-0"
1/2"
5/8" GWB, PTD
2" T&G WOOD DECKING
STEEL BEAM, SEE STRUCT.
5/8" GWB, PTD7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
DRIP CAP TRIM
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
1/2" GYPSUM SHEATHING
R-20 BATT INSULATION
NOM. 2X8 WD FRAMING @ 24"O.C.
NOM. 2X8 WD FRAMING @ 24"O.C.
BATT INSULATION
RESILIENT WALL BASE
DEFLECTION CLIP
POWDER-COATED 16 GAUGE SHEET MTL, EXTEND BEHIND DRIP CAP ABOVE TO CONCEAL FASTENERS AND FORM AROUND CLEAT BLW; PROVIDE CONCEALED SPLICE PLATE AT JOINTS
AIR BARRIER MEMBRANECONT. CLEAT TO RECIEVE SHEET METAL ABOVE
FLASHING TAPE
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
5 3/
4"5
3/4"
'L' CASING BEAD
1
4" NOM. GROUND FACE CMU1" AIR SPACE
5/8" GWB, PTDR-20 BATT INSULATION
1/2"
2 1/
2"
5 3/4"
3/4" SOLID SURFACE SILLSEALANT
STOREFRONT WINDOW (CAULKFRAME TO SILL FLASHING)
AIR BARRIER MEMBRANE1/2" GYPSUM SHEATHINGNOM. 2X8 WD FRAMING @ 24"O.C.
+1'-6"
CLEAT ATTACHED TO F.O. BLOCKING
PT WOOD BLOCKING
SILL FLASHING (SLOPE TOP) -FORM AROUND CONT. CLEATAND EXTEND BLW WDW;PROVIDE CONCEALED SPLICEPLATES AT JOINTS
1/2"
4"
'L' CASING BEAD
2ND FLOOR11'-8"
A
5/8" GWB, PTD
T&G WOOD DECKING
STEEL ANGLE (SEE STRUCT.)
STEEL BEAM (PTD), SEESTRUCT.
BENT SHEET METAL ANGLE (PTD)
2'-0"
1/2"
CURTAINWALL SILL (CAULKFRAME TO AIR BARRIER)
CURTAINWALL HEAD (CAULKFRAME TO FLASHING)
R-20 BATT INSULATION
BACKER ROD & SEALANT
BACKER ROD & SEALANT
AIR BARRIER MEMBRANE1/2" GYPSUM SHEATHING
SEALANT
PT RD BLOCKING AS REQ'D
ACM EXPOSED FASTENERSYSTEM
1 1/2" RIGID INSULATION
SLOPED SILL FLASHING (MATCH ACM) W/ CONT. CLEAT AND CONCEALED SPLICE PLATES
EXTERIOR WALL ASSEMBLY 4A
1'-0 1/4"
6" STEEL STUD FRAMING
10 1/4"
'L' CASING BEAD
F
METAL DRIP-EDGE COPING(CONTINUOUS RADIUS)
8"
ROOF ASSEMBLY 1
CURVED HSS BEAM (PTD),SEE STRUCT.SEALANT
5/8" GWB, PTD
11 1/2"
EXTERIOR WALL ASSEMBLY 17/16" FIBER CEMENT BD W/EXPOSED FASTENERS
NOM. 2X8 WD FRAMING (BRACEBACK TO STEEL)
ROOF FLASHING OVER COPING
'L' CASING BEAD
PT WD BLOCKING AS REQ'D
2ND FLOOR11'-8"
F
1'-0"
1/2"
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
HORIZONTAL TRIM
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
5/8" GWB, PTD
NOM. 2X8 WD FRAMING @ 24"O.C.
STOREFRONT WINDOW (CAULKFRAME TO SILL FLASHING)
SILL FLASHING
STEEL BEAM (PTD), SEESTRUCT.
DEFLECTION CLIP
BENT SHEET METAL ANGLE (PTD)
T&G WOOD DECKING
PT WD BLOCKING AS REQ'D
BENT STEEL ANGLE (SEE STRUCT.)
AIR BARRIER MEMBRANE
EXTERIOR WALL ASSEMBLY 1
1'-1 1/4"
1ST FLOOR0"
6
CMU FOUNDATIONSEE STRUCTURAL DWGSCOORD. BRICK LEDGE W/ SITE GRADING
GROUT AIR CAVITY SOLID BELOW FLASHING LEVEL
MORTAR NET
FLUID APPLIED AIR BARRIER
VENT STRIP INSECT SCREEN INSTALLED BETWEEN VERTICAL FURRING MEMBERS
R-20 BATT INSULATION
1/2"
2 1/
2"1'-
6"
CONTINUOUS CLEAT ATTACHED TO WOOD BLOCKING
1/2" ALUMINUM WALL CAP FLASHING
W/ CONCEALED SPLICE PLATES
STAINLESS STEEL FLASHING & DRIP EDGE
5/8" GWB PAINTED
2X8 @ 24" O.C. MAX
VINYL BASE
COMPRESSIBLE FILLER
SEALANT, TYP.
CONCRETE SLAB ON GRADE
FLASHING TAPE
SELF ADHERED FLEXIBLE FLASHING
WEEPS
AIR SPACE
FLASHING TAPE
UNDERSLAB VAPOR BARRIER
GRAVEL BASE
COMPACTED EARTH
3" RIGID INSULATION EXTEND 24"
BELOW SLAB
DAMPROOFING
TREATED WOOD BLOCKING
GRADE (VARIES)
4" NOM. GROUND FACE CMU
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1 1/2" = 1'-0"
A401
EXTERIOR DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A401 1 1/2" = 1'-0"3 DETAIL SECTION @ ROOF EDGE
A401 1 1/2" = 1'-0"4 DETAIL SECTION @ MASONRY BASE (CURTAINWALL)
A401 1 1/2" = 1'-0"5 DETAIL SECTION @ CURTAINWALL SPANDREL
A401 1 1/2" = 1'-0"6 DETAIL SECTION @ HEAD OF CURTAINWALL
A401 1 1/2" = 1'-0"7 DETAIL SECTION @ STOREFRONT SILL
A401 1 1/2" = 1'-0"10 DETAIL SECTION @ AT BASE OF WALL
A401 1 1/2" = 1'-0"11 DETAIL SECTION @ 2ND FLOOR SLAB EDGE (WDW SILL)
A401 1 1/2" = 1'-0"12 DETAIL SECTION @ WINDOW HEAD
A401 1 1/2" = 1'-0"14 DETAIL SECTION @ 2ND FLOOR EDGE
A401 1 1/2" = 1'-0"13 DETAIL SECTION @ WINDOW SILL
A401 1 1/2" = 1'-0"8 DETAIL SECTION @ CURTAINWALL SPANDREL (MEZZANINE)
A401 1 1/2" = 1'-0"15 DETAIL SECTION AT COL F ROOF EDGE
A401 1 1/2" = 1'-0"2 DETAIL SECTION @ COL LINE F
A ISSUED FOR BID 12/28/2018
A401 1 1/2" = 1'-0"1 MASONRY BASE SECTION DETAIL
A
1.4
CURTAINWALL (CAULK FRAMETO METAL TRIM)
BACKER ROD & SEALANT
STEEL TUBE COLUMN (PTD),SEE STUCT.
SEALANT
1/2" GYPSUM SHEATHINGAIR BARRIER MEMBRANE
1'-0
1/4"
CONTINUOUS STEEL ANGLE (PTD), SEE STRUCT.
1'-0
1/4"
BREAK METAL TO MATCH CURTAINWALL
A
1
5/8" GWB, PTD
STEEL TUBE COLUMN (PTD),SEE STUCT.7/16" FIBER CEMENT BD W/
EXPOSED FASTENERS
J-CHANNEL TRIM
± 5 3/4" 11 1/2" 1/2"
ACM EXPOSED FASTENERSYSTEM
10 1
/4"
ACM EXPOSED FASTENERSYSTEM
EXTERIOR WALL ASSEMBLY 4A
EXTERIOR WALL ASSEMBLY 4B
EXTERIOR WALL ASSEMBLY 1
BREAK METAL TRIM (MATCH ACM)
BREAK METAL TRIM
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL
1'-0"
1/2"
± 3"
SEALANT
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
AIR BARRIER MEMBRANE
J-CHANNEL TRIM
J-CHANNEL TRIM 1'-0
1/4"
'L' CASING BEADSEALANT (1/4")
A
1
1'-0
1/4"
CURTAINWALL (CAULK FRAMETO METAL TRIM)
NOM. 2X8 WD FRAMING @ 24"O.C.
STEEL TUBE COLUMN (PTD),SEE STUCT.
R-20 BATT INSULATION
± 5 3/4" 11 1/2" 1/2"
EXTERIOR WALL ASSEMBLY 4B
1'-0"
1/2"
± 3"
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
J-CHANNEL TRIM
EXTERIOR WALL ASSEMBLY 1
BREAK METAL TRIM (MATCH ACM)
SEALANT
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
AIR BARRIER MEMBRANE
J-CHANNEL TRIM
J-CHANNEL TRIM
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL
'L' CASING BEADSEALANT
(1/4")
1
R-20 BATT INSULATION
NOM. 2X8 WD FRAMING @ 24"O.C.
1/2" GYPSUM SHEATHING
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
AIR BARRIER MEMBRANEVERTICAL TRIM
5/8" GWB, PTD
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
1/2"
1
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
AIR BARRIER MEMBRANE1/2" GYPSUM SHEATHING
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
J-CHANNEL TRIMBACKER ROD & SEALANT
NOM. 2X8 WD FRAMING @ 24"O.C.
5/8" GWB, PTD
R-20 BATT INSULATION
STOREFRONT WINDOW (CAULKFRAME TO AIR BARRIER)
5 3/
4"
1
1/2"
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
AIR BARRIER MEMBRANE
1/2" GYPSUM SHEATHING
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
HORIZONTAL TRIM
R-20 BATT INSULATIONNOM. 2X8 WD FRAMING @ 24"O.C.
5/8" GWB, PTD
2ND FLOOR11'-8"
A.5
___________________2
A411
NOM. 2X8 WD FRAMING @ 24"O.C.
AIR BARRIER MEMBRANE
4'-1"
42" M
IN. (
VERI
FY)
4"
1/8" / 1'-0"2"
TPO MEMBRANE
TPO MEMBRANE
TPO MEMBRANE
1'-1 3/4"
10 3/4" 6'-6" 1'-7 1/4"
GUTTER2"
2" DIA. RAIN LEADER BEYONG
3/4"BENT ALUMINUM PLATE,
POWDERCOATED WITH MATCHING EXPOSED FASTENERS
3"
FORMED METAL GUTTER, SLOPE TO DOWNSPOUT
FIBER CEMENT SOFFIT (HORIZONTAL SIDING)
3/4" PT PLYWOOD DECK
STEEL BEAM, SEE STRUCT. -COORD. HOLE(S) REQ'D TO RUN ELECTRICAL W/ ARCH.
