Cable-in / cable-out miniature circuit breakers and supplementary protectors
Product Guide
1EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Cable-in / cable-out miniature circuit breakers and supplementary protectors
Eaton offers a complete line of circuit breakers with its WMZT and QC product lines engineered for branch circuit protection and its WMZS product line designed for supplementary protection. Optimum product quality, tested reliability and safety standards for the best protection of personnel, installations and plant.
UL 489 Cable-In / Cable-Out Branch QC Circuit BreakersProduct Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 QC Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 QCD Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 QCR Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 QCF Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 QCGF Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
UL 489 Cable-In / Cable-Out Branch WMZ Circuit BreakersProduct Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 WMZT UL 489 Circuit Breakers—10 kAIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 WMZH UL 489 Circuit Breakers—14 kAIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsProduct Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 WMZS—B Curve (3–5X In Current Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 WMZS—C Curve (5–10X In Current Rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 WMZS—D Curve (10–20X In Current Rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQC Circuit BreakersPRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers— Cable-In / Cable-Out Type QC
For Cable-In / Cable-Out Panel-Mount Applications
• Single-, two-, three- and four-pole options
• Built and listed to ULT 489
• All products UL and CSAT listed
• All products 10–100A are HACR rated
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out Type QC—Catalog Numbering System
QC 3 020 H
Breaker Type
QC = QC breaker Number of Poles
1 = Single-pole2 = Two-pole3 = Three-pole4 = Four-pole
Construction
H = 240V (two-, three- and four-pole only)Ampere Rating
010 = 10A015 = 15A020 = 20A025 = 25A030 = 30A035 = 35A040 = 40A045 = 45A
050 = 50A055 = 55A060 = 60A070 = 70A080 = 80A090 = 90A100 = 100A
QUICKLAGT Type QC 10,000 Ampere Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40ºC
Single-Pole120/240 VacCatalog Number
Two-Pole120/240 VacCatalog Number
Three-Pole240 VacCatalog Number
101520
QC1010QC1015
QC1020
QC2010QC2015QC2020
—QC3015HQC3020H
3040
QC1030QC1040
QC2030QC2040
QC3030HQC3040H
5060
QC1050—
QC2050QC2060
QC3050HQC3060H
70100
—QC1100
QC2070QC2100
QC3070HQC3100H
Switching duty rated for 120 Vac fluorescent light applications only. For special low-magnetic breaker, order QC1015L1 or QC1020L1.
otee:N For non-automatic switches, see catalog Volume 4: Circuit Protection, CA08100005E, Tab 24 .
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQC Circuit BreakersProduct Overview
3
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQCD Circuit Breakers
PRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers— Cable-In / Cable-Out Type QCD
For Cable-In / Cable-Out DIN Rail Mount HVAC Applications
• Single-, two- and three-pole options
• Modular construction
• DIN mounted (symmetrical rail 35 x 7 .5 DIN/EN 50 022)
• Flexible power feed connection: wire size, position
• Same breaker size for entire rating range
• Field-mountable accessories: finger-shroud proof, quick-connect terminals, jumper units
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out Type QCD—Catalog Numbering System
QCD 3 020 H
Breaker Type
QCD = QCD breaker Number of Poles
1 = Single-pole2 = Two-pole3 = Three-pole
Construction
H = 240V (two- and three-pole only)Ampere Rating
010 = 10A015 = 15A020 = 20A025 = 25A030 = 30A035 = 35A040 = 40A045 = 45A
050 = 50A055 = 55A060 = 60A070 = 70A080 = 80A090 = 90A100 = 100A
QUICKLAG Type QCD 10,000 Ampere Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40ºC
Single-Pole120/240 VacCatalog Number
Two-Pole120/240 VacCatalog Number
Three-Pole240 VacCatalog Number
10152030
QCD1010QCD1015QCD1020QCD1030
QCD2010QCD2015QCD2020QCD2030
—QCD3015HQCD3020HQCD3030H
4050
QCD1040QCD1050
QCD2040QCD2050
QCD3040HQCD3050H
6070100
QCD1060——
QCD2060QCD2070QCD2100
QCD3060HQCD3070HQCD3100H
QCD Circuit BreakersProduct Overview
4
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQCR Circuit BreakersPRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out 1/2-Inch Wide Types QCR, QCF
When Space is at a Premium
• QCR: For DIN rail mount cable-in/cable-out applications
• QCF: For front-mount through-the-door cable-in/cable-out applications
• 1/2-inch (12 .7-mm) wide per pole
• Three-position handle: ON, Tripped (center), OFF
• Thermal-magnetic protection
• Single-, two- and three-pole
• 10 kAIC at 120/240 Vac, 10–60A
• 10 kAIC at 240 Vac, 10–30A
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out 1/2-Inch Wide Types QCR, QCF—Catalog Numbering System
QCR 1 020 T
Breaker Type
QCR = QCR breaker (rear mount)QCF = QCF breaker (front mount)
Number of Poles
1 = Single-pole2 = Two-pole3 = Three-pole
Construction/Terminals
H = 240V (two- and three-pole only)T = Ring or spade terminals (10–30A only)
Ampere Rating
010 = 10A015 = 15A020 = 20A025 = 25A030 = 30A035 = 35A
040 = 40A045 = 45A 050 = 50A055 = 55A060 = 60A
QUICKLAG Type QCR Breaker 10 kAIC Interrupting Ratings
Continuous Ampere Rating at 40ºC
Single-Pole120/240 VacCatalog Number
Two-Pole120/240 VacCatalog Number
Three-Pole 240 VacCatalog Number
10 QCR1010QCR1010T
QCR2010QCR2010T
——
15 QCR1015 eQCR1015T e
QCR2015QCR2015T
QCR3015HQCR3015HT
20 QCR1020 eQCR1020T e
QCR2020QCR2020T
QCR3020HQCR3020HT
25 QCR1025—
QCR2025—
QCR3025HQCR3025HT
30 QCR1030—
QCR2030—
QCR3030HQCR3030HT
35 QCR1035 QCR2035 —
40 QCR1040 QCR2040 —
45 QCR1045 QCR2045 —
50 QCR1050 QCR2050 —
55 QCR1055 — —
60 f QCR1060 QCR2060 —
Standard breaker terminals are box type lugs. Breakers with “T” catalog number suffix are suitable for line and load side ring terminal
connection (#10-32 plus/minus terminal screw provided). Breakers with “P” catalog number suffix are suitable for terminating two 10 AWG
Quick-Connect type terminals per phase on breaker load side.
Breakers with shunt trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole.
e All 15 and 20A single-pole breakers are SWD (switching duty) rated for fluorescent lighting applications.
f 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
QCR Circuit BreakersProduct Overview
5
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQCF Circuit Breakers
PRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out 1/2-Inch Wide, Types QCR, QCF
QUICKLAG Type QCF Breaker 10 kAIC Interrupting Ratings
Continuous Ampere Rating at 40ºC
Single-Pole120/240 VacCatalog Number
Two-Pole120/240 VacCatalog Number
Three-Pole 240 VacCatalog Number
10 QCF1010QCF1010T
QCF2010QCF2010T
——
15 QCF1015 —
QCF2015—
QCF3015HQCF3015HT
20 QCF1020 —
QCF2020—
QCF3020HQCF3020HT
25 QCF1025—
QCF2025—
QCF3025HQCF3025HT
30 QCF1030—
QCF2030—
QCF3030HQCF3030HT
40 QCF1040 QCF2040 —
50 QCF1050 QCF2050 —
60 e QCF1060 QCF2060 —
Standard breaker terminals are box type lugs. Breakers with “T” catalog number suffix are suitable for line and load side ring terminal
connection (#10–32 plus/minus terminal screw provided). Breakers with shunt trip attachment (extra pole required on breaker right-hand side)
are available. All 15 and 20A single-pole breakers are SWD (switching duty) rated for fluorescent
lighting applications.e 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
Accessories
Description Catalog Number
Steel mounting clip mounts QCR breaker if individual mounting is required. Quantity of two required for single- and two-pole, and four required for three-pole breakers.
