busbars and distribution
TRANSCRIPT
iNTro
in accordance with its policy of continuous improvement, the Company reserves the right to change specifications and designs without notice. All illustrations, descriptions, dimensions and weights in this catalogue are for guidance and cannot be held binding on the Company.
Protection and control of operating circuits are the basic functions of a distribution panel. But upstream there is another function, possibly more discreet, but just as essential: distribution.
Even more than for the protection and control functions, the selection and setup of distribution equipment require an approach that combines selection of products (number of outputs, cross-sections, conductor types, connection method) and checking the operating conditions (current-carrying capacity, short circuits, isolation, etc.) in multiple configurations.
depending on the power installed, distribution is carried out via distribution blocks (up to 400 A) or via busbars (250 A to 4000 A). The former must be selected according to their characteristics (see page 32), while the latter must be carefully calculated and sized according to requirements (see page 06).
01
Distribution and standards 02Statutory conditions for the protection of branch or distributed lines � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 04
Sizing busbars 06Determining the usable cross-section of the bars � � � � � � � � � � � � � � � � 06
Checking the permissible thermal stress � � � � � � � � � � � � � � � � � � � � � � � 12
Determining the distances between supports � � � � � � � � � � � � � � � � � � � �13
Magnetic effects associated with busbars � � � � � � � � � � � � � � � � � � � � � � 20
Checking the insulation characteristics � � � � � � � � � � � � � � � � � � � � � � � � 23
Shaping and connecting bars 26
Rigid bars � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 26
Flexible bars � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 30
Current transformers (Ct) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 31
Distribution blocks 32Characteristics of distribution blocks � � � � � � � � � � � � � � � � � � � � � � � � � � 33
Phase balancing � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 36
Legrand distribution blocks � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 40
Choice of products 46
B u S B a r S a n D D i S T r i B u T i o n
02
DiS
tRib
uti
on
an
D S
tan
Da
RD
S
Distribution and standards Distribution can be defined as supplying
power to a number of physically separate and individually protected circuits from a single circuit.
Upstream protection device
Distribution
Downstream protection devices
I1 I2 I3 I4
I
^ Main busbar at the top of the enclosure with 2 copper bars per pole
^ Branch busbar in cable sleeve: C-section aluminium bars
Depending on the circuits to be supplied, distribution will be via busbars (flat or C-section copper or aluminium bars, see p� 06), via prefabricated distri-bution blocks (power distribution blocks, modular distribution blocks, distribution terminal blocks, see p� 32) or via simple supply busbars� according to the standards, a device providing protection against short circuits and overloads must be placed at the point where a change of cross-section, type, installa-tion method or composition leads to a reduction in the current-carrying capacity (iEC 60364-4-43)�
03
DiS
tRib
uti
on
an
D S
tan
Da
RD
S
P1 S1
P2
S2 < S1
if it were applied to the letter, this rule would lead to over-sizing of cross-sections for fault conditions� the standard therefore allows for there to be no protection device at the origin of the branch line subject to two conditions�
upstream device P1 effectively protects the branch line S2 …
… or the branch line S2 is less than three metres long, is not installed near any combustible materials and every precaution has been taken to limit the risks of short circuits� there is no other tap-off or power socket on the branch line S2 upstream of protection P2�
P1 S1
P2
S2 < S1L < 3 m
P1 S1
P2
S2 < S1
P1
P2 P2
P3
S1
I14I13I12I11
S2
S3
I1
It
I24I23I22I21
S2I2
1st level
2nd level
Multi-level distribution
This layout can be used for exam-ple when several distribution blocks (2nd level) are supplied from a single busbar (1st level). If the sum of the currents tapped off at the first level (I1, I2, etc.) is greater than It, a protection device P2 must be provided on S2.
Conductor cross-sections: S3 < S2 S2 < S1
Theoretical layout
P1 protects S1
P2 protects S2
There is no reduction in cross-section before P2
< Modular distribution block ^ Distribution via supply busbars
B u S B a r S a n D D i S T r i B u T i o n
04
Sta
tuto
RY
Co
nD
itio
nS
FoR
PR
otE
Cti
nG
bR
an
CH
oR
DiS
tRib
utE
D L
inE
S B u S B a r S a n D D i S T r i B u T i o n
0404
Distribution and standards (continued)
STATUTORY CONDITIONS FOR PROTECTING BRANCH OR DISTRIBUTED LINES
1 SUmmARY OF THE GENERAL PRINCIPLE FOR CHECkING THERmAL STRESSFor insulated cables and conductors, the breaking time of any current resulting from a short circuit occurring at any point must not be longer than the time taken for the temperature of the conductors to reach their permissible limit�this condition can be verified by checking that the thermal stress K²S² that the conductor can withstand is greater than the thermal stress (energy i²t) that the protection device allows to pass�
2 CHECkING THE PROTECTION CONDITIONS OF THE BRANCH LINE(S) wITH REGARD TO THE THERmAL STRESSESFor branch lines with smaller cross-sections (S2<S1), check that the stress permitted by the branch line is actually greater than the energy limited by the main device P1� the permissible thermal stress values K²S² can be easily calculated using the k values given in the table below:
the maximum energy values limited by the devices are given in the form of figures (for example 55,000 a²s for modular devices with ratings up to 32 a or in the form of limitation curves (see book 5)�
3 CHECkING THE PROTECTION CONDITIONS USING THE “TRIANGLE RULE”the short-circuit protection device P1 placed at the origin a of the line can be considered to effectively protect branch S2 as long as the length of the branch busbar system S2 does not exceed a certain length, which can be calculated using the triangle rule�- the maximum length L1 of the conductor with cross-section S1 corresponds to the portion of the circuit ab that is protected against short circuits by protection device P1 placed at point a�- the maximum length L2 of the conductor with cross-section S2 corresponds to the portion of the circuit aM that is protected against short circuits by protection device P1 placed at point a�these maximum lengths correspond to the minimum short circuit for which protection device P1 can operate (see book 4)�
K values for conductors
Property/ConditionType of insulation of the conductor
PVC Thermoplastic
PVC Thermoplastic 90°C
EPR XLPE Thermosetting
Rubber 60°C Thermosetting mineral
Conductor cross-sect. mm2 < 300 > 300 < 300 > 300
Initial temperature °C 70 90 90 60 70 105
Final temperature °C 160 140 160 140 250 200 160 250
k values
Copper conductor 115 103 100 86 143 141 115 135 -115
Aluminium conductor 76 68 66 57 94 93 - -
Connections soldered with tin solder for copper conductors
115 - - - - - - -
05
Sta
tuto
RY
Co
nD
itio
nS
FoR
PR
otE
Cti
nG
bR
an
CH
oR
DiS
tRib
utE
D L
inE
S
05
S1 corresponds to the cross-section of the main conductor and S2 to the cross-section of the branch conductor�the maximum length of the branch conductor with cross-section S2 that is protected against short circuits by protection device P1 placed at point a is represented by segment on� it can be seen using this representation that the protected length of the branch line decreases the further away the tap-off point is from protection P1, up to the prohibition of any S2 smaller cross-section tap-off at the apex of the triangle, b�this method can be applied to short-circuit protec-tion devices and those providing protection against overloads respectively, as long as device P2 effectively protects line S2 and there is no other tap-off between points a and o�
4 3 mETRE RULE APPLIED TO OVERLOAD PROTECTION DEVICESWhen protection device P1 placed at the head of line S1 does not have any overload protection function or its characteristics are not compatible with the overload protection of the branch line S2 (very long circuits, significant reduction in cross-section), it is possible to move device P2 up to 3 m from the origin (o) of the tap-off as long as there is no tap-off or power socket on this portion of busbar system and the risk of short circuit, fire and injury is reduced to the minimum for this portion (use of reinforced insulation conductors, sheathing, separation from hot and damaging parts)�
5 EXEmPTION FROm PROTECTION AGAINST OVERLOADSthe diagram above illustrates three examples of tap-offs (S1, S2, S3) where it is possible not to provide any overload protection or simply not to check whether this condition is met�- busbar system S2 is effectively protected against overloads by P1 and the busbar system does not have any tap-offs or power sockets upstream of P2 - busbar system S3 is not likely to have overload cur-rents travelling over it and the busbar system does not have any tap-offs or power sockets upstream of P3 – busbar system S4 is intended for communication, control, signalling and similar type functions and the busbar system does not have any tap-offs or power sockets upstream of P4�
P1
L1
L2
A
A O
N
B
B
M
N
P2
P2
P2S2
S2
S2
S2S1
P1
A O
B
P2
S1
< 3m S2
P1
A O2 O3 O4
S2 S3 S4
B2 B3 B4
P2 P3 P4
S1
B u S B a r S a n D D i S T r i B u T i o n
06
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S
Sizing busbars The busbar constitutes the real “backbone”
of any distribution assembly. The main busbar and branch busbars supply and distribute the energy.
DETERmINING THE USABLE CROSS-SECTION OF THE BARS
the required cross-section of the bars is determined according to the operating current, the protection index of the enclosure and after checking the short-circuit thermal stress�the currents are named in accordance with the definitions in standard iEC 60947-1 applied to the usual operating conditions for a temperature rise At of the bars which does not exceed 65°C�
< Temperature rise test for a 3 x 120 x 10 per pole busbar on support Cat. no. 374 54
• Ie: rated operating current to be taken into consideration in enclosures with natural ventilation or in panels with IP < 30 protection index (ambient internal temperature < 25°C).
• Ithe: thermal current in enclosure corresponding to the most severe installation conditions. Sealed enclosures do not allow natural air change, as the IP protection index is greater than 30 (ambient internal temperature < 50°C).
Currents according to standard iEC 60947-1
The current-carrying capacity in n bars is less than n times the current-carrying capacity in one bar. Use n = 1.6 to 1.8 for a group of 2 bars, n = 2.2 to 2.4 for 3 bars and n = 2.7 to 2.9 for 4 bars.The wider the bars, the more coefficient n is affected, the more difficult they are to cool and the higher the mutual inductance effects.The permissible current density is not therefore constant: it is approximately 3 A/mm2 for small bars and falls to 1 A/mm2 for groups of large bars.
