Calibrating and Trimming Instruments via HART

Agenda:• What is HART? / History / Signal / Message Frame• HART Command Structure• Connecting a HART Transmitter• Trimming Devices• Trimming Conventional Transmitter vs. HART Transmitter• Live Demo

What is HART?

HART = Highway Addressable Remote Transducer

A digital communication protocol designed for industrial process measurement applications.

Uses a low-level modulation (FSK) superimposed on the standard 4 to 20 mA current

HART History

Revision Year2.0 19873.0 19884.0 19895.x 1989 – still delivered today6.0 2001 – never introduced7.0 2007 – introduction of HART

wireless

HART Signal

HART Message Frame

HART Command Structure Three levels of commands• Universal commands• Common practise commands• Device Specific commands

Universal commands•Model ID•Tag ID•Description•Message•Date•Range Values•Instrument Limits•Process Measurements•Device Status

Common practice commands•Read Variables•Calibration (zero, span)•Initiate Self Tests•Serial Number•Time Constant Values

Device Specific commands•Model Specific Functions•Start, Stop, or Clear Totalizer•Select Primary Variable•Special Calibration Options•PID - SP, Tuning, Etc.

Connecting a HART TransmitterPoint-to-point

24V supply

+

_

ResistorTransmitter

HART Communicator

mA

mA

Polling address = 0 !=> HART + mA signal

HART

Connecting a HART transmitterMultidrop

24V supply

+

_

Resistor

Transmitters (max 15 pcs), fixed 4 mA current,Only PV output, different addresses (not 0 !)

HART Communicator

4 mA (fixed)

...

Addr=1 2 15

Trimming Devices

Communicators Smart Calibrators

MC5 Internal Connections

24V supply

+

_

ResistorTransmitter

HART Communicator

mA

mA

MC5

+24V

Ground

HART

HART vs. Conventional Transmitter (1of 2)

Conventional transmitter

Input 4 … 20 mA

Adjustments:• Zero• Span

HART vs. Conventional Transmitter (2 of 2)

HART transmitter

Input 4 .. 20 mA

Digital trim Analog trim

RangeTransfer Function

PV

PV

Input section Output sectionConversion

AO

AO

A/D D/A

Live Demo

Presented by:Ned Espy – Consulting DirectorBeamex, Inc.Office: 770-951-1927Mobile: [email protected]