Continuum como control de accesos Ing. Francisco Olvera Página 1 Content 1. Product Overview a) Hardware Review ACX Series CX Series IOU Modules 2. Change IP Address a) Netcontroller I b) Netcontroller II c) ACX d) CX 3. Software Overview a) System Requirements Hardware requirements Software requirements b) Continuum Software Compatibility Matrix c) Cyber Station Installation d) Cyber Station Access Control Essentials Guide e) Continuum Reports f) Plain English Essentials g) Database Maintenance 4. Diagnostics 5. Final Test

Upload: folveras

Post on 03-Oct-2014

205 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 1

Content

1. Product Overview

a) Hardware Review

ACX Series

CX Series

IOU Modules

2. Change IP Address

a) Netcontroller I

b) Netcontroller II

c) ACX

d) CX

3. Software Overview

a) System Requirements

Hardware requirements

Software requirements

b) Continuum Software Compatibility Matrix

c) Cyber Station Installation

d) Cyber Station Access Control Essentials Guide

e) Continuum Reports

f) Plain English Essentials

g) Database Maintenance

4. Diagnostics

5. Final Test

Page 2: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 2

Page 3: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 3

• Native Ethernet IP Access Controller

• Device capacities

4 Reader inputs

6 Universal inputs

2 Digital lock outputs

1 Tamper input

• xP Module support

• Native Ethernet IP Access Controller

• Device capacities

8 Reader inputs

12 Universal inputs

4 Digital lock outputs

1 Tamper input

• xP Module support

• RS-485 Communication

• Device capacities

Page 4: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 4

8 Card Reader and/or Keypads inputs

32 Supervised inputs

9 Digital lock outputs

1 Tamper input

• RS-485 Communication

• Device capacities

2 Card Reader and/or Keypads inputs

8 Supervised inputs

2 Digital lock outputs

1 Tamper input

• EMX Module support

• Native Ethernet IP Access Controller

• Device capacities

2 Reader inputs

4 Universal inputs

4 Supervised Inputs

2 Digital lock outputs

2 Digital outputs

1 Tamper input

• Choice of RS-485 or FTT-10A Media

• Device capacities

Page 5: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 5

1 Reader input

3 Supervised Inputs

2 Digital outputs

• Choice of RS-485 or FTT-10A Media

• Device capacities

1 Reader input

1 Keypad input

3 Supervised Inputs

2 Digital outputs

• Choice of RS-485 or FTT-10A Media

• Device capacities

1 Reader input

1 Keypad input

5 Supervised Inputs

2 Digital outputs

Page 6: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 6

Page 7: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 7

Connecting to the Netcontroller for the first time.

Commissioning Once the NetController has been mechanically installed and electrically connected, the controller‟s network address information must be entered so the Continuum software can communicate with the controller. This operation is called “commissioning”. What You’ll Need Commissioning a NetController requires a laptop or other computer that is running an ASCII terminal emulator. Terminal emulators are common programs that allow you to communicate simply with RS-232 devices. One emulator program, HyperTerminal, is built into Windows and is available from the Accessories menu off of the Start menu. Connections You can connect to the NetController either directly or through a modem, using a device with a keyboard and display. These devices are often referred to as ASCII terminals, TTY replacements, or terminals. We call them command terminals. Your command terminal must be DEC VT100 or VT220 compatible, or your computer must be running a terminal emulation program for one of these terminals. Communications between the NetController and the command terminal is through the RS-232 interface. Connect the NetController Comm Port and the command terminal‟s Serial or Comm port. Connections made through a modem are straightforward; however, refer to the modem manufacturer‟s guidelines before making the connection. Direct connection requires an RS-232 Null Modem cable. The NetController‟s default state is for connection to the CyberStation via a modem. If you are connecting directly to the controller via a network, select “MODEM RS-232 OVERRIDE” on the NetController‟s display panel. RS-232 communications operates at a number of speeds called the Baud Rate. Both the NetController and the command terminal must be set to the same baud rate to communicate. Use Comm3 on the NetController. The following table shows the correct settings:

RS-232 Settings

Baud rate 9600

Data Length 8 bits

Parity None

Stop bits One

Example NetController Commissioning using HyperTerminal

The following is an example procedure for connecting the CyberStation to the NetController using the emulator program, HyperTerminal, built into Windows 95. Open HyperTerminal from the Accessories menu off the Start menu.

• For modem connection, enter a name for your connection, select an icon, and click OK. • For direct connection, enter a name for your connection and click OK.

Page 8: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 8

The Connect To dialog box appears.

• For modem use, fill in the appropriate dial-up information, select the desired port and click OK. • For direct connection, select the desired port and click OK.

When the Port Settings box appears configure your command terminal Port Settings as follows and click OK:

Page 9: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 9

Logging on to the NetController

After connection, power up the terminal and the NetController. In the blank screen at the command terminal type:

WINDOW

The characters do not echo to your display. If they were received properly, the command terminal interface window appears:

For security reasons, access to the NetController internal setup program is limited to people who need to use it, so you must log on the system. Your System Administrator should have been given a User ID and Password. The default User ID and Password are both ACC. These defaults should be changed as soon as possible to prevent unauthorized users from entering Continuum.

Page 10: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 10

Type your user name and press the TAB key, then type your password and click Enter to log into the controller.

The Command Terminal Main Window appears containing the following features:

Menu Bar There are four menus (View, Edit, Connect, and Logout), with the current menu highlighted. In the

figure above, View is the current menu. Command Prompt Issue commands to the system at the R> prompt in the Command Window. (The R

indicates “Ready.”) Status Bar The status line displays information on the status of the Infinity control system. Controller Path Shows what controller the command terminal is currently connected to.

To enter commands at the Command Prompt, pres the F4 key. To toggle between the Command Prompt and the Menu Bar, press the F4 key again.

Setting the NetController Network Address Information

Select Edit from the Menu Bar. Using the arrow keys, move the curser down to highlight the Controller and press Enter

Page 11: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 11

After the „Open a Controller‟ window appears, type in the name of your NetController and press the Enter key.

Pressing F2 will reveal a list of any known NetControllers available to connect to, just use the arrow keys to select

the controller to connect to and press Enter.

The Network setup form contains all the address information. Enter the requested numbers supplied by your Network Administrator.

Page 12: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 12

Name: Displays the default name for the controller. You can change this through the Command Terminal interface

or through the CyberStation workstation. Do not enter anything here.

Description: The description is also displayed as described above (Name).

Serial Number: Automatically displays the serial number of the controller. You do not enter it.

Model: Automatically displays the controller model number. You do not enter it.

Status: Displays Offline or Online depending on whether or not the controller is on the network.

EnergyNet Id: Enter the ID of this controller on your network.

ProbeTime: Displays the rate per second that the controller probes the network for other devices.

Version: Displays the version of the controller

Ethernet ID: Automatically displays the controller Ethernet ID or Token Ring ID number. You do not enter anything here.

To set the IP address, press TAB until the TCP/IP button is highlighted and press Enter.

Setting the NetController IP Address

Enter the appropriate information when the TCP/IP window appears. Use the arrow keys to move around in the window.

Page 13: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 13

IP Address: Displays the Internet Address of the controller.

Subnet Mask: Displays the Subnet Address of the controller.

Default Router: Displays the Router ID number on your LAN.

PPP IP Address: Displays the Point-to-Point Protocol Address of the controller.

Web Server Port Web server port number (defaults to 80).

Max Response Time: Displays the Number of seconds the system is to wait for a response to a command before it is determined that communications are lost.

When the “Send ACC Modem Initialization String Upon Reset” is set, the following default command strings are sent to initialize the ACC modem:

AT&F\015 ATE\015 ATV&C1&D2&S1S0=1\\N3\\A3%%E1%%C1X3&W\015

After entering the particulars, press the TAB key until the Save button is highlighted and press Enter.

Back at the main form, TAB to the Save button and press Enter.

Commissioning is now complete from the controller end. Power down the controller to write the new settings into EEPROM. Log onto the controller once again and verify your new settings.

You will still have to create a new controller object and fill in much of the same information at the Continuum

workstation or Command Terminal to complete the process.

Hardware, Software, and Communications Requirements

In order to operate the NetController on an IP network, the controller’s network address information must be entered so that

CyberStation can communicate with the controller. This operation is called commissioning.

Requirements

Commissioning a CX968x NetController requires the following:

� A laptop or other computer

� A pocket PC

� An Ethernet adapter for the above Pocket PC or computer

� Web browser software

Note: Commissioning a NetController II is performed using embedded Web Server pages. You do not use the HyperTerminal

emulation program.

� Cable (CAT-5, twisted pair)

Connections

You connect to the CX968x directly through its Ethernet port using a cable connected to the Ethernet port of your PC or you

may connect the CX968x to an Ethernet hub/switch that your PC is connected to.

Page 14: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 14

Default settings

As received from the factory, the IP address settings for the CX968x are set to the following defaults.

SETTINGS VALUE

IP ADRESS 169.254.1.1

SUBNET MASK 255.255.0.0

GATEWAY 0.0.0.0

In order to communicate successfully with the controller while it is set to its default IP address, your computer or Pocket PC

must be configured with an IP address.in the same Network range as the CX968x. Setting your PC to the static IP address of

169.254.1.2 will allow successful communication to the CX968x with its default settings.

During the commissioning process, you may enter a more permanent IP address for the CX968x.

Note: Contact your system administrator for assistance with determining IP addresses, gateway addresses, and subnet masks.

There are many ways to ensure communications between the two depending upon your operating system. It is beyond the

scope of this document to explain network communications. However, the following procedure is one simple method that

ensures communication.

Connection Procedure

To connect from your computer to the NetController II, follow these steps:

1. Disable the Dynamic Host Configuration Protocol (DHCP) Services on your PC. If your PC is not configured for

DHCP, record the static IP address settings that are currently configured.

2. Disconnect your computer from the network, and set your IP address to 169.254.1.2 and your subnet mask to

255.255.0.0.

