building service group assignment
TRANSCRIPT
PKNS Complex,Shah AlamPrepared byLee Pei Gie 0315653Yong Seen Yee 0315883Khoo Xin Yee 0316180Davin Young Qiao Wei 0321065Thun Shao Xun 0315919Tay Sy Min 0320813Shane Sim Ee Han 0321288
Building Services II (QSB 2714)Bachelor of Quantity Surveying
’’Oldest commercial
complex in Shah Alam which
houses offices and shops.
There are hardly any high street
shops. It's more of a bazaar with
small shops/stores/stalls
.
The Selangor Immigration Office here also helps to
cater the crowd
Discussion on Existing System>>>>>>>>>
Fire protection system
• Active fire protection system
• Passive fire protection system
Fire extinguisher• Initial outbreak of
fires• Located at
conspicuous location• Within 20m from a
potential fire hazard• ABC type dry powder
fire extinguisher• Blue colour
Fire Protection System
External fire hydrant• Flow from water main with
the control of a valve• Two way fire hydrant• <10m distance to the
building• <10m distance to high
voltage electrical main• <90m apart along access
road
Fire Protection System
Hose Reel• Early stage of fire• Sited in proper position• Manually operated and
activated by opening a valve enabling the water to flow into hose that is 30m away
Fire Protection System
Water storage tank• Located at roof level• Pressed steel• Painted with a red
band of minimum 200mm
• Two compartments• Level indicator
Fire Protection System
Wet riser• Permanently charged with
water • >30.5 and <70.5m above the
fire appliance access level• Inlet breeching connector at
ground floor and with landing valve on each floor
• Air valve automatically open to release air
• Air valve close when is full of water
Fire Protection System
Sprinkler system• Small glass bulb with a
glycerine based liquid• Block the flow of water• Liquid become hot;
expand; shatter the glass bulb
• Temperature is approximately 68°C/155°F
Fire Protection System
Fireman’s switch• Electrical isolation switch• Permit the disconnection of
electrical power supply • Located in conspicuous
place• <2.75m from the ground• Paint in red colour
Fire Protection System
Manual call point• Raising an alarm manually• Push button / break glass• Installed at a height of
1.2m above floor level• Travel distance from one
place to the nearest call point doesn’t exceed 30m
Fire Protection System
Fire alarm bell• To alarm people who are
at risk• It is relatively loud• Produce a specific sound
pattern to avoid confusion to successfully warn for hazards
Fire Protection System
Smoke detector
• To detect the fire• Ionized smoke detector & light scattering smoke
detector• Reduce current which energies alarm relay and
obstruct the light passing through• Trigger the alarm bell to give signal
Fire Protection System
Voice communication system
• To communicate critical information
• Colour in red• Two way communication
system• A network of telephone
handsets connected to the master headset at the Fire Command Centre
Fire Protection System
Fire door• Allow the flow of
traffic around the building
• A barrier to stop the spread of fire when door is closed
• Provide an escape route for occupants to escape when the door is open
Fire Protection System
Fire escape route
• Emergency exit• Provides a directional exit signs• Mounted beside the lift for showing these
escape routesFire Protection System
Staircase and compartment
• The number of risers per flight <16
• Tread & riser dimension are consistence
• No winders in escape staircase
• Sub-divided into compartment by using compartment walls and compartment floors
• Period of insulation >15min
Fire Protection System
Electrical Supply System
• Main Switch Board• Service Entrance• Branch Circuit• MCCB• Conduit
Main switch board• Consists of various
electric apparatus that are used to operate circuits
• To transmit electricity• It is enclosed • Sheet steel fabricated
Electrical Supply System
Service entrance• Allow the electric to flow
to the building• Electric will pass through
the meter and a device• For overcurrent
protection and electrical current control
• To avoid occurrence of overcurrent
Electrical Supply System
Branch circuit• A metal box that filled
with switches• To supply the power to
the electrical devices in the shop
• Cut off the power without affecting the power supply of the whole building
Electrical Supply System
Miniature circuit breaker (MCCB)
• To protect cables • Lines against overload and short-
circuitElectrical Supply System
Conduit• To protect the cables
from physical damage and heat
• PVC electrical conduit elbow
• Light• High strength • Low cost
Electrical Supply System
Mechanical and Air-conditioning System
• Mechanical Fan• Air Return Diffuser• Air Supply Diffuser• Air Door• AHU Room• Cooling Tower• Ventilation Ducting System
Mechanical Fan
CEILING FAN or WALL MOUNTING FAN Circulate air within a space Reducing the perceived temperature by method of
evaporation of perspiration on the skin of the occupants.