1/2" PT PLYWOOD
FIBER CEMENT HORIZONTALSIDING
PARAPET COPING
2X4 PT WOOD FASTENED TO ONE SIDE OF EACH 2X10 JOIST TO FORM SLOPE
FIBER CEMENT BOARD TRIM AT STOREFRONT PERIMETER
STOREFRONT HEAD (CAULKFRAME TO AIR BARRIER)
STEEL BEAM (PTD), SEESTRUCT.
STEEL BEAMS (SEE STRUCT.) WITH 2X10 PT WOOD FRAMING INFILL
+10'-8"
BASE FLASHINGROOF FLASHING OVER GUTTER
BUILDING SIGNAGE T.B.D.
LL-01 LIGHT FIXTURE - COORD. LOCATION W/ ARCHITECT
AIR BARRIER MEMBRANE
SEALANT
STEEL CHANNEL SUPPORTS (SEE STRUCT.)
1'-0"
PT WD BLOCKING AS REQ'D
5/8" GWB, PTD3 1/
2"
TPO ROOF-TO-WALLEXPANSION JT.
RECESSED DOWNLIGHT (SEE RCP)
2ND FLOOR11'-8"
2
PT WD BLOCKING AS REQ'D
5/8" GWB, PTD
STEEL BEAM (PTD), SEESTRUCT.
ROOF TRUSS
NOM. 2X8 WD FRAMING @ 24"O.C.
BATT INSULATION
BATT INSULATION
___________________2
A411
ROOF ASSEMBLY 2
SEE INTERIOR PARTITION TYPE MARK
GWB EXPANSION JT
___________________3
A601SIM.
___________________7
A601
DEFLECTION TRACK:
A.5
NOM. 2X8 WD FRAMING @ 24"O.C.
5/8" GWB, PTD
1/2" GYPSUM SHEATHING
AIR BARRIER MEMBRANE
FIBER CEMENT HORIZONTALSIDING
R-20 BATT INSULATION
SILL FLASHING (SLOPE TOP) -FORM AROUND CONT. CLEATAND EXTEND BLW WDW;PROVIDE CONCEALED SPLICEPLATES AT JOINTS
ACM EXPOSED FASTENERSYSTEM
FLASHING TAPE
GWB RETURN, PROVIDE CONT. SEALANT AT JOINT
5/8" GWB, PTD
STOREFRONT WINDOW (CAULKFRAME TO AIR BARRIER)
EXTRUDED ALUMINUM FURRING, BY ACM MANUFACTURER
ACM EXPOSED FASTENERSYSTEM
1/2" GYPSUM SHEATHING
AIR BARRIER, TURN INTO OPENING
BACKER ROD & SEALANT
C
1
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL5/8" GWB, PTD
NOM. 2X8 WD FRAMING @ 24"O.C.
STEEL TUBE COLUMN (PTD),SEE STUCT.
R-20 BATT INSULATION
VERTICAL TRIM
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
C
2
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL5/8" GWB, PTD
NOM. 2X6 WD FRAMING @ 16"O.C.
STEEL TUBE COLUMN (PTD),SEE STUCT.
BATT INSULATION
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL
Z-SHAPE ALUM. TRIM W/ 3/4"REVEAL
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1 1/2" = 1'-0"
A402
EXTERIOR DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A402 1 1/2" = 1'-0"1 DETAIL PLAN @ EAST CURTAINWALL
A402 1 1/2" = 1'-0"2 DETAIL PLAN @ CORNER (2)
A402 1 1/2" = 1'-0"3 DETAIL PLAN @ CORNER (1)
A402 1 1/2" = 1'-0"5 DETAIL PLAN @ VERTICAL FIBER CEMENT BOARD JT.
A402 1 1/2" = 1'-0"6 DETAIL PLAN @ WINDOW JAMB
A402 1 1/2" = 1'-0"7 DETAIL SECTION @ HORIZONTAL FIBER CEMENT BOARD JT.
A402 1 1/2" = 1'-0"11 DETAIL SECTION @ ENTRY CANOPY/PARAPET
A402 1 1/2" = 1'-0"8 DETAIL SECTION @ LOW ROOF
A402 1 1/2" = 1'-0"10 DETAIL SECTION @ HORIZONTAL SIDING TO ACM
A402 1 1/2" = 1'-0"4 PLAN DETAIL - EXT. STOREFRONT JAMB
A ISSUED FOR BID 12/28/2018
A402 1 1/2" = 1'-0"9 DETAIL PLAN @ TUBE STEEL
A402 1 1/2" = 1'-0"12 DETAIL PLAN @ TENANT SEPARATION WALL
2ND FLOOR11'-8"
1.2 1.81.4 1.6
16" HIGH, INDIVIDUALLY CUT STAINLESS STEEL LETTERS; FONT: FUTURA MD BT; DEPTH AND ATTACHMENT METHOD TO BE VERIFIED BY FABRICATORTENANT 1 SIGN: "CELLULAR TRACKING TECHNOLOGIES"TENANT 3 SIGN: T.B.D.TENANT 5 SIGN: T.B.D.
± 31'-8 3/4"
EQEQ
SIGN
ACM PANEL SPANDREL -SEE DETAIL
2A404
_________
EQEQ
1'-4"
2ND FLOOR11'-8"
A1'-0 1/4"
2'-0"
EQ1'-
4"EQ
ACM PANELS ON VERTICAL ALUM. FURRING
RIGID INSULATION
BUILDING SIGNAGE - SEE DETAIL ELEVATION
CURTAINWALL SILL
CURTAINWALL HEAD
FLASHING
AIR BARRIER MEMBRANE
1/2" GYPSUM SHEATHING
2X6 WOOD FRAMING
2ND FLOOR11'-8"
2.6
1'-11
"
23" HIGH, INDIVIDUALLY CUT SHOP-PAINTED ALUMINUM LETTERS; FONT: FRANKLIN GOTHIC BOOK; DEPTH AND ATTACHMENT METHOD TO BE VERIFIED BY FABRICATOR
23" HIGH, INDIVIDUALLY CUT SHOP-PAINTED ALUMINUM NUMBERS; FONT: FRANKLIN GOTHIC HEAVY; DEPTH AND ATTACHMENT METHOD TO BE VERIFIED BY FABRICATOR
± 24'-5 1/2"
4A404
_________
2ND FLOOR11'-8"
TPO ROOF MEMBRANE
10 3/4"
BENT ALUMINUM PLATE, POWDERCOATED WITH MATCHING EXPOSED FASTENERS
FORMED METAL GUTTER, SLOPE TO DOWNSPOUT
FIBER CEMENT SOFFIT (HORIZONTAL SIDING)
3/4" PT PLYWOOD
1/2" PT PLYWOOD
ROOF FLASHING OVER GUTTER
BUILDING SIGNAGE - SEE DETAIL ELEVATION
1'-0"
PT WD BLOCKING AS REQ'D
1'-11
"
5"
___________________8
A404
8"
± 9'-9 3/4"
8" HIGH, INDIVIDUALLY CUT SHOP-PAINTED ALUMINUM LETTERS; FONT: FRANKLIN GOTHIC BOOK; DEPTH AND ATTACHMENT METHOD TO BE VERIFIED BY FABRICATORTENANT 2 SIGN: T.B.D.TENANT 4 SIGN: T.B.D.
6A404
_________
6"
STEEL BEAM, SEE STRUCT.
FIBER CEMENT BOARD TRIM AT STOREFRONT PERIMETER
STOREFRONT HEAD (CAULKFRAME TO AIR BARRIER)
AIR BARRIER MEMBRANE 5/8" GWB, PTD
SIGNAGE
1ST FLOOR0"
EQEQ
5'-8"
SIGNAGE PLAQUE WITH STANDOFFS. MATERIAL, CONTENT AND SIZE T.B.D. (2 SF MAX)
2ND FLOOR11'-8"
ALUMINUM SIGNAGE LETTERSLINEAR LED LIGHT (SEE LIGHTING SCHEDULE)PTD ALUM. MOUNTING CHANNEL (CONTINUOUS) W/ DRAINAGE HOLES
PTD. ALUM. BRACKETS @ 24" O.C. - SEAL TO ROOFING MEMBRANE
*DETAIL MEANT TO CONVEY INTENT AND IS SUBJECT TO CHANGE UPON COORDINATION WITH SIGNAGE FABRICATOR*
ROOFING MEMBRANE OVER PLYWOOD
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
12/27/2018 3:12:33 PM\\stokes.local\Data\Cape May Airport\TECH BUILDING\DRAWINGS\REVIT\1729_TechBuilding_current.rvt
A404
SIGNAGE
AuthorChecker12/20/18
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A404 1/2" = 1'-0"1 DETAIL ELEVATION @ TENANT 1 / 3 / 5 SIGNAGE
A404 1 1/2" = 1'-0"2 DETAIL SECTION @ TENANT 1 SIGNAGE
A404 1/2" = 1'-0"3 DETAIL ELEVATION @ CANOPY SIGNAGE (TYP. OF 2)
A404 1 1/2" = 1'-0"4 DETAIL SECTION @ CANOPY SIGNAGE
A404 1/2" = 1'-0"5 DETAIL ELEVATION @ TENANT 2 / 4 SIGNAGE
A404 1 1/2" = 1'-0"6 SECTION DETAIL @ TENANT 2 /4 SIGNAGE
A404 1/2" = 1'-0"7 DETAIL ELEVATION @ PLAQUE SIGNAGE (TYP. OF 4)
A404 3" = 1'-0"8 DETAIL SECTION @ CANOPY SIGNAGE CHANNEL
EQEQ
EQ
GALVANIZED STEEL OSHA-COMPLIANT HANDRAIL, BOTH SIDES OF STAIR
11" 11"11"
3'-0"
PRECAST CONCRETE ROOF PAVER (ROOF ASSEMBLY 3)
1'-0"
PT WOOD BLOCKING @ STAIR SUPPORTS AS REQ'D
FLASH AT ALL PENETRATIONS/ CONNECTIONS PER ROOF MANUF'S RECOMMENDATIONS
1 1/2" DIA. GALVANIZED STEEL PIPE, TYP.
OPEN, GALVANIZED STEEL GRATE TREADS, TYP.
