BUCHHOLZ RELAY ON TRANSFORMER

BY

JULIUS TEMITOPE ALOWONLE

JULIU

S A

LO

WO

NLE

Page 2: BUCHHOLZ RELAY ON TRANSFORMER

INTRODUCTION• Buchholz relay in transformer is an oil container

housed the connecting pipe from the main tank to the conservator tank….www.electrical4u.com

• Buchholz relay is a type of oil and gas actuatedprotection relay mainly used on all oil immersed insulation transformer more than 500KVA...www.owlcation.com

• Buchholz relay is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of fault…V.K MEHTA

• Buchholz relay is an oil immersed protective relay located between the connecting pipe of the conservator tank to the main tank, which energized an alarm circuit or trip circuit during transformer faulty conditions.

JULIU

S A

LO

WO

NLE

Page 3: BUCHHOLZ RELAY ON TRANSFORMER

BUCHHOLZ RELAY( INVENTED BY MAX BUCHHOLZ IN 1921)

JULIU

S A

LO

WO

NLE

Page 4: BUCHHOLZ RELAY ON TRANSFORMER

ELEMENTS OF BUCHHOLZ RELAY• UPPER ELEMENT-A hinged float i.e. moving up

and down depending upon the oil level in the Buchholz relay container.

• LOWER ELEMENT-A hinged float or A baffle plate i.e. in front of inlet (main tank side) of the transformer. Movement by oil pressure.

• MAIN ELEMENT-Gas release pockets or cocks (on top).

JULIU

S A

LO

WO

NLE

Page 5: BUCHHOLZ RELAY ON TRANSFORMER

ELEMENTS OF BUCHHOLZ RELAY• MERCURY SWITCH-Depends on the position of

the float(attached to the float).

• OIL SURGE DETECTOR OR FLAP -Detect an oil surge from the main tank to the conservator tank.

• ALARM-Initiate sound for fault attention.

• TRIP CIRCUIT-Actuate Circuit breaker isolation.

JULIU

S A

LO

WO

NLE

Page 6: BUCHHOLZ RELAY ON TRANSFORMER

INTERNAL DIAGRAM

JULIU

S A

LO

WO

NLE

Page 7: BUCHHOLZ RELAY ON TRANSFORMER

INTERNAL DIAGRAM

JULIU

S A

LO

WO

NLE

Page 8: BUCHHOLZ RELAY ON TRANSFORMER

INTERNAL DIAGRAM

JULIU

S A

LO

WO

NLE

Page 9: BUCHHOLZ RELAY ON TRANSFORMER

BUCHHOLZ RELAY

JULIU

S A

LO

WO

NLE

Page 10: BUCHHOLZ RELAY ON TRANSFORMER

BUCHHOLZ RELAY LOCATION

JULIU

S A

LO

WO

NLE

Page 11: BUCHHOLZ RELAY ON TRANSFORMER

BUCHHOLZ RELAY PRINCIPLE• Based on Mechanical phenomenon(Mechanically

actuated).

• Minor Internal Fault.

• Severe or Major types of Fault.

JULIU

S A

LO

WO

NLE

Page 12: BUCHHOLZ RELAY ON TRANSFORMER

MINOR INTERNAL FAULT

• Insulation fault between turns.

• Breakdown of core of transformer.

• Core heating.

JULIU

S A

LO

WO

NLE

Page 13: BUCHHOLZ RELAY ON TRANSFORMER

MAJOR OR SEVERE FAULT

• Short-circuit between phases.

• Short-circuit between phases to earth.

• Fault in tap changing equipment.

JULIU

S A

LO

WO

NLE

Page 14: BUCHHOLZ RELAY ON TRANSFORMER

MINOR FAULT

• Minor

• fault Gas Float Mercury Alarm

• switch energized

• Decomposition Lower the Tilting the Alarm

• of transformer float switch contact

• oil (hydrocarbon) closed

JULIU

S A

LO

WO

NLE

Page 15: BUCHHOLZ RELAY ON TRANSFORMER

MAJOR FAULT

• Major Baffle Mercury Trip Circuit

• fault plate switch circuit breaker

• Surge of Oil Tilting the Energized Opened

• the oil pressure switch LV & HV

• side

JULIU

S A

LO

WO

NLE

Page 16: BUCHHOLZ RELAY ON TRANSFORMER

OIL LEAKAGE

• Oil Air Float Mercury Alarm

• leakage bubbles switch energized

• Lower the Tilting the Alarm

• float switch contact

• closed

JULIU

S A

LO

WO

NLE

Page 17: BUCHHOLZ RELAY ON TRANSFORMER

FALSE OPERATIONS OF BUCHHOLZ RELAY• Buchholz relay operation may be actuated

without any fault in the transformer.

• OIL TOPPAGE-When oil is added to a transformer, air may get in together with oil, accumulate under the relay cover and thus cause false buchholz relay operation.

• Mechanical lock-is provided in the relay so that one can lock the movement of mercury switch when oil is topping up in the transformer and also during transportation of transformer.

• EXTERNAL FAULT-Over currents flowing through the winding cause over heated the copper and causes oil to expand. It increase the oil velocity which is sufficient to trip over the lower float.

JULIU

S A

LO

WO

NLE

Page 18: BUCHHOLZ RELAY ON TRANSFORMER

ADVANTAGES OF BUCHHOLZ RELAY• Buchholz relay prevent accidents during major

fault (isolate the transformer).

• Severity of the fault can be determined without dismantling the transformer (DGA).

• It trapped gases for bleeding.

JULIU

S A

LO

WO

NLE

Page 19: BUCHHOLZ RELAY ON TRANSFORMER

LIMITATIONS

• It can sense the fault occurring below oil level only. Therefore separate protection is needed for connecting cables.

• it is a time delay operating device (0.1 seconds and average of 0.2 operating range).

• it can only be used with oil immersed transformers equipped with conservator tanks

JULIU

S A

LO

WO

NLE

Page 20: BUCHHOLZ RELAY ON TRANSFORMER

REFERENCES

• 33/11KV 15MVA, Mangoro Injection Substation –IKEJAELECTRIC LAGOS.

• www.electrical4u.com

• www.wikipedia.org

• www.owlcation.com

• PRINCIPLE OF POWER SYSTEM BY V.K. MEHTA.