QCRMTGFT
Removable padlock device for single-pole QCR or QCF breaker.
QCRFPL1P
Removable padlock device for multi-pole QCR or QCF breaker.
QCRFPLMP
Padlock bracket assembly for QCR or QCF single- or multi-pole breakers (OFF only).
QCRFLOFF
Padlock bracket for QCR, lock-off only.
QCRPLOFF
QUICKLAG Type C Spacer QCRSPACER
QCR and QCF Ring or Spade Lug Terminals (10–30A ratings only)Factory-installed line and load side terminals each equipped with a #10–32 screw suitable for terminating one 10 AWG wire with insulated ring or spade type terminal as shown.
Suffix “T”
QCF Circuit BreakersProduct Overview
6
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQCGF Circuit BreakersPRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out 1/2-Inch Wide Types QCGF, QCGFEP
For Cable-In / Cable-Out Panel-Mount Applications
• QUICKLAG ground fault circuit breakers, Class A GFCI:
— Built and tested to UL 943
— 5 mA trip sensitivity
• QUICKLAG ground fault equipment protectors:
— Built and tested to UL 1053
— 30 mA trip sensitivity
• All products UL and CSA listed
Type QC Miniature Circuit Breakers—Cable-In / Cable-Out Ground Fault and Equipment Protector Types QCGF, QCGFEP— Catalog Numbering System
QCGFEP 1 020
Breaker Type
QCGF = QC ground fault circuit protectorQCGFEP = QC ground fault equipment protector
Number of Poles
1 = Single-pole2 = Two-pole
Ampere Rating
015 = 15A020 = 20A025 = 25A
030 = 30A040 = 40A050 = 50A
Types QCGF and QCGFEP Thermal-Magnetic Breakers
Continuous Ampere Rating at 40ºC
Single-Pole120/240 VacCatalog Number
Two-Pole120/240 VacCatalog Number
Ground Fault Circuit Breakers—5 mA SensitivityQUICKLAG Type: QCGF 10,000 Ampere Interrupting Capacity
1520304050
QCGF1015QCGF1020QCGF1030QCGF1040—
QCGF2015QCGF2020QCGF2030QCGF2040QCGF2050
Ground Fault Equipment Protectors—30 mA SensitivityQUICKLAG Type: QCGFEP 10,000 Ampere Interrupting Capacity
1520304050
QCGFEP1015QCGFEP1020QCGFEP1030QCGFEP1040—
QCGFEP2015QCGFEP2020QCGFEP2030QCGFEP2040QCGFEP2050
QCGF Circuit BreakersProduct Overview
7
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQC Circuit Breakers
ACCESSORIES
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers
AccessoriesAccessory Description Catalog Number
QL1NPL QL23NPL
Handle locks:non-padlockable
QUICKLAG Type P, B, C—single-poleQUICKLAG Type P, B, C—two-, three-pole
QL1NPLQL23NPL
QL1PL QC123PL
Handle locks:padlockable
QUICKLAG Type P, B, C—single-poleQUICKLAG Type C—single-, two-, three-poleQUICKLAG Type C—single-, two-, three-pole (off only)
QL1PLQC123PLQCD123PLOFF
QL1HT
Handle tie QUICKLAG handle tie—single-poleQUICKLAG handle tie—three-pole
QL1HTQL3HT
QCFCLIP
QC2FP
QC1FP
QC3FP
QCBCLIP
Mounting hardware
QUICKLAG Type C face mounting clipQUICKLAG Type C face mounting plate—single-poleQUICKLAG Type C face mounting plate—two-poleQUICKLAG Type C face mounting plate—three-poleQUICKLAG Type C face mounting plate and lock-off (off only)—two-pole QUICKLAG Type C face mounting plate and lock-off (off only)—three-poleQUICKLAG Type C base mounting clamp
QCFCLIPQC1FPQC2FPQC3FPQC2FPLOFFQC3FPLOFFQCBCLIP
Can lock in ON or OFF position. Suitable for ground fault breakers.
QC Circuit BreakersAccessories
8
UL 489 Cable-In / Cable-Out Branch Circuit BreakerQC Circuit BreakersACCESSORIES
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Type QC Miniature Circuit Breakers
Accessories (Continued)Accessory Description Catalog Number
QC6BP
QCDJ4
QCDINADAPT
QCDFP
Mounting hardware
QUICKLAG base mounting plate—six poles totalQUICKLAG Type C base mounting plate—six poles total— heavy-duty screw-securedQUICKLAG Type C (QCD) two-way jumper unit with coverQUICKLAG Type C (QCD) four-way jumper unit with coverQUICKLAG Type C (QCD) six-way jumper unit with coverQUICKLAG Type C (QCD) two-way jumper unit, no coverQUICKLAG Type C (QCD) four-way jumper unit, no coverQUICKLAG Type C (QCD) six-way jumper unit, no coverQUICKLAG Type QCD finger protection attachmentQUICKLAG Type C DIN rail adapter
QC6BPQC6BPS
QCDJ2QCDJ4QCDJ6QCDJ2TQCDJ4TQCDJ6TQCDFPQCDINADAPT
See page 5 for QCR and QCF accessories.
QC Circuit BreakersAccessories
9
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
PRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Optimum and Efficient Protection
Optimum product quality, tested reliability and safety standards for best protection of personnel, installations and plant . Eaton’s WMZ DIN rail mountable circuit breaker is designed for use in branch service applications .
Powerful Offering for Machine and System Builders
The WMZ is available with C and D characteristics in accordance with UL 489, CSA C22 .2 No .5; UL 1077, CSA C22 .2 No .235 and IEC 60947-2 . These devices are CE marked .
Typical Applications
Feeder and Branch Circuit Protection
• Convenience receptacle circuits (internal/external)
• Motor control circuits
• Load circuits leaving the equipment (external)
• HACR equipment (heating, air conditioning, refrigeration) (internal/external)
• PLC I/O points
• Computers
• Power supplies
• Control instrumentation
• Relays
• UPS
• Power conditioners
Features
• Complete range of UL 489 listed DIN rail mounted miniature circuit breakers up to 40A current rating
• Standard ratings of 10 kAIC at 277/480 Vac
• Select amperages available at 14 kAIC at 277/480 Vac and 10 kAIC at 125 Vdc
• Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit
• Suitable for branch circuit device protection
• Thermal-magnetic overcurrent protection
— Two levels of short-circuit protection, categorized by C and D curves
• Trip-free design—breaker can not be defeated by holding the handle in the ON position
• Captive screws cannot be lost
• SWD (switching duty)—suitable for switching fluorescent lighting loads (In ≤ 20A)
• Fulfill UL 489, CSA C22 .2 No .5 and also IEC 60947-2 Standard
• For use in applications for which UL 1077 or CSA C22 .2 No .235 are also allowed
• Field-installable shunt trip and auxiliary switch subsequent mounting
• Separate version for ring-tongue connection (Type WMZT… .T), terminal screws can be removed (on both sides)
• Module width of only 17 .7 mm (per pole)
• Contact Position Indicator (red/green)
• Easy installation on DIN rail
• Possibility for sealing the toggle in ON or OFF position
WMZ Complies with the Latest National and International Standards
Standards—Feeder and Branch Circuit Protection
UL 489
Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection.
Products meet the requirements of the National Electrical Code® (NEC®).
CSA C22.2 No.5
Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard).
Products meet the requirements of the Canadian Electrical Code (CEC).
RoHS
These devices are RoHS compliant.
WMZ Circuit BreakersProduct Overview
10
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersPRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Tripping Curves to Choose From
Eaton WMZ branch circuit breakers are available with “C” and “D” tripping characteristics .
C-curve devices are suitable for applications where medium levels of inrush current are expected . Applications include small transformers, lighting, pilot devices, control circuits and coils . C-curve devices provide a medium magnetic trip point .
D-curve devices are suitable for applications where high levels of inrush current are expected . The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies .
Eaton WMZ devices are current limiting, which means they interrupt fault currents within one half cycle of the fault . Current limiting devices offer superior protection by reducing peak let-through current and energy .