Parallel bars
busbars can be created using copper or aluminium bars� Flat copper bars are used for busbars up to 4000 a with Legrand supports� they provide great flexibility of use, but require machining on request (see p� 26)� Legrand aluminium bars are made of C-section rails� Connection is carried out without drilling, using special hammer head screws�
they are used for busbars up to 1600 a, or 3200 a by doubling the supports and the bars�the electrical and mechanical characteristics of Legrand busbar supports, and strict compliance with the maximum installation distances, ensure isolation between the poles and that the bars can resist the electrodynamic forces�
07
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S
2 RIGID COPPER BARS
2.1. mounting bars edgewise on supports Cat. Nos. 373 10/15/20/21/22/23
rigid flat copper bars - edgewise mountingle (A) IP < 30 Ithe (A) IP > 30 Cat. No. Dim. (mm) I2t (A2s) Icw1s (A)
110 80 373 88 12 x 2 1�2 x 107 3430
160 125 373 89 12 x 4 4�7 x 107 6865200 160 374 33 15 x 4 7�4 x 107 8580250 200 374 34 18 x 4 1 x 108 10,295
280 250 374 38 25 x 4 2�1 x 108 14,300
330 270 374 18 25 x 5 3�2 x 108 17,875
450 400 374 19 32 x 5 5�2 x 108 22,900
700 630 374 40 50 x 5 1�1 x 109 33,750
1150 1000 374 40 2 x (50 x 5) 4�5 x 109 67,500
800 700 374 41 63 x 5 1�8 x 109 42,500
1350 1150 374 41 2 x (63 x 5) 7�2 x 109 85,500
950 850 374 59 75 x 5 2�5 x 109 50,600
1500 1300 374 59 2 x (75 x 5) 1 x 1010 101,000
1000 900 374 43 80 x 5 2�9 x 109 54,000
1650 1450 374 43 2 x (80 x 5) 1�2 x 1010 108,000
1200 1050 374 46 100 x 5 4�5 x 109 67,500
1900 1600 374 46 2 x (100 x 5) 1�8 x 1010 135,000
C-section aluminium barsIe (A) IP < 30 Ithe (A) IP > 30 Cat. No. Cross-section (mm²) I²t (A²s) Icw1s (A)
800 630 1 x 373 54 524 2�2 x 109 46,900
1000 800 1 x 373 55 549 2�5 x 109 49,960
1250 1000 1 x 373 56 586 2�8 x 109 53,325
1450 1250 1 x 373 57 686 3�9 x 109 62,425
1750 1600 1 x 373 58 824 5�6 x 109 74,985
3500 3200 2 x 373 58 2 x 824 2�2 x 1010 149,970
1 C-SECTION ALUmINIUm BARS (supports Cat. Nos. 373 66/67/68/69)
< Supports Cat. nos. 373 66/67: with aligned bars
< Supports Cat. nos. 373 68/69: with stepped bars
^ Stepped busbar in cable sleeve with supports Cat. no. 373 10
B u S B a r S a n D D i S T r i B u T i o n
08
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S
Sizing busbars (continued)
< Supports Cat. no. 373 24 can be used to create very high current busbars: up to 4000 a in iP 55 XL3 4000 enclosures
2.2. mounting bars edgewise on supports Cat. Nos. 373 24/25
^ Bars mounted edgewise in vertical or horizontal busbars: supports in horizontal position
Ie (A) IP < 30 Ithe (A) IP > 30 Number Dim. (mm) I2t (A2s) Icw1s (A)
700 630 1 50 x 5 1�14 x 109 33,7501180 1020 2 50 x 5 4�56 x 109 67,5001600 1380 3 50 x 5 1�03 x 1010 101,2502020 1720 4 50 x 5 1�82 x 1010 135,000800 700 1 63 x 5 1�81 x 109 42,525
1380 1180 2 63 x 5 7�23 x 109 85,0501900 1600 3 63 x 5 1�63 x 1010 127,5752350 1950 4 63 x 5 2�89 x 1010 170,100950 850 1 75 x 5 2�56 x 109 50,625
1600 1400 2 75 x 5 1�03 x 1010 101,2502200 1900 3 75 x 5 2�31 x 1010 151,8752700 2300 4 75 x 5 4�10 x 1011 202,5001000 900 1 80 x 5 2�92 x 109 54,0001700 1480 2 80 x 5 1�17 x 1010 108,0002350 2000 3 80 x 5 2�62 x 1010 162,0002850 2400 4 80 x 5 4�67 x 1010 216,0001200 1050 1 100 x 5 4�56 x 109 67,5002050 1800 2 100 x 5 1�82 x 1010 135,0002900 2450 3 100 x 5 4�10 x 1010 202,5003500 2900 4 100 x 5 7�29 x 1010 270,0001450 1270 1 125 x 5 7�12 x 109 84,3752500 2150 2 125 x 5 2�85 x 1010 168,7503450 2900 3 125 x 5 6�41 x 1010 253,1254150 3450 4 125 x 5 1�14 x 1011 337,5001750 1500 1 160 x 5(1) 1�17 x 1010 108,0003050 2450 2 160 x 5(1) 4�67 x 1010 216,0004200 3300 3 160 x 5(1) 1�05 x 1011 324,0005000 3800 4 160 x 5(1) 1�87 x 1011 432,000
(1) Stainless steel threaded assembly rod, diameter 8 to be supplied separately and cut to length
rigid flat copper bars, 5 mm thick
09
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S
10 mm5 mm
^ 1 to 4 bars, 5 mm thick, per pole ^ 1 to 3 bars, 10 mm thick, per pole^ Simply rotate the isolating supports to take 5 or 10 mm thick bars
Ie (A) IP < 30 Ithe (A) IP > 30 Number Dim. (mm) I2t (A2s) Icw1s (A)
950 850 1 50 x 10 4�56 x 109 67,500
1680 1470 2 50 x 10 1�82 x 1010 135,000
2300 2030 3 50 x 10 4�10 x 1010 202,500
1150 1020 1 60 x 10 6�56 x 109 81,000
2030 1750 2 60 x 10 2�62 x 1010 162,000
2800 2400 3 60 x 10 5�90 x 1010 243,000
1460 1270 1 80 x 10 1�17 x 1010 108,000
2500 2150 2 80 x 10 4�67 x 1010 216,000
3450 2900 3 80 x 10 1�05 x 1011 324,000
1750 1500 1 100 x 10 1�82 x 1010 135,000
3050 2550 2 100 x 10 7�29 x 1010 270,000
4150 3500 3 100 x 10 1�64 x 1011 405,000
2000 1750 1 120 x 10 2�62 x 1010 162,000
3600 2920 2 120 x 10 1�05 x 1011 324,000
4800 4000 3 120 x 10 2�63 x 1011 486,000
rigid flat copper bars, 10 mm thick
Positioning bars edgewise encourages heat dissipation and is much the best option. If the bars have to be positioned flatwise (with the supports in a vertical position) the current-carrying capacities must be reduced (see next page).
B u S B a r S a n D D i S T r i B u T i o n
10
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S
Sizing busbars (continued)
2.3. mounting bars flatwise on supports Cat. Nos. 373 24/25
< Bars mounted flatwise in horizontal busbars: supports in vertical position
Ie (A) IP < 30 Ithe (A) IP > 30 Number Dim. (mm) I2t (A2s) Icw1s (A)
500 420 1 50 x 5 1�14 x 109 33,750750 630 2 50 x 5 4�56 x 109 67,500
1000 900 3 50 x 5 1�03 x 1010 101,2501120 1000 4 50 x 5 1�82 x 1010 135,000600 500 1 63 x 5 1�81 x 109 42,525750 630 2 63 x 5 7�23 x 109 85,050
1100 1000 3 63 x 5 1�63 x 1010 127,5751350 1200 4 63 x 5 2�89 x 1010 170,100700 600 1 75 x 5 2�56 x 109 50,625
1000 850 2 75 x 5 1�03 x 1010 101,2501250 1100 3 75 x 5 2�31 x 1010 151,8751600 1400 4 75 x 5 4�10 x 1011 202,500750 630 1 80 x 5 2�92 x 109 54,000
1050 900 2 80 x 5 1�17 x 1010 108,0001300 1150 3 80 x 5 2�62 x 1010 162,0001650 1450 4 80 x 5 4�67 x 1010 216,000850 700 1 100 x 5 4�56 x 109 67,500
1200 1050 2 100 x 5 1�82 x 1010 135,0001600 1400 3 100 x 5 4�10 x 1010 202,5001900 1650 4 100 x 5 7�29 x 1010 270,0001000 800 1 125 x 5 7�12 x 109 84,3751450 1250 2 125 x 5 2�85 x 1010 168,7501800 1600 3 125 x 5 6�41 x 1010 253,1252150 1950 4 125 x 5 1�14 x 1011 337,5001150 900 1 160 x 5(1) 1�17 x 1010 108,0001650 1450 2 160 x 5(1) 4�67 x 1010 216,0002000 1800 3 160 x 5(1) 1�05 x 1011 324,0002350 2150 4 160 x 5(1) 1�87 x 1011 432,000
(1) Stainless steel threaded assembly rod, diameter 8, to be supplied separately and cut to length
rigid flat copper bars, 5 mm thick
11
DE
tER
Min
inG
tH
E u
Sab
LE C
Ro
SS-S
EC
tio
n o
F tH
E b
aR
S3 FLEXIBLE COPPER BARS
Flexible copper barsIe (A) IP < 30 Ithe (A) IP > 30 Cat. No. Dim. (mm) I2t (A2s) Icw1s (A)
200 160 374 10 13 x 3 2 x 107 4485
320 200 374 16 20 x 4 8�5 x 107 9200
400 250374 11 24 x 4
1�2 x 108 11,000374 67 20 x 5
470 320 374 17 24 x 5 1�9 x 108 13,800
630 400 374 12 32 x 5 3�4 x 108 18,400
700 500 374 44 40 x 5 5�3 x 108 23,000
850 630 374 57 50 x 5 8�3 x 108 28,700
1250 1000 374 58 50 x 10 3�3 x 109 57,500
2500 2000 2 x 374 58 2 x (50 x 10) 1�3 x 1010 115,000
Ie (A) IP < 30 Ithe (A) IP > 30 Number Dim. (mm) I2t (A2s) Icw1s (A)
880 650 1 50 x 10 4�56 x 109 67,500
1250 1050 2 50 x 10 1�82 x 1010 135,000
2000 1600 3 50 x 10 4�10 x 1010 202,500
1000 800 1 60 x 10 6�56 x 109 81,000
1600 1250 2 60 x 10 2�62 x 1010 162,000
2250 1850 3 60 x 10 5�90 x 1010 243,000
1150 950 1 80 x 10 1�17 x 1010 108,000
1700 1500 2 80 x 10 4�67 x 1010 216,000
2500 2000 3 80 x 10 1�05 x 1011 324,000
1350 1150 1 100 x 10 1�82 x 1010 135,000
2000 1650 2 100 x 10 7�29 x 1010 270,000
2900 2400 3 100 x 10 1�64 x 1011 405,000
1650 1450 1 120 x 10 2�62 x 1010 162,000
2500 2000 2 120 x 10 1�05 x 1011 324,000
3500 3000 3 120 x 10 2�63 x 1011 486,000
rigid flat copper bars, 10 mm thick
B u S B a r S a n D D i S T r i B u T i o n
12
CH
EC
Kin
G t
HE
PE
RM
iSSi
bLE
tH
ER
Ma
L St
RE
SS
Sizing busbars (continued)
)
1010
109
108
107
106
105
104
103
102
101
I2t (A2s
100
Ik (A)100 101 102 103 104 105
I2t of the bar
Limited I2t
160
the thermal stress permitted by the bars must be greater than that limited by the protection device� Curve showing thermal stress limited
by a DPX 250 Er (160 a)
Example: using a 12 x 4 mm rigid flat bar for 160 Apermissible I2t of the bar: 4.7 x 107 A2sProspective rms Ik: 10 kA (104 A)
The thermal stress limited by this device can then be read by plotting the above value on the limitation curve given for the protection device (in this case, a DPX 250 ER 160 A): 5 x 105 A2s, value less than the I2t permitted by the bar.