ADJUSTABLE PAVER PEDESTAL
ROOF ASSEMBLY 2
TPO MEMBRANE
1/2" GYPSUM SHEATHINGMEMBRANE BONDING ADHESIVE
COMPRESSIBLE TUBE
WELDED SPLICE
COMPRESSIBLE INSULATION W/ INSULATION RETAINER
TPO MEMBRANE
(PARAPET WALL)
FASTENERS PER MFR'S STANDARD DTLS
___________________1
A411
4'-1 1/4"
FIXED SKYLIGHT W/ INSULATEDGLASS
GWB (PTD)
EQ
EQ
1/2" GYPSUM SHEATHING
TPO ROOF MEMBRANE (EXTEND OVER T.O. CURB)
PT WOOD BLOCKING
ROOF ASSEMBLY 1
5/4" X 6" SOLID WOOD TRIM
WOOD PURLIN
EXPOSED WOOD DECKING
GWB Z REVEAL
5/8" GWB, PTD
± 7"
CRICKET ROOF THIS SIDE ONLY
± 1'-
0 1/
2"
GWB Z REVEAL
2X12 PT WOOD CURB
FIXED SKYLIGHT W/ INSULATEDGLASS
1/2" GYPSUM SHEATHING
2X12 PT WOOD CURB
PT WOOD BLOCKING
ROOF ASSEMBLY 1
5/4" X 6" SOLID WOOD TRIM
GWB Z REVEAL
5/8" GWB, PTD
EXPOSED WOOD DECKING
CRICKET ROOF THIS SIDE ONLY
TPO ROOF MEMBRANE (EXTEND OVER T.O. CURB)
'L' CASING BEAD
SEALANT
E
3'-6"
1'-6"
PRECAST CONCRETE ROOF PAVER (ROOF ASSEMBLY 3)
OSHA-COMPLIANT GALVANIZED STEEL GUARDRAIL
1 1/2" GAVANIZED STL PIPE POSTS @ 4'-0" O.C.
1 1/2" GALVANIZED STL PIPE RAILS
4"
TPO MEMBRANE
STEEL ANGLE CONNECTION BETWEEN PARAPET AND POSTS(FLASH AROUND ANGLE PER ROOFING MANUF'S RECOMMENDATIONS)
PARAPET WALL W/ STEEL REINFORCEMENT (SEE STRUCT.)
2ND FLOOR11'-8"
A.5
3 1/
2"6"
3 1/
2"
3 1/2" 1'-0" 3 1/2"
ALLOWABLE HEAD OF WATER -5" ABOVE ROOF LOW POINT
2 1/
4"
1/2" GYPSUM SHEATHING
TPO BONDING ADHESIVETPO MEMBRANECONT. SEALANT, TYP.
TPO FLASHING OVER SCUPPER FLANGE
SCUPPER FASTENERS @ 4" O.C.
WELDED METAL SCUPPER SLEEVE
FIBER CEMENT BOARD TRIM
5" TPO FLASHING OVER SCUPPER FLANGE
9" TPO FLASHING OVER 5" FLASHING
PARAPET WALL
3 1/
2"6"
3 1/
2"
TPO MEMBRANE
7/16" FIBER CEMENT BD W/EXPOSED FASTENERS
NOM. 1X4 P.T. WD FURRING W/MEMBRANE
AIR BARRIER MEMBRANE
1/2" GYPSUM SHEATHING
EXTEND AIR BARRIER BEHIND COUNTERFLASHING
METAL COUNTERFLASHING W/3" FACE AND DRIP EDGE
TPO BONDING ADHESIVE
CONT. SEALANT
1" M
IN.
FASTENERS 8" O.C.
COUNTERFLASHING
MEMBRANE ROOF FLASHING PER MFR'S STANDARD DETAILS
BASE OF UNIT EXTENDS 1/2" MIN. BEYOND AND DOWN OVER TOP CURB
SEALING MATERIAL - MUST BE CONTINUOUS ON THE
PERIMETER
WOOD NAILER
FLASHING RECEIVER
8" M
IN.
UNIT MOUNTING CURB CANT - FASTENED TO NAILER
INSULATION
TPO MEMBRANE
COMPRESSION RINGSTRAINER BASKET
SUBSTRATE
12" 1" MAX.
CONTINUOUS BEAD OFWATERBLOCK
BONDING ADHESIVE (ADHERED SYSTEM ONLY)
2X WOOD NAILER, TYP.
PRE-FINISHED METAL COPING CAP. COLOR TO MATCH ADJACENT FINISH.
SLOPE
CONTINIOUS 22 GA. CLEAT
ROOF MEMBRANE, LAP UP AND OVER PARAPET WALL
WALL
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A411
ROOF DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A411 1 1/2" = 1'-0"4 DETAIL SECTION @ ROOF STAIRS
A411 3" = 1'-0"2 SECTION DETAIL @ ROOF EXP. JT.
A411 1 1/2" = 1'-0"3 DETAIL SECTION @ SKYLIGHT
A411 3" = 1'-0"1 SECTION DETAIL @ SKYLIGHT CURB
A411 1 1/2" = 1'-0"5 SECTION DETAIL @ ROOF GUARDRAIL
A411 1 1/2" = 1'-0"9 SECTION DETIAL @ OVERFLOW SCUPPER
A411 3" = 1'-0"7 DETAIL SECTION @ FIBER CEMENT TO ROOFING TRANSITION
A ISSUED FOR BID 12/28/2018
A411 3" = 1'-0"10 DETAIL @ MECHANICAL CURB
A411 3" = 1'-0"6 TYP. ROOF DRAIN DETAIL
A411 3" = 1'-0"8 TPO CAP FLASHING
D
2
3'-4"
12 R
ISER
S @
7" 1
1 TR
EADS
@ 1
1"
10'-1
"11
"3'-
8"
3'-8" 8" 3'-8"
2A501
_________ 3A501
_________
A501
6
4A501
_________
4'-7"
8 RI
SERS
@ 7
" 7
TREA
DS @
11"
6'-5"
C
D
3
A501
11
10A501
_________
2'-3"
20 R
ISER
S @
7"
19 T
READ
S @
11"
17'-9
"
4'-0"
1ST FLOOR0"
2ND FLOOR11'-8"
D
EQ
EQ
EQ
EQ1EQ1
STEEL TUBE AND PLYWOOD PANEL GUARDRAIL; SEE DTL
STEEL STAIR STRINGER
3'-6"11
'-8"
3'-6"
7'-0"
METAL PAN STAIR
___________________5
A501
12A501
_________
PARTITION (SEE PLAN)
PTD GWB
THICKENED SLAB, SEE STRUCT.
1ST FLOOR0"
2ND FLOOR11'-8"
D
EQ
EQ
EQ
4'-8"
7'-0"
___________________5
A501
1-116IT CLOSET
3'-6"STEEL TUBE AND PLYWOOD
PANEL GUARDRAIL; SEE DTL
STEEL TUBE SUPPORT
PARTITION (SEE PLAN)
12A501
_________
6'-8"
MIN
. HEA
D HE
IGHT
D
EQ
4'-8"
7'-0"
EQ
4'-0"
1-116IT CLOSET
STEEL TUBE AND PLYWOOD PANEL GUARDRAIL; SEE DTL
12A501
_________
D
STEEL TUBE SUPPORT
WALL-MOUNTED HANDRAIL
4'-8"
7'-0"
11"
1'-0"
PARTITION (SEE PLAN)
3'-6"
1-116IT CLOSET
7A501
_________
3'-0"
1ST FLOOR0"
2ND FLOOR11'-8"
C D
EQ
EQ
EQ
EQ
EQ
EQ
METAL PAN STAIR
STEEL TUBE AND PLYWOOD PANEL GUARDRAIL; SEE DTL
12A501
_________
11'-8
"
___________________5
A501
2'-3"
6'-8"
± 6'-9" ± 4'-5 3/4"
POST-MOUNTED RAILING BELOW STAIRS PER ADA (1 1/2" X 1 1/2" PTD STEEL TUBES)
THICKENED SLAB, SEE STRUCT.
1ST FLOOR0"
2ND FLOOR11'-8"
C D
WALL-MOUNTED HANDRAIL
3'-0"
7A501
_________
1'-0"
11"
A.F.
F.
3'-6"
STEEL HANDRAIL BRACKET (PTD)
1 1/2" DIA. STEEL TUBE HANDRAIL (PTD)
A.F.
F.
2'-10
"
STEEL STRINGER (PTD)
METAL PAN STAIR W/ RUBBER TREADS
2"2"
1 1/2" SQ. TUBE POSTS (PTD)
3/4" PLYWOOD PANEL(BALTIC BIRCH VENEER W/ CLEAR FINISH BOTH SIDES)
1 1/2" SQ. TUBE TOP RAIL (PTD)
CLR1 1/2"
STEEL WALL-MOUNTED HANDRAIL BRACKET (PTD)
1 1/2" DIA. STEEL TUBE HANDRAIL (PTD)
2ND FLOOR11'-8"
3'-6"
(5'-0" MAX)
SPACE EVENLY
2"3'-
0 1/
2"2"0"
2" 3'-6 1/2" 2"
2"
1 1/2" SQ TUBE TOP RAIL (PTD)
3/4" PLYWOOD PANEL(BALTIC BIRCH VENEER W/ CLEAR FINISH BOTH SIDES)
1 1/2" SQ. TUBE POSTS (PTD)
STEEL U-CLIP, TYP. (PTD)
STEEL ANGLE CONNECTION TO BEAM AND POSTS (PTD)ST
EEL
BEAM
1'-2"
6"
2ND FLOOR11'-8"
D
1'-2"
1 1/
2"2"
3'-0
3/4"
2"
A.F.
F.
3'-6"
3"1/2"
STEEL ANGLE CONNECTION BETWEEN BEAM AND POSTS (PTD)
1 1/2" SQ. TUBE POSTS (PTD)
3/4" PLYWOOD PANEL(BALTIC BIRCH VENEER W/ CLEAR FINISH BOTH SIDES)
1 1/2" SQ. TUBE TOP RAIL (PTD)
FINISH FLOOR
SOLID WOOD FASCIA TO MATCH DECKING
STEEL BEAM (PTD)
WD DECKING
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A501
STAIR PLANS, SECTIONS& DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A501 1/4" = 1'-0"1 STAIR PLAN - TENANT #1
A501 1/4" = 1'-0"9 STAIR PLAN - TENANTS #3 & #5
A501 1/4" = 1'-0"6 TENANT #1 STAIR ELEVATION 1
A501 1/4" = 1'-0"2 TENANT #1 STAIR SECTION 1
A501 1/4" = 1'-0"3 TENANT #1 STAIR SECTION 2
A501 1/4" = 1'-0"4 TENANT #1 STAIR SECTION 3
A501 1/4" = 1'-0"11 TENANTS #3 & #5 STAIR ELEVATION 1
A501 1/4" = 1'-0"10 TENANT #5 STAIR SECTION 1
A ISSUED FOR BID 12/28/2018
A501 1 1/2" = 1'-0"12 DETAIL SECTION @ STAIR HANDRAIL
A501 1 1/2" = 1'-0"7 SECTION DETAIL @ WALL-MTD HANDRAIL
A501 3/4" = 1'-0"8 ELEVATION DETAIL @ GUARDRAIL
A501 1 1/2" = 1'-0"5 DETAIL SECTION @ GUARDRAIL
E
1.8
A5032
A503
3
1-115KITCHEN1E
1E
1E
6'-3"
9'-7"
4'-6"
3'-0"
2'-6"
SINK CABINET
2'-6" 1'-0"
3'-0"
6'-3"
PLAM BASE CABINETS
SOLID SURFACE COUNTERTOP AND BACKSPLASH W/ UNDERMOUNT SINK
1" BALTIC BIRCH PWD. SHELF W/ HEAVY DUTY BRACKETS
EQ.EQ.
FILLER STRIP
1'-6"
1'-0"
5'-8"
3'-0"
1'-6"
3'-0"
3'-6"
EQ.