Catalog Numbering System
Device Printing on Front and Side
Installation options
These branch circuit breakers are available in two terminal configurations: standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to demanding requirements of the semi-conductor industry . All breakers mount on standard 35 mm DIN rail . Bus connectors and feeder terminal facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies . These circuit breakers can also be reverse feed .
tripping characteristic acc . to UL 489 conventional non-tripping
current Int = 1.0 IN (T=40°)
conventional tripping current It = 1.35 IN: t < 1 h (T=25°)
2.0 IN: t = 12–120 s (T=25°)
instantaneous tripping acc . to IEC 60898-1 type C: 5 IN: t > 0.1 s
10 IN: t < 0.1 se type D: 10 IN: t > 0.1 s
20 IN: t < 0.1 s
Conductor Type
Calibration Temperature UL/CSA
Rated Voltage UL/CSA
Breaker Status Indicator
Catalog Number
Rated Current
WMZ T 1 C 16 T
Breaker Family
WMZ = WMZ UL circuit breaker Number of Poles
1 = Single-pole2 = Two-pole3 = Three-pole
Terminal
T = Ring terminals[blank] = Standard box terminals
Breaker Type
T = 10 kAICH = 14 kAIC D = 10 kAIC/DC
Protective Curve
C = C Curve (5–10X In)D = D Curve (10–20X In)
Ampere Rating
X0 = 0.5A01 = 1AX1 = 1.5A02 = 2A03 = 3A04 = 4A05 = 5A06 = 6A07 = 7A08 = 8A
10 = 10A13 = 13A15 = 15A16 = 16A20 = 20A25 = 25A30 = 30A32 = 32A40 = 40A
Limited curve and ampere offerings. 125 Vdc for single-pole, 250 Vdc for two-pole in series. Not offered for Type WMZD.
WMZ Circuit BreakersProduct Selection
11
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
PRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
WMZT Product Selection
• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers
• Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947
• Current limiting device
• Optional connections for ring-tongue terminals
WMZT UL 489 Circuit Breakers—10 kAIC
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
C Curve (5–10X In Current Rating)
0.511.523
WMZT1CX0WMZT1C01WMZT1CX1WMZT1C02WMZT1C03
WMZT2CX0WMZT2C01WMZT2CX1WMZT2C02WMZT2C03
WMZT3CX0WMZT3C01WMZT3CX1WMZT3C02WMZT3C03
45678
WMZT1C04WMZT1C05WMZT1C06WMZT1C07WMZT1C08
WMZT2C00WMZT2C05WMZT2C06WMZT2C07WMZT2C08
WMZT3C04WMZT3C05WMZT3C06WMZT3C07WMZT3C08
1013151620
WMZT1C10WMZT1C13WMZT1C15WMZT1C16WMZT1C20
WMZT2C10WMZT2C13WMZT2C15WMZT2C16WMZT2C20
WMZT3C10WMZT3C13WMZT3C15WMZT3C16WMZT3C20
25303240
WMZT1C25WMZT1C30WMZT1C32WMZT1C40
WMZT2C25WMZT2C30WMZT2C32WMZT2C40
WMZT3C25WMZT3C30WMZT3C32WMZT3C40
D Curve (10–20X In Current Rating)
0.511.523
WMZT1DX0WMZT1D01WMZT1DX1WMZT1D02WMZT1D03
WMZT2DX0WMZT2D01WMZT2DX1WMZT2D02WMZT2D03
WMZT3DX0WMZT3D01WMZT3DX1WMZT3D02WMZT3D03
45678
WMZT1D04WMZT1D05WMZT1D06WMZT1D07WMZT1D08
WMZT2D04WMZT2D05WMZT2D06WMZT2D07WMZT2D08
WMZT3D04WMZT3D05WMZT3D06WMZT3D07WMZT3D08
1013151620
WMZT1D10WMZT1D13WMZT1D15WMZT1D16WMZT1D20
WMZT2D10WMZT2D13WMZT2D15WMZT2D16WMZT2D20
WMZT3D10WMZT3D13WMZT3D15WMZT3D16WMZT3D20
25303240
WMZT1D25WMZT1D30WMZT1D32WMZT1D40
WMZT2D25WMZT2D30WMZT2D32WMZT2D40
WMZT3D25WMZT3D30WMZT3D32WMZT3D40z
WMZT UL 489 Circuit Breakers with Ring-Tongue Terminals—10 kAIC
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
C Curve with Ring-Tongue Terminals (5–10X In Current Rating)
0.511.523
WMZT1CX0TWMZT1C01TWMZT1CX1TWMZT1C02TWMZT1C03T
WMZT2CX0TWMZT2C01TWMZT2CX1TWMZT2C02TWMZT2C03T
WMZT3CX0TWMZT3C01TWMZT3CX1TWMZT3C02TWMZT3C03T
45678
WMZT1C04TWMZT1C05TWMZT1C06TWMZT1C07TWMZT1C08T
WMZT2C04TWMZT2C05TWMZT2C06TWMZT2C07TWMZT2C08T
WMZT3C04TWMZT3C05TWMZT3C06TWMZT3C07TWMZT3C08T
1013151620
WMZT1C10TWMZT1C13TWMZT1C15TWMZT1C16TWMZT1C20T
WMZT2C10TWMZT2C13TWMZT2C15TWMZT2C16TWMZT2C20T
WMZT3C10TWMZT3C13TWMZT3C15TWMZT3C16TWMZT3C20T
25303240
WMZT1C25TWMZT1C30TWMZT1C32TWMZT1C40T
WMZT2C25TWMZT2C30TWMZT2C32TWMZT2C40T
WMZT3C25TWMZT3C30TWMZT3C32TWMZT3C40T
D Curve with Ring-Tongue Terminals (10–20X In Current Rating)
0.511.523
WMZT1DX0TWMZT1D01TWMZT1DX1TWMZT1D02TWMZT1D03T
WMZT2DX0TWMZT2D01TWMZT2DX1TWMZT2D02TWMZT2D03T
WMZT3DX0TWMZT3D01TWMZT3DX1TWMZT3D02TWMZT3D03T
45678
WMZT1D04TWMZT1D05TWMZT1D06TWMZT1D07TWMZT1D08T
WMZT2D04TWMZT2D05TWMZT2D06TWMZT2D07TWMZT2D08T
WMZT3D04TWMZT3D05TWMZT3D06TWMZT3D07TWMZT3D08T
1013151620
WMZT1D10TWMZT1D13TWMZT1D15TWMZT1D16TWMZT1D20T
WMZT2D10TWMZT2D13TWMZT2D15TWMZT2D16TWMZT2D20T
WMZT3D10TWMZT3D13TWMZT3D15TWMZT3D16TWMZT3D20T
25303240
WMZT1D25TWMZT1D30TWMZT1D32TWMZT1D40T
WMZT2D25TWMZT2D30TWMZT2D32TWMZT2D40T
WMZT3D25TWMZT3D30TWMZT3D32TWMZT3D40T
For our complete product offering, see the Distribution Products Catalog (CA08101001E) .
