CAE 331/513 Building Science Fall 2017 November 7, 2017 Ventilation and indoor air quality (part 2)
Dr. Brent Stephens, Ph.D. Civil, Architectural and Environmental Engineering
Illinois Institute of Technology [email protected]
Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter: @built_envi
![Page 2: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/2.jpg)
Internship opportunity
• ESD Global is looking for mechanical and electrical interns
• If interested, contact: – Nathan Snydacker ([email protected]) – Executive Vice President – Chief of Engineering
2
![Page 3: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/3.jpg)
Architectural Engineering courses in Spring 2018
• Undergraduate (or mixed G/UG): – CAE 464 HVAC Design – CAE 463/524 Building Enclosure Design – EG 430 Intro to Building Information Modeling (BIM) – CAE 497 Special Problems
• Graduate: – CAE 550 Applied Building Energy Modeling – CAE 553 Measurements and Instrumentation – CAE 557 Net Zero Energy Home Design Competition II* – CAE 597 Special Problems
3
![Page 4: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/4.jpg)
Last time
• Introduced IAQ
• Types of pollutants and unit conversions – Including ppm to g/m3 for gases
• Mass balances
• Ventilation
4
![Page 5: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/5.jpg)
Last time: Mass balances
5
Ventilation/ Air Exchange
Ventilation/ Air Exchange
Outdoor Pollutants
Indoor Emission
t = time (hour)V = indoor volume (m3)C = indoor concentration (µg/m3)V = volumetric flow rate (m3/hr)Cout = outdoor concentration (µg/m3)P = penetration factor (-)E = mass emission rate (µg/hr)
Cout
V
PV
V
E
C.
. .
dCdt
= PλCout −λC +EV
λ =VV= air exchange rate ( 1
hr)
For an inert pollutant:
Css = PCout +EλV
![Page 6: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/6.jpg)
Ventilation and IAQ
• How do we determine the correct (or at least required) ventilation rate? – ASHRAE Standard 62.1 (commercial) and 62.2 (residential)
6
![Page 7: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/7.jpg)
ASHRAE Standard 62.1: Commercial buildings
7
![Page 8: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/8.jpg)
ASHRAE Standard 62.1: Commercial buildings
8
Ventilation rate procedure (VRP)
![Page 9: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/9.jpg)
ASHRAE Standard 62.1: Commercial buildings VRP
9
![Page 10: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/10.jpg)
ASHRAE Standard 62.1: Commercial buildings VRP
10
![Page 11: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/11.jpg)
ASHRAE Standard 62.1: Commercial buildings VRP
11
![Page 12: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/12.jpg)
Measured air exchange rates: Commercial buildings
• Recent study of ~40 commercial buildings in California
12 Bennett et al. 2011 CEC Report
λ =VV= air exchange rate ( 1
hr)
![Page 13: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/13.jpg)
CO2 concentration in the classroom
• Estimate the ventilation rate in this classroom using measured CO2 concentrations
• How does it compare to the ASHRAE 62.1 minimum ventilation rate requirement?
13
![Page 14: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/14.jpg)
ASHRAE Standard 62.2: Residential ventilation
14
![Page 15: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/15.jpg)
ASHRAE Standard 62.2: Residential ventilation
15
![Page 16: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/16.jpg)
AIR CLEANING/FILTRATION
16
![Page 17: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/17.jpg)
Forced air distribution: Filtration
17
Typical commercial HVAC system:
!VSA
!VRA
!VOA
![Page 18: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/18.jpg)
What if we add HVAC filtration?
• Other loss mechanisms are important to the mass balance – Deposition to surfaces, reactions, control by HVAC filter
18
Indoor Emission
Cout
λ
PV
λ
E
C
Control/Filtration
New termsVf = airflow rate through filter (m3/hr)η = filter removal efficiency (-)
Vf
η
.
.
Deposition/Surface
Reactions kdep
![Page 19: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/19.jpg)
Mass balance with filtration and deposition
• New term to mass balance (derive on the board):
• Assume steady state for now, divide by λ, and solve for C:
• CADR = Clear Air Delivery Rate
19
V dCdt
= P !VCout − !VC +E −η !VfC − kdepVC
dCdt
= PλCout −λC +EV−η !Vf
VC − kdepC
0
Css =PλCout +
EV
λ +η !Vf
V+ kdep
CADR =η Vf
Units of flow (e.g., CFM or m3/s)
![Page 20: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/20.jpg)
What can we filter out in buildings?
