Cabinet HeatersFORCED DRAUGHT GAS AND OIL FIRED CABINET HEATERS
CI/SfB56.83 X
Introduction
The AmbiRad range of cabinet heaterscombines innovative design with a proven four pass heat exchanger technology to provide a high efficiency cost effective and durable range.
The units may be specified for either free blowing applications or for use withductwork.
Units are manufactured in accordancewith ISO 9001 accreditation, all heaterefficiencies are compliant with Part L2Bof the 2010 Building Regulations with themajority of models also meeting the higher efficiency requirements for Enhanced Capital Allowances.
Options
• High/low or fully modulating burners
• Combustion air adaptors
• Stainless steel tubular heat exchanger
• Air inlet spigots
• Air inlet filters
• Manual or motorised inlet dampers
• Up-rated fan motor for increased static pressure
Applications
• Factories
• Warehouses
• Workshops
• Showrooms
• Greenhouses
Model Range
Cabinet heaters are available as either gas or oil fired models.
• Gas fired cabinet heaters are suitable for use with Natural Gas (G20), most units can also be specified for Propane (G31)
• Oil fired cabinet heaters are suitable for use with Class D gas oil (35 sec), most units can also be specified for Kerosene (28 sec oil)
Vertical freestanding models are available from 29kW to 380kW.
Horizontal and Down flow models from 58kW to 380kW.
This symbol verifies that the product has been independently assessed and currently qualifies for the ECA scheme, an upfront tax relief enabling businesses that invest in energy-saving equipment to claim 100% first-year capital allowances against their taxable profits.
ECA
Cabinet HeatersGAS AND OIL FIRED CABINET HEATERS
SpecificationCabinetsCabinets are constructed from electro-zinc coated steel with an inner heat shield skin and an epoxy powder coat finish outer skin to form a rigid and durable casework.
Air DistributionCentrifugal fan(s) circulate large air volumes evenly across the full heat exchanger surface for enhanced life expectancy. Fans on models 30 to 85 are direct drive with a single phase motor whilst larger models are fitted with a three phase motor and v-belt drive.
Free blowing heaters are fitted with long throw discharge nozzles complete with horizontal louvres and can be rotated through 360o. Models 75-375 are supplied with a raised rear nozzle (one per three nozzle heater and two per four nozzle heater).
Heaters for use with ductwork aresupplied with a duct outlet spigot.
Heat Exchanger and BurnerFour pass combustion chamber/heatexchanger assembly provides improvedthermal efficiency with extended life expectancy. A stainless steel chamber is combined with a high efficiency tubular heat exchanger to achieve thermal efficiency in excess of 91%.
The complete assembly is mounted to allow for thermal expansion thereby avoiding undue thermal stress and premature heat exchanger failure.
Gas fired units are fitted with a fullyautomatic forced draught burner completewith full safety controls to EN676 and theheaters are CE certified. A high/lowburner is fitted as standard on model 375.
Oil fired units are supplied complete witha fully automatic burner including safety controls and factory fitted fire valve and oil filter. An additional external fire valve may be required in accordance with BS 5410:Part2:1978.
ControlsA combined fan and limit switch is fittedon all heaters.
In the event of overheating the unit would automatically be shut down by the limitthermostat.
All heaters are supplied with an electronicprogrammer complete with optimisedcontrol, this is factory fitted and wiredon free-blowing vertical models. Forhorizontal, and all duct outlet models down flow heaters the controller is supplied loose for on site wiring by the installer.
Electric MotorsAll electric motors comply with EC motor directive 2005/32/EC
1 Throw is dependent on building height, room temperature and nozzle settings.2 Gas/oil lines must be adequately sized and reduced at appliance as required.