Product Selection
12
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersPRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
WMZH Product Selection
• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers
• Interrupting capacity: 14 kA UL/CSA; 15 kA IEC 60947
WMZH UL 489 Circuit Breakers—14 kAIC
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
C Curve (5–10X In Current Rating)
15162025
WMZH1C15WMZH1C16WMZH1C20WMZH1C25
WMZH2C15WMZH2C16WMZH2C20WMZH2C25
WMZH3C15WMZH3C16WMZH3C20WMZH3C25
D Curve (10–20X In Current Rating)
13151620
WMZH1D13WMZH1D15WMZH1D16WMZH1D20
WMZH2D13WMZH2D15WMZH2D16WMZH2D20
WMZH3D13WMZH3D15WMZH3D16WMZH3D20
WMZD Product Selection
• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers
• Interrupting capacity: 10 kA at 125 Vdc UL/CSA
• 125 Vdc for single-pole, 250 Vdc for two-pole in series
• Current limiting device
• Current limiting device
• Optional connections for ring-tongue terminals
WMZH UL 489 Circuit Breakers with Ring-Tongue Terminals
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
C Curve (5–10X In Current Rating)
15162025
WMZH1C15TWMZH1C16TWMZH1C20TWMZH1C25T
WMZH2C15TWMZH2C16TWMZH2C20TWMZH2C25T
WMZH3C15TWMZH3C16TWMZH3C20TWMZH3C25T
D Curve (10–20X In Current Rating)
13151620
WMZH1D13TWMZH1D15TWMZH1D16TWMZH1D20T
WMZH2D13TWMZH2D15TWMZH2D16TWMZH2D20T
WMZH3D13TWMZH3D15TWMZH3D16TWMZH3D20T
WMZD UL 489 Circuit Breakers— 10 kAIC at 125 Vdc per pole
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
C Curve (5–10X In Current Rating)
2345
WMZD1C02WMZD1C03WMZD1C04WMZD1C05
WMZD2C02WMZD2C03WMZD2C04WMZD2C05
67810
WMZD1C06WMZD1C07WMZD1C08WMZD1C10
WMZD2C06WMZD2C07WMZD2C08WMZD2C10
13151620
WMZD1C13WMZD1C15WMZD1C16WMZD1C20
WMZD2C13WMZD2C15WMZD2C16WMZD2C20
25303240
WMZD1C25WMZD1C30WMZD1C32WMZD1C40
WMZD2C25WMZD2C30WMZD2C32WMZD2C40
13
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
PRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
WMZ UL 489 BreakersAccessory/Description Catalog Number
Two-pole contact or auxiliary contact/ Trip indicating contact
WMZSAUXTRIP
Auxiliary contact WMZTAUX
Shunt trip 110–415 VacShunt trip 12–110 Vac
WMZTST415WMZTST110
Padlock hasp WMZPLK
Busbar—single-pole 6 terminalsBusbar—single-pole 12 terminalsBusbar—single-pole 18 terminalsBusbar—two-pole 6 terminalsBusbar—two-pole 12 terminalsBusbar—two-pole 18 terminalsBusbar—three-pole 6 terminalsBusbar—three-pole 12 terminalsBusbar—three-pole 18 terminals
WMZT1P6TWMZT1P12TWMZT1P18TWMZT2P6TWMZT2P12TWMZT2P18TWMZT3P6TWMZT3P12TWMZT3P18T
Three-pole busbar shroud WMZT3PSHROUD
Extension terminal—35 mm (2–14 AWG) WMZT35EXT
Bus connector—conductors up to 50 mm2 (~1/0 AWG) WMZTBCON
Contact sales office for availability.
Tripping Signal Switch WMZSAUXTRIP, WMZTAUX
• Design according to IEC/EN 60947-5-1, IEC/EN 62019
• Field installable
• The specified minimum voltages are per contact—take into account particularly in case of series connection
• Self-cleaning contacts
• Contact material and design particularly suitable for extra low voltage
• WMZSAUXTRIP: the function of one of the two change-over contacts can be switched from “auxiliary switch” to “tripping signal switch”
• Tripping signal contact transmits message of electric tripping, not mechanical switch-off
• Test key for contact function “electrical tripping”
• WMZTAUX: will allow for > 480Y/277 Vac rating
Connection Diagram
WMZSAUXTRIP
21
4.11
1.11
1.14
1.12
4.12/4.14
4.14/4.12
13
2214
Same Polarity
WMZTAUX
4.13(105.0)
Single-Pole Two-Pole Three-Pole
.70(17.7)
.70(17.7)1.39
(35.3)2.09
(53.1)
.70(17.7)
.70(17.7)
4.13(105.0)
4.13(105.0)
1.17(29.7)39°
1.42(36.1)
—
Dimensions
Miniature Circuit Breakers
WMZ
14
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersTECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Miniature Circuit Breakers WMZ
Connection Diagrams
Miniature Circuit Breakers WMZDescription Specification
Electrical
Design according to UL 489, CSA C22.2 No.5, IEC 60947-2
Rated voltage WMZT UL/CSA UL/CSA UL/CSA IEC 947-2
10 kAIC at 277/480V from 0.5A to 32A10 kAIC at 240 Vac for 40A10 kAIC at 48 Vdc per pole15 kAIC at 240/415 Vac
Rated voltage WMZD UL/CSA 10 kAIC at 125 Vdc per pole
(two poles maximum)10 kAIC at 250 Vdc with two poles connected in series
Rated voltage WMZH UL/CSA IEC 947-2
14 kAIC at 277/480V at listed amperages15 kAIC at 240/415 Vac
Rated frequency 50/60 Hz
Rated breaking capacity WMZT UL/CSA IEC 947-2
10 kA15 kA
Rated breaking capacity WMZH UL/CSA IEC 947-2
14 kA15 kA
Characteristic C, D
Endurance ≥ 20,000 operations
Line voltage connection Suitable for reverse feed
Mechanical
Frame size 45 mm
Device height 105 mm
Device width 17.7 mm per pole
Mounting Quick fastening with two lock-in positions on IEC/EN 60715
Upper and lower terminals Open mouth/lift terminals
Terminal capacity Single-wire Two-wire
AWG 18–6AWG 18–10
Terminal fastening torque AWG 18-21: 21 lb-inAWG 10-8: 25 lb-inAWG 6: 36 lb-in
Mounting Independent of position
Calibration temperatureUL 489, CSA C22.2 No.5IEC 60947-2
40°C30°C
Two-Pole Three-PoleSingle-Pole
Dimensions (mm)
Power Loss at ln Characteristic C Characteristic D
In [A]
Single-Pole
Two- Pole
Three-Pole
Single-Pole
Two- Pole
Three-Pole
P [W] P [W] P [W] P [W] P [W] P [W
0.511.52
1.61.11.31.4
3.22.22.62.8
4.73.43.94.3
1.60.81.01.0
3.21.52.12.1
4.82.33.13.1
3456
1.21.41.91.2
2.42.93.72.3
3.64.35.63.5
1.21.41.51.2
2.42.92.92.3
3.64.34.43.5
781013
1.41.41.82.4
2.82.83.64.7
4.34.25.37.1
1.41.21.52.0
2.82.43.04.1
4.33.74.56.1
15162025
1.92.12.93.1
3.84.35.86.2
5.66.48.79.3
1.51.71.82.6
3.13.53.75.1
4.65.25.57.7
30323540
3.03.43.74.0
6.06.87.48.1
9.010.211.012.1
2.73.13.83.9
5.46.27.67.8
8.19.311.311.6
17 .7
105
5 .5
45
10
44
60
Technical Data
15
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Let-Through Energy
Characteristic C (0.5–32A), 277V
Characteristic D (0.5–32A), 277V
Characteristic C (40A), 240V
Characteristic D (40A), 240V
16
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersACCESSORIES
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Dimensions (mm)
WMZT_ _ 6T WMZT_ _ 12T
WMZT_ _ 18T WMZT35EXT
WMZT3PSHROUD
517,6
5x17,6=88
517,6
17x17,6=299,2
5
717,6 17,6 3,55
17,611x17,6=193,6
310,2
204,6
24
1616
48.2
15,5
46
32,5
71,6
6
13,5
3
31,3
99
WMZT35EXTDescription UL 489 IEC/EN 60947-2
# 2–14 AWG60/75°C Cu
2.5–35 mm2
60/75°C Cu
0.56 in 14 mm
Tested according to Tightening torque of terminal screws
UL 486A # 14 AWG ≥ 2.3 Nm
UL 486B # 8–12 AWG ≥ 2.8 Nm
UL 486E # 6–1 AWG 4 Nm
Lockout Attachment
WMZPLK
Accessories
17
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Influence of Ambient Temperature T on Load Carrying Capacity
Device Market Current Rating In (A) at 40°C
In (A) at Higher Ambient Temperature
15°C 20°C 25°C 30°C 40°C 50°C 55°C 60°C
0.51.01.52.0
0.61.11.72.2
0.51.11.62.2
0.51.11.62.1
0.51.01.62.1
0.51.01.52.0
0.51.01.41.9
0.50.91.41.9
0.5 0.9 1.4 1.8
3.04.05.06.0
3.34.45.56.6
3.24.35.46.5
3.24.25.36.4
3.14.25.26.2
3.04.05.06.0
2.93.84.85.8