3. Using a CAT5 cable (straight-through or crossover), connect your PC to the controller’s Ethernet port.

4. Run your web browser and enter the URL: http://169.254.1.1 to display the following web page.

5. There are two user selections available on the displayed page:

Controller Configuration Options

Custom Reports and Services

6. Select the Controller Configuration Options.

7. For security reasons, the controller is password-protected. A logon dialog appears over the initial page. At the logon

dialog enter the default CyberStation user name and password shown on the following illustration.

Note: The User Name and Password can be configured using Controller user objects.

Page 15: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 15

8. Click OK to logon.

Note: Don’t forget to enable DHCP Services on your PC, and connect the NetController II to the network when it reboots after

you finish the commissioning process.

You may see the following system startup page for a few seconds while system initialization occurs.

After connecting to the IP address of the NetController II, the main Web Commissioning page appears.

Page 16: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 16

The main page features two panes:

� A side navigation pane for accessing the different configuration pages. The options listed on the side navigation pane may differ based on the controller software model, the options you have enabled, or

additional installed options supplied by Schneider Electric.

� The main display pane shows the currently active commissioning web page.

Controller Configuration When you select Controller Configuration from the side navigation pane, the Controller Configuration page appears.

Page 17: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 17

The following table describes the Controller Configuration fields that you can edit, as well as the action buttons. You can

also access this information by clicking Help below the page title.

Field Description/Action Name Contains the name of the controller. You can enter any name you wish in

this field up to a maximum of 16 characters. Spaces between name

segments are not permitted.

Controller device names must be unique across a network

Description Enter a description of the controller up to 32 characters in length

(optional).

ACCNet ID Identifies each controller on an Andover Continuum network by a

unique number between 1 and 190. Each controller must have a unique

ID on its particular network.

IP Address A logical 32-bit address that identifies a TCP/IP host. Each controller

requires a unique IP address. Each address has two parts: a network ID,

which identifies all hosts on the same physical network, and a host ID,

which identifies a host on the network.

Subnet Mask Subnets divide a large network into multiple physical networks

connected with routers. A subnet mask blocks out part of the IP address

so that TCP/IP can distinguish the network ID from the host ID. When

TCP/IP hosts try to communicate, the subnet mask determines whether

the destination host is on a local or remote network.

To communicate within a local network, computers and controllers must

have the same subnet mask.

Gateway Address The Gateway is the intermediate device on a local network that stores

network IDs of other networks in the enterprise or on the Internet. To

communicate with a host of another network, configure an IP address for

Page 18: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 18

the default Gateway. TCP/IP sends packets for remote networks to the

default gateway (if no other route is configured), which forwards the

packets to other gateways until the packet is delivered to a gateway

connected to the specific destination.

If you are using a proxy server, you must define a default router here.

Probe Time Displays the time, in seconds, between controller probes.

A probe is a message that the device sends out to its controllers to check

their COMM status. Controllers respond to probe messages to let the

device know they are online. When a device does not receive a response

from a controller, it changes the controller's COMM status to Offline.

Web Server Port The standard port for Web communications. The default setting is 80.

The Web Server Port can be set to any number from 1 to 65,534. If

changed, browser requests must specify the port number in the URL, for

example, http://<IP Address>:<Web Server Port>.

PPP IP Address Point-to-Point Protocol Address of the controller.

Transport Type UDP - This controller will communicate with other controllers and

Workstations primarily using the UDP protocol.

TCP - This controller will communicate with other controllers and

Workstations primarily using the TCP protocol.

TCP/UDP - This controller will communicate with other controllers and

Workstations primarily using the TCP protocol, but can also speak to

controllers and Workstations that communicate primarily using the UDP

protocol.

IO Configuration Allows the IO bus configuration to be either ACC LON or L-BUS.

Comm4 Port Line Allows Comm4 to be configured as either RS422 or RS485.

Action Buttons

Submit to Controller Submit all form data to the controller. After submitting data, navigate to

the Commit Changes page to write the changes to flash memory and

restart the controller.

Reset Form Undo any changes that were previously submitted.

Commit Changes The following page appears when you select Commit Changes from the side navigation pane.

WARNING:

Press the “Commit Changes/Restart Controller” button to commit the submitted changes to Flash Memory and restart the

controller. Upon restarting, any configuration changes made will be in effect.

Page 19: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 19

Hardware, Software, and Communications Requirements

In order to operate the ACX 57xx series controller on an IP network, the controller’s network address

information must be entered so that CyberStation can communicate with the controller. This operation is

called commissioning.

Requirements

Commissioning a ACX 57xx controller requires the following:

A laptop, pocket PC, or other computer

An Ethernet adapter for the above Pocket PC or computer

Web browser software

Note: Commissioning a ACX 57xx controller is performed using embedded Web Server pages. You do

not use the HyperTerminal emulation program.

Cable (CAT-5, twisted pair)

Connections

You connect to the ACX 57xx directly through its Ethernet port using a cable connected to the Ethernet port

of your PC or you may connect the ACX 57xx to an Ethernet hub/switch that your PC is connected to.

Page 20: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 20

Default settings

As received from the factory, the IP address settings for the ACX 57xx are set to the following defaults.

SETTINGS VALUE

IP ADRESS 169.254.1.1

SUBNET MASK 255.255.0.0

GATEWAY 0.0.0.0

In order to communicate successfully with the controller while it is set to its default IP address, your

computer or Pocket PC must be configured with an IP address.in the same Network range as the ACX 57xx.

Setting your PC to the static IP address of 169.254.1.2 will allow successful communication to the ACX 57xx

with its default settings.

During the commissioning process, you may enter a more permanent IP address for the ACX 57xx.

Note: Contact your system administrator for assistance with determining IP addresses, gateway

addresses, and subnet masks.

There are many ways to ensure communications between the two depending upon your operating system. It is

beyond the scope of this document to explain network communications. However, the following procedure is

one simple method that ensures communication.

Connection Procedure

To connect from your computer to the ACX 57xx Controller, follow these steps:

1. Disable the Dynamic Host Configuration Protocol (DHCP) Services on your PC. If your PC is not

configured for DHCP, record the static IP address settings that are currently configured.

2. Disconnect your computer from the network, and set your IP address to 169.254.1.2 and your subnet

mask to 255.255.0.0.

3. Using a CAT5 cable (straight-through or crossover), connect your PC to the controller’s Ethernet port.

4. Run your web browser and enter the URL: http://169.254.1.1 to display the following web page.

Page 21: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 21

5. There are two user selections available on the displayed page:

Controller Configuration Options

Custom Reports and Services

6. Select the Controller Configuration Options.

7. For security reasons, the controller is password-protected. A logon dialog appears over the initial page.

At the logon dialog enter the default CyberStation user name and password shown on the following

illustration.

Note: The User Name and Password can be configured using ControllerUser objects.

Page 22: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 22

8. Click OK to logon.

Note: Don’t forget to enable DHCP Services on your PC, and connect the ACX 57xx to the network

when it reboots after you finish the commissioning process.

You may see the following system startup page for a few seconds while system initialization occurs.

Commissioning the ACX 57xx Controller

After connecting the IP address of the ACX 57xx controller, the main web commissioning page appears.

Page 23: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 23

The main page features two panes:

A side navigation pane for accessing the different configuration pages. The options listed on the side

navigation pane may differ based on the controller software model, the options you have enabled, or

additional installed options supplied by Schneider Electric.

The main display pane shows the currently active commissioning web page.

Controller Configuration

When you select Controller Configuration from the side navigation pane, the Controller

Configuration page appears.

Page 24: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 24

The following table describes the Controller Configuration fields that you can edit, as well as the

action buttons. You can also access this information by clicking Help below the page title.

Field Description/Action

Name Contains the name of the controller. You can enter any name

you wish in this field up to a maximum of 16 characters.

Spaces between name segments are not permitted.

Controller device names must be unique across a network

Description Enter a description of the controller up to 32 characters in

length

(optional).

ACCNet ID Identifies each controller on an Andover Continuum network

by a unique number between 1 and 190. Each controller

must have a unique ID on its particular network.

IP Address A logical 32-bit address that identifies a TCP/IP host. Each

controller requires a unique IP address. Each address has two

parts: a network ID, which identifies all hosts on the same

physical network, and a host ID, which identifies a host on

the network.

Subnet Mask Subnets divide a large network into multiple physical

networks connected with routers. A subnet mask blocks out

part of the IP address so that TCP/IP can distinguish the

network ID from the host ID. When TCP/IP hosts try to

communicate, the subnet mask determines whether the

destination host is on a local or remote network.

To communicate within a local network, computers and

controllers must have the same subnet mask.

Gateway Address The Gateway is the intermediate device on a local network

that stores network IDs of other networks in the enterprise or

on the Internet. To communicate with a host of another

network, configure an IP address for the default Gateway.

TCP/IP sends packets for remote networks to the default

gateway (if no other route is configured), which forwards the

packets to other gateways until the packet is delivered to a

gateway connected to the specific destination.

If you are using a proxy server, you must define a default

router here.

Probe Time Displays the time, in seconds, between controller probes.

A probe is a message that the device sends out to its

controllers to check their COMM status. Controllers respond

to probe messages to let the device know they are online.

When a device does not receive a response from a controller,

it changes the controller's COMM status to Offline.

Web Server Port The standard port for Web communications. The default

setting is 80.

The Web Server Port can be set to any number from 1 to

Page 25: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 25

65,534. If changed, browser requests must specify the port

number in the URL, for example, http://<IP Address>:<Web

Server Port>.

Transport Type UDP - This controller will communicate with other

controllers and Workstations primarily using the UDP

protocol.

TCP - This controller will communicate with other

controllers and

Workstations primarily using the TCP protocol.

TCP/UDP - This controller will communicate with other

controllers and Workstations primarily using the TCP

protocol, but can also speak to controllers and Workstations

that communicate primarily using the UDP protocol.

Action Buttons

Submit to Controller Submit all form data to the controller. After submitting data,

navigate to the Commit Changes page to write the changes

to flash memory and restart the controller.

Reset Form Undo any changes that were previously submitted.

Commit Changes The following page appears when you select Commit Changes from the side navigation pane.

WARNING:

Press the “Commit Changes/Restart Controller” button to commit the submitted changes to Flash Memory and restart the

controller. Upon restarting, any configuration changes made will be in effect.

