Condenser Compressor Discharge Service Valve Thermal Expansion Valve HT HP SHV HT HP S.M. HT HP SCL Legend HT HP SHV HT HP S.M. HT HP SCL The High Side

TRANSCRIPT

Page 1: BasicRefrigerationSystem 4 Component Flow Diagram

BasicBasicRefrigerationRefrigeration

SystemSystem

4 Component Flow 4 Component Flow DiagramDiagram

Page 2: BasicRefrigerationSystem 4 Component Flow Diagram

The High SideThe High Side

Page 3: BasicRefrigerationSystem 4 Component Flow Diagram

Condenser

Compressor

DischargeServiceValve

Thermal Expansion Valve

HT HP SHV

HT HP S.M.

HT HP SCL

Legend

HT HP SHV

HT HP S.M.

HT HP SCL

The High Side

Page 4: BasicRefrigerationSystem 4 Component Flow Diagram

The Low SideThe Low Side

Page 5: BasicRefrigerationSystem 4 Component Flow Diagram

Thermal Expansion Valve

Evaporator

TXV Bulb

Equalization Line

SuctionService Valve

Compressor

Flash Gas

Legend

LT LP S.M.

LT LP SHVThe Low Side

LT LP S.M.

LT LP SHV

Page 6: BasicRefrigerationSystem 4 Component Flow Diagram

The SystemThe System

Page 7: BasicRefrigerationSystem 4 Component Flow Diagram

High Side

AmbientAir

Low Side

ReturnAir

Supply Air

Conditioned Space

Page 8: BasicRefrigerationSystem 4 Component Flow Diagram

System System PressuresPressures

Page 9: BasicRefrigerationSystem 4 Component Flow Diagram

R-134a

You have a discharge Pressure of 182.00 PSIG. What do you know about the refrigerant?

Saturation Temp. = 124° F.

Page 10: BasicRefrigerationSystem 4 Component Flow Diagram

R-134a

You have a Discharge Pressure of 156.10 PSIG. You find a temperature on the high side of 120° F.

What do you know about the refrigerant?

Saturation Temp. = 114° F.

Temp. Taken in this area!

HT HP SHV Superheated by 6° F.

Page 11: BasicRefrigerationSystem 4 Component Flow Diagram

R-134a

You have a Discharge Pressure of 171.30 PSIG. You find a temperature on the high side of 110° F.

What do you know about the refrigerant?

Saturation Temp. = 120° F.

HT HP SCLSub-cooled by 10° F.

Temp. Taken in this area!

Page 12: BasicRefrigerationSystem 4 Component Flow Diagram

R-134a

You have a Suction Pressure of 5.50 PSIG. What do we know about the refrigerant leaving the TXV?

Saturation Temp. = -2° F.

LT LP S.M.

Page 13: BasicRefrigerationSystem 4 Component Flow Diagram

R-134a

You have a Suction Pressure of 5.50 PSIG. You find a temperature at the TXV Bulb of 5.0° F.

What do you know about the refrigerant?

Saturation Temp. = -2° F.

LT LP SHV Superheated by 7° F.