2.93.84.75.6
2.8 3.7 4.6 5.5
7.08.010.013.0
7.78.811.014.3
7.68.610.814.0
7.48.510.613.8
7.38.310.413.5
7.08.010.013.0
6.77.79.612.5
6.67.59.412.5
6.4 7.4 9.2 12.0
15.016.020.025.0
16.517.622.027.5
16.217.321.627.0
15.917.021.226.5
15.616.620.826.0
15.016.020.025.0
14.415.419.224.0
14.115.018.823.3
13.8 14.7 18.4 23.0
30.032.040.0
33.035.244.0
32.434.643.2
31.833.942.4
31.233.341.6
30.032.040.0
28.830.738.4
28.230.137.6
27.6 29.4 36.8
Ambient Temperature T [°C]Maximum Load IL at ambient temperature T: IL (T) = IN KT(T)
Load
Fac
tor
KT
[I/
I N]
Technical Data
18
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersACCESSORIES
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
AccessoriesDescription WMZSAUXTRIP WMZTAUX
Electrical
Contact function 2CO 1NO + 1NC
Rated voltage 230V 250V
Frequency 50/60 Hz 50/60 Hz
Rated current 2A 6A
Rated thermal current Ith 2A 6A
Utilization category AC13rated operational current Ie 3A/250 Vac 3A/250 Vac
Utilization category AC15rated operational current Ie 2A/250 Vac 2A/250 Vac
Utilization category DC12rated operational current Ie 0.5A/110 Vdc 0.5A/110 Vdc
0.25A/220 Vdc
Rated insulation voltage UI 250 Vac 250 Vac
Minimum operational voltage per contact Umin 5 Vdc 5 Vdc
Minimum operational current Imin 10 mA DC 10 mA AC/DC
Rated peak withstand voltage Uimp (1.2/50µ) 2.5 kV 4 kV
Conditional short-circuit current Ik with backup fuse 6A 1 kA 1 kA
Max. backup fuse, overload and short circuit 6A gL —
Mechanical
Tripping indicator “electrical tripping” Blue/white —
Frame size 45 mm 45 mm
Device height 80 mm 80 mm
Device width 8.8 mm (0.5MU) 8.8 mm (0.5MU)
Mounting Onto switching device —
Degree of protection, built-in IP40 IP40
Terminal protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Finger and hand touch safeaccording to BGV A3, ÖVE-EN 6
Terminals Lift terminals Lift terminals
Terminal capacity 20–14 AWG 0.5–2.5 mm2
Terminal screws M3 (posidrive Z0) M3 (posidrive Z0)
Fastening torque of terminal screws 7 lb-in Max. 1.2 Nm
19
UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers
ACCESSORIES
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors
Shunt Trip Release WMZTST
• Remote release for subsequent mounting onto WMZT
• Additional installation of standard auxiliary switch is possible
• Position indicator red–green
Connection Diagram
Shunt Trip Release WMZTSTDescription WMZTST110 WMZTST415
Electrical
Can be mounted onto WMZT/WMZH/WMZD WMZT/WMZH/WMZD
Operational voltage range 12–110 Vac12–60 Vdc
110–415 Vac110–230 Vdc
Frequency 50/60 Hz 50/60 Hz
Mechanical
Frame size 45 mm 45 mm
Device height 105 mm 105 mm
Device width 17.5 mm 17.5 mm
Mounting Quick fastening with 2 lock-in positions on EN 50022
Degree of protection, built-in
IP40 IP40
Terminal protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Terminals Open mouthed/lift Open mouthed/lift
Terminal capacity single- and two-wire
18–10 AWG 18–10 AWG
Busbar Block UL 489 (Pin)
• Tested according to UL 489
• Do not cut
• Extension terminal 35 mm2 WMZT35EXT for copper conductors
• To cover pins not being used, use busbar tag shrouds WMZT3PSHROUD
Connection Diagram
Busbar Block UL 489 (Pin)Description UL 489 IEC/EN 60947-2
Electrical
Rated operational voltage 480/277 Vac96 Vdc
—
Rated frequency 50/60 Hz —
Rated voltage — 690 Vac
Overvoltage category — III
Rated impulse withstand voltage Uimp
— 9.5 kV
Rated current 80A 80A
Rated conditional short-circuit current AC with 350A gG
— 15 kA
Short-circuit current 10 kA —
Mechanical
Busbar cross section — 16 mm2 Cu
Flame class according to UL 94
V0 —
Pollution degree — 2
Comparative tracking index
— CTI 600
Minimum clearance (internal/external)
— > 9.5/25.4 mm
Minimum creepage distance (internal/external)
— > 12.7/50.8 mm
Resistance to climatic conditions
— According to DIN/EN60068
1
2
WMZT1PWMZT2PWMZT3P
20
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT OVERVIEW
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors20
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT OVERVIEW
Optimum and Efficient Protection
Optimum product quality, tested reliability and safety standards for best protection of personnel, installations and plant . Eaton’s WMZS DIN rail mountable circuit breaker is designed for use in control panel applications .
Powerful Offering for Machine and System Builders
The WMZS is available with B, C and D characteristics in accordance with UL 1077, CSA C22 .2 No .235 and IEC 60947-2 . These devices are CE marked .
Typical Applications
Supplementary protection
• Control circuits
• Lighting
• Business equipment
• Appliances
Features
• Complete range of UL 1077 recognized DIN rail mounted miniature circuit breakers up to 63A current rating
• Standard ratings of 10 kAIC at 277/480 Vac
• Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit
• Suitable for supplementary protection
• Thermal-magnetic overcurrent protection
— Three levels of short-circuit protection, categorized by B, C and D curves
• Trip-free design—breaker can not be defeated by holding the handle in the ON position
• Captive screws cannot be lost
• Fulfill UL 1077, CSA C22 .2 No .235 and also IEC 60947-2 standard
• Field-installable shunt trip and auxiliary switch subsequent mounting
• Module width of only 17 .5 mm (per pole)
• Contact Position Indicator (red/green)
• Easy installation on DIN rail
• Possibility for sealing the toggle in ON or OFF position
WMZS Complies with the Latest National and International Standards
Standards—Supplementary Protection
UL 1077, CSA C22.2 No. 235
Apply to supplementary protectors intended for use as overcurrent, or overvoltage or undervoltage protection within an appliance or other electrical equipment where branch circuit protection is already provided, or is not required.
RoHS
These devices are RoHS compliant.
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersProduct Overview
21
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 21
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
0.0005
t [s
ec]
NI / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
504030201510987654321
954
3
3
2
DCB7
86
1
Discover These Advanced Features Three Tripping Curves to Choose From
Eaton WMZS Supplementary Protectors are available with three different tripping characteristics, including Type B, C and D . Definitions for each trip curve are contained on the ordering pages and can be used to determine the optimal characteristic for your application . For example, low level short-circuit faults in control wiring, such as PLCs, are best protected by devices with Type B trip characteristics (3 to 5X continuous rating of the device (In) .
Even though not required by NEC or CEC for Supplementary Protectors, Eaton’s WMZS devices are current limiting, which means that they interrupt fault currents within one half cycle . Current limiting devices offer superior protection by reducing peak let-through current and energy .