TECHNICAL DATA
Model 30 35 40 60 75 85 120 135 180 205 235 275 350 375
Gas Fired
ECA Approved*Nominal heat outputTemperature rise Gas Consumption Nat gas G20Gas Consumption propane G31 Minimum inlet pressure Nat gas G20Minimum inlet pressure propane G31Gas Connection2
kW
Km3/hm3/hmbarmbar
Rc
29393.71.317.537.0½”
36424.41.617.537.0½”
40454.71.817.537.0½”
58466.92.617.537.0½”
73438.53.217.537.0½”
83489.73.717.537.0½”
11744
13.65.217.537.0¾”
13341
15.36.017.537.0¾”
17746
20.47.817.537.01”
20649
23.99.217.537.01¼”
23744
27.210.417.537.01¼”
27846
33.012.317.537.01¼”
35041
40.716.117.537.01 ½”
38045
45.818.117.537.02”
Oil Fired
ECA Approved*Nominal heat outputTemperature rise Oil Consumption Oil Connection2
kWK
l/hRc
32433.4⅜”
38434.1⅜”
43494.7⅜”
60476.5⅜”
76448.1⅜”
82489.1⅜”
12346
13.3⅜”
13842
15.0⅜”
18448
19.5⅜”
20850
22.5⅜”
24847
27.0⅜”
26544
34.1⅜”
35041
40.4⅜”
38045
45.6⅜”
Air Handling DataAirflowThrow1 (Nozzle outlet) Static pressure (Ducted) Std motor Increased motorMain fan motor FLC 230/1/50FLC 415/3/50Up-rated fan motorFLC 415/3/50
m3/sm
PaPakW
amp ampkW
amp
0.611475n/a0.553.2n/an/an/a
0.7114100n/a0.554.8n/an/an/a
0.7114100n/a0.554.8n/an/an/a
1.0317125n/a0.996.02.2n/an/a
1.3917100n/a0.997.22.2n/an/a
1.3917100n/a0.997.22.2n/an/a
2.15201371751.5012.03.62.25.2
2.65201502002.2014.05.23.06.5
3.11201752253.0n/a6.54.08.4
3.4221882253.00n/a6.54.08.4
4.32221251884.00n/a8.45.511.0
4.86251752255.50n/a11.07.514.0
6.8831250n/a7.50n/a17.011.024.0
6.8831250n/a7.50n/a17.011.024.0
General DataNominal flue diameter Nominal combustion air diameter Noise level3 Net weight
mmø mmødB(A)
kg
12512567196
12512569196
12512569196
15012572241
15012572243
17512572243
17515074330
17515076332
20015078525
20015078540
22515079630
22515081646
25015081
1090
25015081
1090
3 Noise levels measured at 5 metres from appliance.*Please check ETL at time of ordering for latest listings as criteria are subject to change.
Vertical HeatersGAS AND OIL FIRED CABINET HEATERS
Vertical Heaters VN/VD
DIMENSIONS
Model 30 35 40 60 75 85 120 135 180 205 235 275 350 375
A 1650 1650 1650 1900 1900 1900 2025 2025 2125 2125 2110 2110 2667 2667
B 660 660 660 660 660 660 740 740 916 916 1100 1100 1244 1244
C 662 662 662 925 925 925 1085 1085 1315 1315 1550 1550 1550 1550
D 95 95 95 170 170 170 170 170 195 195 195 195 203 203
E mmø 125 125 125 150 150 175 175 175 200 200 225 225 250 250
F 250 250 250 320 320 320 320 320 380 380 380 380 355 355
G OilGas
229349
229349
229349
267362
267362
267362
298432
298432
298432
476580
476580
476580
476580
476580
H 280 280 280 280 280 280 305 305 355 355 406 406 474 474
J1 StandardExtended
240n/a
330n/a
300n/a
300n/a
330660
330660
360720
360720
410815
410815
460915
460915
6131115
6131115
K 1500 1500 1500 1778 1778 1778 1878 1878 1980 1980 1965 1965 2610 2610
L 835 835 835 984 984 984 968 968 1068 1068 1054 1054 1372 1372
1. Heaters with 3 or 4 nozzles are supplied with extended head on the rear nozzle(s). For applications with restricted headroom, units may be specified with all nozzles at standard height.
Front View Side View
F
L
D
J
Eø
G
A K
J
H
INSTALLATION DIMENSIONS
Model 30 35 40 60 75 85 120 135 180 205 235 275 350 375
Head plan (VN) 1 1 1 1 2 2 2 3 3 3 3 3 3 3
Nozzle detail(VN)
no.Spigot ø
2240
2240
2240
2240
3240
3240
3280
4280
4320
4320
4370
4370
4370
4370
Outlet Spigot(VD)
AB
570570
570570
570570
634770
634770
634770
714950
714950
8901120
8901120
10001450
10001450
10861365
10861365
Side Inlet Spigot(VN/VD)
CD
522348
522348
522348
702427
702427
702427
904542
904542
1078692
1078692
1145654
1145654
1150796
1150796
Rear Inlet Spigot(VN/VD)
EF
620445
620445
620445
520550
520550
520550
608550
608550
790560
790560
935654
935654
n/an/a
n/an/a
Inlet Filter Assembly(VN/VD)
GHJ
420660300
420660300
420660300
600800300
600800300
600800300
680990300
680990300
7651165300
7651165300
7201245450
7201245450
8601530450
8601530450
Installation ClearancesFrontSideRear
500300700
500300700
500300700
5003001000
5003001000
5003001000
6003001200
6003001200
6003001500
9003001500
9004002000
9004002000
9005002000
9005002000
Filter cassettes can be withdrawn from either side, ensure adequate clearance for withdrawal i.e. full width of filter box.
Air Discharge and Inlet Details VN/VD
J
H
Side inlet spigotleft (as shown) or right -
please specify at time of order
Rear inlet spigot Side inlet filterLeft (as shown) or right - please specify at time of order.