CHECkING THE PERmISSIBLE THERmAL STRESS
The maximum thermal stress value I2t taken into consideration for a short-circuit current of less than 5 s is calculated using the formula I²t = K²S², where:- k = 115 As0.5/mm² for flexible copper bars (max. temperature: 160°C) - k = 135 As0.5/mm² for large cross-section rigid copper bars (width greater than 50 mm; max. temperature: 200°C) - k = 143 As0.5/mm² for small cross-section rigid copper bars (width less than 50 mm) and C-section bars (max. temperature: 220°C)- k = 91 As0.5/mm² for rigid aluminium bars (max. temperature: 200°C)- S = bar cross-section in mm²
The conventional value of the short-time withstand current with regard to thermal stress, in relation to a period of 1 s, is expressed by the formula:
Icw1s = I²t
Calculating the thermal stress
√
13
DE
tER
Min
inG
tH
E D
iSta
nC
ES
bE
tWE
En
Su
PP
oR
tS
Prospective Ik
Limited Ipk
Non-limitedprospective Ipk
Prospectiverms Ik
Limited Ik
I
t
the distance between the supports is determined according to the electrodynamic stress generated by the short circuit�the forces exerted between the bars during a short circuit are proportional to the peak value of the short-circuit current�
1 RmS VALUE OF THE PROSPECTIVE SHORT-CIRCUIT CURRENT (Ik)this is the prospective maximum value of the current which would circulate during a short circuit if there were no protection device� it depends on the type and power of the source� the actual short-circuit current will generally be lower in view of the impedance of the busbar system� the calculation of the values to be taken into account is described in book 4: “Sizing conductors and selecting protection devices”�
2 PEAk CURRENT VALUE (Ipk)the limited peak current is determined from the characteristics of the protection device (see book 5: “breaking and protection devices”)� it represents the maximum (peak) value limited by this device� if there is no limiting protection device, the prospective peak value can be calculated from the prospective short-circuit current and an asymmetry coefficient (see next page)�
DETERmINING THE DISTANCES BETwEEN SUPPORTS
This is the rms value of the short-circuit current that would circulate if there were no protection device.Ik1: between phase and neutralIk2: between 2 phasesIk3: between 3 phasesThese values were formerly called Isc1, Isc2 and Isc3.
Do not confuse Ik with Ipk, which is defined below.
Prospective ik
If in doubt or the actual prospective Ik value is not known, use a value of at least 20 x In.
The electrodynamic forces are proportional to the square of the peak current. It is this value which must be taken into consideration when determining the distances between the sup-ports.
B u S B a r S a n D D i S T r i B u T i o n
14
DE
tER
Min
inG
tH
E D
iSta
nC
ES
bE
tWE
En
Su
PP
oR
tS
Sizing busbars (continued)
non-limiting protection deviceLimiting protection device
Prospective Ik
Limitationcurve Non-lim
ited Ip
k
limited Ipk
rms Ik (kA)
Ipk (kÂ)
The limitation curves of the protection devices (DX and DPX) give the limited peak current according to the prospective short-circuit current (see Book 5 “Breaking and protection devices”). The non-limited peak Ik curve corresponds to no protection.
The table below gives the limited peak value (Ipk) directly for the maximum prospective short-circuit value equal to the breaking capacity (Icu) of the device. For lower prospective short-circuit values, reading the curves will provide an optimised value.
when the busbar is protected by a non-limiting protection device (for example DmX³), the maximum value of the peak current is developed during the first half-period of the short circuit. This is referred to as the asymmetric 1st peak.
The relationship between the peak value and the rms value of the prospective short-circuit current is defined by the coefficient of asymmetry n:
Ipk (peak) = n x prospective rms Ik Device Rating Ipk (peak) max. (A) (kÂ) DPX 125 16-25 11�9
DPX 125 40-63 15
DPX 125 100-125 17
DPX 160 25 14�3
DPX 160 40 to 160 20
DPX 250 ER 100 to 250 22
DPX 250 40 to 250 27
DPX-H 250 40 to 250 34
DPX 630 250 to 630 34
DPX-H 630 250 to 630 42
DPX 1600 630 to 1600 85
DPX-H 1600 630 to 1600 110
Value of asymmetric 1st peak
Ik rms value
I
Time
Prospective rms Ik n (kA)
ik < 5 1�5
5 < ik < 10 1�7
10 < ik < 20 2
20 < ik < 50 2�1
50 < ik 2�2
15
DE
tER
Min
inG
tH
E D
iSta
nC
ES
bE
tWE
En
Su
PP
oR
tS
General formula for calculating the forces in the event of a short circuit
D: length of the conductor (distance between supports in the case of bars)
E: spacing between conductors
with F in daN, I in A peak, and D and E in the same unit.
In practice, this formula is only applicable to very long (D > 20 E) round conductors. When D is shorter, a correction, called the “end factor” is applied:
- For 4 <
Fmax = 2 x I2 x D x 10-8E
Fmax = 2 x I2 x ( D -1) x 10-8E
Fmax = 2 x I2 x (D)2+1 - 1 x 10-8
E
DE
s - a aa + b b
< 20, use
Fmax = 2 x I2 x D x 10-8E
Fmax = 2 x I2 x ( D -1) x 10-8E
Fmax = 2 x I2 x (D)2+1 - 1 x 10-8
E
DE
s - a aa + b b
- For < 4, use
Fmax = 2 x I2 x D x 10-8E
Fmax = 2 x I2 x ( D -1) x 10-8E
Fmax = 2 x I2 x (D)2+1 - 1 x 10-8
E
DE
s - a aa + b b
Correction factors must be inserted in these formulae to take account of the layout and shape of the conductors when they are not round.
E
DI I
Fmax = 2 x I2 x D x 10-8E
Fmax = 2 x I2 x ( D -1) x 10-8E
Fmax = 2 x I2 x (D)2+1 - 1 x 10-8
E
DE
s - a aa + b b
The calculation of the forces in the event of short circuits (Fmax), can be defined as follows:
Fmax = 2 x I2 x D x 10-8E
Fmax = 2 x I2 x ( D -1) x 10-8E
Fmax = 2 x I2 x (D)2+1 - 1 x 10-8
E
DE
s - a aa + b b
The electrodynamic forces that are exerted between conductors, in particular in busbars, are the result of the interaction of the magnetic fields produced by the current flowing through them. These forces are proportional to the square of the peak current intensity that can be recorded in  or kÂ. when there is a short circuit, these forces can become considerable (several hundred daN) and cause deformation of the bars or breaking of the supports.The calculation of the forces, prior to the tests, is the result of applying Laplace's law, which states that when a conductor through which a current i1 passes is placed in a magnetic field H with induction B, each individual element dl of this conductor is subjected to a force of dF
= idl ^ B.
If the magnetic field originates from another conductor through which i2 passes, there is then an interaction of each of the fields H1 and H2 and forces F1 and F2 generated by B1 and B2.
The directions of the vectors are given by Ampère's law. If currents i1 and i2 circulate in the same direction, they attract, if they circulate in opposite directions, they repel.
^ Schematic representation at a point in space (Biot-Savart law)
→ →→
→ →
→ → → →→ →
→
B u s B a r s a n d d i s t r i B u t i o n
16
De
ter
min
ing
th
e D
ista
nc
es
be
twe
en
su
pp
or
ts
sizing busbars (continued)
the following tables can be used to determine the maximum distances D (in mm) between the supports, based on the required ipk value, and thus create busbars. the shorter the distance between the supports, the higher the permissible ik. with single pole supports, it is also pos-sible to vary the spacing between bars e. the wider the spacing between bars, the higher the permissible ik.Distance D’ after the last support must always be less than 30% of distance D.