Catalog Numbering System
WMZS 1 B 10
Breaker Family
WMZS = Supplementary protector Number of Poles
1 = Single-pole2 = Two-pole3 = Three-pole
Protective Curve
B = B Curve (3–5X In) C = C Curve (5–10X In)D = D Curve (10–20X In)
Ampere Rating
00 = 0.5A01 = 1A02 = 2A03 = 3A04 = 4A05 = 5A06 = 6A
07 = 7A08 = 8A 10 = 10A13 = 13A15 = 15A16 = 16A20 = 20A
25 = 25A30 = 30A32 = 32A40 = 40A50 = 50A63 = 63A
Captive posidrive terminal screws with finger and back-of-hand protection (IP20)
Trip-free design; breaker cannot be defeated by holding the handle in the ON position
Breaker information printed on the front of the device for quick identification
Breakers install on standard DIN rail
Available in single-, two- and three-pole models
Color-coded indicator provides breaker status for easy troubleshooting
Time-current characteristic acc . to UL 1077 conventional
non-tripping current Int = 1.13 IN: t > 1 h
conventional tripping current It = 1.45 IN: t < 1 h
2.55 IN: t = 1–60 s (IN < 32A) t = 1–120 s (IN < 32A)
Type B: 3 IN: t > 0.1 se Type B: 5 IN: t < 0.1 sf Type C: 5 IN: t > 0.1 sg Type C: 10 IN: t < 0.1 sh Type D: 10 IN: t > 0.1 si Type D: 20 IN: t < 0.1 s
Product Selection
22
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors22
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT SELECTION
0.0005
t [s
ec]
NI / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
504030201510987654321
732
1
1
DCB5
64
WMZS Product Selection— B Curve (3–5X In Current Rating)
• Designed for resistive or slightly inductive loads
• Response time of instantaneous trip: 3–5X In current rating
• UL Recognized and CSA Certified as Supplementary Protectors
• For international and domestic use (conform to IEC 60947-2)
Suitable for applications where protection against low-level short- circuit faults in control wiring is desired . Instantaneous trip is 3–5X continuous rating of device (In) . Applications include PLC wiring, business equipment, lighting, appliances and some motors . Low magnetic trip point .
B Curve (3–5X In Current Rating)— Designed for Resistive or Slightly Inductive Loads
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
678
WMZS1B06WMZS1B07WMZS1B08
WMZS2B06WMZS2B07WMZS2B08
WMZS3B06WMZS3B07WMZS3B08
101315
WMZS1B10WMZS1B13WMZS1B15
WMZS2B10WMZS2B13WMZS2B15
WMZS3B10WMZS3B13WMZS3B15
162025
WMZS1B16WMZS1B20WMZS1B25
WMZS2B16WMZS2B20WMZS2B25
WMZS3B16WMZS3B20WMZS3B25
303240
WMZS1B30WMZS1B32WMZS1B40
WMZS2B30WMZS2B32WMZS2B40
WMZS3B30WMZS3B32WMZS3B40
50 63
WMZS1B50WMZS1B63
WMZS2B50WMZS2B63
WMZS3B50WMZS3B63
In North America, these switches are UL Recognized and CSA Certified as Supplementary Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
Specified non-tripping currentINT = 1.13 x IN for t > 1 h
Specified tripping currentIT = 1.45 x IN for t < 1 h
2.55 IN: t = 1–60 s (IN < 32A) t = 1–120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s Type B: 5 x IN: t < 0.1 s Type C: 5 x IN: t > 0.1 se Type C: 10 x IN: t < 0.1 sf Type D: 10 x IN: t > 0.1 sg Type D: 20 x IN: t < 0.1 s
product selection
23
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 23
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
WMZS Product Selection— C Curve (5–10X In Current Rating)
• Designed for inductive loads
• Response time of instantaneous trip: 5–10X In current rating
• UL Recognized and CSA Certified as Supplementary Protectors
• For international and domestic use (conform to IEC 60947-2)
Suitable for applications where medium levels of inrush current are expected . Instantaneous trip is 5–10X rating of device (In) . Applications include small transformers, lighting, pilot devices, control circuits and coils . Medium magnetic trip point .
C Curve (5–10X In Current Rating)— Designed for Inductive Loads
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
0.512
WMZS1C00WMZS1C01WMZS1C02
WMZS2C00WMZS2C01WMZS2C02
WMZS3C00WMZS3C01WMZS3C02
345
WMZS1C03WMZS1C04WMZS1C05
WMZS2C03WMZS2C04WMZS2C05
WMZS3C03WMZS3C04WMZS3C05
678
WMZS1C06WMZS1C07WMZS1C08
WMZS2C06WMZS2C07WMZS2C08
WMZS3C06WMZS3C07WMZS3C08
101315
WMZS1C10WMZS1C13WMZS1C15
WMZS2C10WMZS2C13WMZS2C15
WMZS3C10WMZS3C13WMZS3C15
162025
WMZS1C16WMZS1C20WMZS1C25
WMZS2C16WMZS2C20WMZS2C25
WMZS3C16WMZS3C20WMZS3C25
303240
WMZS1C30WMZS1C32WMZS1C40
WMZS2C30WMZS2C32WMZS2C40
WMZS3C30WMZS3C32WMZS3C40
5063
WMZS1C50WMZS1C63
WMZS2C50WMZS2C63
WMZS3C50WMZS3C63
In North America, these switches are UL Recognized and CSA Certified as Supplementary Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
0.0005
t [s
ec]
NI / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
504030201510987654321
732
1
1
DCB5
64
Specified non-tripping currentINT = 1.13 x IN for t > 1 h
Specified tripping currentIT = 1.45 x IN for t < 1 h
2.55 IN: t = 1–60 s (IN < 32A) t = 1–120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s Type B: 5 x IN: t < 0.1 s Type C: 5 x IN: t > 0.1 se Type C: 10 x IN: t < 0.1 sf Type D: 10 x IN: t > 0.1 sg Type D: 20 x IN: t < 0.1 s
For our complete product offering, see the Distribution Products Catalog (CA08101001E) .
24
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors24
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersPRODUCT SELECTION
WMZS Product Selection— D Curve (10–20X In Current Rating)
• Designed for highly inductive loads
• Response time of instantaneous trip: 10–20X In current rating
• UL Recognized and CSA Certified as Supplementary Protectors
• For international and domestic use (conform to IEC 60947-2)
Suitable for applications where high levels of inrush current are expected . Instantaneous trip is 10–20X rating of device (In) . The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies .
D Curve (10–20X In Current Rating) — Designed for Inductive Loads
AmperesSingle-Pole Catalog Number
Two-Pole Catalog Number
Three-Pole Catalog Number
0.512
WMZS1D00WMZS1D01WMZS1D02
WMZS2D00WMZS2D01WMZS2D02
WMZS3D00WMZS3D01WMZS3D02
345
WMZS1D03WMZS1D04WMZS1D05
WMZS2D03WMZS2D04WMZS2D05
WMZS3D03WMZS3D04WMZS3D05
678
WMZS1D06WMZS1D07WMZS1D08
WMZS2D06WMZS2D07WMZS2D08
WMZS3D06WMZS3D07WMZS3D08
101315
WMZS1D10WMZS1D13WMZS1D15
WMZS2D10WMZS2D13WMZS2D15
WMZS3D10WMZS3D13WMZS3D15
162025
WMZS1D16WMZS1D20WMZS1D25
WMZS2D16WMZS2D20WMZS2D25
WMZS3D16WMZS3D20WMZS3D25
303240
WMZS1D30WMZS1D32WMZS1D40
WMZS2D30WMZS2D32WMZS2D40
WMZS3D30WMZS3D32WMZS3D40
In North America, these switches are UL recognized and CSA Certified as Supplementary Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
0.0005
t [s
ec]
NI / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
504030201510987654321
732
1
1
DCB5
64
Specified non-tripping currentINT = 1.13 x IN for t > 1 h
Specified tripping currentIT = 1.45 x IN for t < 1 h
2.55 IN: t = 1–60 s (IN < 32A) t = 1–120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s Type B: 5 x IN: t < 0.1 s Type C: 5 x IN: t > 0.1 se Type C: 10 x IN: t < 0.1 sf Type D: 10 x IN: t > 0.1 sg Type D: 20 x IN: t < 0.1 s
25
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 25
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
PRODUCT SELECTION
Pin Type Incoming Supply Terminals
Accessories DescriptionCatalog Number
Incoming Terminal• Accommodates
conductors from 6–35 mm2/ #10–2 AWG
• 4–5.5 Nm/ 35–50 lb-in
• Finger-safe connection
WMZS35EXT
Protective Accessories
Accessories DescriptionCatalog Number
Busbar Terminal Cover
For covering unused terminals
WMZSBBTC
Padlock Hasp
•Prevents reactivation of the device during maintenance
•Holds one padlock
WMZPLK
Bus Incoming Supply Terminals
Accessories DescriptionCatalog Number
Incoming Terminal
• 50 mm2
• #14–1 AWG
• 75 deg wire
• 115 A/Y, 480V UL
• 160 A/Y 690V IEC
WMZSBCONA
Busbar End Cap
Accessories Description PolesCatalog Number
Fork Connector• Install after
cutting busbar
• Protects end of busbar
2 and 3 WMZS3CAP
1 WMZS1CAP
26
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors26
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
Technical DataDescription B Curve C Curve D Curve
ElectricalApprovals UR (UL 1077), CSA (CSA 22.2 No. 235), CEStandards IEC/EN 60947-2Short-circuit trip response 3 x 5 In 5 x 10 In 10 x 20 In
Supplementary Protectors—UL/CSACurrent range 6–63A 0.5–63A 0.5–40AMaximum voltage ratings—UL/CSA Single-pole Two-, three-pole Two poles in series
277 Vac48 Vdc480Y/277 Vac96 Vdc
277 Vac48 Vdc480Y/277 Vac96 Vdc
277 Vac48 Vdc480Y/277 Vac96 Vdc
Thermal tripping characteristics Single-pole Multi-pole
1.35 x In @ 40°C1.45 x In @ 40°C
1.35 x In @ 40°C1.45 x In @ 40°C
1.35 x In @ 40°C1.45 x In @ 40°C
Short-circuit ratings (at max. voltage) Single-pole Two-, three-pole Single-pole Two poles in series
10 kA (5 kA for 40–63A device)10 kA (5 kA for 40–63A device)10 kA @ 48 Vdc10 kA @ 96 Vdc
10 kA (5 kA for 40–63A device)10 kA (5 kA for 40–63A device)10 kA @ 48 Vdc10 kA @ 96 Vdc
5 kA5 kA10 kA @ 48 Vdc10 kA @ 96 Vdc
Miniature Circuit Breaker—IECCurrent range 6–63A 0.5–63A 0.5–40AMaximum voltage ratings—IEC 60947-2 Single-pole Two-, three-pole
230 Vac48 Vdc230/400 Vac
230 Vac48 Vdc230/400 Vac
230 Vac48 Vdc230/400 Vac
Maximum voltage ratings—IEC 60898 Single-pole Two-, three-pole
240 Vac48 Vdc240/415 Vac
240 Vac48 Vdc240/415 Vac
240 Vac48 Vdc240/415 Vac
Thermal tripping characteristics Single-pole Multi-pole
> 1 Hour @ 1.05 x In< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In< 1 Hour @ 1.3 x In
Interrupt ratings (at max. voltage) IEC 60947-2 IEC 60898Operational switching capacityMax. backup fuse (gL/gG)Rated impulse withstand—UimpRated insulation voltage—Ui
15 kA10 kA7.5 kA125A4000 Vac440 Vac
15 kA10 kA7.5 kA125A4000 Vac440 Vac
15 kA10 kA7.5 kA125A4000 Vac440 Vac
Environmental/GeneralSelectivity classLifespan (operations)Shock (IEC 68-2-22)Operating temperature rangeShipment and short-term storageHousing material
3> 10000 (1 operation = ON/OFF)10g–120 ms+23 to +104°F (–5 to +40°C)–40 to +185°F (–40 to +85°C)Nylon
3> 10000 (1 operation = ON/OFF)10g–120 ms+23 to +104°F (–5 to +40°C)–40 to +185°F (–40 to +85°C)Nylon
3> 10000 (1 operation = ON/OFF)10g–120 ms+23 to +104°F (–5 to +40°C)–40 to +185°F (–40 to +85°C)Nylon
MechanicalStandard front dimensionDevice heightTerminal protectionMounting width per pole
80 mmFinger and back-of-hand proof to IEC 53617.5 mm
80 mmFinger and back-of-hand proof to IEC 53617.5 mm
80 mmFinger and back-of-hand proof to IEC 53617.5 mm
MountingDegree of protectionTerminals top and bottomSupply connection
IEC/EN 60715 top-hat railIP20Twin-purpose terminalsLine or load side
IEC/EN 60715 top-hat railIP20Twin-purpose terminalsLine or load side
IEC/EN 60715 top-hat railIP20Twin-purpose terminalsLine or load side
Terminal capacity (mm2)TorqueImperial torque
Thickness of busbar materialMounting position
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)2.4 Nm21 lb-in (AWG 18–12), 25 lb-in (AWG 10–8), 36 lb-in (AWG 6–4)0.8–2 mmAs required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)2.4 Nm21 lb-in (AWG 18–12), 25 lb-in (AWG 10–8), 36 lb-in (AWG 6–4)0.8–2 mmAs required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)2.4 Nm21 lb-in (AWG 18–12), 25 lb-in (AWG 10–8), 36 lb-in (AWG 6–4)0.8–2 mmAs required
Technical Data
27
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 27
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
Let-Through Energy I2t
Characteristic B and C
Characteristic D
2 A
1 A
0.5 A
10 A 13 A 16 A 20 A 25 A 32 A 40 A
50 A 63 A
4 A
3 A
6 A
0.5 1.5 151 2 3 4 5 6 7 8 910
103
104
105
8
6
4
2
1.5
8
6
4
2
8
6
4
3
1.5
∫i2dt[A2s]
Icc rms [kA]
WMZS-...-B4HI
10 A
13 A 16 A 20 A 25 A 32 A 40 A
6 A
0.5 1.5 151 2 3 4 5 6 7 8 910
103
104
105
8
6
4
2
1.5
8
6
4
2
8
6
4
1.5
∫i2dt[A2s]
Icc rms [kA]
Let-Through Current ID
Characteristic B and C
Characteristic D
63 A 40 A
50 A 32 A
20 A 25 A 16 A 13 A 10 A
6 A 4 A 3 A
2 A
1 A
0.5 A
0.5 1.5 151 2 3 4 5 6 7 8 910
103
104
987
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
40 A 32 A 20 A
25 A
16 A 13 A 10 A
6 A
0.5 1.5 151 2 3 4 5 6 7 8 910
103
104
987
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
28
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors28
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
In (A)
Ambient Temperature T
–25°C –20°C –10°C 0°C 10°C 20°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C
0.160.250.50.75
0.200.310.610.92
0.190.300.600.90
0.190.290.580.87
0.180.280.560.84
0.170.270.540.81
0.170.260.520.78
0.160.250.500.75
0.160.250.490.74
0.150.240.480.73
0.150.240.470.71
0.150.230.460.69
0.140.230.450.68
0.140.220.440.66
11.51.62
1.21.82.02.4
1.21.81.92.4
1.21.71.92.3
1.11.71.82.2
1.11.61.72.2
1.01.61.72.1
1.01.51.62.0
0.991.51.62.0
0.971.51.51.9
0.951.41.51.9
0.931.41.51.9
0.901.41.41.8
0.891.31.41.8
2.533.54
3.13.74.34.9
3.03.64.24.8
2.93.54.14.7
2.83.43.94.5