Page 26: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 26

Page 27: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 27

Page 28: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 28

Hardware Requirements This section presents the hardware requirements for CyberStation version 1.93.

Minimum/Recommended Hardware Requirements

The following table shows the minimum and recommended hardware requirements for CyberStation version 1.93.

Hardware Requirements

Minimum Recommended

Intel® CoreTM 2, Duo, 1.66 GHz

or better1 Quad Core, 2 GHz or better

2 Gb RAM or higher1 4 Gb 15 Gb free space 30 Gb free space CD ROM drive CD ROM drive Video resolution: 1024 x 768 pixels Video resolution: 1024 x 768 pixels Parallel or USB port Parallel or USB port

1 Use Recommended requirement for systems with integrated video.

The following table shows the video-specific requirements for CyberStation version 1.93.

Video-Specific Requirements

Minimum Recommended 100 Mbps network port 1 Gb network port Graphics card with DirectX 9.x or later

with 256 Mb of dedicated RAM DirectX 10 graphics device with WDDM

1.0 or higher driver with 512 Mb of

dedicated RAM

Note: Andover Continuum uses stream 2 to display video through video interfaces. Per standard Pelco Endura video configuration, you should configure

stream 2. When doing so, be sure to set a lower resolution and smaller frame rate. Otherwise, the performance on your PC may be negatively affected. Be

aware that Andover Continuum only supports H.264 and MPEG4 video formats.

Upgrading from Previous Versions The same computer that you used to run previous versions of CyberStation may not be able to run Version 1.93. Please be sure

that your computer adheres to these hardware requirements, as well as the software requirements in the following section.

Note: Be sure that the hardware keys are the correct type for either a parallel or USB port on each PC.

Depending on the configuration of your system (standalone or multiuser), you must meet a set of software requirements for

your workstation PC prior to installing CyberStation. See the software requirements table that follows.

Stand Alone Multi-User (LAN)

Note: For all operating systems, Workstation:

Page 29: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 29

only the 32-bit environment is

supported; the 64-bit version is

not supported.

Windows Vista Ultimate (SP2)

OR:

Windows Vista Business (SP2)

OR:

Windows XP Professional (SP3)

OR:

Windows Server 2008 (SP2)

(does not include Windows Server

2008 R2)

OR:

Windows 7 Professional

OR:

Windows 7 Ultimate

Internet Explorer 7.0 or

Internet Explorer 8.0 on Windows

XP, Windows Server 2003, or

Windows Vista

.NET Framework 2.0 and .NET

Framework 3.5 (SP1)

Windows Installer 3.1

Microsoft Outlook 2007 for Windows

XP and Vista

Full Microsoft Outlook or Microsoft

Exchange software package1

Windows XP Professional (SP3)

OR:

Windows Vista Ultimate (SP2)

OR:

Windows Vista Business (SP2)

OR:

Windows 7 Professional

OR:

Windows 7 Ultimate

Internet Explorer 7.0 or Internet Explorer 8.0 on

Windows XP or

Windows Vista

.NET Framework 2.0 and .NET Framework 3.5

(SP1)

Windows Installer 3.1

Microsoft Outlook 2007 for Windows XP and

Vista

Full Microsoft Outlook or Exchange software

package1

Database Server - OS:

Note: For all operating systems, only the 32-

bit environment is supported; the 64-bit

version is not supported.

Windows Vista Ultimate (SP2)

OR:

Windows Vista Business (SP2)

OR:

Windows Server 2003 (SP2)

OR:

Windows Server 2003 R2 (SP2)

OR:

Windows Server 2008 (SP2) using SQL 20082

OR:

Windows Server 2008 R2 32-bit or 64-bit

modes using

SQL 20082

NET Framework 2.0 and .NET Framework 3.5

(SP1)

OR:

Windows 7 Professional

OR:

Windows 7 Ultímate

Database Server - SQL:

Microsoft SQL Server 2008 (SP1)

Microsoft SQL Server 2005 (SP3) or:

Microsoft SQL Server 2000 (SP4) 1. Required only for emailing or paging alarms and emailing reports.

2. No CyberStation or web.Client software installed.

Virtual Memory Requirements

Page 30: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 30

The virtual memory “Initial size (MB)” setting on your workstation PC should be set to a minimum of 1 GB. To make this

change:

In Windows XP:

1. Go to Start, Settings, Control Panel.

2. In the Control Panel, double click System. The System Properties dialog, shown on the next page, appears.

3. Click the Advanced tab and click Settings in the Performance box. The Performance Options dialog, also shown on the

next page, appears.

4. Click the Advanced tab. In the Virtual Memory box, click Change. When the Virtual Memory dialog appears, fill in the

desired paging file memory size (initial and Maximum).

5. Click OK as you back out of the dialogs.

Page 31: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 31

In Windows Vista and Windows 7:

1. Go to Start, Control Panel.

2. Click System and Maintenance (Windows Vista) or System and Security (Windows 7).

3. Click System.

4. Click Advanced system settings. The System Properties dialog displays.

5. Click the Advanced tab and click Settings in the Performance box. The Performance Options dialog, also shown on the

next page, appears.

6. Click the Advanced tab. In the Virtual Memory box, click Change. When the Virtual Memory dialog appears, fill in the

desired paging file memory size (initial and Maximum).

7. Click OK as you back out of the dialogs.

Page 32: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 32

Disabling Windows Firewall and Automatic Windows Updates

Be sure to disable Windows Firewall for all Windows operating systems. It is also mandatory that you turn off Automatic

Windows Updates for all Windows operating systems. To do so, access the Firewall and Automatic Updates through the

Control Panel and ensure that they are disabled.

Page 33: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 33

Andover Continuum Software and Firmware Compatibility Matrix Version 1.93

DB Server OS15Win Svr 2003 (SP2), Win Svr 2003 R2,

MS Win Svr 2008 (SP2)12, 13, MS Win Svr 2008 R212, 13

SQL Vers ion

MS SQL 20001 (SP4), MS SQL 2005 (SP3),

MS SQL 2008 (SP1)16, MS SQL 2008 R2 (SP1)16

Standard & Enterprise Editions

CyberStation PC OS15

Win XP Pro (SP3), MS Vis ta Bus iness (SP2)11, MS Vis ta Ultimate (SP2)11,

MS Win 7 Pro11, MS Win 7 Ultimate 11,

Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) 14

.NET v2.0 & .NET v3.5 SP

web.Cl ient Server OS15

Win XP Pro (SP3), MS Vis ta Bus iness (SP2)11, MS Vis ta Ultimate (SP2) 11

,MS Win 7 Pro11, MS Win 7 Ultimate 11,

(up to 2 connections)

Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) 14

(both up to 25 connections) .NET v2.0 & .NET v3.5 SP1

SQL Vers ion MS SQL Express

CyberStation SU (Cyber

/DB Server OS)15

Win XP Pro (SP3), MS Vis ta Bus iness (SP2)11, MS Vis ta Ultimate (SP2)11,

MS Win 7 Pro11, MS Win 7 Ultimate 11,

Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) 14

.NET v2.0 & .NET v3.5 SP1

web.Cl ient SU (CyberStation,

web.Cl ient Server, & DB Server OS) 15

Win XP Pro (SP3), MS Vis ta Bus iness (SP2)11, MS Vis ta Ultimate (SP2)11,

MS Win 7 Pro11, MS Win 7 Ultimate 11,

Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) 14

(a l l up to 2 connections) .NET v2.0 & .NET v3.5 SP1

web.Cl ient: Browser PC OS15

Win XP Pro (SP3), MS Vis ta Bus iness (SP2)11,

MS Vis ta Ultimate (SP2)11, MS Vis ta Home Premium (SP2)11, MS Win 7 Pro11, MS Win 7 Ultimate 11,

Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) 14

.NET v2.0 & .NET v3.0 (Video Only)

web.Cl ient: Browser MS IE 7.0, MS IE 8.0

Compatible Fi rmware Vers ions

NetControl ler I I 2.18, 9

ACX Series (5720/5740) 1.18

CX Control lers 1.5x

CX 9702 1.x

bCX1-CR-INF (Infinet) 1.0, 1.1, 1.24

i2 Control lers (Infinet) 3.x (3.3 to use xPUI4 Expans ion module)

2 Control lers -WL (Wireless

Only Infinet)3.5

i2608, i2624, i2804,

i2814, i2885, i28873.x

i2865-V, i2866-V, i2885-V 3.5

i2 Controllers-WL

(Wireless Only Infinet)3.5

Infinet Control lers 1.4 or grater

ACX 700 1.5x

ACX 780 1.5x

DCX 250 2.16

LSX 280 Not suported

bCX1-R, bCX1-CR (BACnet) 4.3, 4.4, 4.55, 10

b4920 4.2

b3 Control lers (BACnet) 4.3, 4.4, 4.5

b3865-V, b3866-V, b3885-V 4.5

b3 Control lers -WL

(Wireless Only BACnet)4.5

LAN

Con

figu

rati

onSi

ngle

Use

r Co

nfig

urat

ion

Exceptions :

Exceptions :

Exceptions :

1 MS SQL 2000 Standard and Enterprise (English) Editions supported. SQL Server 2000 10 Minimum v4.500047 required for XDriver Support on the BACnet bCX1-4040, & minimum v1.82.

Personal Edition is not supported. Please use MSDE 2000 for standalone installations. 11 Remote Access Service (RAS) not supported on MS Vista and MS Windows 7 machines. 2 .NET Framework 2.0 is not supported. 12 MS Windows Server 2008 is only supported with use of MS SQL 2008. 3 Requires CyberStation/web.Client 1.73 to use firmware’s new features. 13 MS Win Svr 2008 and MS Win Svr 2008 R2 are supported in 32-bit and 64-bit 4 v1.2 required on bCX1-CR-INF to set comm. port for Wireless. environments only when used for a LAN system database server (with no CyberStation 5 v4.5 required on bCX1-R/bCX1-CR to set comm. port for Wireless. and/or web.Client software installed on it). 6 BACnet schedules are not compatible for versions below v1.73, only Infinity schedules. 14 MS Windows Server 2008 R2 version is not supported. 7 v1.81 Video Features are not supported on Win2000 Pro or Win2000 Svr. 15 For all machines with CyberStation or web.Client software installed, only operating systems 8 v1.74 SP2 required for hardware support. Does not support v1.8x features. running in 32-bit environments are supported. 64-bit environments are not supported. 9 Special IOU module firmware versions required for FIPS support: 16 SQL Native Client version 10 and above are not supported.