3 Practical determination of the distances between the suPPorts according to the Peak current (ipk)
Maximum distance d (in mm) between single pole supports (E adjustable)
supports 373 98 374 37
bars 373 88 (12 x 2) or 373 89 (12 x 4)
374 33 (15 x 4), 374 34 (18 x 4) or 374 38 (25 x 4)
e (mm) 50 75 100 125 50 75 100 125
ipk (peak)(in kÂ)
10 400 600 800 350 600 750
15 300 450 600 800 250 400 500 700
20 250 350 450 600 150 225 300 375
25 200 250 300 400 125 150 200 250
30 100 125 150 175
35 100 125 150
Maximum distance d (in mm) between multipole supports Cat. nos. 373 96, 374 10/15/32/36 (E fixed)
supports
373 96 374 32 374 36 374 15 374 10
bars 373 88(12 x 2)
373 89(12 x 4)
374 33/34(15 x 4)(18 x 4)
374 38(25 x 4)
374 34(18 x 4)
374 18(25 x 5)
374 19(32 x 5)
374 34(18 x 4)
374 38(25 x 4)
374 18(25 x 5)
374 19(32 x 5)
ipk (peak)(in kÂ)
10 200 400 550 650 1000 1200 1500 550 650 800 90015 150 300 400 500 700 1000 1200 400 600 700 80020 125 200 300 400 550 750 950 300 450 550 70025 100 150 200 350 400 600 750 250 350 400 50030 150 200 350 500 650 200 300 350 40035 100 150 300 400 550 150 250 300 35040 100 250 350 450 150 200 300 30045 150 200 20050 200 300 400 150 175 10055 100 150 10060 200 250 300 15070 150 200 25080 150 200 250
the ipk values to be taken into account must be determined according to the limitation curves for the devices (see p. 12)
D
E
D'
17
De
ter
min
ing
th
e D
ista
nc
es
be
twe
en
su
pp
or
ts
supports
bars 50 mm thick
1 flat bar per pole 1 c-section bar per pole 1 flat bar per pole374 18(25 x 5)
374 19(32 x 5)
374 40(50 x 5)
374 41(63 x 5) 155 mm2 265 mm2 440 mm2 374 40
(50 x 5)374 41(63 x 5)
374 59(75 x 5)
374 43(80 x 5)
ipk (peak)(in kÂ)
10 800 900 1100 1600 1600 1000 1200 1200 120015 600 600 700 800 800 1000 1300 800 900 1000 100020 450 500 600 700 600 800 1000 650 700 750 75025 350 400 500 550 450 650 800 500 600 600 60030 300 350 400 450 400 550 700 400 500 550 55035 250 300 350 400 350 450 600 350 450 450 45040 200 250 275 300 300 400 550 300 350 400 40045 200 200 225 250 250 350 500 300 300 350 35050 150 150 200 200 250 300 450 250 250 300 30060 125 125 150 150 200 300 400 200 250 250 25070 100 100 150 150 150 250 350 150 200 200 20080 100 100 200 300 100 150 200 20090 200 250 100 150 200 200
100 150 250 100 150 150 150110 150 200 100 100 150 150120 150 200 100 100 100 100
Maximum distance d (in mm) between multipole supports Cat. nos. 373 20/21 (E fixed: 75 mm)
373 20 373 21
supports
bars 50 mm thick
1 flat bar per pole 2 flat bars per pole374 40(50 x 5)
374 41(63 x 5)
374 59(75 x 5)
374 43(80 x 5)
374 46(100 x 5)
374 40(50 x 5)
374 41(63 x 5)
374 59(75 x 5)
374 43(80 x 5)
374 46(100 x 5)
ipk (peak)(in kÂ)
10 1000 1200 1200 1200 120015 800 900 1000 1000 120020 650 700 750 750 90025 500 600 600 600 70030 400 500 550 550 600 700 80035 350 450 450 450 55040 300 350 400 400 450 550 600 650 650 70045 300 300 350 350 40050 250 250 300 300 350 450 500 500 500 55060 200 250 250 250 300 350 400 400 400 45070 150 200 250 250 250 250 350 350 350 40080 100 150 200 200 200 250 300 300 300 30090 100 150 200 200 200 200 250 300 300 300
100 100 150 150 150 150 200 200 250 250 250110 100 100 150 150 150 200 150 200 200 200120 100 100 100 100 100 150 150 200 200 200
373 22/23 and 374 53
Maximum distance d (in mm) for multipole supports Cat. nos. 373 22/23 (E fixed: 75 mm)
B u s B a r s a n d d i s t r i B u t i o n
18
De
ter
min
ing
th
e D
ista
nc
es
be
twe
en
su
pp
or
ts
sizing busbars (continued)
supports 373 24, 373 25, 374 54
1 bar per pole 2 bars per pole 3 bars per pole 4 bars per pole bars 75 x 5 75 x 5 75 x 5 75 x 5 50 x 5 63 x 5 80 x 5 100 x 5 125 x 5 50 x 5 63 x 5 80 x 5 100 x 5 125 x 5 50 x 5 63 x 5 80 x 5 100 x 5 125 x 5 50 x 5 63 x 5 80 x 5 100 x 5 125 x 5
ipk (peak) 10 1550 1700 1700 1700 1700 1700 1700 1700 1700 1700 (in kÂ) 15 1050 1200 1350 1550 1700 1550 1700 1700 1700 1700 1700 20 800 900 1000 1150 1350 1200 1350 1500 1700 1700 1550 1700 1700 1700 1700 1700 1700 1700 1700 1700 25 650 750 800 950 1100 950 1100 1200 1400 1550 1250 1450 1600 1700 1700 1550 1700 1700 1700 1700 30 550 600 700 800 900 800 900 1000 1150 1300 1050 1200 1350 1550 1700 1300 1500 1700 1700 1700 35 450 550 600 650 800 700 800 900 1000 1150 900 1050 1150 1300 1500 1150 1250 1450 1650 1700 40 400 450 550 600 700 600 700 800 900 1000 800 900 1050 1150 1300 1000 1100 1300 1450 1650 45 350 400 450 550 600 550 600 700 800 900 700 800 900 1050 1200 900 1000 1150 1300 1450 50 350 350 450 500 550 500 550 650 700 800 650 750 850 950 1050 800 900 1050 1150 1350 60 300 300 350 400 450 400 450 550 600 700 550 600 700 800 900 650 750 850 1000 1100 70 250 250 300 350 400 350 400 450 500 650 450 550 600 700 750 600 650 750 850 950 80 250 250 300 350 300 350 400 450 550 400 450 550 600 700 500 600 650 750 850 90 250 250 300 300 300 350 400 500 350 400 500 550 600 450 500 600 650 750 100 250 300 250 300 300 350 500 350 400 450 500 550 400 450 550 600 700 110 250 250 250 250 300 350 450 300 350 400 450 500 350 450 500 550 600 120 250 250 250 300 450 300 300 350 400 450 350 400 450 550 550 130 250 250 300 400 250 300 350 350 450 300 350 400 500 550 140 250 250 400 250 250 300 350 400 300 350 400 450 500 150 250 350 250 250 300 350 350 300 300 350 400 450 160 250 350 250 250 300 350 250 300 350 400 350 170 350 250 250 300 350 250 300 300 350 300 180 300 250 300 300 250 250 300 350 300 190 250 250 300 250 250 300 300 250 200 250 300 250 250 300 250 210 250 250 250 250 250 200 220 250 250 250 250 200
Maximum distance d (in mm) between multipole supports Cat. nos. 373 24/25 with 5 mm thick bars
the distances take the most severe short-circuit conditions into account:- ik2 two-phase short-circuit value resulting in non-uniform forces- ik3 three-phase short-circuit value resulting in maximum force on the central bar- ik1 value (phase/neutral) is generally the weakest
19
De
ter
min
ing
th
e D
ista
nc
es
be
twe
en
su
pp
or
ts
supports 373 24, 373 25 and 374 54
1 bar per pole 2 bars per pole 3 bars per pole bars 80 x 10 100 x 10 120 x 10 80 x 10 100 x 10 120 x 10 80 x 10 100 x 10 120 x 10 ipk (peak) 20 1700 1700 1700 1700 1700 1700 1700 1700 1700 (in kÂ) 25 1600 1700 1700 1700 1700 1700 1700 1700 1700 30 1350 1550 1700 1700 1700 1700 1700 1700 1700 35 1150 1300 1450 1700 1700 1700 1700 1700 1700 40 1050 1150 1300 1500 1700 1700 1700 1700 1700 45 900 1050 1150 1350 1550 1700 1700 1700 1700 50 850 950 1050 1200 1400 1550 1600 1700 1700 60 700 800 850 1000 1150 1300 1350 1550 1700 70 600 700 750 900 1000 1100 1150 1300 1500 80 550 600 650 750 900 1000 1000 1150 1300 90 500 550 600 700 800 900 900 1050 1100 100 450 500 550 600 700 800 850 900 950 110 400 450 500 550 650 750 750 800 800 120 350 400 450 550 600 650 700 750 750 130 350 350 400 500 550 600 650 700 700 140 300 350 400 450 500 600 600 650 650 150 300 350 350 450 500 550 550 650 600 160 250 300 350 400 450 500 550 600 500 170 250 300 300 350 450 500 500 500 500 180 250 300 300 350 400 450 500 450 450 190 250 250 300 350 400 450 450 400 400 200 200 250 300 300 350 400 450 400 400 210 200 250 250 300 350 350 400 350 350 220 250 250 300 350 300 350 300 300 230 200 250 300 300 300 300 300 300 240 200 250 300 250 300 250 250 250 200 250 300 250 250 250 250
Maximum distance (in mm) between multipole supports Cat. nos. 373 24/25 with 10 mm thick bars
additional supports are used in addition to fixed supports to hold the bars together and maintain the recommended spacing (ik withstand).
additional supports Cat. nos. 373 23 and 373 25
B u s B a r s a n d d i s t r i B u t i o n
20
De
ter
min
ing
th
e D
ista
nc
es
be
twe
en
su
pp
or
ts/m
ag
ne
tic
eff
ec
ts a
sso
cia
teD
wit
h b
usb
ar
s
the magnetic effects can be divided into transient effects, which are the short-circuit electrodynamic forces, and permanent effects created by induction due to circulation of high currents. the effects of induction have several consequences:
• Increased impedance in the conductors due to the effects of mutual inductance
• Temperature rise linked to magnetic saturation of the mate-rials in the fields formed around the conductors
• Possible interference in sensitive devices for which it is recommended that minimum cohabitation distances are observed (see book 8)
sizing busbars (continued)
magnetic effects associated with busbars
Maximum distance d (in mm) between multipole supports Cat. nos. 373 66/67 and 373 68/69
supports
373 66/67 373 68/69
bar1 c-section aluminium bar per pole 1 c-section aluminium bar per pole
373 54 373 55 373 56 373 57 373 58 373 54 373 55 373 56 373 57 373 58
ipk (in kÂ)
30 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600
40 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
52 800 800 800 800 800 800 800 800 800 800
63 700 700 700 700 700 600 600 600 600 600
73 600 600 600 600 600 500 500 500 500 500
80 600 600 600 600 600 500 500 500 500 500
94 500 500 500 500 500 400 400 400 400 400
105 500 500 500 500 500 400 400 400 400 400
132 - - 500 500 500 - - 400 400 400
154 - - 400 400 400 - - 300 300 300
< Cables are connected to C-section aluminium bars without drilling, using hammer head screws
21
ma
gn
eti
c e
ffe
cts
ass
oc
iate
D w
ith
bu
sba
rs
the formation of magnetic fields around high power busbars must be prevented. the structures of Xl3 enclosures, which incor-porate non-magnetic elements (which create air gaps), are ideal for the highest currents.