2.73.33.84.3
2.63.13.74.2
2.53.03.54.0
2.53.03.43.9
2.42.93.43.9
2.42.83.33.8
2.32.83.23.7
2.32.73.23.6
2.22.73.13.5
5678
6.17.38.69.8
6.07.28.49.6
5.87.08.19.3
5.66.77.99.0
5.46.57.68.7
5.26.37.48.4
5.06.078.0
4.95.96.97.9
4.85.86.87.7
4.75.76.77.6
4.65.66.67.4
4.55.46.47.2
4.45.36.37.1
10121315
12151618
12141618
12141517
11131517
11131416
10131416
10121315
9.9121315
9.7121315
9.5111214
9.3111214
9.0111214
8.9111213
16202532
20243139
19243038
19232937
18222836
17222735
17212633
16202532
16202532
15192431
15192430
15192330
14182329
14182228
405063
496177
486076
475873
455671
435468
425266
405063
394962
394861
384760
374658
364557
354456
Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA of the instantaneous release
Mains Frequency f [Hz]
16-2/3 50 60 100 200 300 400
IMA(f)IMA (50 Hz) [%] 91 100 101 106 115 134 141
Load Carrying Capacity of Adjoining Miniature Circuit Breakers
Number of circuit breakers
Rat
ed d
iver
sity
fac
tor
1 2 3 4 5 6 7 80.70
0.80
0.90
1.00
29
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 29
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
Auxiliary Contacts and Voltage Trips
ModuleCircuit Diagram Description
Rated Operational Voltage
Catalog Number
Standard Auxiliary Contacts
2
14 1112H
• 1NO/1NC
• Installs on left side of WMZS or shunt trip
• Max. one per WMZS (1077) device
• Switches when WMZS is tripped electrically or manually
230 Vac WMZSAUX
Auxiliary/Trip Indicating Contact• Small selector screw changes mode
• Two Form C (changeover) contacts
• Installs on left side of WMZS or shunt trip
• Auxiliary contacts switch when WMZS is tripped electrically or manually
• Trip indicating contact switches only when WMZS is tripped electrically
230 Vac WMZSAUXTRIP
Undervoltage Trip
D2
U
D1
• Prevents WMZS from operating unless voltage is presen
• Installs on left side of WMZ
• Includes Test button
115 Vac WMZSUVR115
230 Vac WMZSUVR230
400 Vac WMZSUVR400
Shunt Trip
C2
C1
• Allows remote trip of WMZS
• Installs on left side of WMZS
110–415 Vac110–230 Vdc
WMZSST415
12–110 Vac12–60 Vdc
WMZSST110
Allowable Combinations of Accessories
1
2 4 1.12 4.14
1.14 4.12
1.11
OFF
4.11N
AUXTRIP
AUX AUX AUXTRIP
WMZS WMZS WMZS
CircuitBreaker
or
CircuitBreaker
ShuntTrip
or
CircuitBreaker
UnderVTrip
30
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors30
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
Busbar System
DescriptionRated Operational Current (A)
Number of Poles per Device
Number of Terminals
Catalog Number
Without Auxiliary Contacts
For connecting WMZS Supplementary Protectors without auxiliary contacts. May be fed from line or load side.
80 1 57 WMZS1P57T
2 56 WMZS2P56T
3 57 WMZS3P57T
100 1 57 WMZS1P57T25
2 56 WMZS2P56T25
3 57 WMZS3P57T25
Auxiliary/Trip Indicating Contact
For connecting WMZS Supplementary Protectors with auxiliary contacts. May be fed from line or load side.
80 1 37 WMZS1P37TAUX
2 46 WMZS2P46TAUX
3 48 WMZS3P48TAUX
100 1 37 WMZS1P37T25AUX
2 46 WMZS2P46T25AUX
3 48 WMZS3P48T25AUX
WMZS WMZS WMZS
WMZS WMZS
35 lb-in(4 Nm)
22 lb-in(2.5 Nm)
WMZSBCONA
WMZS35EXT
WMZS3CAPor
WMZS1CAP
WMZSBBTC
50 lb-in(5.5 Nm)
31
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 31
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
Technical Data
DescriptionWMZSAUXWMZSAUXTRIP WMZSST WMZSUVR
Electrical
Contact function
1A + 1B2 C/O
——
——
Rated operational voltage Un 250 Vac — 115 Vac—WMZSUVR115230 Vac—WMZSUVR230400 Vac—WMZSUVR400
Voltage range WMZSST110 — 12–110 Vac12–60 Vdc
—
Voltage range WMZSST415 — 110–415 Vac110–230 Vdc
—
Closing threshold (x Un) — — 0.8
Tripping threshold (x Un) — — 0.5
Rated frequency ƒ 50/60 Hz 50/60 Hz 50/60 Hz
General use (UL/CSA) AC—230/240 Vac DC—110/120 Vdc
2/2A0.5/0.5A
——
——
Pilot duty A600/Q600 — —
Conventional free air thermal current Ith 4A — —
Rated operational current AC-13 Ie AC-15 Ie DC-13 Ie
3A (250 Vac)2A (250 Vac)0.5A (110 Vdc)
———
———
Rated insulation voltage Ui 250 Vac — —
Minimum operating voltage per contact Umin 5 Vdc — —
Rated impulse withstand voltage (1.2/50μ) Uimp 2.5 kV — —
Rated conditional short-circuit current with 6A backup fuse ISC 1 kA — —
Maximum admissible backup fuse 4A gL — —
Mechanical
Standard front dimension 45 mm 45 mm 45 mm
Device height 80 mm 80 mm 80 mm
Mounting width 8.8 mm 17.6 mm 17.8 mm
Mounting On MCB IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail
Degree of protection—enclosed IP40 IP40 IP40
Terminal protection Protection against electric shock to IEC 536
Protection against electric shock to IEC 536
Protection against electric shock to IEC 536
Terminals Lift terminals Twin-purpose terminals Twin-purpose terminals
Terminal capacity Solid Flexible
0.5–2.5 mm2
0.5–2.5 mm21–2.5 mm2
1–2.5 mm22 x (1–2.5) mm2
2 x (1–2.5) mm2
Tightening torque of terminal screws 0.8–1.0 Nm (7–9 lb-in) 2.4 Nm (21 lb-in) 0.8 Nm (7 lb-in)
32
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors32
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit BreakersTECHNICAL DATA
Dimensions
Miniature Circuit Breakers
WMZS
80
1P 2P 3P
17.5
80 80
35 52.5
45
4.55.530.5
44
60
11
Auxiliary Contacts
WMZSAUX
WMZSAUXTRIP
Shunt Releases
WMZSST
Undervoltage Releases
WMZSUVR
44
2
8.9 5.5
60
3.4
80 85.4 45
9.6
9.6
449
60
4580
5.5
17.6 30.55.5
44
60
80
26.2
45
10
80
17.8 5.5 44
60
45
33
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
EATON CORPORATION Cable-in / cable-out circuit breakers and protectors 33
UL 1077 Cable-In / Cable-Out Supplementary ProtectorsWMZS Circuit Breakers
TECHNICAL DATA
Busbar and Accessory Weights and Dimensions
Catalog Number
Unit Weight (kg)
Length (mm)
Width (mm)
Height (mm)
WMZS1P57TWMZS2P56TWMZS3P57T
0.290.640.83
10099911009
152222
153737
WMZS1P37TAUXWMZS2P46TAUXWMZS3P48TAUX
0.260.630.79
9851009982
152222
153737
WMZS1P57T25WMZS2P56T25WMZS3P57T25
0.360.791.04
10099911009
152222
153737
WMZS1P37T25AUXWMZS2P46T25AUXWMZS3P48T25AUX
0.310.730.97
9851009982
152222
153737
WMZS35EXTWMZSBCONAWMZSBBTCWMZS1CAPWMZS3CAP
0.030.030.0030.0010.001
6040851424
171812522
2930241010
v
L W
H
Eaton CorporationElectrical Sector1111 Superior Ave .Cleveland, OH 44114United States877-ETN-CARE (877-386-2273)Eaton .com
© 2011 Eaton CorporationAll Rights ReservedPrinted in USAPublication No . PG01101008E / Z9904 April 2011
Eaton’s Electrical Sector is a global leader in power distribution, power quality, control and automation, and monitoring products . When combined with Eaton’s full-scale engineering services, these products provide customer- driven PowerChainE solutions to serve the power system needs of the data center, industrial, institutional, public sector, utility, commercial, residential, IT, mission critical, alternative energy and OEM markets worldwide .
PowerChain solutions help enterprises achieve sustainable and competitive advantages through proactive management of the power system as a strategic, integrated asset throughout its life cycle, resulting in enhanced safety, greater reliability and energy efficiency . For more information, visit www .eaton .com/electrical .