• Particles – Fibrous filters – Electrostatic precipitators – Every forced air HVAC system
will have some kind of particle filter
• Gases – Activated carbon
• Relies on adsorption of VOCs/other gases to high surface area carbon – Very few buildings will have gas-phase filtration
20
![Page 21: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/21.jpg)
Particulate matter (PM)
• Particulate matter (PM) is its own class of pollutant – PM consists of a mixture of solid particles and liquid droplets
suspended in air – Primary emissions are emitted directly by sources
• Outdoors: Industry, construction, roads, smokestacks, fires, vehicles • Indoors: Smoking, cooking, resuspension of dust, transport from outdoors
– Secondary emissions are formed in atmospheric reactions and some indoor reactions
• Health effects – Respiratory, cardiovascular,
lung cancer, and others
• Visibility effects outdoors
http://www.aerosols.wustl.edu/education/AerosolBasics/What%20is%20an%20aerosol.htm
![Page 22: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/22.jpg)
Particulate matter
• Usually referring to a characteristic dimension – Diameter for sphere – Diameter for fibers (e.g. asbestos) – Equivalent diameter for non-spherical
Important units: • Micrometer (µm)
– 1 µm = 10-6 m
• Nanometer (nm) – 1 nm = 10-9 m = 1000 µm
V =π6dp3
dp
22
![Page 23: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/23.jpg)
Particle sizes
23 Hinds 1999
ß PM2.5 ß PM10 ß UFP
![Page 24: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/24.jpg)
Particle deposition in respiratory system
24
Hinds, 1999 Ch. 11
Nasopharyngeal Tracheobronchial (N&T regions �cleaned� by mucus)
Alveolar
![Page 25: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/25.jpg)
Total efficiency for an example filter
25
![Page 26: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/26.jpg)
High efficiency particle filtration
• Particle filtration efficiency standards for central HVAC filters
26
http://www.king-filters.com/?page_id=58
MERV: Minimum Efficiency Reporting Value FPR: Filter Performance Rating MPR: Micro-particle Performance Rating
In general, the higher the rated efficiency, the greater the removal for most particle sizes
![Page 27: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/27.jpg)
Filtration efficiency: ASHRAE Standard 52.2
27
![Page 28: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/28.jpg)
ASHRAE Standard 52.2
• Method of test for filter performance for particles – Controlled laboratory conditions – Subject filter to test aerosol – Measure particle removal efficiency and pressure drop – Load filter with dust and test again (and again)
• Result is “MERV” – “Minimum efficiency reporting value” – Based on minimum values for three particle size ranges:
• E1: 0.3-1 µm • E2: 1-3 µm • E3: 3-10 µm
28
![Page 29: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/29.jpg)
ASHRAE Standard 52.2
29
![Page 30: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/30.jpg)
HEPA à 99.9% or greater removal efficiency for most particle sizes
![Page 31: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/31.jpg)
Filter efficiency and dust loading
31 Hanley and Owen 2003 ASHRAE Research Project Final Report 1190-RP Owen et al. 2013 ASHRAE Research Project Final Report 1360-RP
Non-electret media filters (MERV 5 when clean)
Electret media filters (MERV 11 when clean)
![Page 32: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/32.jpg)
Newer measurements of filtration efficiency
• Recent lab tests covering 30 nm to 10 µm and MERV classified filters (remember MERV only covers 0.3-10 µm):
32 Hecker and Hofacre, 2008 EPA Report 600/R-08/013
![Page 33: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/33.jpg)
Recent MERV 7 lab tests
33 Hecker and Hofacre, 2008 EPA Report 600/R-08/013
![Page 34: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/34.jpg)
Recent MERV 14 lab tests
34 Hecker and Hofacre, 2008 EPA Report 600/R-08/013
![Page 35: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/35.jpg)
Filtration and ventilation example problem: ETS
• A 500 m3 restaurant that still allows smoking has a constant volume HVAC system with an air filter installed that has an efficiency of 70% for environmental tobacco smoke (ETS) – There are 10 occupants; 3 are smokers – Each cigarette emits 7.5 µg/s of ETS – The outdoor ETS concentration is zero – The indoor ETS deposition rate is 0.3 per hour – The outdoor airflow rate is 20 cfm per person – The return airflow rate is 40 cfm per person – The supply airflow rate is 60 cfm per person
• What is the steady-state concentration of ETS in the building?
35
![Page 36: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/36.jpg)
36
Pressure, flow, and energy relationships
• Higher efficiency filters usually have a higher pressure drop – Widely assumed to increase energy consumption
![Page 37: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/37.jpg)
37
Energy consequences of filters
• In large commercial buildings with variable speed fans…
Flow
Filter
Return Duct
Fan Coil
Supply Duct
Pressure Drop
Fan Power
Constant
Flow
Energy Consumption ↑
![Page 38: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/38.jpg)
38
Residential and light-commercial buildings
Flow
Filter
Return Duct
Fan Coil
Supply Duct
Flow Pressure
Drop Fan
Power
Cooling Capacity
How does overall energy consumption change?
Low MERV
High MERV
Atmospheric Pressure
Atmospheric Pressure
PSC blower w/ constant speed fan
![Page 39: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/39.jpg)
Fan and system curve interactions
39
0 10 20 30 40 50 60 70 80 90 1000
10
20
30
40
50
60
70
80
90
100
Mid-MERV
A
C
System Curve
Low-MERV
Pres
sure
[% of
Max
imum
Pres
sure]
Flow [% of Maximum Flow]
High-MERV
Fan Curve
B
Fan
Pres
sure
, ΔP
(%)
Flow, Q (%)
Low MERV
High MERV
Stephens et al., 2010 HVAC&R Research
![Page 40: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/40.jpg)
Airflow rates and brand new filters
40
![Page 41: CAE 331/513 Building Science - Built Envibuilt-envi.com/wp-content/uploads/cae331_513_lecture19_ventilation...CAE 331/513 Building Science Fall 2017 ... – CAE 464 HVAC Design](https://reader034.vdocuments.mx/reader034/viewer/2022050722/5adb7f167f8b9a4a268b6153/html5/thumbnails/41.jpg)
Next time
• Natural ventilation and air infiltration
• HW #5 due Thursday November 9th
41