EQ. 2'-6"EQ.
3'-6" EQ.
PLAM BASE CABINETS
SOLID SURFACE COUNTERTOP AND BACKSPLASH
PLAM UPPER CABINETS
FILLER STRIP, TYP.
REF. (N.I.C.)
1'-6"
GWB SOFFIT (WA-01)
CLR.
2'-8"
3
2-106J.C.
2-101TENANT #2
A503
5
2'-6"
3'-6"
2-10
6-1
6'-0" 2'-8"
1A
3'-0"
CLR.
2'-8"
SINK CABINET
3'-0" 3'-0"
REF. (N.I.C.)
2-106-1
PLAM BASE CABINETS
SOLID SURFACE COUNTERTOP AND
BACKSPLASH W/ UNDERMOUNT SINK
1" BALTIC BIRCH PWD. SHELF W/ HEAVY DUTY BRACKETS
1'-6"
1'-0"
5'-8"
n
3
3-101TENANT #3
A503
7
2'-8"
8'-9"
REF. (N.I.C.)
1" SINK CABINET
3'-0" 3'-0"
CLR.
2'-8"
3'-0"
1'-6"
1'-0"
PLAM BASE CABINETS
SOLID SURFACE COUNTERTOP AND
BACKSPLASH W/ UNDERMOUNT SINK
1" BALTIC BIRCH PWD. SHELF W/ HEAVY DUTY BRACKETS
7'-0"
2'-0"W-1
FILLER STRIP
5'-8"
GWB SOFFIT
1" SINK CABINET
2'-6 1/4" 2'-6"
CLR.
2'-8"
7'-0"
2'-0"
REF. (N.I.C.)
PLAM BASE CABINETS
SOLID SURFACE COUNTERTOP AND
BACKSPLASH W/ UNDERMOUNT SINK
1" BALTIC BIRCH PWD. SHELF W/ HEAVY DUTY BRACKETS
FILLER STRIP
4'-8"
W-1
GWB SOFFIT
E
5
A503
9
5-101TENANT #5
7'-9
1/4"
2'-8"ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR.
THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3/8" = 1'-0"
A503
KITCHENETTE PLANSELEVATIONS AND DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A503 3/8" = 1'-0"1 1-115 TENANT #1 KITCHENETTE PLAN
A503 3/8" = 1'-0"3 1-115 TENANT #1 KITCHENETTE ELEVATION NORTH
A503 3/8" = 1'-0"2 1-115 TENANT # 1 KITCHENETTE ELEVATION SOUTH
A503 3/8" = 1'-0"4 2-101 TENANT #2 KITCHENETTE PLAN
A503 3/8" = 1'-0"5 2-101 TENANT #2 KITCHENETTE ELEVATION
A503 3/8" = 1'-0"6 3-101 TENANT #3 KITCHENETTE PLAN
A503 3/8" = 1'-0"7 3-101 TENANT #3 KITCHENETTE ELEVATION
A503 3/8" = 1'-0"9 5-501 TENANT #5 KITCHENETTE ELEVATION
A503 3/8" = 1'-0"8 5-101 TENANT #5 KITCHENETTE PLAN
A ISSUED FOR BID 12/28/2018
D
E
2 2.6
3A301
_________
3
6 1/2" 8'-0"
1-104-1
1-10
2-1
1-10
3-1
5'-2"
3'-1"
8'-7
3/8"
8'-8"
8'-8"
8'-8"
3'-5
3/8"
5'-1"
5'-1
3/8"
2-10
2-1
2-10
3-1
3'-2"
3-10
3-1
3-104-1
3-10
2-1
2-10
4-1
2-10
6-1
2-10
5-1
3-101-2
2-10
4-2
1-101-2
8'-8"
1-102WOMENS
1-104J.C.
1-103MENS
2-102WC
2-103WC
2-104CORRIDOR
3-102WOMENS
3-103MENS
2-105MECHANICAL CLOSET
2-101TENANT #2
1-101TENANT #1
A512
7
A5126
A512
8
A51210
A512
12
A512
11
A512
4
A512
1
A512
3
A5122
A512
9
1C
1C
1C
1C
1C
1C
1D
1D
1C
1E
1D1D1D
1A
1C
2B
1D1D
1C
4" TYP.
1'-11"
1'-1"
± 6'-
9 1/
2"
8'-0" 1'-4"
16'-8 1/2" ± 5'-5 1/2" 17'-3"
± 6'-
7 1/
4"
4'-3 1/4"
2B
2B
1'-4"
1'-4"
5'-4"
6'-0"
5'-0"
3-104J.C. ±
5'-7
1/4"
1'-11"
9"1'-
4"
MOP SINK (SEE PLUMBING FIXTURE SCHEDULE)
D
E
4 4.4 5
6A302
_________
4-10
2-1
4-10
3-1
4-10
4-1
5-10
2-1
5-104-1
4-10
4-2
4-10
5-1 5-101-2
5'-0"± 3'-
6"
1'-1"
4-102WC
4-103WC
4-105MECHANICAL CLOSET
4-104CORRIDOR
3-101TENANT #3
4-101TENANT #4
5-102WOMENS
5-103MENS
5-101TENANT #51C
1C
1E1D
1D
1C
1D1D
2B
1B
1C
8'-3" 8'-3"
16'-10 3/4" 16'-4"± 6'-2 1/4"
6'-8"
± 11
'-0"
5-10
3-1
± 8'-
10"
8'-10
"
7'-2"
5'-1
1/4"
± 5'-
0"±
1'-3"
8'-0"
3 1/
4"
4'-4"
4-10
6-1
MOP SINK (SEE PLUMBING FIXTURE SCHEDULE)
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1/4" = 1'-0"
A511
ENLARGED TOILET ROOMPLANS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A511 1/4" = 1'-0"3 ENLARGED PLAN @ TENANT 1-3 TOILET ROOMS
A511 1/4" = 1'-0"1 ENLARGED PLAN @ TENANT 4 & 5 TOILET ROOMS
A ISSUED FOR BID 12/28/2018
B-2
PT-A
PT-B
ab
eB-2
PT-B
PT-A
b
kPT-B
PT-A
B-2
1-103-1
d
e
fh
g
EQ. AEQ. A
EQ. B
EQ. B
c
EQ. C EQ. C
bb
B-2
W-2
W-2
PT-A
PT-B
m
WALL SCONCE, SEE LIGHTING SCHEDULE, TYP. OF (3)
j a b
eB-2
PT-B
m
PT-A
k
B-2PT-B
PT-A
1-103-1
d
g
e e
h
j
c c
EQ. A EQ. A
EQ. B
EQ. B
EQ. C EQ. C
W-2
JUNC
TIO
N BO
X CL
.
7'-0"
TO
LIG
HT F
IXTU
RE
W-2
WALL SCONCE, SEE LIGHTING SCHEDULE, TYP. OF (3)
PT-B
W-1
B-2
m
aj
EQ. B
EQ. B
W-2
PT-B
PT-A
B-2
g
h
d
PT-B
PT-A
B-2e
b
g
b
PT-B
?
B-2
k
2-102-1
PT-B
PT-A
B-2
a
bb
e
PT-B
PT-A
B-2
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3/8" = 1'-0"
A512
RESTROOM ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A512 3/8" = 1'-0"9 1-103 - MENS WC - WEST
A512 3/8" = 1'-0"11 1-103 - MENS WC- EAST
A512 3/8" = 1'-0"10 1-103 MENS WC- SOUTH
A512 3/8" = 1'-0"12 1-103 MENS WC - NORTH
A512 3/8" = 1'-0"7 1-102 - WOMENS - EAST
A512 3/8" = 1'-0"8 1-102 WOMENS - NORTH
A512 3/8" = 1'-0"6 1-102 WOMENS - SOUTH
A512 3/8" = 1'-0"5 1-102 - WOMENS - WEST
TAG DESCRIPTION MANUFACTURER MODEL REMARKS
a TOILET TISSUE DISPENSER BOBRICK SURFACE MOUNTED TWIN JUMBO-ROLL B-2892b GRAB BARS BOBRICK 1/4" SS. GRAB BAR W/ SNAP FLANGEc SEAT COVER DISPENSER BOBRICK CLASSIC SERIES SURFACE MOUNT B-221CRd MIRROR BOBRICK CHANNEL FRAME B-165-2436e FLOOR-MOUNTED TOILET AMERICAN STANDARD MADERA ECO POWER TOILET FLUSH VALVE, 1.5 GPF, CHROMEEXTERIOR WALLASSEMBLY 4Af URINAL AMERICAN STANDARD PINTBROOK FLUSH VALVE: TOTO ECO POWER ULTRA HIGH
EFFICENCY URINAL FLUSH VALVE 0.125 GPF, CHROMEg WALL MOUNTED SINK KOHLER SOHO 20C18 K-2084 FAUCET: KOHLER K97283-4-CPh SOAP DISPENSER BOBRICK CLASSIC SERIES SURFACE MUNT B-2111j SANITARY RECEPTACLE BOBRICK CLASSIC SERIES SURFACE MOUNT B-254k PAPER TOWEL + TRASH COMBO BOBRICK CLASSIC SERIES SEMI RECESSED B-3942m TOILET / URINAL PARTITIONS AMERICAN SPECALTIES INC SOLID PLASTIC FLOOR MOUNT PARTITIONS COLOR TBS.n KITCHENETTE SINK (17" X 17") AMERICAN STANDARD 18SB.8171700.075 FAUCET: AMERICAN STANDARD 7074.010.002o MOP SINK FIAT MSB2424
A512 3/8" = 1'-0"3 2-102 WC - EAST
A512 3/8" = 1'-0"4 2-102 WC - NORTH
A512 3/8" = 1'-0"2 2-102 WC - SOUTH
A512 3/8" = 1'-0"1 2-102 WC - WEST
reStroom plumbing fixture & accessory schedule
PRODUCTS INDICATED ARE THE BASIS OF DESIGN. SUBJECT TO COMPLIANCE WITH THE REQUIREMENTS, PROVIDE SPECIFIED PRODUCTS OR APPROVED EQUAL.
A ISSUED FOR BID 12/28/2018
CONSTRUCTION
PARTITION TYPES SCHEDULE
TYPE REMARKS
1A
1B
2A
5/8" GYPSUM WALL BOARD [W-1]
5/8" GYPSUM WALL BOARD [W-1]
2X6 WOOD STUDS@ 16" O.C. MAX.
ACOUSTICAL BATT INSULATION AS SCHEDULED
5/8" GYPSUM WALL BOARD [W-1]
5/8" GYPSUM WALL BOARD [W-1]
2X4 WOOD STUDS@ 16" O.C. MAX.
ACOUSTICAL BATT INSULATION AS SCHEDULED
TYPE 1A: UNCONNECTED WALL HEIGHT 9'-0" A.F.F.