Page 34: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 34

AC-1 and AC-1A: Minimum v25; AC-1 Plus: Minimum v29. Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at v3.3 and b3 controllers must be at least at v4.3.

The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be construed as a commitment by Schneider Electric.

Installing CyberStation

The following installation procedures for CyberStation are based on the Windows XP Professional user interface. Note that the

installation process is similar for other operating systems if Windows XP is specified.

Installing Continuum CyberStation Files

The following procedure installs the Continuum CyberStation files on your workstation PC. This procedure applies to both

first-time and upgrade installations.

1. Power up the workstation PC.

2. Install a printer on LPT1, or enable the printer port on LPT1 of each workstation PC so the security key connected to the

parallel port will be recognized. (This is not required if the USB key is used.)

3. Insert the CyberStation CD into the CD drive in your PC.

4. The installer application should automatically begin. If it does, go to step 9. If it does not, go to step 6.

5. Double click the My Computer icon on your desktop.

6. Double click the Compact Disk drive icon.

7. Double click the Setup.exe file.

8. When the CyberStation Installation window appears, click Install CyberStation as shown.

Page 35: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 35

9. If you do not have the Microsoft VS 2008 C++ Redistributable installed, an InstallShield Wizard appears and indicates that

this application is required before the CyberStation installation begins.

Click Install.

Continuum then checks to ensure that Microsoft .NET Framework 3.5 is also installed. If not, the following message displays:

10. Follow these instructions, discontinue this CyberStation installation, and install the .NET Framework 3.5 from the

Continuum release CD.

Once these requirements are installed, return to this installation and when the initial CyberStation Installation screen displays

once more, click Install.

When the Welcome to InstallShield Wizard for CyberStation displays, click Next.

Page 36: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 36

11. The License Information window appears. Read the agreement, select I accept the terms in the license agreement, and

click Next.

12. The Customer Information window appears. Enter your User Name and Organization:

Page 37: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 37

13. Click Next.

14. The Destination Folder window appears:

The default location where CyberStation files are installed is shown in the Destination Folder field. If the location is

acceptable, go to Step 16. If it is not acceptable go to Step 14.

15. Click the Change button to bring up the Change Current Destination Folder dialog.

Page 38: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 38

16. Select the folder that you wish to use for the CyberStation installation program. Click OK. Click Next.

17. From the Ready to Install the Program dialog, click Install to start the installation.

18. The Installing Continuum window appears and displays a progress bar that indicates the percentage of completion as the

installation progresses.

19. A question popup dialog appears asking if you want to view the Read Me file. Click Yes to open the file or No to continue.

20. Toward the end of the installation a Question dialog appears, asking you if you want to run the Database Initialization

program now. Click Yes to start Database Initialization (Proceed to Installing the Continuum Database. If you click No, go to

Step 21.

22. Click Finish and then click Exit. You need to complete the Continuum Database Initialization. If you have a standalone

system, please proceed to Installing the Continuum Database. If you have a multi-user system, please proceed to the section,

Installing the Continuum Database on Multi-User LANs.

For first time installations:

23. Insert the hardware key found in the CyberStation shipment box into the respective port connector (parallel or USB) of each

workstation PC.

For an installation upgrade:

24. If you are upgrading to version 1.93, you may need to update your hardware security key based on the version of

CyberStation you are running. If your CyberStation software is a pre-1.9 version (such as, v1.6, or v1.81), you will have to

upgrade your key to support v1.93.

If you are running version 1.9 or higher, you will not need to update your security key; your key is already enabled to support

version 1.93.

Page 39: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 39

Note: During an upgrade, you will be prompted to remove and reinsert your

security key. Click OK to acknowledge this message and continue with

the upgrade.

Installing the Continuum Database This procedure covers the following sections:

Enabling Local Administrator Permissions for Windows Vista and Windows 7

Installing the Continuum Database for the First Time on a Standalone System

Creating a New Continuum Database

Updating a Standalone Continuum Database

Enabling Local Administrator Permissions for Windows Vista and Windows 7 If you are installing on a Windows Vista or Windows 7 machine, follow this procedure before installing the Continuum

standalone database. If you are not using Windows Vista or Windows 7, proceed to the next section, Installing the Continuum

Database for the First Time on a Standalone System.

You must enable the system’s local administrator account permissions when using Windows Vista or Windows 7. First, change

the Administrator password: Step 1: In the Start menu, click Control Panel.

Step 2: Click the User Accounts link.

Step 3: Click the Change account type link.

Step 4: Make sure the Administrator account is selected, then click the Advanced tab.

Step 5: Under the Advanced User Management group, click Advanced.

Step 6: To first set the password, double-click the Users folder.

Step 7: Right-click the Administrator entry. Step 8: Click Password (Windows Vista) or Set Password (Windows 7).

Step 9: Click Proceed.

Page 40: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 40

Step 10: Enter a new password and then re-enter that password to confirm.

Step 11: Click OK.

Next, enable the administrator account: Step 1: Right-click the Administrator entry.

Step 2: Click Properties.

Step 3: Click to clear the check from the Account is disabled checkbox.

Page 41: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 41

Step 4: Click OK.

Installing the Continuum Database for the First Time on a Standalone System

A first-time database installation on a standalone system happens in two steps via the Database Initialization dialog:

Step 1: Installing the SQL Express database engine.

Step 2: Creating a new Continuum database.

Note: After successful installation, the Continuum Database Initialization dialog automatically appears.

Installing SQL Express Via Database Initialization Dialog Follow this procedure:

1. From the Start menu, select Programs > Continuum > Database Initialization.

2. Select Stand Alone from the Continuum Database Initialization dialog.

Page 42: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 42

Note: After clicking Stand Alone, it may take several minutes for the data to populate during the first database initialization.

The Database Initialization dialog appears.

Page 43: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 43

3. Select the Create New Database radio button. Note that Microsoft SQL Server is shown in the DBMS Name field

dropdown menu.

4. Ensure that Continuum (default setting) appears in the Data Source Name field.

5. Ensure that (Workstation Name)\SQLEXPRESS appears in the Server Name field. For example, QUALPC217 is the

workstation name used in the previous dialog.

6. Leave the Database Name at its default, ContinuumDB.

7. Enter the default login ID, Andover97, in the User Login ID field.

8. Enter your user password in the User Password field.

9. Re-enter your password in the Confirm Password field.

10. DB File Location: If you leave DB File Location at its default path, then you must leave SQL Express at its default path

when it is installed. If you browse a different path for DB File Location, then you must browse SQL Express to the same file

path when it is installed.

11. Leave the Database Size at its default setting.

12. Enter a system administrator password of your choice into the Sa Password field.

Page 44: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 44

This password must meet Microsoft SQL Server rules for the composition of a password: The password must be at least eight characters long.

The password must not contain all or part of the user’s account name (three or more alphanumeric characters).

The password must not contain the following characters: comma (,), period (.), hyphen (-), underscore (_), or number sign (#).

The password must contain characters from three of the following four categories:

o Uppercase letters (A...Z)

o Lowercase letters (a...z) o Digits (0...9)

o Non-alphanumeric characters, such as exclamation (!) and dollar ($)

Otherwise you may receive this warning:

13. In the Windows User Name field, enter your Microsoft Windows system user name here. This is necessary with SQL

Express. You must have administrative access in order to run the automated scripts that are part of the database initialization

process.

14. Enter your Microsoft Windows system password and confirm that password in the Windows Password and Confirm

Password fields, respectively.

15. In the Device Information group, verify that the Database and Log names are unique.

Note: The device information and log file name should be unique for each database created. An error occurs, and database creation fails, if these fields are not

unique.

16. Check the checkboxes as follows:

Note: Be sure the Create Default List Views, Create System List Views, Create System Alarm Enrollments, and Enhanced Alarm Logging boxes are

checked. If you leave them unchecked, CyberStation does not import the necessary dump files. The dump files generate all of the default views, so the

listviews and alarms are not created. In addition, faster alarm logging is not activated. The dump file import happens as soon as the workstation is started for

the first time after installation and the appropriate files are placed in folders. For more information on Listviews, alarms, and alarm logging, please see the

Continuum CyberStation online help.

a. Create Default List Views - Check this box to import and create listviews (from the ASCII dump file, DefaultListViews.dmp) for all

Cyber- Station object classes.

b. Create System List Views - Check this box to import and create listviews (from the ASCII dump file, List.dmp) for system information

other than object class defaults (for example, all events).

c. Create System Alarm Enrollments - Check this box to import configured system AlarmEnrollment objects (from the ASCII dump file, SystemAlarms.dmp). These define the basic conditions under which CyberStation points go into alarm.

CAUTION

The password you enter here is required to execute scheduled SQL Server tasks. Should you later change

your Windows password, these scheduled tasks will no longer execute. To correct this, access the Scheduled

Tasks in Windows and change their password with the Set Password button in their Properties dialog

Page 45: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 45

d. Create/Update Graphical Report Settings - Check this box to import graphical report templates. CyberStation supplies many Report

templates that include bar-chart templates, pie-chart templates, and trend templates, giving Reports a certain default “look and feel.” If you

do not check this box, then these report templates will not be available. For more information on Reports, see the Continuum CyberStation online help.

e. Enhanced Alarm Logging - Check this box to activate an enhanced method that automatically speeds up the process of logging alarms

with workstations. Without enhanced alarm logging, configuration of workstation recipients in EventNotification objects becomes more cumbersome.

f. Enhanced Alarm Delivery - This checkbox is intended for a system with multiple workstations. Check this box only if you intend to add more workstations to the system. If more workstations will not be added, then leave it unchecked.

g. Extended Logging Backwards Compatibility - If you want to use pre-Version 1.7 “old” extended logging, in addition to “new” extended

logging, be sure this checkbox is checked.