Mechanical and Air-conditioning System
Ventilation Conducting System
FLEXIBLE DUCTWORKS Insulated with fiberglass to avoid losing valuable
conditioned air Enhance thermal performance and prevent
condensation and dripping
PKNS COMPLEXMechanical and Air-conditioning System
Cooling Tower
Specialized heat exchanger Located on the roof of PKNS building WHY ? Noise and vibration they generate, the tower
should be isolated acoustically from the frame of the building and noise sensitive areas
Mechanical and Air-conditioning System
AHU Room
Located in a large mechanical room AHU connects to the ductwork that distributes the
conditioned air throughout the areas of the building Warmed air is returned to the AHU room to be cooled after
going through the cooling coil and filter
Mechanical and Air-conditioning System
Air Door
Installed air doors at every entrance or customer entryways
Help keep flying insects out by creating forceful turbulence
Help keep out outside air and prevent loss of cool air, thus reducing infiltration through the opening
Mechanical and Air-conditioning System
Air Supply Diffuser
CONE DIFFUSER Mounted on the
ceiling Cones can be taken
out by pushing inward, turn around and pull down
4 - WAYS LOUVER BLADED DIFFUSER
Mounted on the ceiling
Provide excellent diffusion performance
Mechanical and Air-conditioning System
Air Return Diffuser
Attached to the wall as well as mounted on the ceiling
Connects to ductwork that allows air to return to any cooling or heating system
The openings that connect to ducts and other spaces for the returning air are covered with grillwork.
Mechanical and Air-conditioning System
Vertical Transport System
• Escalator• Elevator
ESCALATOR
Located at the center of ground floor and second floor Double bank in two travel direction Used in the objects in which persons travel in two opposite
direction Normally use in major department stores where transportation
time between several levels should be kept to a minimum
Vertical Transport System
ELEVATOR
Three fire fighter lift and three electric lifts The elevators can support up to 800kg, 11 people can go in at
one time The speed of these elevators is between 100-150 feet per minute
Fire Lift and Electirc Lift Fire Lift and
Electirc Lift
Vertical Transport System
ELEVATOR
Call Buttons are used to request an elevator Hall lanterns or position indicators are used to indicate the
arriving elevator and the direction it will travel Audible signals sound once for elevators going up and
sound twice for elevators going down
Hall Lantern
Hall Lantern
Vertical Transport System
ELEVATOR
Equipped with lighting and ventilation fan Floor Selection Buttons are used to select floors that the
elevator will stop at Operation and Emergency Buttons are offset below the floor
selection buttons. These buttons include door open, door close, emergency stop and emergency alarm. All these button panels are clear and easily reached at appropriate level
Vertical Transport System
Analysis on System Problems>>>>>>>>>
Problems on Fire
Protection System
1.Fire Alarm System• Most of the fire alarm trigger
system are not functioning
Problems on Fire Protection System
Only a few of the old alarm were replaced by new ones.
• lacking of visible indicator alarm signal which one of the requirement stated in UBBL 241.
• To notify deaf people during a fire
Fire alarm within the building
visible indicator alarm signal that the building should have
Problems on Fire Protection System
2. Voice communication System
Telephone for users to contact the
control centre looks very dirty and
faulty.