TYPE 1B: FULL HEIGHT WALL ATTACHED TO STRUCTURE ABOVE
TYPE 1C: FULL HEIGHT WALL ATTACHED TO STRUCTURE ABOVE, PROVIDE ACOUSTICAL BATT INSULATION1C
TYPE 2A: FULL HEIGHT WALL ATTACHED TO STRUCTURE ABOVE
2B TYPE 2B: FULL HEIGHT WALL ATTACHED TO STRUCTURE ABOVE, PROVIDE ACOUSTICAL BATT INSULATION AND ACOUSTICAL SEALANT WHERE GWB TERMINATES AT SLAB, STEEL OR PENETRATION, TYP. SEE BASE DETAIL.SEE SPECIFICATION SECTION GYPSUM WALL BOARD "SOUND CONTROL PARTITIONS". FOLLOW SPECIFICATIONS.
3A
5/8" GYPSUM WALL BOARD [W-1]
2X4 WOOD STUDS@ 16" O.C. MAX.
TYPE 3A:@ EXPOSED CEILINGS: FULL HEIGHT WALL ATTACHED TO STRUCTURE ABOVE@ CEILING: EXTEND TO 6" ABOVE CEILING(UNFINISHED SIDE)
(FINISHED SIDE)
1D TYPE 1D: FULL HEIGHT WALL - RUN FRAMING TO STRUCTURE ABOVE, GWB TO EXTEND 6" ABOVE FINISHED CEILING,PROVIDE ACOUSTICAL BATT INSULATION
1E TYPE 1E: FULL HEIGHT WALL - RUN FRAMING TO STRUCTURE ABOVE, GWB TO EXTEND 6" ABOVE FINISHED CEILING (WHERE PRESENT) OR TO UNDERSIDE OF STRUCTURE @ EXPOSED CEILING
5/8" 3 1/2" 5/8"
DOUBLE TOP PLATE
BOTTOM CHORD OF OPEN WEB WOOD
JOISTS, BEYOND
J-BEAD
SEE PARTITION TYPE SCHEDULE
5/8" GWB, TYP.
2X4 WD. FRAMING
1/2"
SEALANT
SIMPSON STRONG TIE ROOF TRUSS CLIP AT EACH OPEN WEB JOIST
3/4" WOOD WALL CAP, PAINTED
J-BEADSEALANT
DEFLECTION TRACK:16ga 3 5/8" METAL TRACK W/ 2" LEG FASTENED TO WOOD DECKING
DOUBLE TOP PLATE
STRUCTURAL WOOD DECKING,
EXPOSED
DO NOT FASTEN DRYWALL TO DEFLECTION TRACK
J-BEAD SEALANT JOINT
J-BEAD
SEE PARTITION TYPE SCHEDULE
SEALANT JOINT
5/8" 3 1/2" 5/8"
5/8" GWB, TYP.
2X4 WD. FRAMING
PLYWOOD SHIM AS REQUIRED TO PROVIDE SNUG FIT WITHIN SLIP TRACK
DEFLECTION TRACK:16ga 6" METAL TRACK W/ 2" LEG FASTENED TO STEEL BEAM
5/8" GWB, TYP.DOUBLE
TOP PLATE
STEEL BEAM, SEE STRUC.
DO NOT FASTEN DRYWALL TO DEFLECTION TRACK
J-BEAD
SEALANT JOINT
J-BEAD
SEE PARTITION TYPE SCHEDULE 5/8" 5 1/2" 5/8"
2X6 WD. FRAMING
PLYWOOD SHIM AS REQUIRED TO PROVIDE SNUG FIT WITHIN SLIP TRACK
DEFLECTION TRACK:16ga 6" METAL TRACK W/ 2" LEG FASTENED TO WOOD DECKING
5/8" GWB, TYP.
DOUBLE TOP PLATE
STRUCTURAL WOOD DECKING,
EXPOSED
DO NOT FASTEN DRYWALL TO DEFLECTION TRACK
J-BEAD
SEALANT JOINT
J-BEADSEE PARTITION
TYPE SCHEDULE
SEALANT JOINT
5/8" 5 1/2" 5/8"2X6 WD. FRAMING
1. REFER TO REFLECTED CEILING PLANS AND/OR FINISH SCHEDULE FOR INFORMATION ON CEILING TYPE, FINISH AND HEIGHTS. COORDINATE REQUIREMENTS FOR CEILING BLOCKING REQUIREMENTS COMPROMISE THE FIRE RATING SPECIFIED FOR ANY ASSEMBLY.
2. REFER TO INTERIOR ELEVATIONS AND/OR FINISH SCHEDULE FOR INFORMATION ON WALL FINISHES, BASE TRIM, MOLDINGS, ETC.
3. PROVIDE INTERIOR TRIM BEADS AT EXPOSED EDGES OF GYPSUM BOARD. PROVIDE INTERIOR TRIM BEADS AT BOUNDARIES OF GYPSUM BOARD AREAS ABUTTING DISSIMILAR MATERIALS SUCH AS BUT NOT LIMITED TO WOOD ROOF DECKING ELEMENTS, WOOD FLOOR DECKING ELEMENTS, STEEL COLUMNS, STEEL BEAMS/GIRDERS, WINDOW FRAMES, WINDOW SILLS, DOOR FRAMES AND WHERE INDICATED.
4. ALL PARTITIONS SHALL BE SECURELY FASTENED ABOVE AND BELOW TO THE STRUCTURAL SLAB OR STRUCTURAL FLOOR FRAMING.
5. ROCKWOOL BATT INSULATION SHALL BE PROVIDED AT INTERSECTIONS OF ALL CONCEALED HORIZONTAL AND VERTICAL SPACES, AS WELL AS ALL OTHER AREAS AS DEFINED IN THE CODE.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE METHOD AND SPACING OF SCREW ATTACHMENT OF GYPSUM WALL BOARD TO STRUCTURAL STUDS TO MEET ALL REQUIREMENTS OF THE MANUFACTURER, PERTAINING TO, BUT NOT LIMITED TO: FIRE RATING, LIMITING HEIGHT, DEFLECTION, ETC.
7. PROVIDE BATT INSULATION AT RESTROOM PERIMETER PARTITIONS FOR FULL EXTENT OF WALL (FROM FLOOR TO CEILING).
8. PROVIDE MOLD & MOISTURE RESISTANT GYPSUM WALL BOARD AT ALL JANITOR CLOSET PARTITIONS, RESTROOMS, BACK BAR & FOOD SERVICE AREAS. PROVIDE 5/8" CEMENT BOARD AT ALL TILE PARTITIONS.
9. SEE SPECIFICATIONS FOR MINIMUM STUD MATERIAL THICKNESS AND DEFLECTION CRITERIA.10. ALL PARTITIONS ARE TO BE FULLY SEALED TO ADJACENT CONSTRUCTION, INCLUDING FLOOR SLAB AND
STRUCTURAL DECK TO RESIST THE PASSAGE OF AIR AND/OR SMOKE ACROSS THE PARTITION.11. ALL PENETRATIONS THROUGH FIRE-RATED PARTITIONS ARE TO BE FULLY SEALED WITH UL LISTED
SYSTEMS AS REQUIRED TO MAINTAIN THE REQUIRED WALL RATING. SEE UL DETAILS FOR ADDITIONAL INFORMATION.
12. ALL ACOUSTIC PARTITIONS ARE TO BE SEALED WITH ACOUSTIC SEALANT TO ADJACENT CONSTRUCTION (WALLS, FLOOR AND STRUCTURE) AS REQUIRED TO MAINTAIN THE ACOUSTICAL RATING OF THE ASSEMBLY.
PARTITION TYPES GENERAL NOTES13. AT NON-LOAD BEARING CMU PARTITIONS, PROVIDE PRECAST CONCRETE LINTELS OVER OPENINGS,
DOORS, WINDOWS, DUCTS, ETC., PER REQUIREMENTS OF DIVISION 4 SECTION "UNIT MASONRY ASSEMBLIES".
14. PROVIDE BLOCKING FOR ALL FIXED AND ADJUSTABLE SHELVING USING 6" WIDE CONTINUOUS, 16 GA GALV. STRAP METAL. SHELVING STANDARDS TO BE ANCHORED TO BLOCKING AT 12" O.C. MINIMUM
15. PROVIDE FULL HEIGHT DOUBLE STUDS (BACK TO BACK OR NESTED) AT ALL DOOR JAMBS.16. ALL DOOR FRAMES LOCATED ADJACENT TO PERPENDICULAR PARTITIONS ARE TO BE SET INSIDE FACE OF
FRAME 4" FROM FACE OF PARTITION UNLESS OTHERWISE NOTED. 17. SET STUDS SO THAT FINISHED FACE OF GYPSUM WALL BOARD AT DISSIMILAR PARTITIONS ALIGNS AS
INDICATED ON DRAWINGS.18. APPLY "LEVEL 4" FINISH TO ALL GYPSUM WALL BOARD PARTITIONS UNLESS OTHERWISE NOTED IN THE
CONTRACT DOCUMENTS.19. APPLY "LEVEL 5" FINISH TO ALL GYPSUM WALL BOARD PARTITIONS AND SOFFITS AS IDENTIFIED ON THE
DRAWINGS. 20. PROVIDE BLOCKING FOR ALL WALL CABINETS USING A MINIMUM OF 2 ROWS OF 6" WIDE CONTINUOUS, GA
GALV. STRAP METAL. PROVIDE AN ADDITIONAL ROW FOR EVERY 2' OF CABINET HEIGHT ABOVE 30". TOP OF BASE CABINETS TO BE SECURED TO ONE ROW OF BLOCKING.
21. PROVIDE A SLIP TRACK ALLOWING 3/4" DEFLECTION AT ALL STUD FRAMING THAT EXTENDS TO STRUCTURE.
22. PROVIDE A MINIMUM OF 5/8" CEMENT BOARD, 8" HIGH, BACKER ROD & SEALANT @ INTERSECTION WITH FLOOR AT THE BASE OF PARTITIONS IN ROOMS CONTAINING TILE FLOORING WITH A WATERPROOF MEMBRANE OR FLUID APPLIED FLOOR SYSTEM/WATERPROOFING SYSTEM.
GWB CONTROL JT.
5/8" GWB, PTD
2X WOOD FRAMING5/8" GWB, PTD
2X WOOD FRAMING5/8" GWB, PTD
ACOUSTICAL SEALANT, TYP.
RESILIENT WALL BASE
BATT INSULATION
GWB EXPANSION JT. (BASIS-OF-DESIGN: FRY REGLET DB.1 3-PIECE DRYWALL EXPANSION JOINT)
5/8" GWB, PTD
5/8" GWB, PTD
DEFLECTION TRACK
NOM. 2X6 WD FRAMING @ 16"O.C.
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A601
PARTITION TYPESSCHEDULE
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A601 3" = 1'-0"4 INTERIOR 2X4 PARTITION HEAD DETAIL @ OPEN WEB JOIST (TYP.)
A601 3" = 1'-0"1 INTERIOR 2X4 PARTITION HEAD DETAIL @ WOOD DECK (TYP.)
A601 3" = 1'-0"3 INTERIOR PARTITION HEAD DETAIL @ STEEL BEAM (TYP.)