17. Click the Continue button.

The Is SQL Express Installed dialog appears.

For first time installations, you should see this dialog. If, in the very unlikely event, you do not see this dialog, it means SQL

Express is already on your computer for some other reason.

If you see this dialog, go to the next step. If you do not see this dialog, and SQL Express is installed, proceed to the next

section, Creating a New Continuum Database.

18. Select the Install SQL now radio button and click OK. SQL Express is then installed automatically.

During SQL Express installation, the software checks your computer for certain problems that could complicate SQL

installation and/or the creation or update of the Continuum database. There are several different scenarios. For example,

thirdparty software may generate license-agreement issues. For a detailed description of these issues, how CyberStation

resolves them, and a list of error messages, please see SQL Express Installation Error Messages.

If there are no problems, the Select Folder dialog appears.

Page 46: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 46

19. The Extracting Files progress window appears. The unpacking takes approximately 1 to 5 minutes. Next, the Microsoft

SQL Server 2005 Setup progress window appears. This also can take several minutes. After the installation has completed,

the reboot dialog appears, which may take up to 60 seconds. Do not proceed

until this dialogue appears. Click OK and reboot your computer.

Creating a New Continuum Database

Once the installation of the SQL Express database engine is successfully completed, the Continuum Database Initialization

window automatically reappears on your workstation PC. Follow this procedure to install the Continuum database:

1. Click the Stand Alone button. The Database Initialization dialog appears.

2. Select Create New Database.

Page 47: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 47

3. Fill out this dialog the way you did in the Installing SQL Express Via Database Initialization Dialog. This includes checking

the appropriate items in the database initialization checkboxes.

4. Click Continue.

5. When the database has been successfully created, the Database Installation Progress screen appears with the message:

Database successfully created.

6. Click the OK button and proceed to Setting Up Workstation Parameters.

Setting Up Workstation Parameters

Setting up workstation parameters is the final CyberStation installation procedure. Go to the Continuum Database

Initialization dialog.

1. Click Workstation.

The Workstation Configuration dialog, shown on the next page, appears.

2. Select the Workstation tab.

3. In the Workstation Name field, enter a name for the workstation.

The following rules apply:

The name can be up to 16 characters.

Be sure that the workstation name starts with an alphabetic character (A-Z) and only contains alphanumeric

characters, underscores (_), or periods (.) For example: Engws

Page 48: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 48

The name you supply here can be changed to a Windows standard long file name after starting the software.

4. In the Folder Name field, enter the same workstation name (above) followed by the word “Folder”. Avoid using spaces. For

example: EngFolder

This name can also be changed to a Windows standard long file name after starting the CyberStation software.

5. All workstations require an ID. If you have a BACnet system, in the Device Node ID field, enter the BACnet ID for the

workstation. (Each workstation requires a unique BACnet ID number.) It can be any unique ID number between 1 and

4194302. Survey your site and consult your network administrator before setting this ID to be sure that there are no conflicts.

Note: In a BACnet network, this ID is unique for workstations and controllers alike and is vendor-independent.

Note: The Device Node ID number must be recorded for future reference.

6. In the Network ID field, enter the EnergyNet ID number assigned for the workstation. The ID number must be between 191

and 254 and is usually assigned by the site administrator. The Network ID number should be recorded for future reference.

Note: If you have exceeded 64 workstations, set the Network ID to 0 and set the Device ID to a unique number.

7. Select the Database tab.

Page 49: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 49

8. Verify that the fields on the Database tab contain the correct information. This is the information that you entered during the

database initialization procedure (for standalone and multi-user) earlier in this guide.

9. Click OK to return to the Continuum Database Initialization dialog.

10. Click Close to complete the CyberStation installation.

Page 50: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 50

Create a Network When you configure an access control network, the first object you create is the network itself.

1. In Continuum Explorer, right click Root, select New, and then select Network.

2. Enter a name for the network for Object Name, and click the Create button.

3. In the Network editor, enter the Universal Time Coordinate (UTC) offset in minutes for Time Zone.

The UTC offset is the difference between your local time and Greenwich Mean Time (GMT). Enter “-” if local time is behind

GMT.

Note: “-300” minutes is an example of the Time Zone offset for

Eastern Standard time.

4. Click OK.

Page 51: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 51

Create a Controller

1. In Continuum Explorer, right click the existing network object, select New, and then select InfinityController.

2. Enter a controller name for Object Name, and click the Create button.

3. In the InfinityController editor, enter a unique number from 1 to 190 for ACCNetID.

Note: This must match what was entered in the web configuration page.

The ACCNetID value uniquely identifies the controller within the access control network.

4. Select the controller model from the Controller Type dropdown menu.

For example, select 5740 for an ACX 5740 controller.

Page 52: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 52

5. Select the Network tab.

6. Enter the IP address of the controller and subnet mask, and if required, enter the default router. You obtain this information

from your IT administrator.

7. Click Apply.

8. Select the General tab, and then click the Teach button.

9. In the Select Teach Mode dialog, select the InfinityController Teach radio button, and click OK.

Note: To confirm that the Comm Status is online, click the Refresh button.

10. Click OK to close the InfinityController editor.

Configure IOU Modules

After you finish configuring a controller with the Comm port editor, you can define your input and output. Start by defining the

IOU modules with the IOUModule editor.

IOU modules are electrical units that contain a number of input and/or output circuits that are electrically and sometimes

physically attached to controllers. They provide controllers with the ability to interface with the outside world. There are four

types of IOU Modules:

� Input modules

� Output modules

� Mixed input and output modules

� Special-purpose modules

Page 53: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 53

Creating an IOU Module Object

The following steps allow you to add an IOU Module object for an IOU Module connected to a controller.

1. Right click the controller that you want to own this module, select New, and then select IOUModule.

2. When the New dialog appears, name the IOUModule and click Create.

Use the General tab to enter basic information about the IOU module.

Description

The description is optional, but a good description of the IOUModule object helps others when they need to test, modify or

manipulate the network. To enter a description, type up to 32 characters (including spaces) in the text field.

IOU Number

Enter the IOU number here. You must manually assign a unique number (between 1 and 32) for each IOU module on a

network controller. Physically label the IOU modules with the numbers you assign. This number is not the same as the 12-digit

module ID # assigned to the individual module at the factory. You will use this number when you configure points on this

controller.

Model Number

The model number identifies the type of the IOU Module and is read from the module.

Module ID and Program ID

Page 54: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 54

These Schneider Electric-assigned numbers appear after the Learn process. The only time you will need these numbers is when

speaking to a Schneider Electric Support Representative. These numbers will help our staff to answer your questions. You may

manually enter the Module ID number in this field, (if you know it), rather than following the Learn process.

Commissioning an IOU Module

Perform this procedure after installing the IOU module on the controller.

1. In the IOUModule editor, click the Learn button. A dialog displays requesting the operator to press the Commission button

on the physical module.

2. At the IOU Module, press the Commission button on the front panel. The dialog at the workstation should disappear

indicating that it received the information from the module. If the module is not easily accessible, you can enter the module ID

found on the label inside the cover of the module into field, and click the Apply button.

3. In the IOUModule editor, click the Refresh button. The ModuleID for commissioned module, the ProgramID field, and the

IO model type (i.e., AO-4-8) are automatically entered. This information was received from the module. Also, the Comm

Status should be Online.

Designate the Primary Access Server

The Primary Access Server is the CyberStation workstation that you designate to record access events in the CyberStation

database. If your network has multiple CyberStation workstations, you also should designate another workstation as a

Secondary Access Server.

1. In Continuum Explorer, right click the workstation that you want to make the primary access server, and select Edit.

2. In the General tab of the Device editor, check the Primary Access Server check box, and click OK.

Page 55: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 55

3. When prompted to teach the controllers and workstations about this workstation, click Yes.

Create CyberStation Points

A point is an object that stores a value, such as an input indicating the status of a door lock, an output that locks or unlocks a

door, or a True-False condition that triggers an alarm. In access control systems, you most often work with the following types

of point objects:

Point Type Use in Access Control Systems

Supervised

InfinityInput

Used to monitor contact status as well as the condition of the

wiring, allowing CyberStation to detect that wiring was

tampered with.

Digital InfinityOutput Used to specify a digital (On or Off) value, allowing

CyberStation to change the status of a switch or a contact.

InfinityNumeric Software point that stores a number value, including an

On/Off value (1 or 0).

InfinityDateTime Software point that stores a date and time value.

InfinityString Software point that stores text.

Points enable you to monitor and control access events. You use these points with schedules, alarms, and other objects to

establish routine access control and to respond to unauthorized access events.

Create an InfinityInput Point Supervised input points can monitor:

� The status of a contact or switch, and

� Whether the wiring for the contact or switch was tampered with.

Supervised points can have one of three values: On, Off, or Trouble.

You create a supervised input point for each input (for example, from a contact sensor) from the devices wired to channels at

each controller in your network.

1. In Continuum Explorer, right click the controller where you want to create the point, select New, and then select

InfinityInput.

2. Enter a point name for Object name, and click the Create button.

3. In the General tab of the InfinityInput editor, enter the units for this point.

Page 56: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 56

For example, define the meaning of the On value: “On = Closed.”

Leave the Value field at 0. The system updates the value with the input from the associated controller channel.

4. Select the Settings tab.

5. Select Supervised for Elec Type.

6. Enter the controller channel number (marked on the controller) to which this input is wired.

7. Enter $####### for Format.

$ indicates a text value. Each # is a placeholder for one character. This format enables On, Off, or Trouble to be reported for

the value.

$ indicates a text value. Each # is a placeholder for one character.

Use a period to indicate the position of the decimal point, if needed An example for the Format value is “$#####.#”

Page 57: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 57

8. Select the appropriate input type based on the wired configuration of the switch (normally open with a resistor in series,

normally closed with a resistor in series).

9. Click OK.

Create an InfinityOutput Point

An InfinityOutput point is a digital point that stores the value of a signal sent to an access control device. The value is sent via

the controller channel to which the device is wired, and is used to control the device. For example, the output may lock a door.