Measuring the magnetic field lines around a busbar
^ a knowledge of the induction phenomena generated by the power conductors enables appropriate mounting and cohabitation conditions to be stipulated.
magnetic field values are generally expressed using two units:• The tesla (T) represents the magnetic induction value, which, directed perpendicular to a 1 m2 surface, produces a flux of 1 weber across this surface. as the tesla expresses a very high value, its sub-units are generally used: the millitesla (mt) and the microtesla (µt). the old unit, the gauss (g) should not be used (1 t = 10,000 g). • The ampere per metre (A/m), a non-SI unit, formerly called the “ampere-turn per metre”, indicates the intensity of the magnetic field created at the centre of a 1 m diameter circular circuit crossed by a constant 1 a current.
the induction b (in t) and the field h (in a/m) are linked by the formula: b = µ0 µr h where :
- µ0 = 4 π 10-7 (magnetic permeability of air or the vacuum) - µr = 1 (relative permeability of iron)giving: 1µt = 1.25 a/m and 1a/m = 0.8 µt
the recommended mounting distances correspond to magnetic field values read close to a busbar at 4000 a:0.1 mt (125 a/m) at a distance of 1 m (sensitive equipment)0.5 mt (625 a/m) at a distance of 50 cm (limited sensitivity equipment)1 mt (1250 a/m) at a distance of 30 cm (very low sensitivity equipment)
^ the corner pieces of XL3 4000 enclosures are made of non-magnetic alloy
the specified separation distances between conductors and devices will be increased in the event of cohabitation with very high power busbars (up to 4000 a).if there are no instructions from the manu-facturers, the minimum distances will be increased to:- 30 cm for devices with very low sensitivity (fuses, non residual current devices, connections, mccbs, etc.)- 50 cm for devices with limited sensitivity (secondary circuit breakers, including rcds, relays, contactors, transformers, etc.)- 1 m for sensitive devices (electronics and digital measuring devices, bus-based systems, remote controls, electronic switches, etc.)- devices which are very sensitive to magnetic fields (analogue gauge, meters, oscillographs, cathode ray tubes, etc.) may require greater separation distances.
B u s B a r s a n d d i s t r i B u t i o n
22
sizing busbars (continued)
ma
gn
eti
c e
ffe
cts
ass
oc
iate
D w
ith
bu
sba
rs
the circulation of high currents in busbars leads to the induction of magnetic fields in the surrounding exposed metal conductive parts (enclosure panels, frames and chassis, etc.).the phenomenon is similar to that used for creating elec-tromagnetic shielding, but in this case it must be limited to avoid temperature rises in these exposed conductive parts and the circulation of induced currents.
Minimum distances between bars and metal panels
induction is higher facing the flat surface of bars (distance X).above 2500 a, maintain minimum distances:X > 150 mm and Y > 100 mm.
Y
X
^ supports on aluminium crosspieces to prevent the formation of magnetic fields.
^ non-magnetic stainless steel screws perform the same function on supports Cat. no. 373 24
in practice the values of the magnetic fields generated by the power bars considerably exceed the standard values for exposure of the devices. much more severe tests, such as those to undergone by lexic range devices, are therefore essential to ensure they will operate correctly in these conditions.
in addition to the heat dissipation aspects which require the provision of adequately sized dissipation volumes, it is essential to take these notions of magnetic induction in the exposed conductive parts of the enclosures into consideration by ensuring they are large enough to maintain the appropriate distances between bars and walls.above 2500 a, this can lead to providing enclosures (for example, at the rear) just to take the busbars.
23
ch
ec
kin
g t
he
insu
lati
on
ch
ar
ac
ter
isti
cs
checking the insulation characteristics
1 insulation voltage ui this must be the same as or higher than the maximum value of the rated operating voltage for the assembly, or the reference voltage. the latter depends on the mains supply voltage and the structure of the source (star, delta, with or without neutral).
reference voltage values (in V) to be taken into consideration according to the nominal supply voltage
nominal power supply voltage
for insulation between phases for insulation between phase and neutral
all supplies 4-wire three phase supplies neutral connected to earth
3-wire three phase supplies not connected to earth or one phase connected to earth
60 63 32 63
110 - 120 - 127 125 80 125
160 160 - 160
208 200 125 200
220 - 230 - 240 250 160 250
300 320 - 320
380 - 400 - 415 400 250 400
440 500 250 500
480 - 500 500 320 500
575 630 400 680
600 630 - 630
660 - 690 630 400 630
720 - 830 800 500 800
960 1000 630 1000
1000 1000 - 1000
a check must be carried out to ensure that the reference voltage is not higher than the insulation voltage ui of the devices, busbars and distribution blocks.
the insulation between live conductors and the earth of the legrand busbar supports and distribution blocks is at least equal to that between phases. the insulation value ui can be used for all mains supplies.
B u s B a r s a n d d i s t r i B u t i o n
24
ch
ec
kin
g t
he
insu
lati
on
ch
ar
ac
ter
isti
cs
sizing busbars (continued)
2 imPulse withstand voltage uimpthis value characterises the permissible overvoltage level in the form of a voltage wave representative of a lightning strike. its value (in kV) depends on the mains voltage, and also the location in the installation. it is highest at the origin of the installation (upstream of the incoming mcb or the transformer).equipment can be designated or marked according to two methods.
• Two values indicated (example: 230/400 V): these refer to a 4-wire three-phase supply (star configura-tion). the lower value is the voltage between phase and neutral, and the higher is the value between phases.
• A single value indicated (example: 400 V): this normally refers to a 3-wire single phase or three phase supply with no earth connection (or with one phase connected to earth) and for which the phase-earth voltage must be considered capable of reaching the value of the phase-to-phase voltage (full voltage between phases).
impulse voltage values to be taken into consideration according to the voltage in relation to earth and location in the installation
maximum rated operating voltage value in relation
to earth (rms or dc value)
(v)
Preferred rated impulse withstand voltage values (1.2/50 µs) at 2000 m (in kv)
to be considered generally can be considered for underground power supplies
overvoltage category overvoltage category
iv iii ii i iv iii ii i
installation origin level
distribution level
load level (devices,
equipment)
specially protected
level
installation origin level
distribution level
load level (devices,
equipment)
specially protected
level
50 51.5 0.8 0.5 0.33 0.8 0.5 0.33 -
100 2.5 1.5 0.8 0.5 1.5 0.8 0.5 0.33
150 4 2.5 1.5 0.8 2.5 1.5 0.8 0.5
300 6 4 2.5 1.5 4 2.5 1.5 0.8
600 8 6 4 2.5 6 4 2.5 1.5
1000 12 8 6 4 8 6 4 2.5
nb: the impulse withstand voltage given for an altitude of 2000 m implies that tests are carried out at higher values at sea level: 7.4 kV for 6 kV - 9.8 kV for 8 kV - 14.8 kV for 12 kV.
all the specifications relating to insulation are defined by international standard IEC 60664-1 “Insulation coordination in low-voltage systems (networks)”. they are also contained in standards iec 60439-1 and iec 60947-1.
25
ch
ec
kin
g t
he
insu
lati
on
ch
ar
ac
ter
isti
cs
legrand busbar supports are designed and tested for the harshest operating conditions corresponding to the highest overvoltage risks. the uimp value characterises this safety requirement.
the insulation voltage ui of supports and distribution blocks is determined by measuring the creepage distances, by the insulating properties of the material and by the degree of pollution.
• The creepage distance is the distance measured on the surface of the insulation in the most unfavourable conditions or positions between the live parts (phases, phases and neutral) and between these parts and the exposed conductive part.
• The insulating properties of the material are characterised amongst other things by the comparative tracking index (cti). the higher this value, the less the insulation will be damaged by conductive pollution deposits (legrand busbar supports, made of fibreglass reinforced polyamide 6.6, have an index of more than 400).
• The degree of pollution characterises the risk of conductive pollution deposits, using a number from 1 to 4: - 1 : no pollution - 2 : no pollution and temporary condensation - 3 : conductive pollution possible - 4 : Persistent pollution
level 2 is similar to household, commercial and residential applicationslevel 3 is similar to industrial applications
design of the isolating supports for busbars and distribution blocks
insulation characteristics of busbar supports (degree of pollution: 3), similar
to industrial applications
cat. no. 373 98374 37 373 15/96 373 10/20/21/22/23/24/25
37 4 14/32/36/53/54
ui (v) 500 690 1000
uimp (kv) 8 8 12
A. Conductive elementsB. ScreenC. Distance in air or clearanceD. Creepage distance
A D
C
A
B
^ General principle of measuring the clearances and creepage distances
B u s B a r s a n d d i s t r i B u t i o n
26
rig
iD b
ar
s
Connection on extension rod, adaptor or spreader
1 siZes of the contact areasthe contact area (sc) must be at least 5 times the cross-section of the bar (sb). sc > 5 x sbfor main busbar continuity links, it is advisable to establish contacts along the entire length of the bar in order to ensure optimum heat transfer.
shaping and connecting bars
creating busbars generally involves machining, bending and shaping which require a high degree of expertise to avoid weakening the bars or creating stray stresses. the same applies to connections between bars, whose quality depends on the sizes and conditions of the contact areas, and the pressure of this contact (number of screws and effectiveness of tightening).