There is no key to access the telephone in it.
Problems on Fire Protection System
The command and control centre which is closed and looked abandoned
• violates the requirement of UBBL 239 part 3 - voice communication system is required in every office area exceeding 92.9m2
• violates the requirement of UBBL 238 - not having a command and control system in such a big building.
Problems on Fire Protection System
3. Fire Extinguisher• Fire extinguishers can found at almost
every corner of the building especially at fre hazards area.
• However, most of them are left unsecured while some of them are hard to excess.
Problems on Fire Protection System
Glass is broken
fire extinguishers that are not
kept properly but instead it
is just left unsecured.
No access key.
Problems on Fire Protection System
4. Sprinkler System• Very poorly maintained.• Almost every visible sprinkler is
covered with a thick layer of dust.• Could result in a false alarm to
trigger.
Problems on Fire Protection System
• Moreover, there are even some sprinkles then are badly corroded.
• This will impact the functionality of the system and also result in leakage.
Corroded Sprinklers
Problems on Fire Protection System
5. Firemen Lift• There are no signs indicating which
is the firemen lift.• All the lifts including the firemen lift
have very small capacity.• Very inconvenient for firemen to use
during a fire.
Problems on Fire Protection System
No signs indicating which is the firemen
lift.
Lift with small capacity
Problems on Fire Protection System
6. Escape Route• diffusers of the staircase
pressurization system are covered with a very layer of dust.
• The stairs will not be pressurised the way it should.
• Smoke can enter the escape route.• Besides, few of the lockset of fire
doors which leads to the escape route is broken.
Problems on Fire Protection System
Diffusers covered with a lot of dust
Fire doors with broken locksetProblems on Fire Protection System
Problems on Mechanical
and Air-conditioning
System
COOLING TOWER
Water Leakage
Problems on Mechanical and Air-conditioning System
Water flows to the electrical cabling nearby
Problems on Mechanical and Air-conditioning System
Cooling tower located at the top floor in the middle of the building is not functioning.
Fans are used on the entire ground floor level.
Problems on Mechanical and Air-conditioning System
Big fans are used in
shoppinng complex
Problems on Mechanical and Air-conditioning System
AHU DOOR
Gap between the door
Problems on Mechanical and Air-conditioning System
DUCTING
Ducting expose
Problems on Mechanical and Air-conditioning System
Suggestion on ImprovingSystems>>>>>>>>>
Fire Protection
System
1. Fire Alarm SystemEmployees have to stay alert if there is any broken system
to prevent it from not functioning during an event of fire which will cause loss of lives within the complex
Recommendation on Fire Protection System
The volume of the siren may be increased when the fire alarm system is activated
the occupants can clearly hear the directions that are being given
Recommendation on Fire Protection System
Some frequent maintenance should also be carried out
such as battery changing and cleaning it to make it free from dust
Recommendation on Fire Protection System
Decrease the distance between alarms
it would take a long time for the occupants to hear the fire alarm which the valuable escape time would be lost because of this.
Recommendation on Fire Protection System
Quantity of fire alarm system within the complex may also be increased.
if some fire alarms are broken down, at least there are a few more still can carry out its function in the case of emergency.
Recommendation on Fire Protection System
2. Voice Communication System
Can be improved by frequent testing and maintenance
to ensure it can be functioned
Recommendation on Fire Protection System
Prepare more spare keys which can access the telephones for users to contact the control centre
as the size of key is usually small which could be lost easily.
Recommendation on Fire Protection System
Telephone should also be cleaned frequently so that it would not be covered with dust or unwanted rubbish
which may hiding them away or mixing them with other items and lead to the confusion for people in the complex in the case of emergency.
Recommendation on Fire Protection System
Ensure that the connection line of control centre is still working
because it could assist to contact fire fighters during emergencies
Recommendation on Fire Protection System
The command and control centre should be reopened
To receive information from the occupants when there is an event of fire for them to contact the fire fighters immediately without delaying the time.