An output point can have a value of On or Off. You create an output point for each output (for example, to a door lock) to the

devices wired to channels at each controller in your network.

1. In Continuum Explorer, right click the controller where you want to create the point, select New, and then select

InfinityOutput.

2. Enter a point name for Object name, and click the Create button.

3. In the General tab of the InfinityOutput editor, enter the units for this point.

For example, define the meaning of the On value: “On = Unlock.” Leave the Value field at 0.

4. Select the Settings tab.

5. Select Digital for Elec Type.

6. Enter the controller channel number (marked on the controller) to which this output is wired.

7. Enter $### for Format.

$ indicates a text value. Each # is a placeholder for one character. This format enables On or Off to be reported for the value.

Page 58: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 58

8. Click OK.

Create an Infinity Numeric Point An Infinity Numeric point stores a number value, such as:

VALUE EXAMPLE

System constant Maximum occupancy for a specific area

Result of a calculation Current occupancy of the area

Logical value On or Off value set by a schedule

1. In Continuum Explorer, right click the controller where you want to create the point, select New, and then select Infinity

Numeric.

2. Enter a point name for Object name, and click the Create button.

3. In the General tab of the Infinity Numeric editor, enter the units for this point.

For example, define the meaning of the point value: “Max. Occupancy = 100” or “On=Occupied.”

4. Leave Value empty, or enter a value, depending on how you intend to use this point.

For example, if the point will be a constant, enter the number. If the value will be the result of a calculation, do not enter

anything in the field.

5. Enter the format of the value for Format.

$ indicates a text value. Each # is a placeholder for one character. Use a period to indicate the position of the decimal point, if needed

An example for the Format value is “$#####.#”.

Page 59: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 59

6. Click OK.

Create Areas

An area is a space that can be accessed only by passing through an access control device, such as a card reader or keypad. Each

area can be accessed through one or more doors where access control devices are configured.

Page 60: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 60

For example, the manufacturing floor of a small facility might have doors leading to other areas of the facility, such as an

office area, stock room, and emergency exit to the outside.

Factors to Consider When Defining Areas

Unlike Door objects, which correspond to actual doors in your facility, Area objects are not necessarily direct representations

of each physical space in your facility. The number of Area objects that you need to create depends on many factors, including:

The size and physical layout of your facility

The movement of personnel into, out of, and through your facility

The degree of access control that you require for the movement of personnel within the facility

The types of personnel who need access to various locations in your facility and when access is needed

After you create an area object, you configure doors that access the area. You also assign the area to personnel who need

access to it. In addition, you can attach schedule points to Door and Personnel objects to determine when access can occur.

Create an Area Because the doors accessing an area may be managed by different controllers, you typically create a folder for Area objects

from Root.

1. In Continuum Explorer, right click Root, select New, and then select Folder.

2. Enter a folder name, and click the Create button.

3. Right click the folder, select New, and then select Area.

4. Enter an area name, and click the Create button.

5. In the Area editor, click OK.

You can now assign doors and personnel to this area.

Create Doors

Door objects, along with Area and Personnel objects, are the fundamental elements of your access control system. Door objects

are highly customizable, and you can configure doors to meet the access control requirements of specific locations. You can

configure access control devices, such as card readers and keypads, on one side of a door (single-reader door) or on both sides

(dual-reader door).

When to Create a Door

You create Door objects only for doors that have access control devices associated with them. If you want to monitor a door

that is simply closed or locked under normal circumstances, such as a fire door, you can do this by setting up supervised input

points for the door switch and contacts.

Data that Defines a Door

You will need the following information to define each door:

Card-format information for access-card sets

Site codes (Wiegand or ABA card formats only) accepted at the door

Area(s) to which the door provides access

Page 61: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 61

Type of validation needed at the door (by site code, card number, personal identification number [PIN], etc.)

Channel numbers for card reader and keypad inputs

Channel numbers for door inputs and outputs

You can also attach schedule points to a door to determine when the door is locked or unlocked or when no access is allowed.

Create a Door You create Door objects in the controller to which the door and reader inputs and outputs are wired.

1. In Continuum Explorer, right click the controller where you want to add the door, select New, and then select Door.

2. Enter a door name, and click the Create button.

3. In the Door editor, select the Card Formats tab.

4. If you use Wiegand cards, enter the site code(s) used with your access cards.

Note: You can have up to four site codes per door.

5. Select the card format, Wiegand or ABA, and then select the individual formats that you want the reader to recognize.

Note: The FIPS-PIV options are included in the Wiegand Formats section. Cyberstation version 1.9 and higher supports this

special personnel category for federal employees and contractors whose security identification must comply with the Federal

Information Processing Standard for Person Identity Verification (FIPS-PIV). In Cyberstation you can configure door and

Personnel objects to accommodate FIPS-PIV card or “credential” holders and FIPSPIV card readers. For more information, see

Adding FIPS-PIV Card Credentials in Chapter 4, Advanced Topics for Access Control. Refer also to the CyberStation help

topic, “Defining a Custom FIPS-PIV String Format.”

6. Select the Entry Reader tab.

7. Enter the channel number on the controller that is connected to the card reader at this door.

8. Select the area to which the door provides access.

9. Select the access validation options required at this door.

Page 62: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 62

10. If the door has readers on both sides, select the Exit Reader tab, and repeat steps 7 - 9 to configure the second reader.

11. Select the Channels tab.

12. Enter the channel number where each input or output is wired.

Channel Description

Door Output Channel to which the door lock is wired.

ADA (Americans

with Disabilities

Act) Output

Channel to which an electronic door opener is wired.

Alarm Output Channel that will be energized when an alarm condition is

active at this door.

Exit Request Input Channel that receives input from a motion detector, request-

to-exit (REX) button, or other REX device.

Door Switch Input Channel to which the door switch is wired.

The door switch monitors whether the door is open or closed.

Page 63: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 63

You also select the resistor type for the switch.

Bond Sensor Input Channel to which a bond sensor is wired. A bond sensor

determines the physical position of the door latch. You also

select the resistor type for the sensor.

ADA (Americans with Disabilities Act) Exit Request Input Channel for input that requests that the door be opened for a

person to leave the area accessed by this door.

ADA (Americans with Disabilities Act) Input Channel for input indicating that the card holder has ADA

access enabled on his or her access card.

13. Select the Options tab.

14. Under Send Access Events, select the events you want to log for this door.

The events that you select for this door can be shown in logs, ListView and EventView windows, and reports. Events not

selected here are not captured and cannot be retrieved for later viewing and reporting.

15. Click OK.

View Doors Assigned to an Area

1. In Continuum Explorer, expand the folder where you created areas, and double click the area to which you assigned the new

door.

2. In the Area editor, select the Doors to Area tab.

The door you created now appears in the list. The list indicates whether the door provides access to the area, exits the area, or

both.

Page 64: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 64

3. Click Cancel.

Create Personnel A Personnel object stores the access information for each person authorized to enter your facility. Personnel objects can also

store personal and employee data for each person.

Access-Control Information in a Personnel Object

You can specify access control information for each Personnel object, such as:

Card format

Site code

Page 65: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 65

Card number

Card expiration date

Areas to which the person has access rights

Schedules points that determine when the person can access assigned areas

More advanced access control settings, such as area clearance levels and executive privilege, can also be defined in a Personnel

object. These are described in greater detail in the CyberStation online help.

In addition, if you have purchased the badging option, you can create ID badges for Personnel objects. The badges can include

a photo, signature, fingerprint, etc., to identify the card holder.

Methods of Creating Personnel Objects You have several options for creating Personnel objects:

You can enter new Personnel objects in the Personnel Manager dialog.

You can use the Personal Import Utility to import personnel records from another application into CyberStation. Once

imported, these records become Personnel objects that you can edit and manage in the Personnel Manager.

You can import personnel records from a .CSV file and save the imported data as Personnel objects.

You can create Personnel objects from templates.

You can add new Personnel objects from Continuum Explorer.

Open the Personnel Manager for the First Time

The Personnel Manager automatically opens when you double click a Personnel object in Continuum Explorer. However, if

you have not yet created any Personnel objects, you create a new Personnel object in Continuum Explorer, which also opens

the Personnel Manager.

You typically create one or more folders in which to store Personnel objects.

1. To create a Personnel folder in Continuum Explorer, right click Root, select New, and then select Folder.

2. Enter a folder name, and click the Create button.

3. Right click the folder, select New, and then select Personnel.

4. Enter a name for the Personnel object (for example, you might want to enter the last name and first initial of the person), and

click the Create button.

The Personnel Manager opens.

Page 66: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 66

5. In the Details tab, enter the person’s full name.

6. Select the card format for Card Type.

7. For Wiegand cards, enter the site code for the card. For FIPS-PIV cards, enter agency code and system code.

8. Enter the card number. For FIPS-PIV cards, enter credential number.

9. Under Access Rights, expand the UnAssigned areas list.

10. Select the check box next to areas this person can access.

Page 67: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 67

You can expand an area to attach a schedule point. Schedule points are described in “Task 10: Create Schedules” on page 68.

11. Click Apply.

Note: Cyber station version 1.9 and higher supports a special personnel category for federal employees and contractors whose

security identification must comply with the Federal Information Processing Standard for Person Identity Verification (FIPS-

PIV).

In Cyber station you can configure door and Personnel objects to accommodate FIPS-PIV card or “credential” holders and

FIPSPIV card readers. For more information, see Adding FIPS-PIV Card Credentials in Chapter 4, Advanced Topics for

Access Control.

Create a Personnel Object in the Personnel Manager

When the Personnel Manager is open, you can continue creating Personnel objects without closing and reopening it each time.

1. In the Personnel Manager, click the Add Record button.

2. Repeat steps 5 - 11 above to enter information for this person.

3. When you finish adding Personnel objects, click OK to save the current object and close the Personnel Manager.

4. Proceed to “Task 10: Create Schedules” on page 68.

Note: An alternate method for creating a Personnel object is with the Personnel Editor. Refer to the “Personnel Editor” topic in

the Cyber Station online help for more details.