Sc
Sb
Contact area (Sc)
Cross-section (Sb)
Main busbar Horizontal
Vertical
Transfer
2 contact Pressurethe contact pressure between bars is provided using screws whose size, quality, number and tightening torque are selected according to the current and the sizes of the bars.too high a tightening torque or not enough screws can lead to distortions which reduce the contact area. it is therefore advisable to distribute the pressure by increasing the number of tightening points and using wide washers or back-plates.
avoidPreferable
for branch busbars, the contact area can be smaller, complying with the condition sc > 5 x sb.for equipment connection plates, contact must be made over the whole surface of the plate for use at nominal current.
rigid bars
27
rig
iD b
ar
s
tightening torques that are too high lead to the limit of elasticity of the bolts being exceeded and creeping of the copper.
recommended screws and minimum characteristics
Serrated or split lock washer
Wide flat washers
Nut
Self-locking nut
Wide flat washers
NutNomel, Belleville combined washer
Wide flat washer
�
�
373 59 (M10)
50 Nm
^ Connection on 120 x 10 bars (4000 a)
^ double connection: 100 x 10 bars (3200 a) and 80 x 10 bars (2500 a) on common 120 x 10 bars
^ applying a mark (paint, brittle coating) will show any loosening and can also be used to check that tightening has been carried out correctly (tell-tale)
devices to prevent loosening
C-section aluminium bars
the lugs or flexible bars connect directly with no need to add washers or spacers
i (a)bar width
(mm)
number of
screws
Ø screw (mm)
minimum quantity
tightening torque (nm)1 bar 2+ bars
< 250 - < 25 12
m8m6
8-88-8
15/2010/15
< 400 - < 32 1 m10 6-8 30/35
< 630 - < 50122
m12m10m8
6-86-88-8
50/6030/3515/20
800 1250 < 80 44
m8m10
8-86-8
15/2030/35
1000 1600 < 100 42
m10m12
6-86-8
30/3550/60
1600 2500 < 125 4 m12 6-8 50/60
B u s B a r s a n d d i s t r i B u t i o n
28
rig
iD b
ar
s
3 condition of the contact areas apart from pronounced oxidation (significant blackening or presence of copper carbonate or “verdigris”), bars do not require any special pre-paration. cleaning with acidified water is prohi-bited, as, apart from the risks, it requires neutrali-sation and rinsing. surface sanding (240/400 grain) can be carried out, complying with the direction of sanding so that the “scratches” on bars that are in contact are perpendicular.
4 machining coPPer bars copper is a soft, “greasy” or “sticky” metal in terms used in the trade. shaping is generally carried out dry, but lubrication is necessary for high-speed cutting or drilling operations (up to 50 m/mn).
5 bending bars it is strongly recommended that a full-scale drawing is made of the bars, in particular for bends and stacking of bars.
the bars are separated by their thickness “e”.the total centre line length before bending is the sum of the straight parts (l1 + l2) that are not subject to any distortion and the length of the curved elements on the neutral line (in theory at the centre of the thickness of the metal).
^ the hydraulic punch is used to make precision holes easily … and with no chips
^ it is possible to make holes with drills for steel, but it is preferable to use special drills (with elongated flutes for easy detachment of chips)
^ sawing (8d medium tooth) in a clamping vice
shaping and connectingbars (continued)
L1
L2
ee
120°
29
rig
iD b
ar
s
the calculation must be carried out based on the tool used and its actual bending radius r.
< Example of bending three bars one on top of the other to create power sockets
^ Creating a twist. the length L of the twist is at least twice the width l of the bar
Bending a 10 mm thick copper bar on a portable hydraulic tool
Bending on bending machine:r = 1 to 2e
Bending on V-block:r min. = e
Calculation of the length
bending to 90°
= 2 ∏ r4 =
∏4
(2 r + e)
useful formula: = r x 1.57
bending to any angle α
= ∏ (180-α)
360 (2 r + e)
r: bending radius (or radius of the tool)r: radius to the neutral line r = r + e
2: length to the neutral line
e
r
e
r
Ll
e
R
r
e
a
r
R
B u s B a r s a n d d i s t r i B u t i o n
30
fle
xib
le b
ar
s
shaping and connectingbars (continued)
flexible bars can be used for making connections on devices or for creating links that can be adapted to vir-tually any requirement. guaranteeing safety and high quality finish, they provide an undeniably attractive touch.based on the most commonly used sizes and the electrical capacities of the usual nominal values, the legrand range of flexible bars is suitable for most connection or linking requirements.as with any conductor, the current-carrying capacities of flexible bars may vary according to the conditions of use:- ambient temperature (actual in enclosure)- period of use (continuous or cyclic load), or installa-tion conditions- bars on their own or grouped together (side by side in contact or with spacers)- Ventilation: natural (ip < 30), forced (fan) or none (ip > 30)- Vertical or horizontal routing.the considerable variability of all these conditions leads to very different current-carrying capacities (in a ratio of 1 to 2, or even more).
< Connection of a dPX to a distribution block using flexible bars
incorrect use can result in temperature rises that are incompatible with the insulation, disturbance or even damage to connected or surrounding equipment.flexible bars are shaped manually without the need for any special tools, although some dexterity is required to achieve a perfect finish.
Current-carrying capacities of Legrand flexible barscat. no. 374 10 374 16 374 11 374 67 374 17 374 12 374 44 374 57 374 58
cross-section (mm) 13 x 3 20 x 4 24 x 4 20 x 5 24 x 5 32 x 5 40 x 5 50 x 5 50 x 10
ie (a) iP < 30 200 320 400 400 470 630 700 850 1250
ithe (a) iP > 30 160 200 250 250 520 400 500 630 800
flexible bars have higher current-carrying capacities than cables or rigid bars with the same cross-section due to their lamellar structure (limitation of eddy currents), their shape (better heat dissipation) and their permissible temperature (105°c high temperature Pvc insulation).
the currents ie (a) and ithe (a) of legrand flexible bars are given for the following conditions:- ie (iP < 30): maximum permanent cur-rent-carrying capacity in open or ventilated enclosures, the positions of the bars and relative distance between them allow correct cooling. the temperature in the enclosure must be similar to the ambient temperature.- ithe (iP > 30): maximum permanent current-carrying capacity in sealed enclosures. the bars can be installed close to one another, but must not be in contact.the temperature in the enclosure can reach 50°c.
fleXible bars
31
cu
rr
en
t tr
an
sfo
rm
er
s (c
t)
current transformers (ct)
Cat. no. transformation ratio
dimensions(mm)
aperture for cables Ø max.
(mm)
apeture for bar
width x thick. (mm)
Fixing on rail
Fixing on plate
direct fixing on cables
or bars
single phase cts
046 31
046 34
046 36
50/5
100/5
200/5 47,5
653044
21 16 x 12.5 • •
047 75 300/5
60
94
4256
45
23
20.5 x 12.5
25.5 x 11.5
30.5 x 10.5• • •
046 38 400/5
54 45
107
4677
35 40.5 x 10.5 • •
047 76
047 77
047 78
600/5
800/5
1000/5
90
40
94
90
32 x 65 •
047 79 1250/5
87
58
116
96
34 x 84 •
046 45
046 46
1500/5
2000/558
87
160
99
38 x 127 •
047 80
046 48
2500/5
4000/540
87
160
125
54 x 127 •three-phase cts
046 98 250/5
37
56
58,5
25
9
107
8 20.5 x 5.5 •
046 99 400/5
3756
66,5
30
9
135
30.5 x 5.5 •
^ Fixing Cts on busbars
measuring devices such as ammeters, electricity meters and multifunction control units are connected via current transformers which provide a current of between 0 and 5 a. the transformation ratio will be chosen according to the maximum current to be measured. these transformers can be fixed directly on flat, flexible or rigid bars.
B u s B A r s A n d d I s t r I B u t I o n
32
dis
trib
uti
on
blo
Ck
s
distribution blocks
the distribution block is a prefabricated device. It is therefore sized to suit its rated current and, unlike busbars, does not require manufacturing definitions. however, the diversity of distribution blocks according to their capacity, their connection mode and their installation calls for careful selection while adhering to precise standards.
When a change of conductor cross-section or type results in a reduction of the current-carrying capacity, standard Iec 60364-473 stipulates that a protection device must be placed at this point. In certain conditions, it is however possible to depart from this rule (see p. 03)
Possible locations for distribution blocks
location example of legrand solution
at panel supply end or output for connecting incoming or outgoing conductors
connection boxes
directly at the output of an upstream device
distribution terminals
directly at the input of downstream devices
supply busbars
Independently of the upstream and downstream devices with the need to connect the input and outputs
modular distribution blocks
33
Ch
ar
aC
ter
isti
Cs
of
dis
trib
uti
on
blo
Ck
s
In practice, it is possible to select one or more distribution blocks with a lower nominal current if the downstream circuits are not on-load simultaneously (bulking factor) or are not 100% on-load (diversity coefficient) (see Book 2).
125 A 125 A
160 A
I1 I2 I3 I4
I1 + I2 + I3 + I4 = I
I
It
I1 I2 I3 I4
before making the final choice of product, a few essential characteristics must be checked. these are given for all legrand distribution blocks.
1 Rated cuRRentoften called nominal current (in), this should be chosen according to the current of the upstream device or the cross-section of the power supply conductor.as a general rule, use a distribution block with the same current as or immediately above that of the main device (it), ensuring that the sum of the currents of the distributed circuits is not higher than the nominal current (in) of the distribution block.
125 A modular distribution block equipped with an
additional neutral terminal block >
In > It or In > I1 + I2 + I3 + I4
chaRacteRIstIcs of dIstRIButIon Blocks
B u s B A r s A n d d I s t r I B u t I o n
34
Ch
ar
aC
ter
isti
Cs
of
dis
trib
uti
on
blo
Ck
s
legrand distribution blocks are designed to minimise the risks of short circuits between poles: individual insulation of the bars on modular distribution blocks, partitioning of power distribution blocks, new totally isolated concept of single pole distribution blocks cat. nos. 048 71/73/83, all innovations to increase safety. Providing the highest level of fire resistance (960°c incandescent wire in accordance with standard Iec 60695-2-1), legrand distribution blocks meet the standard requirement for non-proximity of combustible materials.
Concern for maximum safety
< 160 A modular distribution block Cat. no. 048 87: total insulation of each pol
distribution blocks (continued)
2 PeRmIssIBle shoRt-cIRcuIt value• Value Icw characterises the conventional current-carrying capacity for 1 s from the point of view of thermal stress.
• Value Ipk characterises the maximum peak current permitted by the distribution block. this value must be higher than that limited by the upstream protec-tion device for the prospective short circuit.
3 InsulatIon value• The insulation voltage Ui must be at least equal to the maximum value of the rated operating voltage of the assembly, or the reference voltage (see p. 23).
• The impulse withstand voltage Uimp characterises the permissible overvoltage level when there is a lightning strike (see p. 24).
legrand distribution blocks are designed to resist thermal stress at least as high as that of the conductor with the cross-section corresponding to the nominal current, which means that no other checks are usually necessary.they are tested for the harshest operating conditions corresponding to the highest overvoltage risks. the uimp value characterises this safety requirement.
It is not generally necessary to check the Ipk when the distribution block is protected by a device with the same nominal current. however it must be checked if the rating of the upstream device is higher than the current of the distribution block.
