bc woodworks 10 13.ppt · 23 • scl has the same char rate as timber & glulam • methodology...
TRANSCRIPT
![Page 1: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/1.jpg)
1
Copyright Materials
This presentation is protected by US and International
Copyright laws. Reproduction, distribution, display and
use of the presentation without written permission of the
speaker is prohibited.
© Boise Cascade 2013
![Page 2: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/2.jpg)
2
Canadian Wood Council, Wood WORKS! and the Wood Solutions Fair is a Registered Provider with The American Institute of Architects Continuing Education System; the Architectural Institute of British Columbia and the
Engineering Institute of Canada. Credit earned on completion of this program will be reported on behalf of members of each CES provider for those who complete
a participation form at the registration counter. Certificates of Completion for non-AIA, AIBC or EIC members are available on request.
This program is registered with the AIA/CES for continuing professional
education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing
in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
Program Education Credit Information
• Prefabricated Wood I-Joists
• BCI®, TJI®, LPI®
• Structural Composite Lumber (SCL)
• Laminated Veneer Lumber (LVL)
• VERSA-LAM®, Microllam®
• Parallel Strand Lumber (PSL)
• Laminated Strand Lumber (LSL)
![Page 3: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/3.jpg)
3
Other EWP Products
•Plywood
•Glue Laminated Timber (Glulam)
•Metal-Plate Wood Trusses
•Oriented Strand Board (OSB)
•Cross Laminated Timber (CLT)
![Page 4: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/4.jpg)
4
Knots and other defects
reduce resistance
Defects dispersed in EWP
Higher strengths obtained
![Page 5: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/5.jpg)
5
• Higher Specified Strengths
• Dimensional Stability
• Manufactured at low moisture content (6-8%)
• No shrinkage in the field if product kept dry
• Slight swelling to equilibrium
• Orthotropic material
• Shrink/swell ratios: Tangential, Radial, Longitudinal: 20-10-1
• Floor joist depth
• MC <= 12% for floor joists in mid-rise lower floors
![Page 6: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/6.jpg)
6
Recommended installation to account for lumber shrinkage
Not required for wood I-joists –shrinkage is typically not an issue
FPInnovations/CWC: Vertical Movement in Wood Platform Frame Structures
![Page 7: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/7.jpg)
7
Multiple Series & Depths for Various Applications within Residential / High Density / Light Commercial Construction
Proprietary Factored Resistance Values
![Page 8: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/8.jpg)
8
• Each manufacturer tests to establish equivalency to lumber joists
• Original APA testing of lumber joists (1950’s) – Current wood horizontal diaphragm tables in CWC Wood Design Manual and IBC
• Wood I-joist testing per ICC Acceptance Criteria (Full and small scale testing)
![Page 9: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/9.jpg)
9
Failure of
sheathing
Flange
thickness not
limiting factor
• Consult manufacturer for diaphragm values and limits
• Typical closest allowable nail spacing = 4”
Case 1 Diaphragm: Staggered Sheathing Perpendicular to Joist
Length
![Page 10: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/10.jpg)
10
• Staggered nailing at panel edges
Concentrated loads shall not bear directly on I-joists
![Page 11: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/11.jpg)
11
• Typical Rimboard Thickness
• 1 1/8” – 1 1/4” OSB
• 1 1/4” – 3 1/2” LVL / LSL
• Vertical load and lateral nail resistance for diaphragms
• Dimension lumber should never be used as rim board with wood I-Joists
![Page 12: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/12.jpg)
12
Proprietary Factored Resistance Values
• Closest allowable nail spacing
controls lateral design• Thicker rim = tighter allowable
spacing
![Page 13: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/13.jpg)
13
Options for increased lateral load transfer
• Uniform vertical load
resistance (typically 2500 lb/ft)
• Squash blocks
required under columns
• Wider flanges allow for additional nail
rows
![Page 14: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/14.jpg)
14
Laminated Veneer Lumber (LVL)
• Widths: 1 ¾”, 3 ½”, 5 ¼”, 7”
• Depths: Up to 24”
• Different grades possible depending upon mix of veneer
• High Specified Strengths• COV 10-15%
• 4800 – 6270 psi Bending, 1.7 – 2.0 x 106 psi MOE
![Page 15: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/15.jpg)
15
•Parallel Strand Lumber (PSL)
• Long strips of veneer glued together
• Developed in B.C. 70’s – early 80’s
•Laminated Strand Lumber (LSL)
• 12” long strands
•Oriented Strand Lumber (OSL)
• 3” – 6” long strands
SCL: Specified Strengths & MOEProduct Bending Shear MOE
Doug Fir
SS Grade
2830 220 1.7 x 106
24F-E DF
Glulam
4435 290 1.9 x 106
LSL 4300 575 1.3 – 1.6 x 106
PSL 5360 540 2.0 - 2.2 x 106
LVL 4800 -6280
530 – 580 1.7 – 2.0 x 106
![Page 16: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/16.jpg)
16
• Multiple 1 3/4” ply
beams must be connected properly
for load to be
distributed evenly
• Higher grade SCL
typically equivalent to DF in specific
gravity
![Page 17: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/17.jpg)
17
Wall Height
Blocking
Blocking
Top of Floor
• US Test Criteria: AC
202 (ICC-ES)
• Minimum nail spacing
requirements to ensure ductile failure
• EWP industry has
funded a test program
with cyclic testing at FPInnovations via
CCMC
![Page 18: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/18.jpg)
18
•Flame Spread
• Surface flammability
• Typically for exposed framing
•Fire Endurance• System resistance for assemblies
• Product char rate
• CAN/ULC S-101 Fire Tests (ASTM E119)
• Higher severity of fire exposure
Flame Spread Test – Steiner Tunnel
Fire Endurance –ULC S-101 ASTM E119
![Page 19: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/19.jpg)
19
• Floor/ceiling assembly based on CAN/ULC S-101 / ASTM E-119 fire test (45 min, 1 & 2
hour)
• Most common 1 hour assembly requires two
layers of fire-rated gypsum board
• Single gypsum layer assemblies require
additional fire resistance (mineral wool insulation, etc.)