Create Schedules A schedule is a graphical calendar of events that CyberStation uses to determine when activities occur. Access-control

activities that you can manage with schedules include:

When doors are locked or unlocked

When personnel have access to areas

Page 68: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 68

About Schedule Points Schedules use the following points to determine when the schedule is active and which CyberStation objects are controlled by

the schedule:

Infinity DateTime points that are updated with occupied and unoccupied times

An Infinity Numeric or Infinity Output point whose value is set by the schedule. Other objects that reference this

point, such as a door, are controlled by the schedule that sets the point value.

Create and Configure a Schedule You create schedules in the controller where the schedule will be used. (Later, you can use the Schedule editor’s Mass Create

feature to copy the schedule to other controllers in your network, if needed.)

1. In Continuum Explorer, right click the controller, select New, and then select Schedule.

2. Enter a schedule name, and click the Create button.

3. In the Schedule editor, select the Configuration tab.

Page 69: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 69

4. Under Point Configuration, use the browse button to locate each of the following points:

An InfinityDateTime point that the schedule updates with the next occupancy time (the date and time at which an area

will next be occupied)

An InfinityDateTime point that the schedule updates with the next unoccupancy time (the date and time at which an

area will next be unoccupied)

5. Use the browse button to locate the InfinityNumeric point that the schedule will set for Occupancy Point.

The value of this point will be set to On (Occupancy Time is now.) or Off (Unoccupancy Time is now.).

6. Check the Automatic Download check box, and select the day of the week and the time you want CyberStation to

download the schedule to the controller.

7. Click OK.

8. In Continuum Explorer, right click the workstation that you want to perform the schedule download, and select Open.

9. In the General tab of the Device editor, click the Auto Download check box, and click OK.

Page 70: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 70

Each week, at the day and time you selected in the schedule, this workstation downloads the next seven days of the schedule to

the controller.

Attach a Schedule Point to a Door After you create and configure a schedule, you attach the point you selected for the Occupancy Point to the objects you want

the schedule to control.

1. In Continuum Explorer, double click the door to which you want to attach the schedule point.

2. In the Door editor, select the Options tab.

3. Click the browse button next to one of the schedule fields, and navigate to and select the schedule point you want to attach.

You can use schedule points to control the door in two ways:

Attach the point to . . . To . . . Door Force Lock Schedule Lock the door, with access allowed to valid personnel when the

schedule is On, and

Lock the door, with no access allowed when the schedule is Off.

Door Force Unlock Schedule Unlock the door, with no access validation required when the

schedule is On, and

Lock the door, with access allowed to valid personnel when the

schedule is Off.

4. If you are using the Force Lock option, select the Entry Reader tab, and ensure that the Door Force Lock Schedule check

box is selected for Normal under Access Validation. Repeat for the Exit Reader tab if this is a dual-reader door.

5. Click OK.

Attach a Schedule Point to an Area in a Personnel Object

Page 71: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 71

Attaching schedule points to areas in a Personnel object enables you to specify when this person can access the assigned areas

without affecting access to the areas by other personnel.

For example, you may want permanent employees to have access to your facility at any time. You may also want temporary

workers to have access only during the regular business day and be denied access after hours. You can limit the times of access

for temporary workers by attaching schedule points to area assignments in their Personnel objects.

If . . . Then . . .

A schedule point is attached to

an area in the Personnel object

the person can access the area only when the schedule

associated with the point is active.

No schedule point is attached

to an area in the Personnel

object

the person can access the area as determined by schedules (if

any) that are attached to doors to the area.

1. In Continuum Explorer, double click the Personnel object that you want to edit.

2. In the Personnel Manager, under Access Rights, expand Assigned, and then expand an area where you want to attach a

schedule point.

3. Click the icon next to Add Schedule to display the Add Schedule dialog.

4. Select the browse button next to Schedule Points Location to locate, and select the controller with the schedule point that

you want to add.

5. Select a schedule point, select the area(s) where you want to attach the point, and click OK.

Page 72: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 72

6. Click OK.

Monitoring an Access Control System

When your access control system is configured and operating, CyberStation has numerous features that enable you to monitor

access control activity. This chapter introduces the following features:

Alarm Status bar and Active Alarm View window

EventView windows

ListView windows

Responding to Alarms When you configure alarms, you typically specify that an alarm message be displayed at one or more Cyber Station

workstations. At a workstation, alarm messages appear either in the Alarm Status bar or in the Active Alarm View window,

depending on settings in the Event Notification object associated with the alarm.

About the Alarm Status Bar

Page 73: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 73

An alarm message is displayed in the Alarm Status bar when an alarm is triggered. If multiple alarms are active, the alarm

displayed in the status bar is the first alarm that would appear in the list of alarms in the Active Alarm View window.

Buttons to the left of the message enable you to silence, mute, or acknowledge the alarm, and to perform other related actions.

About the Active Alarm View Window The Active Alarm View window notifies you of alarms and provides information about current alarm conditions. The window

displays automatically when an alarm occurs if you selected the Display Alarm View option in the EventNotification object

associated with the alarm.

If the window does not display automatically, you can display it by clicking the Alarm icon in the Alarm Status bar. You can

open this window whether or not any alarms are currently active.

This window updates in real time as alarms occur, are responded to, and/or the affected objects return to their normal state.

By default, alarms are sorted by priority. Alarms with a priority of 1 are considered the most urgent. They appear at the top of

the list. Use buttons to the left of the entries in the list to respond to alarm notifications.

Monitoring Live Access Events Active EventView windows are objects that provide real-time information about access events at doors that you specify. Using

EventView windows, you can monitor ongoing activity, both routine and unexpected.

Page 74: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 74

About Creating EventView Objects You create EventView objects in the EventView editor. You can create multiple EventView objects, each customized to

display selected events from specific doors.

Settings you can define in the EventView editor include:

Sort criteria to determine the display order of events

Doors and events that you want to monitor

Fonts and colors for different event types

You can further customize an EventView window from menu options in the window itself. For example, the Add/Remove

Columns option in the View menu lets you select the columns you want to display. You can also drag columns to change their

sequence in the window.

Using ListView Windows

ListView windows are objects that display a list of attribute values for an object class, such as Door objects or Personnel

objects. You typically use ListView windows when you want to review the event history of an object or a person. For example,

reviewing the event history may help you resolve a recurring problem, such as frequent Door Ajar events at a specific door.

Page 75: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 75

About Predefined ListView Objects

Several predefined ListView windows for access events are available from the ListViews page of the CyberStation main menu.

The Personnel page also has predefined Listview windows for personnel related lists.

You can customize ListView windows using menu options in the windows. You can create and edit ListViews in the ListView

editor.

About Creating ListView Objects

ListView objects are highly customizable. Settings that you can define include:

Object class, including special ListView object classes, such as AlarmInformation, that you can use to track system

events

Whether the data displayed when you open a ListView window is the most recent available from the controllers or is

retrieved from the CyberStation database (You can also update the window to get “live” data.)

Filters for time intervals

Path in which to look for objects of the selected class, which enables you to focus on objects of interest

Columns included in the ListView window, their arrangement, fonts, and colors

Qualifiers that further refine the selection of objects whose data is shown in the ListView window

Continuum Reports Continuum reports are more powerful than listviews. With reports, you can specify configuration parameters, narrow the information, and perform powerful custom searches in the form of reports. Quick-pick buttons also allow you to filter the data and narrow the report information. For example, you may narrow the information according to

Page 76: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 76

time – today, yesterday, this week, this month, and so on. A calendar allows you to highlight the beginning and ending dates, as well as start and stop times. The following sections describe three types of Continuum reports:

Access Reports

Alarm Reports

User Activity Reports

Access Report Select Access Report from the Reports menu to bring up a Continuum Access Events window that contains

configuration parameters and filters by which door reports and cardholder reports are generated. Via this window, you define these parameters to filter information that is displayed in a report. There are three general sets of filters you may use:

Door access events

Cardholder access events

Both door and cardholder access events Use the following Access Events buttons to customize a report according to certain parameters and filters:

Note: While using these Reports windows, you may use the Tab key to move the cursor from one user-interface feature to the next. However, when the cursor moves into the Cardholder Selection listview and/or Door Selection listview, Tab-key navigation becomes disabled. Press the Ctrl-Tab keys to re-enable Tab-key navigation and move the cursor out of the listview.

Door Access Event Report

Click the Door Access Event Report button to bring up the Access Events window with a Door Selection set of filters, as shown below. This Access Events window lets you customize a door access events report according to your special requirements.

Page 77: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 77

Perform the actions in the followingButton, Box, or Field Action

Button, Box, or Field Action

Yesterday Click one of these buttons to view a report for the specific time period. These selections will be reflected on the Access Events calendar. Today

This week

Last week

This month

Last Month

This year

All time

Start time Select the time that you want to start the report.

Valid Access Check the events you want to display. Also, click the radio buttons to sort by door or by time.

Invalid Attempt

Other events

Sort by door

Sort by time

End time Select the time that you want to end the report.

Door selection boxes Check the box next to the object for which you want to see a report.

Include all Click this button to include events for all doors in the report.

Exclude all Click this button to exclude events for all doors in the report.

Cardholder Access event report Click this button to bring up the Access Events window filter parameters for cardholders.

Cardholder / Door report Click this button to bring up the Access Events window filter parameters for both cardholders and doors.

Cardholder Access Event Report Click the Cardholder Access Event Report button to bring up the Continuum Access Events window with a Cardholder Selection set of filters, as shown below. This window lets you customize a cardholder access events

report according to your special requirements. That is, you can include or exclude any cardholder names in the report.

Page 78: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 78

This window‟s QuickKey feature allows you to find cardholder names quickly from the Cardholder Selection list. Simply type the name of the desired person into the QuickKey entry field, located at the bottom of the Cardholder Selection list. As you type the name, the list is narrowed until the desired name appears in the asterisk field,

located in the middle of the selection list:

Cardholder / Door Report Click the Cardholder/Door Report button to bring up the Access Events window with both the Door Selection and Cardholder Selection sets of filters, as shown below.

