    National Building Code 2005 Part IV on Fire and Life Safety gives the Planning Considerations for Buildings

  • Page 2

  • Page 3

    Fire Safety Regulations

    NBC Considerations

    Any area exceeding 500 m2 shall be divided into compartments by fire

    resistant walls

  • Page 4

    Fire Safety Regulations

    Staircase/Exit Requirements

    Minimum width the minimum width of staircase shall be as follows:

    a) Residential buildings (dwellings) 1.0 m

    NOTE for row housing with 2 storeys, the minimum width shall be 0.75 m

    b) Residential hotel buildings 1.5 m

  • Page 5

    Fire Safety Regulations

    Staircase/Exit Requirements

    Minimum width the minimum width of staircase shall be as follows:

    c) Assembly Buildings like Auditoria,

    Theatres, Cinema Halls, etc. 2.0 m d) Educational Building- 1.5 m

    e) Industrial Building- 2.0 m

    f) All other Buildings- 1.5 m

  • Page 6

    Fire Safety Regulations

    Staircase/Exit

    Requirements

    The minimum width of tread without nosing shall

    be 250 mm for residential

    buildings

    The minimum width of tread for other buildings shall be 300 mm

  • Page 7

    Fire Safety Regulations

    Staircase/Exit Requirements

    The maximum height of riser shall be-

    190 mm for residential buildings and

    50 mm for other buildings and

    these shall be limited to 16 per flight

  • Page 8

    Fire Safety Regulations

    Staircase/Exit

    Requirements

    The minimum head-room in a passage under

    the landing of a staircase

    shall be 2.2 m

    The minimum clear head-room in any

    staircase shall be 2.2 m

  • Page 9

    Fire Safety Regulations

    Staircase/Exit Requirements

    All aspects of exit requirements for corridors, doors, staircases, ramps, etc.

    in respect of widths, travel distance shall

    be as per NBC 2005, Part 4 Fire and Life Safety Lobbies should not carry more than 30 people per 100m2

  • Page 10

    Fire Safety Regulations

    Provisions for Physically Handicapped

    The minimum width of corridors in buildings serving patients bedrooms and from the point of

    view of physically handicapped people, shall be

    2400 mm

  • Page 11

    Fire Safety Regulations Requirements of IS 1643-

    1977

    some persons or people should be trained to use methods & equipments

    according to IS 1648-1961

    All fire escape routes, emergency exits, and location of fire fighting equipment

    should be clearly marked and sign

    posted, both in English and in the local

    language

  • Page 12

    Fire Safety Regulations

    Requirements of IS

    1643-1977

    Warning and alarm devices are installed

    Fire resisting doors or roller shutters conforming to

    relevant Indian Standard

    are provided at selected

    places along all escape

    routes

  • Page 13

    Fire Safety Regulations

    Fire Resisting Door

  • Page 14

    Fire Safety Regulations

    Requirements of IS

    1643-1977

    Typical corridor and lobby escape routes

    should be as shown in IS

    I 643-77

  • Page 15

    Fire Safety Regulations

    Requirements of IS

    1643-1977

    Roof Escapes: The roof or any associated routes

    shall have direct access

    to the ground

    Horizontal Escapes: The application shall depend

    on the layout of the

    building and any adjoining

    building(s)

  • Page 16

    Fire Safety Regulations

    Requirements of IS

    1643-1977

    Fire Escape Chutes: The Special Tunnels provided

    for rescue operations

  • Page 17

    Fire Safety Regulations

    Internal Staircases :

    The factors used in the calculation

    for width of internal staircases are:

    (a) Unit Width: Fifty centimetres

    shall be considered the unit

    width required by people moving

    in single line

    (b) Experiments have shown that 40

    people can easily be evacuated

    per minute through a one- unit,

    width. The rate of evacuation is

    also known as 'discharge rate

  • Page 18

    Fire Safety Regulations

    Internal Staircases :

    The factors used in the

    calculation for width of

    internal staircases are:

    c) Each storey of a building

    shall be evacuated on to

    the stairs in a maximum

    time of 2-1/2 minutes and

    the ground floor in the

    same interval

  • Page 19

    Fire Safety Regulations

    STAIRCASES SERVING A SINGLE

    FLOOR :

Recommended