cable type bs5308
TRANSCRIPT
-
7/27/2019 cable type BS5308
1/[email protected] tel +44 (0)20 7241 8787fax+44 (0)20 7241 8700
Find this product online at www.eland.co.uk | Electrical Cable | Instrumentation Cable
Eland Product Group I
Dimensions
Collectively Screened CablesEland Part Number Insulation
Type
No. of
Pairs
No. of
Cores
Nominal
Cross
Sectional
Areamm2
Conductor
Diametermm2
Minimum
Average
Thickness
of
Insulationmm
Nominal
Overall
Diameter
over
Insulationmm
Nominal
Thickness
of
Beddingmm
Nominal
Overall
Diameter
of
Beddingmm
Nominal
Diameter
Over
Armour
Wiresmm
Nominal
Diameter
of
Armouringmm
NominalThicknessof OuterSheath
mm
NominalOverall
Diameterof Cable
mm
Weightkg/km
I0175P1T2CL* XLPE 1 2 0.75 1.14 0.50 2.14 0.80 6.0 0.87 7.8 1.40 10.57 255
I0175P1T2CPBK PE 1 2 0.75 1.14 0.50 2.14 0.80 6.0 0.87 7.8 1.40 10.57 240
I0315P1T2CLBL XLPE - 3 1.50 1.55 0.45 2.45 0.89 7.0 0.87 8.8 1.40 11.56 410
I0475P1T2CLBK XLPE - 4 0.75 1.14 0.50 2.14 0.80 9.2 0.87 11.0 1.40 13.77 324
I0475P1T2CP* XLPE - 4 0.75 1.14 0.50 2.14 0.80 9.2 0.87 11.0 1.40 13.77 324
I0505P1T2CPBK PE 5 10 0.50 0.89 0.50 1.89 1.20 12.1 0.87 13.9 1.50 16.90 416
I0575P1T2CLBK XLPE 5 10 0.75 1.14 0.50 2.14 1.2 12.4 0.87 14.1 1.50 17.11 700
I1005P1T2CPBK PE 10 20 0.50 0.89 0.50 2.14 1.3 17.3 1.21 19.7 1.70 23.12 850
I1075P1T2CPBK PE 10 20 0.75 1.14 0.50 2.14 1.3 17.3 1.21 19.7 1.70 23.12 1130
*Designates the sheath colour. For Black substitute * for BK and for Blue substitute * for BL
ConductorClass 2 or 5 plain copper conductors
PairingTwo insulated conductors uniformly twisted together
InsulationPE (Polyethylene) or XLPE (Cross Linked Polyethylene)
ShieldingAluminium / Polyester Tape
Drain WireClass 2 Tinned copper
BeddingPE (Polyethylene)
ArmouringGalvanised SWA (Steel Wire Armour)
SheathPVC (Polyvinyl Chloride) or LSZH (Low Smoke Zero Halogen)
Sheath ColourBlue or Black
Voltage Rating300/500V
Temperature RatingFixed: +90CInstallation: +50C
Minimum Bend Radius18 x Overall Diameter
BS5308 Instrumentation Cable Part 1 Type 2
ISSuE
03.1
010
ApplicationBS5308 cables are designed to carry communication and control signals in a variety of installation types including those found in thepetrochemical industry. The signals can be of analogue, data or voice type and from a variety of transducers such as pressure, proximity ormicrophone. BS 5308 cables are designed to form part of an intrinsically safe system and the technical information required to determinetheir suitability for this application is contained within the datasheet. Part 1 Type 2 cables are designed where a greater degree of mechanicalprotection is required namely outdoor / exposed or direct burial at suitable depth. Being BS 5308 Part 1 the insulation material is either PEor XLPE. The PVC sheathing material has an OI >30% and HCL
-
7/27/2019 cable type BS5308
2/[email protected] tel +44 (0)20 7241 8787fax+44 (0)20 7241 8700
Find this product online at www.eland.co.uk | Electrical Cable | Instrumentation Cable
Individually and Collectively Screened Cables
Eland Part Number Insulation
Type
No. of
Pairs
No. of
Cores
Nominal
Cross
Sectional
Areamm2
Conductor
Diametermm2
Minimum
Average
Thickness
of
Insulationmm
Nominal
Overall
Diameter
over
Insulationmm
Nominal
Thickness
of
Beddingmm
Nominal
Overall
Diameter
of
Beddingmm
Nominal
Diameter
Over
Armour
Wiresmm
Nominal
Diameter
of
Armouringmm
NominalThicknessof OuterSheath
mm
NominalOverall
Diameterof Cable
mm
Weightkg/km
I0275P1T2ICPBK PE 2 4 0.75 1.14 0.50 2.14 0.9 9.9 0.87 11.7 1.4 14.5 240
I0505P1T2ICLBK XLPE 5 10 0.50 0.89 0.50 1.89 1.2 12.1 0.87 13.9 1.50 16.90 684
IO575P1T2ICP* PE 5 10 0.75 1.14 0.50 2.14 1.2 13.3 0.87 15.1 1.50 18.10 714
I1005P1T2ICPBK PE 10 20 0.50 0.89 0.50 1.89 1.3 16.9 1.21 19.3 1.70 22.70 1104
Electrical CharacteristicsIndividually Screened Cables
Eland Part
Number
No. of Pairs No. of Cores Nominal Cross
Sectional Areamm2
Maximum DC
Resistance per
Core at 20Cohms/Km
Maximum
Insulation
Resistance at
20CG ohms/Km
Maximum
Mutual
CapacitancepF/m
Maximum
L/R RatioH/ohm
I0175P1T2CL* 1 2 0.75 26.50 >5 115 25
I0175P1T2CPBK 1 2 0.75 26.50 >5 115 25
I0475P1T2CPBL 2 4 0.75 26.50 >5 115 25
IO315P1T2CLBL - 3 1.50 12.30 >5 115 40
I0475P1T2CLBK - 4 0.75 26.50 >5 75 25
I0475P1T2CP* - 4 0.75 26.50 >5 75 25
I0505P1T2CPBK 5 10 0.50 39.70 >5 75 25
I0575P1T2CLBK 5 10 0.75 26.50 >5 75 25
I1005P1T2CPBK 10 20 0.50 39.70 >5 75 25
I1075P1T2CPBK 10 20 0.75 26.50 >5 75 25
Individually and Collectively Screened Cables
Eland Part
Number
No. of Pairs No. of Cores Nominal Cross
Sectional Areamm2
Maximum DC
Resistance per
Core at 20Cohms/Km
Maximum
Insulation
Resistance at
20CG ohms/Km
Maximum
Mutual
CapacitancepF/m
Maximum
L/R RatioH/ohm
I0275P1T2ICPBK 2 4 0.75 26.50 >5 115 25
I0505P1T2ICLBK 5 10 0.50 39.70 >5 115 25
IO575P1T2ICP* 5 10 0.75 26.50 >5 115 25
I1005P1T2ICPBK 10 20 0.50 39.70 >5 115 25
The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable
dimensions may vary due to manufacturing tolerances.
PAGE 2 OF 2