total equipment room controls provide continuous monitoring and control of sanitizers (standard ORP probe or optional Cl/Br amperometric probe), oxidizers, pH, conductivity, turbidity, system flow rate, system pressures, chemical inventory levels, surge tank and backwash holding tank levels. The controller is reliable, flexible, expandable, easy to install and even easier to operate. The can be configured for functions such as dual pH feeds, heater control, a primary Cl/Br sanitation feed, Cl/Br booster feed, a reducer feed (dechlor), an ozone generator, alarm relay, filter backwash, polymer feed, auto fill, recirculation pump operation for power savings & bather entrapment prevention, pool water TDS control and water chemistry balance calculations. Every controller comes with a comprehensive installation, operation and service manual with field start-up and service support provided by local distribution.
All controllers come with a PVC machined flow cell, which includes proprietary potentiometric pH & ORP probes, reed flow switch (rotary flow switch is an optional upgrade), temperature sensor, optional amperometric probe, optional flow meter & saddle, optional conductivity probe, optional turbidity probe, optional analog gauges or pressure transducers and optional proprietary water level sensor or float controls. controllers are suitable for gas chlorine, sodium & calcium hypochlorite, bromine and ozone in a variety of installations such as pools, spas, fountains, zoos, aquariums and cooling towers. With an interactive information system that provides remote control and data acquisition, the is the most advanced total equipment room control and monitoring system available today. With over 30,000 controls manufactured over a span of 14 years, is a proven leader in the design and manufacture of commercial recreational water chemistry controls.
BECSys7
BECSys7
BECSys7
BECSys7
BECSys7
July 06
CONTROL DISPLAYS· LCD display backlit 12X40 character
alpha/ numeric, graphical· pH: 0.0 to 14.0, 0.1 or 0.01 resolution
(programmable)· ORP: -1000 to 1000 mV, 1 mV resolution· PPM: 0 to 20 ppm 0.1 or 0.01 resolution
(programmable)O· Temperature: 32-212 F, 1 F resolution; 0-
O O100 C, 1 C resolution· Flow rate: 0-8800 gpm, 0.1 gpm
resolution; 0-33265 liter/min, 0.1 liter resolution
· Flow volume: 999 trillion gallons, 1 gallon resolution; 999 trillion liters, 1 liter resolution
· Conductivity/TDS: 0 to 20,000 micromhos; 0 to 10,000 ppm;
· Turbidity: 0 to 20 NTU, 0.01 resolution· Pressure: programmable range PSI, kPa· Vacuum: 0 to 31 in./Hg; 0 to 78 cm/ Hg· Surge tank and backwash holding tank:
programmable range 0.01 ft.; 0.01 m· Chemical Inventory: programmable range
0.1 ft.; 0.1 m· Heater set point & alternate heater set
point (4 Event 28 day timer) · Alternate ORP control set point (4 Event
28 day timer) · Cl/ Br booster ORP and/or ppm feed
points with a separate trigger set points· Ozone ORP and/or ppm set points· Dechlorination ORP or ppm set point· Superchlorination ORP or ppm set point· Display of Ca hardness & alkalinity· Langelier & Ryznar index calculated· Smart menus w/ integrated help
O
PHYSICAL SPECIFICATIONS FLOWCELL
· PVC flowcell body· Threaded ports for sensors
and sample stream fittings· Clear acrylic viewing face· PVC ½” isolation ball valves· PVC ¼” wet test valve
FEED MODEAuto/Off/Manual, On/Off or Proportional·
BECSys7
Warranty - 5 year electronics and 2 year sensorsProduct Certifications - UL 508, (CSA) C22.2 Number 205 - M1983, FCC part 15 sub part B
Alliance Partner
EMATO CORP.
1605 McEwen Dr., Whitby, Ont., Can. L1N 7L4 Www.nemato.com [email protected]
Head Office1 (800) 361-5025Tel: (905) 571-5305Fax: (905) 571-3935
Rhode Island Office
Tel: (401) 667-7171Fax: (401) 667-7171
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Distributor
BECS BECSTECHNOLOGY
REMOTE OPERATIONS· PC direct connect · Data Modem· BECSys for Windows with
graphical display· BECSysRF Wireless
Communication Module monitor and control BECSys7 from remote location without phone lines or cables.
PHYSICAL SPECIFICATIONS CONTROLLER
· <1A 120 VAC fused input· Four outputs 3A powered solid state
relays for master alarm and pump control
· Five outputs 3A powered mechanical relays for backwash control
· Optional fifteen outputs 3A solid state and/or mechanical relays
· NEMA 4X polycarbonate (IP66) enclosure
ALARM INDICATORS· Flashing alarm LED· All specific alarms indicated with
auto scrolling on LCD· Hi/Low out of range, over feed and
low or no flow
DATA LOGGING Readings· Data logging of pH, ORP, Cl/Br ppm,
temperature, flow rate, conductivity, turbidity, pressure differential, vacuum, surge tank level, backwash holding tank level, chemical inventories
Events· Alarms, menu changes, operational
cycles· pH, ORP & ppm Hi /Low/interlocked
failsafe· Temperature & TDS Hi/Low/heater &
TDS failsafe· System Low flow & sample stream No
Flow· Turbidity, pressure differential &
vacuum Hi· Surge tank & backwash holding tank
Hi/Low· Auto fill & polymer feed failsafe· Chemical inventory· Backwash initiation, backwash cycle
duration, backwash valve time out alarm & failsafe
· Battery Low Feed Mode· Auto/Off/Manual, On/Off or
Proportional
SAFETY SYSTEMS·
o 3 levels: 6 Op, 2 Mgr, 1 Rep· Programmable alarms (some disabling
chemical feed)o pH, ORP, Cl/Br ppm, temp,
TDS, low flow & no flow, chemical overfeed, turbidity, pressure & vacuum, surge & holding tank levels, chemical inventory, backwash initiation & cycle duratio
Security passwords
FLOW SWITCH· Reed (standard)· Rotary w/ in-line check
valve (upgrade)
SENSORS· Potentiometric pH & ORP; inorganic
electrolyte· Temperature· Pressure gauge· Amperometric Free Chlorine w/replaceable
PTFE membrane & electrolyte (optional)· Conductivity (optional)· Turbidity (optional)· Flow meter & saddle (optional)· Two Pressure & One Vacuum; digital
(optional) or transducer (optional)· Surge tank & backwash tank level; proprietary
level sensor (optional) or 4 to 20 mA sensor (optional) or digital sensor (optional)
· Chemical Inventory; proprietary level & weight sensor (optional) or 4 to 20 mA sensor (optional) or digital sensor (optional)
July 06
EQUIPMENT ROOM CONTROL