BACnet VAV Settings
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 1 of 14
INTRODUCTION
Learn how to setup Simens VAV settings
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 2 of 14
Step 1 — Enter Advanded Menu
ONLY AUTHORIZED MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU ANDMAKE CHANGES
Picture 1. Press Menu Button
Picture 2. Press Advanced to enter Advanced menu
Picture 3. Enter Admin Password Menu appears
Use the numbers to enter 4 digit factory preset pin. Number is being displayed in the blue ribbon
Press DEL button to delete incorrect number
Press OK to confirm input
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 3 of 14
Step 2 — Enter BACnet VAV Menu
Picture 1. Press BACnetVAV button to enter BACnet VAV menu
Picture 2. You entered BACnetVAV menu
Picture 2. Use Home button to return to Home Screen
Picture 2. Use Up button to return to Advanced Menu
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 4 of 14
Step 3 — BACnet VAV Menu
Press the number to enter BACnet VAV external controller ID you want to control
A single Codis device can control up to six BACnet VAV controllers
ID can be anywhere between 0 and 4194303, and should match the one previously set in theSiemens VAV controller
You should not have two same IDs in the same table
The communication between Codis and the BACnet VAV controller will not start until you set it toEnabled
If the setting is Disabled, the ID button looks empty, for better overview
Press Save to confirm changes and start the communcation
Press Settings for each VAV controller to see and control his status. You will enter a new screen,BACnet VAV Settings (picture 2)
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 5 of 14
Step 4 — Siemens or Belimo
Press Device Type button to select if the BACnet VAV device is either Siemens or Belimo
Depending on the choice, the Screens BACnet VAV 2 / 2 will change. Different options will beavailable for each device
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 6 of 14
Step 5 — Siemens 1 Settings - part 1
Actual / Nominal flow - READONLY - display the values of actualand nominal flow read from SiemensVAV controller
Actual flow
Nominal flow
Actual position - READ ONLY -displays the value of current positionof the VAV damper (can be from 0%to 100%)
Unit switch - WRITE ONLY (doesnot read value) - sets the units weuse, and converts the valuesimmediately.
Must press Save button to send toVAV controller
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 7 of 14
Step 6 — Siemens 1 Settings - part 2
Min Flow Vmin - WRITE ONLY -sets the minimum flow VAVcontroller will will allow through thedamper. Value is shown inABSOLUTE value in the unitselected (e.g. m3/h), NOTPRECENTAGE
Max Flow Vmin - WRITE ONLY -sets the maximum flow VAVcontroller will allow through thedamper. Value is shown inABSOLUTE value in the unitselected (e.g. m3/h), NOTPRECENTAGE
Use + and - buttons to change thevalues. Press the number forkeyboard input of the values
Press Save to send these settingsto the VAV device
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 8 of 14
Step 7 — Siemens 2 settings - part 1
Override control - WRITE ONLY -sets the VAV controller to one offollowing states: Open (100% inabsolute position), Close (0% inabsolute position), Go To Min (0%in adapt position), Go To Max(100% in adapt position), Stop (oncurrent position). Default setting fornormal work should be Off
Opening direction - WRITE ONLY -direction in which the VAV controllerdamper moves. Can be Normal CW(Clockwise) or Inverted CCW(Counter-clockwise). Installersshould set this value so that whenVAV is open it corresponds to 100%and when closed it corresponds to0%
Positioning - WRITE ONLY - canbe Abs Position (Absolute position)and Adapt Position (adapt)
Absolute position shows thecurrent value
Adapt position searches for theminimum and maximumreachable position and proclaimsthose positions 0% or 100%
Bus termination - WRITE ONLY -can be Off or On
Press Save to confirm changes andset to VAV controller
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 9 of 14
Step 8 — Siemens 2 settings - part 2
Device Jammed - READ ONLY -shows the state of damper. If thereis a block in the damper preventing itto reach the desired position errorhere will appear
Yes - if there is a blockage in thedamper trying to do so. If theblockage is on purpose orunaviodable, we recommendputting the Positioning value toAdapt position to aovid gettingthe error
No - no error
Pressure sensor state - READONLY - shows the state of thesensor reading the pressure - theflow - in the VAV controller. Valuecan be:
No Error - everything is okay
Wrong Connect - the tubes forpressure sensing are eitherdisconnected or oppositlyconnected. We recommendchecking the connection
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 10 of 14
Step 9 — Belimo 1 Settings - part 1
Actual / Nominal flow - READONLY - display the values of actualand nominal flow read from SiemensVAV controller
Actual flow
Nominal flow
Actual position - READ ONLY -displays the value of current positionof the VAV damper (can be from 0%to 100%)
Unit switch - WRITE ONLY (doesnot read value) - sets the units weuse, and converts the valuesimmediately.
Must press Save button to send toVAV controller
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 11 of 14
Step 10 — Belimo 1 Settings - part 2
Min Flow Vmin - WRITE ONLY -sets the minimum flow VAVcontroller will will allow through thedamper. Value is shown inABSOLUTE value in the unitselected (e.g. m3/h), NOTPRECENTAGE
Max Flow Vmax - WRITE ONLY -sets the maximum flow VAVcontroller will allow through thedamper. Value is shown inABSOLUTE value in the unitselected (e.g. m3/h), NOTPRECENTAGE
Use + and - buttons to change thevalues. Press the number forkeyboard input of the values
Press Save to send these settingsto the VAV device
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 12 of 14
Step 11 — Belimo 2 settings - part 1
Override control - WRITE ONLY -sets the VAV controller to one offollowing states: Open (100% inabsolute position), Close (0% inabsolute position), Min Vmin (reachminimum flow), Mid Vmid (half ofVmin and Vmax), Max Vmax (reachmaximum flow). Default setting fornormal work should be None
Control Source - READ ONLY -reads from Belimo device what isthe source of Setpoint. Must read"BUS"
Actuator command - WRITE ONLY- can be None, Adaptation, Test,Reset
Bus termination - READ ONLY -can be Off or On.
Press Save to confirm changes andset to VAV controller
BACnet VAV Settings Draft: 2018-12-03Guide ID: 158 -
This document was generated on 2019-10-04 05:54:32 AM (MST).
© 2019 products.koer.com/ Page 13 of 14
Step 12 — Belimo 2 settings - part 2
Device Status - READ ONLY -shows the state of device. If there isa block in the damper preventing itto reach the desired position errorhere will appear
Error or No Error
Actuator Status - READ ONLY -Error message if Device Status is inError
No Error - everything works ok
Act. jam - Actuator cannot move
Gear fault - Gear disengaged. Nomovement
Travel inc - Mechanical travelincreased.