Additional side inlet spigot is required to connect filter box to inlet ductwork
Nozzle outlet 30-60 Nozzle outlet 75-120 Nozzle outlet 135-375 Duct outlet spigot
Return Air spigots and Filters VN/VD
G
F
E5050C
D
A
B
Horizontal CabinetsGAS AND OIL FIRED CABINET HEATERS
DIMENSIONS
Model 60 75 85 120 135 180 205 235 275 350 375
A 1865 1865 1865 1993 1993 2093 2093 2076 2076 2667 2667
B 660 660 660 740 740 916 916 1100 1100 1244 1244
C 925 925 925 1085 1085 1315 1315 1550 1550 1550 1550
D 170 170 170 170 170 200 200 225 225 203 203
E mmø 150 150 175 175 175 200 200 225 225 250 250
F 320 320 320 320 320 380 380 380 380 355 355
G 560 560 560 640 640 816 816 1000 1000 1086 1086
H 790 790 790 952 952 1182 1182 1450 1450 1365 1365
J OilGas
267362
267362
267362
298432
298432
298432
476580
476580
476580
476580
476580
K 160 160 160 225 225 320 320 320 320 320 320
L mmø 209 209 209 290 290 425 425 425 425 480 480
M 676 676 676 790 790 790 790 769 769 1054 1054
N 984 984 984 968 968 1068 1068 1054 1054 1372 1372
P 568 568 568 607 607 740 740 840 840 1396 1396
Q 1806 1806 1806 1934 1934 2034 2034 1475 1475 2612 2612
R 1081 1081 1081 1244 1244 1474 1474 1750 1750 1750 1750
S 1157 1157 1157 1320 1320 1550 1550 1826 1826 1826 1826
Horizontal Heaters HN/HD
C F
L D
JP
B
R
S
92
Eø
Plan View
End View
Side View
Note: Units may be specified for airflowright to left which is the standard configurationas shown. Alternatively units can be specified for airflow left to right.
HH
K
G
45 45
A
M N
G
Q
Downflow CabinetsGAS AND OIL FIRED CABINET HEATERS
DIMENSIONS
Model Ref 60 75 85 120 135 180 205 235 275 350 375
A 1865 1865 1865 1993 1993 2093 2093 2076 2076 2667 2667
B 660 660 660 740 740 916 916 1100 1100 1244 1244
C 925 925 925 1085 1085 1315 1315 1550 1550 1550 1550
D 170 170 170 170 170 200 200 225 225 203 203
E mmø 150 150 175 175 175 200 200 225 225 250 250
F 320 320 320 320 320 380 380 380 380 355 355
G 560 560 560 640 640 816 816 1000 1000 1086 1086
H 790 790 790 952 952 1182 1182 1450 1450 1365 1365
J OilGas
267362
267362
267362
298432
298432
298432
476580
476580
476580
476580
476580
K 160 160 160 225 225 320 320 320 320 320 320
L 209 209 209 290 290 425 425 425 425 480 480
M 676 676 676 790 790 790 790 769 769 1054 1054
N 984 984 984 968 968 1068 1068 1054 1054 1372 1372
P 476 476 476 515 515 648 648 748 748 1304 1304
Downflow Heaters RN/RD
Front View Side View
B
G45
A
G45 P
K
CH
H
L
F
D
N
M
Eø
J
Plan View
AmbiRad Limited Fens Pool AvenueBrierley Hill West Midlands DY5 1QA United Kingdom
Telephone: 01384 489700Facsimile: 01384 489707Email: [email protected]: www.ambirad.co.uk
Doc
umen
t ref
eren
ce n
umbe
r: G
B/W
A/0
85/0
611
1 Top clearance applies to units with side air inlet. For units with top air inlet allow 1000mm
AmbiRad UK is a registered trademark of AmbiRad Limited. Because of continuous product innovation, Ambirad reserves the right to change product specification without due notice.
Air Discharge and Inlet Details
INSTALLATION DIMENSIONS
Model 60 75 85 120 135 180 205 235 275 350 375
Nozzle ø (HN/RN) 203 203 203 284 284 419 419 419 419 470 470
Duct Spigot(All)
AB
790560
790560
790560
952640
952940
1182816
1182816
14501000
14501000
13651086
13651086
Top & Side Inlet(HN/HD & RN/RD)
CD
702427
702427
702427
904542
904542
1078692
1078692
1145654
1145654
1150796
1150796
Rear Inlet(HN/HD)
EF
520520
520520
520520
608550
608550
790560
790560
935654
935654
n/an/a
n/an/a
Installation ClearancesFrontTop (RN/RD)Top1 (HN/HD)Rear
5001501501000
5001501501000
5001501501000
6001501501200
6001501501200
6001501501500
9001501501500
9001504002000
9001504002000
9001505002000
9001505002000
B
A
B
A
C
D
F
E
F
EC
D
Discharge outlets (HN/RN)
(All HN/RN models are supplied with 4 louvred outlets)
Alternative Return Air Spigots
Air Filters
Top or bottom inlet spigot HN/HD
Rear inlet spigot HN/HD
Side inlet spigot RN/RD
Rear inlet spigot RN/RD
Top or bottom inlet filterHN/HD
Side inlet filter RN/RD
Outlet spigot (HD/RD)
(Flue location shown for standard R-L horizontal airflow)
End inlet spigot (HN/RN HD/RD)
(Burner location shown for standard R-L horizontal airflow)