![Page 20: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/20.jpg)
20
Time – Temperature Curve
• 5:00: 550 ○C
• 10:00: 700 ○C
• 15:00: 760 ○C
• 30:00: 820 ○C
• 60:00: 930 ○C
![Page 21: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/21.jpg)
21
• Certification defined in NBCC
• Assemblies listed by agency accredited by Standards Council of Canada (SCC)
• Example agencies:
• ULC®
• InterTek®
• APA – The Engineered Wood Association®
• PFS® Corporation
![Page 22: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/22.jpg)
22
Noise from footsteps
Noise from footsteps
Noise from televisions
and voices
Noise from televisions
and voicesNoise from stereos
Noise from stereos
Noise from phones
Noise from phones
• Sound Transmission Class (STC)
• Impact Insulation Class (IIC)
• Important Components
• Floor Covering
• Resilient Channels
![Page 23: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/23.jpg)
23
• SCL has the same char rate as timber & glulam
• Methodology prescribed in NBCC 2010 D-2.11.1 can
be applied to SCL
• Simple design procedure based on NRC research,
calculate endurance time of a wood member exposed
to standard fire based upon:
• the size of wood beam or column
• percent of maximum allowable design load
applied.
• More information – American Wood Council: TR10
• ASTM - American Society For Testing and
Materials, recognized in NBCC as non-Canadian accepted standard organization
• Members include industry, manufacturing, designers,
scientists, code officials.
• Provides qualification requirements
• Mandates independent third-party inspection, in-house
quality assurance, periodic re-evaluation.
![Page 24: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/24.jpg)
24
• Evaluation Services evaluate product based on testing standards provided by ASTM
• Canada: CCMC
• US: International Code Council (ICC)
• Allows proprietary product as an alternate in the code
Destructive
• Web stock
• Flange tension
• Full joist reaction
Non-Destructive
• Veneer stress wave grading
• Flange proof load
![Page 25: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/25.jpg)
25
I-Joist “Reaction”
20+ possible shear/reaction failure modes
Factored resistance determined empirically
Tension testing of glulam
lamination stock
![Page 26: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/26.jpg)
26
In grade, full scale
Glulam testing
Sizing Software
![Page 27: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/27.jpg)
27
• Manufacturers have product engineering support
staff to consult
• Product Technical Notes available from
manufacturers and testing agencies
• Product Warranties
![Page 28: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/28.jpg)
28
![Page 29: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/29.jpg)
29
![Page 30: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/30.jpg)
30
• Consult manufacturer for repairs
• Testing conducted to verify repairs for common field conditions
![Page 31: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/31.jpg)
31
Testing of common
field issues & repairs
• BC WoodWorks: http://www.wood-works.org/bc
• Canadian Wood Council: www.cwc.ca
• Wood I-Joist Manufactures Association (WIJMA): www.i-joist.org
• American Wood Council: www.awc.org
• APA – Engineered Wood Association: www.apawood.org
• US Forest Products Laboratory: www.fpl.fs.fed.us
![Page 32: BC WoodWorks 10 13.ppt · 23 • SCL has the same char rate as timber & glulam • Methodology prescribed in NBCC 2010 D-2.11.1 can be applied to SCL • Simple design procedure based](https://reader035.vdocuments.mx/reader035/viewer/2022062603/5f72bbda772e235f2a513821/html5/thumbnails/32.jpg)
32
This concludes the:
• American Institute of Architects
•Architectural Institute of British Columbia
• Engineering Institute of Canada
Continuing Education Systems Program
Engineered Wood Products:
Current Design Topics
Jeff Olson, P.E., [email protected]
.
Questions/ Comments?