35
Ch
ar
aC
ter
isti
Cs
of
dis
trib
uti
on
blo
Ck
s
4 connectIon method
4.1. direct connectionthe conductors are connected directly in the terminals without any special preparation. This is the preferred on-site method for H07 V-U, H07 V-R rigid conductors and FR-N05 VV-U and FR-N05 VV-R cables. Use of a ferrule (such as StarfixtM) is recommended for flexible conductors (H07 V-K) connected in butt terminals (under the body of the screw) and for external flexible cables (h07 rn-f, a05 rr-f, etc.) which may be subject to pulling.
4.2. connection via terminalsthis type of connection is normally used for large cross-section conductors, and mainly for panels that are wired in the factory. it is characterised by excellent mechanical withstand, excellent electrical reliability and its ease of connection/disconnection.
Lexic modular distribution blocks for totally “universal” use >
Correspondence between cross-section (in mm2) and template (Ø in mm)
cross- section(mm2)
template for circular shape B rigid conductor
(Iec 60947-1)
template for flexible conductor
with or without cable end
Ø in mm Ø in mm
1 1.5 2
1.5 1.9 2.4
2.5 2.4 2.9
4 2.7 3.7
6 3.5 4.4
10 4.4 5.5
16 5.3 7
25 6.9 8.9
35 8.2 10
50 10 12
70 12 14
63/100 a terminal blocks, 125/160 a modular distribution blocks and 250 a lexiclic distri-bution blocks can be connected directly.125/250 a extra-flat distribution blocks and 125/400 a stepped distribution blocks are connected via terminals.
B u s B A r s A n d d I s t r I B u t I o n
36
Ph
ase
ba
lan
Cin
g
a well-designed installation should never require rebalancing after it has been built. however, there are always unforeseen circumstances:- the loads may not have been correctly identified (uses on power sockets)- the loads may be irregular, or even random: holiday homes, office blocks, etc.three-phase loads connected with motive power, heating, air conditioning, furnaces and in general any uses with a direct three-phase supply do not generate any significant unbalance.however, all household applica-tions (lighting, heating, domestic appliances) and office applications (computers, coffee machines, etc.) represent single phase loads that must be balanced.
row of single phase outputs supplied via a dPX 125 (100 A)
Phase 1 supplies: 2 dX 32 A, 2 dX 20 A, 1 dX 10 APhase 2 supplies: 1 dX 32 A, 2 dX 20 A, 3 dX 10 APhase 3 supplies: 1 dX 32 A, 3 dX 20 A, 1 dX 10 A
Phase BalancIng
the neutral conductor must be the same cross-section as the phase conductors:- In single phase circuits, regardless of the cross-section, and in polyphase circuits up to a phase conductor cross-section of 16 mm2 for copper (25 mm2 for aluminium)- above this, its cross-section can be reduced in line with the load, unbalance, short-circuit thermal stress and harmonic conditions (see Book 4: “sizing conductors and selecting protection devices”).
distribution blocks (continued)
If the neutral breaks (maximum unbalance), the neutral point moves according to the load of each phase. the greater the load on a phase (phase 1 in this diagram), the lower its impedance. v1 drops, v2 and v3 increase and may reach the value of the phase-to-phase voltage on the phases with the lowest loads, which generally supply the most sensitive devices.
Breaking of the neutral
0
V2
V1
V3
→ → →
37
Ph
ase
ba
lan
Cin
g
Currents and voltages in star configuration three-phase system
In unbalanced system with neutral
In unbalanced system without neutral
V1
V2
V3
I1
I2
I2
I3
I3
In
1 = 0
2
3
0V1
V2
V3U31
U23
U12
0'
Neutre0
V1
V2V3
I1
I2
I3
U31 U12
U23
Z1
Z2Z3
In balanced system
Z1 = Z2 = Z3
I1 = I2 = I3
I1 + I2 + I3 = 0
v1 = v2 = v3 = v→ → → →
Z1 = Z2 = Z3
I1 = I2 = I3
I1 + I2 + I3 = In
v1 = v2 = v3 = vthe phase-to-neutral voltages remain balanced.the neutral conductor maintains the balance of the phase-to-neutral voltages v by discharging the current due to the unbalance of the loads. It also discharges the current resulting from the presence of harmonics.
→ → → →
Z1 = Z2 = Z3
I1 = I2 = I3
I1 + I2 + I3 = 0
v1 = v2 = v3
the phase-to-neutral voltages v are unbalanced even though the phase-to-phase voltages u remain equal.
→ → →
v1, v2, v3: Phase-to-neutral voltages
u12, u23, u31: Phase-to-phase voltages
u12 = v1 - v2
u23 = v2 - v3
u31 = v3 - v1
u = v u 3
(400 = 230 u 3)
(230 = 127 u 3)
0
V3 -V
2
-V1 V1
V2
-V3
U12U31
U23
→
→
→
→
→ → →
→ →
→ →
→ →
→ →
EF
EF
EF
B u s B A r s A n d d I s t r I B u t I o n
38
Ph
ase
ba
lan
Cin
g
Currents and voltages in delta configuration three-phase system
Balanced delta configuration
unbalanced delta configuration
unbalance does not have any consequences on the voltage in delta configurations, but the balance of the currents remains necessary to avoid line overcurrents (one phase overloaded) and limit inherent voltage drops.
in three-phase installations, the various circuits should be distributed on each phase, taking into account their power, their load factor (ratio of the actual power consumption to the nominal power), their operating factor (ratio of the operating time and the stoppage time to be weighted with the operating schedules) and their coincidence factor (ratio of the load of the circuits operating simultaneously to the maximum load of all of these circuits). see book 2 “Power balance and choice of power supply solutions”.distribution optimises the energy management.
the maximum number of lighting points or socket outlets supplied by one circuit is 8.special or high power circuits (water heater, oven, washing machine) must be provided for this use only.the maximum number of heaters must be appropriate for continuity of service.
distribution blocks (continued)
I1
I3
I2
J2
U31
U12
U23
Z2
Z1Z3
J3
J1
Z1 = Z2 = Z3
J1 = J2 = J3
I1 = I2 = I3 but I1 = I2 = I3 = 0→ → →
Z1 = Z2 = Z3
J1 = J2 = J3
I1 = I2 = I3 = 0→ → →
J: phase-to-neutral currentI: phase-to-phase current
I1 = J1 - J3
I2 = J2 - J1
I3 = J3 - J2
I = J u 3
U12
U31
U23
1
2
3
I1
I3
I2
J2
J3
J1
-J3
-J1-J2
30
→
→
→
→
→
→
→
→
→
EF
39
Ph
ase
ba
lan
Cin
g
care must be taken to maintain the minimum required cross-sections during balancing operations: each circuit must remain protected by the recommended device.
Cable cross-sections and ratings of protection devices according to circuits
230 v single phase circuitcopper cross-section (mm2)
fuse rating (a)
circuit-breaker rating(a)
signalling 0.75/1 2 6
lighting 1.5 10 16
16 a power socket 8 max. 5 max.
2.51.5 16 20
16
Water heater 2.5 16 20
Washing machine/tumble dryer/oven, etc. 2.5 16 20
cooking appliance single phase three-phase
62.5
3220
3220
electric heating 2250 W 4500 W
1.52.5 10 10
20
legrand electricity meters and measuring devices give the significant values of the installation at all times: current, voltage, actual power, power consumption, in order to optimise the load factor. Programmable time switches and programmers can be used to shift the operating ranges and “smooth out” consumption over time (operating factors). ^ Modular central
measuring unit
^ time switch ^ Electrical energythree-phase meter
^ Flush-mounted central measuring unit
B u s B A r s A n d d I s t r I B u t I o n
40
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
Electrical characteristics of distribution blockstype cat. nos. In (a) I2t (a2s) (1) Icw (ka) Ipk (kÂ) ui (v) uimp (kv)
unprotected terminal blocks
screw 048 01/03/05/06/07
63/100 1.2 107 3.5 17 400 8
on support 048 20/22/24/25
IP 2x terminal blocks screw terminals
green 048 30/32/34/35/36/38
blue 048 15/40/42/44/45/46/48
black 048 16/50/52/54
modular distribution blocks
one-piece
048 81/85 40 0.9 107 3 20
500 8
048 80/84 100 2.0 107 4.5 20
048 82/88 125 2.0 107 4.5 18
048 86 160 1.8 107 4.2 14.5
048 77 250 6.4 107 8 27
can be joined
048 71 125 3.6 107 6 23
048 83 160 1.0 108 10 27
048 73 250 3.2 108 18 60
Power distribution blocks for lugs
extra-flat374 47 125 1.1 107 4.1 25 500 8
374 00 250 3.2 108 8/12 (2) 60 1000 12
stepped
373 95 125 1.7 107 4.1 20 600 -
374 30 125 7.4 107 8.5 35
1000 12374 31 160 1.0 108 10 35
374 35 250 2.1 108 14.3 35
373 08 400 3.4 108 17 50/75 (3)
aluminium/copper connection boxes374 80 300 2.1 108 14.5 > 60 - 10
374 81 400 4.9 108 22.2 > 60 - 12
(1) the thermal stress limited by the upstream device must be less than the i2t of the distribution block, and the thermal stress limited by the downstream device must be less than the i2t of the cable: if necessary adapt the cross-section of the cable.(2) upper/lower ranges - (3) spacing between 50 mm/60 mm bars
legRand dIstRIButIon Blocks
the following installation possibilities and charac-teristics that have previously been described: rated current, short-circuit resistance, insulation values, number and capacities of outputs, connection method, enable the most suitable choice of distribution block to be determined.
the legrand range of distribution blocks meets the needs of a wide variety of requi-rements, providing both ease of use and maximum safety.
distribution blocks (continued)
41
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
thermal stress permitted by conductors with PVC insulation
s (mm2) 1.5 2.5 4 6 10 16 25 35 50 70 95
copperI2t (a2s) 0.3 x 105 0.8 x 105 0.2 x 106 0.5 x 106 1.3 x 106 3.4 x 106 8.3 x 106 1.6 x 107 3.3 x 107 6.4 x 107 1.2 x 108
Icw (ka) 0.17 0.29 0.46 0.69 1.15 1.84 2.9 4 5.7 8 10.9
alumin.I2t (a2s) 5.7 x 105 1.5 x 106 3.6 x 106 7 x 106 1.4 x 107 2.8 x 107 5.2 x 107
Icw (ka) 0.76 1.2 1.9 2.7 3.8 5.3 7.2
1 IndePendent dIstRIButIon teRmInal Blockstotally universal in their application, this type of terminal block can be used to distribute up to 100 a on between 4 and 33 outputs, depending on the catalogue number. the incoming cross-section is between 4 and 25 mm2, and the outputs between 4 and 16 mm2. They are fixed on 12 x 2 flat bars or th 35-15 and th 35-7.5 rails.
