battery cooler - cosmoteccosmotec.stulz.com/repository/1b497b61/battery_cooler_eng.pdf · stulz...

4
Stulz S.p.A. Cosmotec Industrial Cooling Via Torricelli, 3 37067 Valeggio sul Mincio (VR) Phone: +39 (045) 633 16 00 Fax: +39 (045) 633 16 35 [email protected] www.stulz.it

Upload: ngoquynh

Post on 26-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BATTERY COOLER - Cosmoteccosmotec.stulz.com/repository/1B497B61/Battery_Cooler_ENG.pdf · Stulz range of air conditioners fulfill the requirements of battery banks cooling : EVE04

Stulz S.p.A.Cosmotec Industrial CoolingVia Torricelli, 337067 Valeggio sul Mincio (VR)Phone: +39 (045) 633 16 00Fax: +39 (045) 633 16 35

[email protected] www.stulz.it

Page 2: BATTERY COOLER - Cosmoteccosmotec.stulz.com/repository/1B497B61/Battery_Cooler_ENG.pdf · Stulz range of air conditioners fulfill the requirements of battery banks cooling : EVE04

BATTERY COOLER

Page 3: BATTERY COOLER - Cosmoteccosmotec.stulz.com/repository/1B497B61/Battery_Cooler_ENG.pdf · Stulz range of air conditioners fulfill the requirements of battery banks cooling : EVE04

Stulz range of air conditioners fulfill the requirements of battery banks cooling :

EVE04 air conditioner for installation inside the cabinet

BATTERY COOLER

The best working temperature range for battery banks is around 25 °C; is very important to maintain the correct temperature for the battery banks, in fact, if the cabinet temperature goes too higher the batteries life could be shortened .

Batteries in telecom cabinets function as a backup in case of power failure and are essential to assure the continuity of the data flow.

In Telecom cabinets and electronic facility rooms are, however, present some devices which can work at higher temperature.

In this case the best solution is to separate the cabinet in two areas with a different temperature control: one area dedicated to the batteries and maintained the correct temperature and protect from dust , wind, etc.; whereas the other area can be maintened at higher temperature. In this way is possible to significantly reduce the energy consumption for cooling.

Furthermore, both EVE and EVO units are powered at 48VDC, like the battery banks, so there’s no need to have an inverter to transform the Direct current in Alternate Current, with considerably energy costs savings.

EVO04 air conditioner for installation outside the cabinet

Page 4: BATTERY COOLER - Cosmoteccosmotec.stulz.com/repository/1B497B61/Battery_Cooler_ENG.pdf · Stulz range of air conditioners fulfill the requirements of battery banks cooling : EVE04

EVE04

EVO04

• Powder painted steel plate• Alternative hermetic compressor including protection• Centrifugal condenser fan with thermic protection• Axial evaporator fan with thermic protection• Refrigerant R134a• Condenser coil in copper pipe and hydrophillic aluminium fins• Evaporator coil in copper pipe and aluminium fins• Refrigerant high pressure safety switches• Regulation electronic thermostat set at 25°C, regulation range 25-35°C, differential 2°C• Outputs: - high temperature alarm - low temperature alarm - high pressure alarm - probe malfunctioning alarm• Input: - remote enable

CODE EVE0400212

POWER SUPPLY V DC 48

COOLING CAPACITY L35L35 W 400

AIR FLOW mc/h 290

EXTERNAL OPERATING CONDITIONS °C +20 / +55

INTERNAL OPERATING CONDITIONS °C +25 / +35

NOISE LEVEL db(A) 65

DIMENSIONS (H X W X D) mm 634 / 308 / 221

CODE EVO0400212

POWER SUPPLY V DC 48

COOLING CAPACITY L35L35 W 400

AIR FLOW mc/h 290

EXTERNAL OPERATING CONDITIONS °C -20 / +55

INTERNAL OPERATING CONDITIONS °C +25 / +35

NOISE LEVEL db(A) 65

DIMENSIONS (H x W x D) mm 634 / 308 / 221

• Powder painted steel plate• Alternative hermetic compressor including protection• Centrifugal condenser fan with thermic protection• Axial evaporator fan with thermic protection• Refrigerant R134a• Condenser coil in copper pipe and hydrophillic aluminium fins• Evaporator coil in copper pipe and aluminium fins• Dehidrating filter and capillary tube • Refrigerant high pressure safety switches• Low temperature (ambient) device• Regulation mechanical thermostat set at 25°C, regulation range 25-35°C, differential 4°C