Recommendation on Fire Protection System
3. Fire Extinguisher
Test the extinguisher during annual fire protection inspections
ensure that it can be functioned because the extinguisher would have easily been knocked and damaged.
Recommendation on Fire Protection System
All the employees should have training lesson on how to use the fire extinguisher correctly
so they can use it to prevent the spread of fire
Recommendation on Fire Protection System
Ensure that the fire extinguishers are always in place with accessible keys beside
it may only take a few seconds to remove the blockage on the extinguisher, but every second is vital in the event of a fire
Recommendation on Fire Protection System
The date of issue in their label of the extinguisher should be checked frequently
If they are out of date, they are useless and the employees need to replace them
Recommendation on Fire Protection System
Check fire extinguishers’ hose
If there are any signs of breakage, holes or cracks, the extinguisher must be replaced
Recommendation on Fire Protection System
4. Sprinkler System
Increase the water volume that can be spread out from the sprinkler
stop the fire in a short time
Recommendation on Fire Protection System
Sprinklers should be cleaned frequently
dust will block the sprinkler head
Recommendation on Fire Protection System
Old rusted sprinkler should be replaced to a new one
when the sprinkler is rusted, this can interfere with the valves or even stop them breaking altogether.
Recommendation on Fire Protection System
Frequent checking of the condition of the piping system of sprinkler should also be carried out
as closed sprinkler valve is the most common cause of failure in a sprinkler system
Recommendation on Fire Protection System
Sensitivity of sprinkler should be tested and maintenance is required for broken sprinkler.
checked weekly to ensure they are open, and a full flow test should be conducted at least yearly.
Recommendation on Fire Protection System
5. Fireman LiftShould be identified by placing a sign stated ‘FIREMAN LIFT’
because the obfuscating signage in any way will make this more difficult for people who are not familiar with the layout of the building
Recommendation on Fire Protection System
Size of the fireman lift should be enlarged
more fire fighters can be sent to upper floor to control the fire spread the save the occupants who are trapped in the fire.
Recommendation on Fire Protection System
Velocity of the lift should be slightly increased
reduce the time taken for fire fighters to stop the spread of fire on the upper floor.
Recommendation on Fire Protection System
Make sure installation and maintenance are carried out properly
the maintenance of fireman life should be done frequently to prevent it from not functioning
Recommendation on Fire Protection System
Fire resistance coating can also be applied for internal and external wall surface of the lift
form a barrier to stop the spread of fire
Recommendation on Fire Protection System
6. Escape RouteProvide the diagrams to show the route to escape
well displayed signs can quickly guide everyone to safety.
Recommendation on Fire Protection System
Diffusers should be cleaned weekly by the cleaner
residues inside diffuser combined with heat can cause serious life-threatening fires.
Recommendation on Fire Protection System
Change the fire door lockset if it is broken
it could lead to very dangerous situation if people are trying to the fire door in a panic
Recommendation on Fire Protection System
Do monthly check up of the condition of the fire door.
If there is a hole or crack on the fire resistant door, the door is considered as useless because smoke will be able to come through the cracks and the fire will continue to spread to other places
Recommendation on Fire Protection System
Ensure that the fire door is accessible
so that when people are trying to escape from the complex, they do not need to interfere with any equipment, tools or objects that could cause them further harm.
Recommendation on Fire Protection System
Mechanical and Air-
conditioning System
Water leak from cooling tower
• Blocked or clog pipe
*For illustration purpose only
Recommendation on Mechanical and Air-Conditioning System
Recommendation……
Recommendation on Mechanical and Air-Conditioning System
Mechanical fan
Recommendation on Mechanical and Air-Conditioning System
Round Cone Diffuser
Recommendation on Mechanical and Air-Conditioning System
AHU Door
Recommendation on Mechanical and Air-Conditioning System
Exposed ducting
Recommendation on Mechanical and Air-Conditioning System
Recommendation on Mechanical and Air-Conditioning System