    1/[email protected] tel +44 (0)20 7241 8787fax+44 (0)20 7241 8700

    Find this product online at www.eland.co.uk | Electrical Cable | Instrumentation Cable

    Eland Product Group I

    Dimensions

    Collectively Screened CablesEland Part Number Insulation

    Type

    No. of

    Pairs

    No. of

    Cores

    Nominal

    Cross

    Sectional

    Areamm2

    Conductor

    Diametermm2

    Minimum

    Average

    Thickness

    of

    Insulationmm

    Nominal

    Overall

    Diameter

    over

    Insulationmm

    Nominal

    Thickness

    of

    Beddingmm

    Nominal

    Overall

    Diameter

    of

    Beddingmm

    Nominal

    Diameter

    Over

    Armour

    Wiresmm

    Nominal

    Diameter

    of

    Armouringmm

    NominalThicknessof OuterSheath

    mm

    NominalOverall

    Diameterof Cable

    mm

    Weightkg/km

    I0175P1T2CL* XLPE 1 2 0.75 1.14 0.50 2.14 0.80 6.0 0.87 7.8 1.40 10.57 255

    I0175P1T2CPBK PE 1 2 0.75 1.14 0.50 2.14 0.80 6.0 0.87 7.8 1.40 10.57 240

    I0315P1T2CLBL XLPE - 3 1.50 1.55 0.45 2.45 0.89 7.0 0.87 8.8 1.40 11.56 410

    I0475P1T2CLBK XLPE - 4 0.75 1.14 0.50 2.14 0.80 9.2 0.87 11.0 1.40 13.77 324

    I0475P1T2CP* XLPE - 4 0.75 1.14 0.50 2.14 0.80 9.2 0.87 11.0 1.40 13.77 324

    I0505P1T2CPBK PE 5 10 0.50 0.89 0.50 1.89 1.20 12.1 0.87 13.9 1.50 16.90 416

    I0575P1T2CLBK XLPE 5 10 0.75 1.14 0.50 2.14 1.2 12.4 0.87 14.1 1.50 17.11 700

    I1005P1T2CPBK PE 10 20 0.50 0.89 0.50 2.14 1.3 17.3 1.21 19.7 1.70 23.12 850

    I1075P1T2CPBK PE 10 20 0.75 1.14 0.50 2.14 1.3 17.3 1.21 19.7 1.70 23.12 1130

    *Designates the sheath colour. For Black substitute * for BK and for Blue substitute * for BL

    ConductorClass 2 or 5 plain copper conductors

    PairingTwo insulated conductors uniformly twisted together

    InsulationPE (Polyethylene) or XLPE (Cross Linked Polyethylene)

    ShieldingAluminium / Polyester Tape

    Drain WireClass 2 Tinned copper

    BeddingPE (Polyethylene)

    ArmouringGalvanised SWA (Steel Wire Armour)

    SheathPVC (Polyvinyl Chloride) or LSZH (Low Smoke Zero Halogen)

    Sheath ColourBlue or Black

    Voltage Rating300/500V

    Temperature RatingFixed: +90CInstallation: +50C

    Minimum Bend Radius18 x Overall Diameter

    BS5308 Instrumentation Cable Part 1 Type 2

    ISSuE

    03.1

    010

    ApplicationBS5308 cables are designed to carry communication and control signals in a variety of installation types including those found in thepetrochemical industry. The signals can be of analogue, data or voice type and from a variety of transducers such as pressure, proximity ormicrophone. BS 5308 cables are designed to form part of an intrinsically safe system and the technical information required to determinetheir suitability for this application is contained within the datasheet. Part 1 Type 2 cables are designed where a greater degree of mechanicalprotection is required namely outdoor / exposed or direct burial at suitable depth. Being BS 5308 Part 1 the insulation material is either PEor XLPE. The PVC sheathing material has an OI >30% and HCL

  • 7/27/2019 cable type BS5308

    2/[email protected] tel +44 (0)20 7241 8787fax+44 (0)20 7241 8700

    Find this product online at www.eland.co.uk | Electrical Cable | Instrumentation Cable

    Individually and Collectively Screened Cables

    Eland Part Number Insulation

    Type

    No. of

    Pairs

    No. of

    Cores

    Nominal

    Cross

    Sectional

    Areamm2

    Conductor

    Diametermm2

    Minimum

    Average

    Thickness

    of

    Insulationmm

    Nominal

    Overall

    Diameter

    over

    Insulationmm

    Nominal

    Thickness

    of

    Beddingmm

    Nominal

    Overall

    Diameter

    of

    Beddingmm

    Nominal

    Diameter

    Over

    Armour

    Wiresmm

    Nominal

    Diameter

    of

    Armouringmm

    NominalThicknessof OuterSheath

    mm

    NominalOverall

    Diameterof Cable

    mm

    Weightkg/km

    I0275P1T2ICPBK PE 2 4 0.75 1.14 0.50 2.14 0.9 9.9 0.87 11.7 1.4 14.5 240

    I0505P1T2ICLBK XLPE 5 10 0.50 0.89 0.50 1.89 1.2 12.1 0.87 13.9 1.50 16.90 684

    IO575P1T2ICP* PE 5 10 0.75 1.14 0.50 2.14 1.2 13.3 0.87 15.1 1.50 18.10 714

    I1005P1T2ICPBK PE 10 20 0.50 0.89 0.50 1.89 1.3 16.9 1.21 19.3 1.70 22.70 1104

    Electrical CharacteristicsIndividually Screened Cables

    Eland Part

    Number

    No. of Pairs No. of Cores Nominal Cross

    Sectional Areamm2

    Maximum DC

    Resistance per

    Core at 20Cohms/Km

    Maximum

    Insulation

    Resistance at

    20CG ohms/Km

    Maximum

    Mutual

    CapacitancepF/m

    Maximum

    L/R RatioH/ohm

    I0175P1T2CL* 1 2 0.75 26.50 >5 115 25

    I0175P1T2CPBK 1 2 0.75 26.50 >5 115 25

    I0475P1T2CPBL 2 4 0.75 26.50 >5 115 25

    IO315P1T2CLBL - 3 1.50 12.30 >5 115 40

    I0475P1T2CLBK - 4 0.75 26.50 >5 75 25

    I0475P1T2CP* - 4 0.75 26.50 >5 75 25

    I0505P1T2CPBK 5 10 0.50 39.70 >5 75 25

    I0575P1T2CLBK 5 10 0.75 26.50 >5 75 25

    I1005P1T2CPBK 10 20 0.50 39.70 >5 75 25

    I1075P1T2CPBK 10 20 0.75 26.50 >5 75 25

    Individually and Collectively Screened Cables

    Eland Part

    Number

    No. of Pairs No. of Cores Nominal Cross

    Sectional Areamm2

    Maximum DC

    Resistance per

    Core at 20Cohms/Km

    Maximum

    Insulation

    Resistance at

    20CG ohms/Km

    Maximum

    Mutual

    CapacitancepF/m

    Maximum

    L/R RatioH/ohm

    I0275P1T2ICPBK 2 4 0.75 26.50 >5 115 25

    I0505P1T2ICLBK 5 10 0.50 39.70 >5 115 25

    IO575P1T2ICP* 5 10 0.75 26.50 >5 115 25

    I1005P1T2ICPBK 10 20 0.50 39.70 >5 115 25

    The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable

    dimensions may vary due to manufacturing tolerances.