^ Combining IP 2x terminal blocks and support Cat. no. 048 10 enables a 2P, 3P or 4P distribution block to be created
< Fixed on 4 or 1 rail, the universal support Cat. no. 048 11 takes all terminal blocks
^ Empty support for terminal blocks enables exactly the right number of connections to be created
^ unprotected terminal blocks on supports are generally fixed on 12 x 2 flat bars for connecting protective conductors
Independent distribution terminal blocks
B u s B A r s A n d d I s t r I B u t I o n
42
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
^ supply busbar supplied via universal terminal Cat. no. 049 06
2 lexIc suPPly BusBaRssupply busbars can be connected directly and supply power to Lexic modular devices up to 90 A. They are available in single, two, three and four pole versions. They are a flexible solution, taking up little space, and are easy to adapt for distribution in rows.
^ total combination of functions using the Lexic concept. Power, control and signalling are grouped together in wiring areas corresponding to the physical areas of the installation
^ A space is made in the devices that do not need to be connected to the supply busbar
distribution blocks (continued)
^ distribution via four pole supply busbar Cat. no. 049 54 fitted with end protectors Cat. no. 049 91
43
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
3 dIstRIButIon teRmInalsThese single pole distribution blocks are fixed directly in the terminals of dPX 125, 160 and 250 er devices and modular Vistop devices from 63 to 160 A. They are used for simplified distribution for panels where the number of main circuits is limited.
^ totally universal, distribution blocks are suitable for all types of application
^ For the supply end of medium power distribution panels, the 250 A modular distribution block Cat. no. 048 77 can also be fixed on a plate
4 modulaR dIstRIButIon Blocksthese combine compactness and high connection capacity. With a modular profile, they are fixed by clipping onto th 35-15 rails (en 50022). legrand modular distribution blocks are totally isolated: they are used at the supply end of the panel up to 250 a or in subgroups of outputs in panels with higher power ratings.
^ single pole modular profile distribution blocks, total insulation of the poles to distribute 125 to 250 A
^ six 35 mm2 rigid outputs (25 mm2 flexible) for the output terminal Cat. no. 048 67
B u s B A r s A n d d I s t r I B u t I o n
44
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
6 stePPed dIstRIButIon Blocksthese are available in catalogue versions, complete and fully-assembled from 125 to 400 a, and in a modular version (bars and supports to be ordered separately) that can be used to create customised distribution.
5 extRa-flat dIstRIButIon Blockstheir lower height and their current-carrying capacities mean that the same panel can manage the power requirements for the supply end (up to 250 a) combined with the compactness of modular rows in slim panels.
< the key features of extra-flat distribution blocks are power, capacity to connect large cross-section cables and compactness.
< 125 A stepped distribution block
< 250 A distribution blocks Cat. no. 374 35
^ 400 A stepped distribution block
distribution blocks (continued)
45
leg
ra
nd
dis
trib
uti
on
blo
Ck
s
7 sIngle Pole alumInIum/coPPeR connectIon Boxesdesigned to provide the interface between large cross-section conductors entering the panel, including those made of aluminium, and internal
wiring conductors.two models 120 mm2/70 mm2 (Cat. no. 374 80) and 300 mm2/185 mm2
(Cat. no. 374 81) are available. they can also be used for alumi-nium operating circuits (outgoing cables) or when the line lengths require the use of large cross- sections.
8 vIkIng™3 PoWeR teRmInal Blocksthese single pole blocks are used for the junction between the enclosure and the external cables. They are fixed on a 4 rail or a plate and take Cab 3 and Duplix labelling. They provide numerous solutions for connection with aluminium or copper cables, with or without lugs.
different connection configurations can be created by simply moving the cable clamp strips.
Equipotential link between two boxes using strips provided
All Viking™3 terminal blocks: see Book 11➔
< Alumin./copper direct connection
Cable/cable
terminal for cable lug/Cable
terminal for cable lug/terminal for cable lug
Cable/terminal for cable lug
Al/Cu
Junction distribution Branch-line
Cu Cu
Cu Cu
Al/Cu
Cu
B u s B A r s A n d d I s t r I B u t I o n
46
Ch
oiC
e o
f P
ro
du
Cts
choice of products
supply busbars from 63 to 90 A (Ipk 17 kÂ)
type lengthuniversal
1-pole + neutral or 1-pole
2-pole 2-pole balanced on 3-phase 3-pole 4-pole
Prong-type1 row 049 26 049 38 049 40 049 42 049 44meter 049 37 049 39 049 41 049 43 049 45
fork-type1 row 049 11 - 049 17meter 049 12 049 14 049 18 049 20
distribution terminal blocks from 63 to 100 A (Ipk 10 kÂ)
number of outputs
Bare terminal blocks Insulated terminal blocks IP 2x (xxB)
with screws on support black blue green4 048 01 048 20 048 50 048 40 048 306 048 16 048 158 048 03 048 22 048 52 048 42 048 32
12 048 24 048 54 048 44 048 3414 048 0516 048 25 048 45 048 3519 048 06 21 048 26 048 46 048 3624 048 0733 048 28 048 48 048 38
Modular distribution blocks from 40 to 250 A (Ipk 14.5 to 42 kÂ)
admissible maximum rating (a)
2-pole 4-pole terminal blocks IP 2x
cat.nosnumber and section of
fl exible conductors (mm²) cat.nosnumber and section of
fl exible conductors (mm²) earth neutraladditional
outputs (mm²)Inputs outputs Inputs outputs
40 048 81 2 x 10 11 x 4 048 85 2 x 10 11 x 4 048 34 048 44 12 x 6100 048 80 2 x 16 5 x 10 048 84 2 x 16 5 x 10 048 32 048 42 8 x 6
125
048 82 2 x 25 2 x 16 + 11 x 10 048 86 2 x 25 2 x 16 + 7 x 10 048 44 12 x 6048 88 2 x 25 2 x 25 + 11 x 10 048 35 048 45 16 x 6
048 76 1 x 35 1 x 25 + 1 x 16 + 14 x 10 048 46 21 x 6
160 048 79 1 x 70 2 x 25 + 4 x 16 + 8 x 10 048 45 16 x 6
250 048 77 1 x 120 1 x 35 + 2 x 25 + 2 x 16 + 6 x 10
049 26 049 11
048 03 048 15 048 68
47
Ch
oiC
e o
f P
ro
du
Cts
single pole modular distribution blocks and distribution terminal from 125 to 250 A (Ipk 27 to 60 kÂ)
admissible maximum rating (a) cat.nos
number and section of conductor per pole (mm²)
Inputs outputs
modular distribution blocks
125 048 71 4 x 35 12 x 10160 048 83 1 x 50 3 x 25 + 2 x 16 + 7 x 10250 048 73 1 x 120 6 x 25 + 4 x 10
distribution terminal160 048 67 direct into downstream
terminal 6 x 25
250 048 68 direct into downstream terminal 4 x 35 + 2 x 25
Power distribution blocks from 125 to 400 A (Ipk 20 to 75 kÂ)
admissible maximum rating (a)
extra-flat stepped
cat.nosnumber and section of
conductor per pole (mm²) cat.nosnumber and section of
conductor per pole (mm²)
Inputs outputs Inputs outputs
125374 47 1 x 35 10 x 16 (Ph)
17 x 16 (N) 373 95 4 bars 12 x 4 mm receiving 5 connectors 2 x 10 each
374 30 1 x 35 5 x 25160 374 31 1 x 70 5 x 35
250 374 00 1 x 150 1 x 70 or 1 x 50 + 1 x 35 or 2 x 35 374 35 1 x 120 5 x 50
400373 08 2 x 8.5 mm
21 holes M6 70 mm² max. connectors
374 42 2 x 185 15 holes M6 + 15 holes M8
Aluminium/copper distribution boxes
admissible maximum rating (a) cat. nos
number and section of conductor per pole (mm²)
Input aluminium Input copper output copper300 374 80 1 x 120 1 x 95 1 x 70540 374 81 1 x 300 1 x 150 1 x 150
048 83 048 88 374 00 373 08
B u s B A r s A n d d I s t r I B u t I o n
48
Ch
oiC
e o
f P
ro
du
Cts
Isolating supports and copper bars
Busbar supportsI admissible maximum rating (a)
125 160 250 400 800 1000 1600 4000
universal supports1-pole 373 98 374 374-pole 373 96 374 32 374 36 373 10
xl³ supports 4-pole 373 15 373 20 373 21 373 22/23 373 24/25maximum number of bars per pole
copper bars
12 x 2 373 88 112 x 4 373 89 1 115 x 4 374 33 118 x 4 374 34 1 1 1 125 x 4 374 38 1 125 x 5 374 18 1 132 x 5 374 19 1 150 x 5 374 40 1 1 2 463 x 5 374 41 1 2 475 x 5 374 59 1 2 480 x 5 374 43 1 2 4
100 x 5 374 46 2 4125 x 5 - 450 x 10 - 360 x 10 - 380 x 10 - 3
100 x 10 - 3125 x 10 - 3
Isolating supports for C-section busbars and aluminium bars (up-to 1600 A)
Isolating supportenclosure depth (mm) Bars aligned Bars staggered
475 or 725 373 66 373 67975 373 68 373 69
373 24 373 10 373 66
aluminium c-section bars
cross section (mm²) cat.nos524 373 54549 373 55586 373 56686 373 57824 373 58
Power guide:A complete set of technical documentation
world Headquarters and international department87045 Limoges Cedex - France☎ : + 33 (0) 5 55 06 87 87 Fax : + 33 (0) 5 55 06 74 55
11 | Cabling components and control auxiliaries
CERTIFIED
10 | enclosures and assembly certification
09 | operating functions
08 | Protection against external disturbances
01 | Sustainable development
02 | Power balance and choice of power supply solutions
03 | electrical energy supply
04 | Sizing conductors and selecting protection devices
05 | Breaking and protection devices
06 | electrical hazards and protecting people
07 | Protection against lightning effects
Annexes glossary Lexicon
13 | Transport and distribution inside an installation
EX29
016
12 | Busbars and distribution