A601 3" = 1'-0"2 INTERIOR 2X6 PARITION HEAD DETAIL @ WOOD DECK (TYP.)
A ISSUED FOR BID 12/28/2018
A601 3" = 1'-0"5 TYP. GWB CONTROL JOINT
A601 3" = 1'-0"6 BASE DETAIL @ PARTITION TYPE 2B
A601 3" = 1'-0"7 SECTION DTL @ GWB EXPANSION JT.
SEE SCHED.
WIDTH
SEE SCHED.
WIDTH
SEE SCHED.
WIDTH
SEE
SCHE
D.
HEIG
HT
3'-4"
2'-8"
8"
SEE
SCHE
D.
HEIG
HT
SEE
SCHE
D.
HEIG
HT
DOOR TYPE A
F.F0'-0"
DOOR TYPE B
DOOR TYPE C
DOOR TYPE
DOOR TYPE D
SEE
SCHE
D.
HEIG
HT
WIDTH SEE SCHED.
EQ.
PANEL 1
EQ.
PANEL 2
DOOR TYPE H
INSULATED OVERHEAD ROLLING
SEE SCHED.
WIDTH
SEE
SCHE
D.
HEIG
HT
DOOR TYPE E
STOREFRONT DOOR
SEE SCHED.
WIDTH
SEE
SCHE
D.
HEIG
HT 2'-0"
2'-0"
SEE
SCHE
D.
HEIG
HT
SEE SCHED.
WIDTH
SEE SCHED.
WIDTH
SEE
SCHE
D.
HEIG
HT1'-0"
1'-0"
DOOR TYPE F
LOUVERED DOOR50% OPEN
DOOR TYPE G
LOUVERED DOOR50% OPEN
SEE SCHED.
WIDTH
SEE
SCHE
D.
HEIG
HT
F.F0'-0"
FRAME TYPE
FRAME TYPE A
SEE SCHED.
WIDTH SIDELITE1'-0"
SEE
SCHE
D.
HEIG
HT
FRAME TYPE B
1/4" CLR. TEMPERED GLASS
SEE
SCHE
D.
HEIG
HT
SEE SCHED.
WIDTH
SEE STOREFRONT ELEVATIONS
FRAME TYPE C
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3/8" = 1'-0"
A602
DOOR SCHEDULE
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
DOOR NO. ROOM NAME
DOOR
GLAZ.
FRAMEHEAD
DETAILJAMB
DETAILSILL
DETAIL RATINGHDWRGROUP REMARKSTYPE
SIZEMAT. FIN. TYPE MAT. FIN.WIDTH HEIGHT THICK
1ST FLOOR1-101-1 TENANT #1 E 3'-0" 7'-0" 1 3/4" AL ANNOD FT D AL ANNOD 10/A402 4/A402 S-02 SIM. - 1.0 CARD READER1-101-2 TENANT #1 D 6'-0" 7'-0" 1 3/4" FG PTD - A FG PTD H-02 J-02 S-02 - 3.0 CARD READER1-102-1 WOMENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.01-103-1 MENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.01-104-1 J.C. A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 11.02-101-1 TENANT #2 E 3'-0" 7'-0" 1 3/4" AL ANNOD. FT D AL ANNOD 10/A402 PER MNFR S-02 SIM. - 1.0 CARD READER2-102-1 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.02-103-1 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.02-104-1 CORRIDOR B 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 J-04 - 9.02-104-2 CORRIDOR A 3'-0" 7'-0" 1 3/4" FG PTD - A FG PTD H-02 J-02 S-02 - 2.02-105-1 MECHANICAL CLOSET D 6'-0" 7'-0" 1 3/4" FG PTD - A FG PTD H-02 J-02 S-02 - 4.0 CARD READER2-106-1 J.C. A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 10.03-101-1 TENANT #3 E 3'-0" 7'-0" 1 3/4" AL ANNOD FT D AL ANNOD 10/A402 4/A402 S-02 SIM. - 1.0 CARD READER3-101-2 TENANT #3 A 3'-0" 7'-0" 1 3/4" FG PTD - A FG PTD H-02 J-02 S-02 - 2.0 CARD READER3-101-3 TENANT #3 H 8'-0" 8'-0" 1" STL PTD - - - - H-03 J-03 S-02 SIM - 19.03-102-1 WOMENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.03-103-1 MENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.03-104-1 J.C. A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 11.04-101-1 TENANT #4 E 3'-0" 7'-0" 1 3/4" AL ANNOD FT D AL ANNOD 10/A402 PER MNFR S-02 SIM. - 1.0 CARD READER4-102-1 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.04-103-1 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.04-104-1 CORRIDOR B 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 9.04-104-2 CORRIDOR A 3'-0" 7'-0" 1 3/4" HM PTD - A HM PTD H-02 J-02 S-02 - 2.0 CARD READER4-105-1 MECHANICAL CLOSET D 6'-0" 7'-0" 1 3/4" HM PTD - A HM PTD H-02 J-02 S-02 - 4.04-106-1 J.C. A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 10.05-101-1 TENANT #5 E 3'-0" 7'-0" 1 3/4" AL ANNOD FT D AL ANNOD 10/A402 4/A402 S-02 SIM - 1.0 CARD READER5-101-2 TENANT #5 A 3'-0" 7'-0" 1 3/4" FG PTD - A FG PTD H-02 J-02 S-02 - 2.0 CARD READER5-101-3 TENANT #5 H 8'-0" 8'-0" 1" STL PTD - - - - H-03 J-03 S-02 SIM - 19.05-102-1 WOMENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.05-103-1 MENS A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 18.05-104-1 J.C. A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 11.0
2ND FLOOR1-201-1 TENANT 1 MEZZANINE A 3'-6" 6'-8" 1 3/4" FG PTD - A FG PTD H-03 J-02 SIM. S-03 - 5.05-201-1 TENANT 5 MEZZANINE A 3'-6" 6'-8" 1 3/4" FG PTD - A FG PTD H-03 J-02 SIM S-03 - 5.0
DOOR SCHEDULE: CORE & SHELL
DOOR NO. ROOM NAME
DOOR
GLAZ.
FRAMEHEAD
DETAILJAMB
DETAILSILL
DETAIL RATINGHDWRGROUP REMARKSTYPE
SIZEMAT. FIN. TYPE MAT. FIN.WIDTH HEIGHT THICK
5-108-2 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.05-108-3 WC A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-01 - 16.05-108-4 CORRIDOR B 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 9.0
1ST FLOOR1-100-1 LOBBY E 3'-0" 7'-0" 1 3/4" AL ANNO FT C AL ANNOD PER MNFR. 6-A801 S-04 - 6.01-105-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T A HM PTD H-01 J-01 S-04 - 13.01-106-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-107-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-108-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-109-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-110-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-111-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-112-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-113-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-114-1 STORAGE D 6'-0" 7'-0" 1 3/4" HM PTD - A HM PTD H-01 J-01 S-04 - 14.01-116-1 IT CLOSET A 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 12.01-117-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-118-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-119-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-120-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.01-121-1 CONFERENCE C 3'-0" 7'-0" 1 3/4" WD CLR T B HM PTD H-01 J-01 S-04 - 13.05-105-1 SHOWROOM D 6'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 15.05-106-1 SHOWROOM D 6'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 15.0
5-107A-1 CORR. C 3'-0" 7'-0" 1 3/4" WD CLR T A HM PTD H-01 J-01 S-04 - 8.05-107A-2 CORR. C 3'-0" 7'-0" 1 3/4" WD CLR T A HM PTD H-01 J-01 S-04 - 8.05-108-1 VESTIBULE E 3'-0" 7'-0" 1 3/4" AL ANNOD FT C AL ANNOD PER MNFR. 6-A801 S-04 - 7.0
2ND FLOOR1-202-1 FABRICATION F 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.01-203-1 FABRICATION F 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.01-204-1 STAGING G 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.05-202-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.05-203-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.05-204-1 OFFICE C 3'-0" 7'-0" 1 3/4" WD CLR - A HM PTD H-01 J-01 S-04 - 13.0
DOOR SCHEDULE: TENANT 1 FITOUT
DOOR SCHEDULE ABBREVIATIONSAL ALUMINUMANNO ANNODIZEDFG FIBERGLASSPTD PAINTEDFT FULL TEMPEREDSTL STEEL
A ISSUED FOR BID 12/28/2018
AIR BARRIER MEMBRANE
(INTERIOR) (EXTERIOR)
PER MFR.
1 15/16"1 15/16"
2"
SEALANT TYP. FIBERGLASS DOOR & FRAME
VENT STRIP INSECT SCREEN INSTALLED BETWEEN VERTICAL FURRING MEMBERS
WOOD HEADERSEE STRUCT.
INSULATION BATTS
EXTERIOR WALL ASSEMBLY NO.1
FLASHING TAPE
DRIP EDGE BY PANEL MANUFACTURER5/8" GWB TYP.
type h2
BACKER ROD AND SEALANT, SEAL MEMBRANE TO DOOR FRAME
ROUGH OPENING TREATMENT
FIBER CEMENT BD. W/ EXPOSED FASTENERS. PROVIDE J-CHANNEL TERMINATION AT DOOR OPENING
PERIMETER
AIR BARRIER MEMBRANE, TURN INTO OPENING
ROLLING OVERHEAD DOOR WITH TYPE "E" STEEL ANGLE GUIDES,
SECURE TO HSS COLUMN
3/8" STL. PL. PTD.
5/8" PWD. BLOCKING MECHANICALLY ATTACHED TO COLUMN
PT. WD. FURRING
HSS COLUMN, SEE STRUC
WAL
L AS
SEM
BLY
#1
BACKER ROD AND SEALANT, SEAL MEMBRANE TO DOOR FRAME
ROUGH OPENING TREATMENT
SPLIT FACE CMU CORNER CLOSER
AIR BARRIER MEMBRANE, TURN INTO OPENING
ROLLING OVERHEAD DOOR WITH TYPE "E" STEEL ANGLE GUIDES,
SECURE TO HSS COLUMN
3/8" STL PL. PTD.
5/8" PWD. BLOCKING MECHANICALLY ATTACHED TO COLUMN
PT. WD. FURRING
HSS COLUMN, SEE STRUC
UPPER
LOWER PLAN
TYPE J3PER PARTITION
TYPE THICKNESS
HOLLOW METAL FRAME
SEALANT BOTH SIDES, TYP.
DOUBLE 2X6 WOOD HEADER
5/8" GWB OVER WOOD STUDS. SEE PARTITION TYPES.
1 15/16" 1 15/16"
5/8"
2"
1/2"
SOUND BATTS PER PARTITION TYPE
type h1
HSS STEEL ABOVE
AIR MEMBRANE, TURN INTO OPENING
BACKER ROD AND SEALANT, SEAL DOOR FRAME TO MEMBRANE
SHEET METAL FLASHING DRIP EDGE
DOOR HEAD INSTALLED AT UNDERSIDE OF STEEL BEAM ABOVE TO PROVIDE MAXIMUM DISTANCE BETWEEN SILL AND ROOF MEMBRANE. SHIM AS REQ.