Page 79: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 79

Run Report, Select Printer, and Exit Buttons In all three version of the Access Events window, use these three buttons, as follows:

Click the Run Report button to generate your report. The report lists information according to the parameters that

you have specified. The report appears with a navigation bar that allows you to select page forward and backward, page zooming, and printing. Click the Select Printer button to bring up the Printer dialog:

From this dialog, verify that you have the correct printer selected and click OK to print your report. Click Cancel to dismiss the dialog. Click the Exit button to exit the Access Events window.

Alarm Report Select Alarm Report to bring up the Continuum Alarms window, as shown below. This window contains

configuration parameters and filters by which alarm reports are generated. Via this window, you define these parameters to filter information that is displayed in an alarm report.

Page 80: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 80

Note: While using these Reports windows, you may use the Tab key to move the cursor from one user-interface feature to the next. However, when the cursor moves into the alarms listviews, Tab-key navigation becomes disabled. Press the Ctrl-Tab keys to reenable Tab-key navigation and move the cursor out of the listview. Perform the actions in the following table to customize your alarm report from the Alarms window:

Button, Box, or Field Action

Yesterday Click one of these buttons to view a report for the specific time period. These selections will be reflected on the Access Events calendar. Today

This week

Last week

This month

Last Month

This year

All time

Start time Select the time that you want to start the report.

Alarm Events Check the events and faults you want to display. Also, use the radio buttons to sort by alarm or by time. RTN Events

Faults

Sort by Alarm

Sort By Time

End Time Select the time that you want to end the report.

Gather Alarms

After specifying the first set of criteria in the main Alarms window, you may specify a second set of filters for your alarm report. Click the Gather Alarms button to bring up this second set of filters in the Alarms window, as shown on the next page. The filters that appear in this second window have been narrowed by the alarm parameters that you specified in the first window.

Page 81: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 81

Run Report, Select Printer, and Exit Buttons Click the Run Report button to generate your alarm report. The report lists information according to the parameters that you have specified. The report appears with a navigation bar that allows you to select page forward and backward, page zooming, and printing:

Click the Select Printer button to bring up the Printer dialog:

Verify that you have the correct printer selected, and click OK to print your report. Click Cancel to dismiss the dialog. Click the Exit button to exit the Alarms window.

User Activity Report

Page 82: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 82

Select User Activity from the Reports menu to bring up a Continuum Activity Reports window, as shown below.

This window contains configuration parameters and filters by which user activity reports are generated. Via this window, you define these parameters to filter information that is displayed in a report.

Note: While using these Reports windows, you may use the Tab key to move the cursor from one user-interface feature to the next. However, when the cursor moves into the User Selection listview, Tab-key navigation becomes disabled. Press the Ctrl-Tab keys to re-enable Tab-key navigation and move the cursor out of the listview. Perform the actions in the following table to customize your user activity report from the Activity Reports window:

Button, Box, or Field Action

Yesterday Click one of these buttons to view a report for the specific time period. These selections will be reflected on the Access Events calendar. Today

This week

Last week

This month

Last Month

This year

All time

Start time Select the time that you want to start the report.

Sort by User Click the radio buttons to sort by door or time.

Sort by Time

End Time Select the time that you want to end the report.

Door Selection Check the box next to the object for which you want to see a report.

Include all Click this button to include all users in the report.

Exclude all Click this button to exclude all users from the report.

Run Report, Select Printer, and Exit Buttons

Page 83: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 83

Click the Run Report button to generate your user activity report. The report lists information according to the

parameters that you have specified. The report appears with a navigation bar that allows you to select page forward and backward, page zooming, and printing:

Note: Resize window to view the entire report

Click the Select Printer button to bring up the Printer dialog:

Verify that you have the correct printer selected and click OK to print your report. Click Cancel to dismiss the dialog. Click the Exit button to exit the User Activity window.

Page 84: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 84

¿Qué es Plain English?

Es el lenguaje de programación desarrollado por Schneider Electric para personalizar las secuencias de control

para BMS y seguridad

Es similar a Basic y tiene una amplia variedad de funciones

¿Qué puede hacer Plain English?

Controlar equipo de HVAC

Imprimir reportes

Ajustes de fecha/hora

Control de iluminación

Secuencias entre subsistemas

Etc.

¿Qué es un programa?

Una serie de instrucciones para definir que controlar y cuando hacerlo

Programs: Creados en la WS, usualmente usados para obtener datos del sistema

InfinityPrograms: Creados en los controladores de red ó de campo para controlar salidas y numéricos en base a

las entradas

Page 85: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 85

Una instrucción condicionada requiere que se cumpla cierto criterio para poder ejecutar la tarea

asignada

Ej: If TimeOfDay=8 then Puerta1=off

Directamente se ejecuta un comando sin ninguna condición

Ej: Ventilador1=on

● Keywords

Palabras que los controladores ó estaciones de trabajo conocen

Ej: Endif, Stop, Run, Else, etc.

Cuando se crea el código de un programa éstas palabras no pueden ser usadas para definir el nombre

de una variable (Palabras reservadas)

● Objetos

Bloques básicos de control a ser manipulados por programas

Page 86: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 86

IDE (Plain English Integrated Development Environment)

Barra de check

Barra de herramientas Barra de búsqueda

Page 87: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 87

Explorador IDE

Editor IDE

● Área donde ese inserta el código de cada programa

● Se puede trabajar con múltiples programas

Page 88: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 88

Asistente IDE

Ventana de Watch ó Status

● Ayuda para monitorear/comandar objetos asociados con la secuencia a desarrollar

● Para agregar objetos es suficiente con arrastrar y soltar del explorador IDE

● Para quitar objetos hay que dar click derecho sobre el objeto seleccionado y dar click en

“Remove Object”

Page 89: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 89

Expresiones usando operadores matemáticos

Usando paréntesis para controlar el orden

Orden de ejecución:

1. TempSetPoint – SpaceTemp (Paréntesis interno)

Page 90: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 90

2. * 0.1 (El resultado se multiplica por 0.1)

3. + HotWaterValve (Al resultado se le agrega HotWaterValve)

CONTROLANDO EL FLUJO DEL PROGRAMA

Page 91: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 91

Page 92: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 92

Page 93: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 93

Para realizar el mantenimiento a las bases de datos de Continuum, ejecutar los siguientes pasos:

1. Cerrar Continuum.

2. Respaldo de base de datos.

a. Agregar una carpeta para guardar los respaldos considerando el espacio disponible; en este

manual, por ejemplo: C:\Backup.

b. Comando en “Commnad Promt” para ejecución Manual:

osql –SPC_NAME\sqlexpress –Usa –P1370 –Q”Backup Database ContinuumDB to disk =

‘C:\Backup\Continuum.bak’ with Init”

El parámetro ‘With Init’ indica que se sobre escribirá le archivo de respaldo, si no se agrega esta

opción, el archivo indicado almacenara los diferentes respaldos.

c. Respaldo automatico.

i. Generar un Archivo batch con el siguiente comando:

OSQL –SPC_NAME\sqlexpress –Usa –P –Q”Backup Database ContinuumDB to disk =

‘C:\Backup\Continuum.bak’ with Init”

ii. Aplicar una Tarea Programada para ejecutar el batch, cada dia, preferente en la

madrugada, entre las 01 y 05 horas.

3. Eliminación de Registros Históricos.

a. Eventos de Acceso.

Comando en “Commnad Promt”:

OSQL –SPC_NAME\sqlexpress –Usa –P –dContinuumDB –Q”Delete AccessEvent where

Timestamp < ‘2010-11-01’”

Indicar entre apostrofes la fecha a partir de la cual se conservaran los registros.

b. Eventos de alarma.

Comando en “Commnad Promt”:

OSQL –SPC_NAME\sqlexpress –Usa –P –dContinuumDB –Q”Delete AlarmEvent where

Timestamp < ‘2010-11-01’”

Indicar entre apostrofes la fecha a partir de la cual se conservaran los registros.

c. Comando en “Commnad Promt”.

Comando:

OSQL –SPC_NAME\sqlexpress –Usa –P –dContinuumDB –Q”Delete ActivityEvent where

Timestamp < ‘2010-11-01’”

Indicar entre apostrofes la fecha a partir de la cual se conservaran los registros.

4. Compresión de base de Datos.

Comando en “Commnad Promt”:

Page 94: Capacitacion Continuum

Continuum como control de accesos

Ing. Francisco Olvera Página 94

OSQL –SPC_NAME\sqlexpress –Usa –P –Q” DBCC SHRINKDATABASE (ContinuumDB, 10)

El parámetro con valor 10 indica que se deberá conservar un 10% del espacio libre disponible, y el

log de datos (ldf) se vaciara, quedando en algunos kb.

5. Revisión de integridad de base de datos.

Ejecutar la aplicación Continuum Analyzer, la cual revisa la integridad de la base de datos, y en su caso

solucionar los problemas existentes.

a. Abrir aplicación en: Inicio/Program Files/Continuum/Continuum Analyzer.exe.

b. Capturar Usuario y Pasword (Andover97/Pyramid97)

c. Ejecutar prueba de sistema.

d. Generar y revisar reporte.

e. Si se observan resultados con error en la prueba (texto en color rojo), hacer click en el botón

“Clean” para solucionar los errores.

f. Si al limpiar los errores, estos persisten, se debe solicitar soporte para reconstruir la base de

datos.

6. Respaldo de base de datos.

Generar un respaldo de la base de datos, al final del mantenimiento.

7. Inicializar la base de datos.

8. Abrir Continuum.

Notas:

Si la base de datos está en SQL Server 2000 o menor (Continuum 1.81 o menor), no será necesario colocar el nombre

del servidor –SPC_NAME\sqlexpress

Si el espacio disponible en la unidad del disco duro es poca, es conveniente eliminar registros gradualmente (por

ejemplo cada 3 meses) y ejecutar la compresión de la base de datos entre cada periodo.

Los respaldos son importantes, para asegurar la continuidad en la operación, ante fallos de operación, de hardware

o de software.

Considerar las tamaños máximos para las bases de datos en los motores de SQL Server:

o MSDE – 2 Gb. (Continuum 1.7, 1.8)

o SQLExpress -4 Gb. (Continuum 1.9)