SIM
WALL ASSEMBLY #1
CONT. SEALANT AT JOINT
(INTERIOR) (EXTERIOR)
TYPE H4
1/2"
MAX
. TRA
NSIT
ION
ALIG
N
LARGE FORMAT PORCELAIN TILE IN THIN SET, TAPER AS REQUIRED SUCH THAT MAXIMUM CHANGE IN FLOOR HEIGHT IS 1/2"
POLISHED CONCRETE FLOOR
SLOPED ALUMINUM THRESHOLD, SCHLUTER 1.8 RENO RAMP OR EQ. MAXIMUM SLOPE 1:8
TYPE S1
SLOPE
EDGE OF SPLIT FACE BEYOND
EDGE OF DOOR AND FRAME
PREMOLDED FILLER
GASKETED THRESHOLD SET IN FULL BED OF SEALANT
TYPE S2
EXTERIOR FINISH BEYOND
EDGE OF DOOR FRAME
ROOFING MEMBRANE, TURN INTO OPENING AND SEAL TO WALL 6" MIN.
SHEET METAL SILL FLASHING WITH END DAMS SET IN FULL BED OF SEALANT
GASKETED ALUMINUM THRESHOLD SET IN FULL BED OF SEALANT
PAINTED BULLNOSE WOOD SILL
PVC TRIM BOARD, PAINT TO MATCH ADJACENT WALL FINISH
WALL BASE AS SCHEDULED
INTERIOR FINISH BEYOND
MIN
.
6"
PERIMETER CANT
2ND FLOOR
DOOR WITH CONTINIOUS GASKET AT SILL
2X8 PT. WD. CURB
ROO
F AS
SEM
BLY
#2
TYPE S3
FIBER CEMENT PANELS W/ EXPOSED FASTENERSTREATED 1X FURRING
SEALANT, TYP.
5/8" GWB, TYP.
FIBERGLASS DOOR & FRAME
2X8 WOOD STUDS @ 16" O.C.
SEALANT AND BACKER ROD
CMU BASE (BELOW)
J-MOLDING BY PANEL MANUFACTURER
AIR BARRIER MEMBRANE
J-BEAD
SEALANT, TYP.
(INTERIOR)
(EXTERIOR)
UPPER PLAN
FIBERGLASS DOOR & FRAME
SEALANT AND BACKER ROD
AIR BARRIER MEMBRANE
J-BEAD
GROUND FACE CMU
LINE OF SIDING, ABOVE
PROVIDE MFR'S FINISHED OUTSIDE CORNER UNIT
(INTERIOR)
(EXTERIOR)
LOWER PLAN 5/8" GWB, TYP.
2X8 WOOD STUDS @ 16" O.C.
type j2
PER
PART
ITIO
NTY
PE T
HICK
NESS
1 15
/16"
1 15
/16"
1/2"
5/8" GWB OVER WOOS STUDSSEE PARTITION TYPES
HOLLOW METAL FRAME, PTD.
SEALANT BOTH SIDES, TYP.
2X WOOD FRAMING
SOUND BATTS PER PARTITION TYPE
FRAME ANCHOR
2" 5/8"
type j1
SELF ADHEREING SHEET FLASHING
VENT STRIPSHEET METAL FLASHING W/ DRIP EDGE
AIR BARRIER MEMBRANE
ROUGH OPENING TREATMENT
3/8" STEEL PLATE, PTD.
WALL ASSEMBLY #1
5/8" PWD. BLOCKING
2X8 WD. STUD
HSS BEAM, SEE STRUC.
OVERHEAD DOOR, REFER TO MNFR. SPECIFIC WRITTEN
INSTALLATION INSTRUCTIONS
OVERHEAD ROLLING DOOR
TYPE H3
POLISHED CONCRETE FLOOR
TYPE S4
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3" = 1'-0"
A603
DOOR DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A ISSUED FOR BID 12/28/2018
PRIME AND PAINT EXPOSED VISIBLE SURFACES OF STRUCTURAL STEEL ELEMENTS SUCH AS BUTNOT LIMITED TO COLUMNS, BEAMS, GIRDERS, X-BRACING, TIE-RODS, AND BRACES.
1.
FINISH SHEET GENERAL NOTES
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
12" = 1'-0"
A604
FINISH SCHEDULES
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
ROOM NO. ROOM NAMEFINISHES
AREA (NET SF) PERIM. (LF) REMARKSFLOOR BASE WALL CEILING
1ST FLOOR1-100 LOBBY F-1 B-1 W-1 213.5 58.9
1-100A VESTIBULE F-1 B-1 W-1 C-2 64.5 32.11-101 OPEN OFFICE AREA F-1 B-1 W-1 N/A 1,303.0 230.3
1-101A LOUNGE F-1 B-1 W-1 N/A 473.4 96.31-102 WOMENS F-1 B-1 W-1 C-1 119.1 50.51-103 MENS F-1 B-1 W-1 C-1 119.9 50.61-104 J.C. F-1 B-1 W-1 C-1 10.7 13.11-105 OFFICE F-1 B-1 W-1 N/A 97.5 40.71-106 OFFICE F-1 B-1 W-1 N/A 120.9 44.41-107 OFFICE F-1 B-1 W-1 N/A 120.9 44.41-108 OFFICE F-1 B-1 W-1 N/A 120.9 44.41-109 OFFICE F-1 B-1 W-1 N/A 120.8 44.41-110 OFFICE F-1 B-1 W-1 N/A 120.8 44.41-111 OFFICE F-1 B-1 W-1 N/A 120.7 44.41-112 OFFICE F-1 B-1 W-1 N/A 286.6 70.21-113 OFFICE F-1 B-1 W-1 N/A 246.0 67.31-114 SHIPPING F-1 B-1 W-1 C-2 85.8 38.4
1-114A STORAGE F-1 B-1 W-1 N/A 306.1 80.41-115 KITCHEN F-1 B-1 W-1 C-2 60.8 32.11-116 IT CLOSET F-1 B-1 W-1 N/A 74.6 45.41-117 OFFICE F-1 B-1 W-1 N/A 99.6 41.01-118 OFFICE F-1 B-1 W-1 N/A 120.9 44.41-119 OFFICE F-1 B-1 W-1 N/A 120.9 44.41-120 OFFICE F-1 B-1 W-1 N/A 138.2 46.11-121 CONFERENCE F-1 B-1 W-1 N/A 321.1 78.22-101 TENANT #2 F-1 B-1 W-1 N/A 1,820.6 171.52-102 WC F-1 B-1 W-1 C-1 54.3 29.62-103 WC F-1 B-1 W-1 C-1 54.3 29.62-104 CORRIDOR F-1 B-1 W-1 C-1 135.7 60.62-105 MECHANICAL CLOSET F-1 B-1 W-1 C-1 116.4 48.12-106 J.C. F-1 B-1 W-1 N/A 8.6 11.93-101 TENANT #3 F-1 B-1 W-1 N/A 4,916.4 352.33-102 WOMENS F-1 B-1 W-1 C-1 123.5 51.73-103 MENS F-1 B-1 W-1 C-1 127.3 51.73-104 J.C. F-1 B-1 W-1 N/A 11.0 13.34-101 TENANT #4 F-1 B-1 W-1 N/A 2,087.3 184.94-102 WC F-1 B-1 W-1 C-1 55.0 29.84-103 WC F-1 B-1 W-1 C-1 55.0 29.84-104 CORRIDOR F-1 B-1 W-1 C-1 111.6 48.54-105 MECHANICAL CLOSET F-1 B-1 W-1 C-1 185.9 55.84-106 J.C. F-1 B-1 W-1 N/A 9.3 12.55-101 D-TECH F-1 B-1 W-1 N/A 2,914.2 260.35-102 WOMENS F-1 B-1 W-1 C-1 117.6 50.25-103 MENS F-1 B-1 W-1 C-1 131.1 50.25-104 J.C. F-1 B-1 W-1 C-1 9.9 12.75-105 SHOWROOM F-1 B-1 W-1 N/A 416.2 81.65-106 SHOWROOM F-1 B-1 W-1 N/A 439.1 83.95-107 OFFICES F-1 B-1 W-1 N/A 884.2 136.9
5-107A CORR. F-1 B-1 W-1 C-1 101.6 50.15-108 VESTIBULE F-1 B-1 W-1 C-2 72.0 34.0
2ND FLOOR1-201 MEZZANINE F-2 B-1 W-1 C-3 965.2 139.81-202 FABRICATION F-2 B-1 W-1 C-3 316.8 86.11-203 FABRICATION F-2 B-1 W-1 C-3 316.4 84.81-204 STAGING F-2 B-1 W-1 C-3 313.2 73.63-201 TENANT #3
MEZZANINEF-2 B-1 W-1 C-3 1,888.3 189.9
5-201 MEZZANINE F-2 B-1 W-1 C-3 933.3 138.25-202 OFFICE F-2 B-1 W-1 C-3 327.4 74.15-203 OFFICE F-2 B-1 W-1 C-3 316.0 71.75-204 OFFICE F-2 B-1 W-1 C-3 285.0 74.1
ROOM FINISH SCHEDULE: TENANT 1 FITOUT
ROOM NO. ROOM NAMEFINISHES
AREA (NET SF) PERIM. (LF) REMARKSFLOOR BASE WALL CEILING
1ST FLOOR1-101 TENANT #1 F-1 B-1 W-1 N/A 4,930.3 310.0 PAINT EXPOSED STEEL1-102 WOMENS F-3 B-2 W-1/W-2 C-1 119.1 50.51-103 MENS F-3 B-2 W-1/W-2 C-1 119.9 50.61-104 J.C. F-2 B-2 W-3 N/A 10.8 13.22-101 TENANT #2 F-1 B-1 W-1 N/A 1,820.6 171.5 PAINT EXPOSED STEEL2-102 WC F-3 B-2 W-1/W-2 C-1 54.3 29.62-103 WC F-3 B-2 W-1/W-2 C-1 54.3 29.62-104 CORRIDOR F-1 B-1 W-1 C-1 135.7 60.62-105 MECHANICAL CLOSET F-3 B-1 W-1 N/A 116.4 48.12-106 J.C. F-2 B-2 W-3 N/A 8.7 12.03-101 TENANT #3 F-1 B-1 W-1 N/A 4,922.0 320.0 PAINT EXPOSED STEEL3-102 WOMENS F-3 B-2 W-1/W-2 C-1 123.5 51.73-103 MENS F-3 B-2 W-1/W-2 C-1 127.3 51.73-104 J.C. F-2 B-2 W-3 N/A 11.1 13.44-101 TENANT #4 F-1 B-1 W-1 N/A 2,091.8 185.1 PAINT EXPOSED STEEL4-102 WC F-3 B-2 W-1/W-2 C-1 55.0 29.84-103 WC F-3 B-2 W-1/W-2 C-1 55.0 29.84-104 CORRIDOR F-1 B-1 W-1 C-1 111.6 48.54-105 MECHANICAL CLOSET F-3 B-1 W-1 C-1 185.9 55.84-106 J.C. F-2 B-2 W-3 C-1 9.8 12.75-101 TENANT #5 F-1 B-1 W-1 N/A 4,914.1 317.8 PAINT EXPOSED STEEL5-102 WOMENS F-3 B-2 W-1/W-2 C-1 117.6 50.25-103 MENS F-3 B-2 W-1/W-2 C-1 131.1 50.25-104 J.C. F-2 B-2 W-3 N/A 10.0 12.7
2ND FLOOR1-201-1 TENANT 1 MEZZANINE 1,951.4 190.5 SEE FITOUT FOR FINISHES3-201-1 TENANT 3 MEZZANINE 4,808.8 312.55-201-1 TENANT 5 MEZZANINE 1,895.6 192.0 SEE FITOUT FOR FINISHES
ROOM FINISH SCHEDULE: CORE & SHELL
TAGINFORMATION
REMARKSDESCRIPTION FINISH MANUFACTURER MODEL SIZE COLOR
B-2 TILE BASE - ERGON STONE PROJECT 4" X 24" CHARCOALC-1 2'X2' ACT CORTEGA, TEGULAR ARMSTRONG 15/16" STANDARD GRID 24" X 24 WHITEC-2 GYPSUM WALL BOARD PAINT BY GC - - -C-3 EXPOSED WOOD DECKING CLEAR MATTE SEALER - PROVIDE SAMPLEF-1 GROUND & POLISHED CONCRETE CLEAR MATTE SEALER - - -F-2 STATIC DISSAPATIVE VINYL TILE - JOHNSONITE IQ TORO SC 24" X 24" SIDEWALK 0578 MOUNT OVER 1/4" PWD.F-3 PORCELAIN TILE - ERGON STONE PROJECT 12" X 24" GRAY VEIN CUTPT-A PAINT - BY GC - -PT-B PAINT - BY GC - -W-1 GYPSUM WALL BOARD PAINT BY GC - -W-2 PORCELAIN TILE ERGON STONE PROJECT 12" X 24" GRAY VEIN CUTW-3 FRP TEXTURED - - - WHITE
finish materials schedule
A ISSUED FOR BID 12/28/2018
W02 W03
F.F
WINDOW TYPE
W01SKYLIGHT
2'-0"
7'-6
1/2"
6'-5"
2'-0"4'-2"
7'-8"
IGU-2, TYP.
1-100-1
B-1W-1
8'-3 3/4" V.I.F.
SEAL MULLION TO CURTAIN WALL FRAME WITH CONT. SEALANT
ALIGN
5A801
_________
1'-6"
5-108-1
W-1B-1
8'-1 3/4" V.I.F.
1'-6"
5A801
_________
STOREFRONT DOOR
SEE PLAN
8'-2"
3'-4"
B-1 W-1
9'-2 1/2" V.I.F.
SEAL MULLION TO CURTAIN WALL FRAME WITH CONT. SEALANT
1'-6"
ALIGN
___________________2
A801ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR.
THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A605
WINDOW SCHEDULE
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A605 3/8" = 1'-0"1 1-100A-VESTIBULE - EAST
A605 3/8" = 1'-0"3 5-102 VESTIBULE - NORTH
INTERIOR STOREFRONT
A605 3/8" = 1'-0"4 TENANT ENTRY DOORS
A605 3/8" = 1'-0"2 5-102 VESTIBULE EAST
TRANSOM
A ISSUED FOR BID 12/28/2018
B-1
1-202-1 1-204-1W-1
CURVED GLU-LAM BEAM
1-203-1
GWB C.J.
GWB C.J.
DRYWALL CONTROL JOINT
B-1
JUNC
TIO
N BO
X CL
.
8'-6"
TO
LIG
HT F
IXTU
RE
5-107A-1
W-1
ALIGNGWB C.J.
2-103-12-102-1 2-104-1
JUNC
TIO
N BO
X CL
.
8'-6"
TO
LIG
HT F
IXTU
RE
2-106-1
B-1
W-1___________________
5A503
W-1
B-1
1-121-1
1ST FLOOR0"
2ND FLOOR11'-8"
5.45.6
GWB C.J.
5-105-1 5-107A-2 5-106-1
GUARDRAIL
Sim5
A501_________
W-1
B-1
2ND FLOOR11'-8"
5.45.6
5-203-1
GWB C.J.
B-1
W-1
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
As indicated
A701
INTERIOR ELEVATIONS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A701 1/4" = 1'-0"3 1-201-MEZZANINE - NORTH
A701 1/4" = 1'-0"2 5-103 OFFICES - NORTH
A701 1/4" = 1'-0"1 2-101 TENANT #2 - NORTH
A701 3/8" = 1'-0"6 1-101 OPEN OFFICE AREA - SOUTH
A ISSUED FOR BID 12/28/2018
A701 1/4" = 1'-0"4 5-101 D-TECH - SOUTH
A701 1/4" = 1'-0"5 5-201 MEZZANINE - SOUTH
12A501
_________
1-117-1 1-118-1 1-119-1 1-120-1 1-100-1W-1
B-1
PAINTED WOOD TRIM, SEE DETAIL
10'-6
"
W-1
W-1
W-1
W-1
GWB C.J.
ALIGN
DRYWALL CONTROL JOINT
OPEN TO BEYONDW-1
B-1
8'-0"
W-1
7'-6"OPEN TO BEYOND
B-1
W-1
1-107-11-106-1 1-108-1 1-109-1 1-110-1 1-111-1 1-112-11-105-1
6A801
_________
PAINTED WOOD TRIM, SEE DETAIL
10'-6
"
8'-0"
GWB C.J. GWB C.J. GWB C.J.
8'-0"
W-3 W-1
B-1
EXHAUST HOOD, SEE MEP FOR DETAILS
SPRAY ENCLOSURE WITH CURTAIN
1A801
_________
6'-6"
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
3/8" = 1'-0"
A702
INTERIOR ELEVATIONSTENANT 1
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A702 3/8" = 1'-0"4 1-101 OPEN OFFICE AREA - EAST
A702 3/8" = 1'-0"2 1-101 OPEN OFFICE AREA - NORTH
A702 3/8" = 1'-0"3 1-101 OPEN OFFICE AREA WEST
A702 3/8" = 1'-0"1 1-203 SPRAY AREA
A ISSUED FOR BID 12/28/2018
3/4"
1/4"
SEEPLAN
1/4" LATTICE PAINTED BLACK
L-CASING BEAD AT GWB TERMINATION
WOOD FRAMED PARTITION
1/2"PAINTED RECTANGULAR
WOOD CAP
CONTINIOUS BEAD OF SEALANT AT JOINT, BOTH SIDES
INTERIOR STOREFRONT SYSTEM
SEEPLAN
(2) 2X10 WD. HEADER
5/8" GWB, TYP.
PAINTED WD. CAP, SEE DETAILS
2X4 WD FRAMING, TYP.
SEE RCP
EDGE OF WALL BEYOND
2X4 WD. CEILING JOIST
SEE PLAN
GWB CORNER BEAD
1/2"
MAX
.
POLISHED CONCRETE FLOOR
LARGE FORMAT PORCELAIN TILE IN
THINSET, TAPER AS REQUIRED SUCH THAT
MAXIMUM CHANGE IN FLOOR HEIGHT IS 1/2"
SLOPED ALUMINUM THRESHOLD, SCHLUTER
1.8 RENO RAMP OR EQ. MAXIMUM SLOPE 1:8
ALIG
N
FACE OF WALL BEYOND
(2) 2X8 WD. HEADER, TYP.
5/8" GWB, TYP.
8'-0" A.F.F.
EDGE OF WALL BEYOND
2X4 SOFFIT FRAMING, SECURE TO STRUCTURE ABOVE
EXHAUST HOOD, SEE MEP FOR
NON-COMBUSTIBLE SPRAY CURTAIN WITH CEILING-MTD INDUSTRIAL TRACK. HEAVY DUTY CARRIERS(BASIS-OF-DESIGN: AKON)
6'-6" A.F.F.
2X4 CEILING JOIST @ 16" O.C.
THREADED ROD CEILING HANGING KIT, PER MNFR. SPECIFIC WRITTEN INSTRUCTIONS
PROVIDE CONT. SLNT. AT JOINT
1'-6"
CURTAINWALL SYSTEM
PROVIDE CONT. SLNT. AT JOINT
2X8 WD. BLOCKING
OPEN WEB WD. JOIST, TRIM BOTTOM CORD AS REQUIRED TO
ACCOMIDATE CEILING SOFFIT
5/8" GWB. CEILING, TYP
HORIZONTAL 2X4 WD. CEILING FRAMING @ 16" O.C.
+9'-7"WD. BLOCKING 1'-8 1/2"
STEEL BEAM, SEE STRUC.
ALL DIMENSIONS AND RELATIONSHIPS MUST BE VERIFIED BY CONTRACTOR. THE ARCHITECT IS TO BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE CONSTRUCTION. DO NOT SCALE FROM DRAWINGS.
SCALE:
DATE:
DRAWN:FILENAME:
DRAWING TITLE
REVISIONSMARK DATE
CHECKED:
SEAL
CLIENT:
ARCHITECTSTOKES ARCHITECTURE
1700 SANSOM ST 12TH FL.PHILADELPHIA, PA 19103
PH: 215.523.9190
CIVIL ENGINEERS
ATLANTIC COUNTY IMPROVEMENT AUTHORITY
1333 ATLANTIC AVE SUITE 700ATLANTIC CITY, NJ 08203
PH: 609.343.2390
STRUCTURAL ENGINEERSO'DONNELL & NACCARATO
701 MARKET STREET SUITE 6000PHILADELPHIA, PA 19106
PH: 215.925.3788
MEP ENGINEERSPOLARIS CONSULTING
ENGINEERS, PC14 W. MAIN ST. SUITE 208
MOORESTOWN, NJ 08057PH: 856.778.5400
STANTEC1599 RT. 34, SUITE 3
WALL TWP., NJ 07727PH: 732.449.0099
OWNER:CAPE MAY COUNTY
4 MOORE ROADCAPE MAYCOURTHOUSE, NJ
08210
1 1/2" = 1'-0"
A801
INTERIOR DETAILS
JCRS
11/09/2018
ISSUED FOR BID
CAPE MAY COUNTYMULTI-TENANT UAS BLDG
HORNET ROADLOWER TOWNSHIP NJ 08242
PROJECT NO.: 01-01-14807
A801 1 1/2" = 1'-0"6 1 WOOD WALL CAP
A801 1 1/2" = 1'-0"5 PLAN DETAIL @ INT. STOREFRONT JAMB
A801 1 1/2" = 1'-0"3 CONFERENCE ROOM SOFFIT
A801 1 1/2" = 1'-0"4 TILE TRANSITION DETAIL
A801 1 1/2" = 1'-0"1 EXHAUST HOOD SOFFIT
A801 1 1/2" = 1'-0"2 5-102 - VESTIBULE SOFFIT
A ISSUED FOR BID 12/28/2018