b l u e r i d g e relay panel 32 basic t e c h n o l o g i e...
TRANSCRIPT
B l u e R i d g eT e c h n o l o g i e s
Data Sheet : Catalog Page 20
Project Part Number Ref.
Relay Panel 32 Basic
OverviewRelay Panel Basic (RP Basic) is a UL Listed lighting control panel. RP Basic may be scheduled from any BACnet BAS and is compatible with all low voltage switches, occupancy sensors, and light level sensors. RP Basic mounts near the circuit breaker panel to provide centralized control of branch lighting circuits. Relay Panel 32 Basic (RP32 Basic) features up to 32 Lighting Tough Relays (LTR) in a black powder coated steel enclosure with a hinged reversible door.
Features UL ListedBACnet MS/TP communication to BAS networkLine and low voltage compartment separationUpgradable Controller Board firmwareAvailable options: • Low/Line Voltage Bays• Multi-pole Lighting Contactors• 24VAC Auxiliary Transformer• 24VDC Power Supply• BACnet IP Router• UL924 Emergency Bypass• 347VAC Transformer
General SpecificationsConstruction: 16ga steel with black powder coat finish Dimensions:
Enclosure: 25.00”(635mm)H x 18.00”(457mm)W x 5.75”(146mm)DDoor Surface Mount: 25.25”(641mm)H x 18.08”(459mm)WDoor Recessed (Flush): 26.50”(673mm)H x 19.58”(497mm)W
Weight: 47.5lbs(21.5kg)Mounting: Surface or recess mountedOperating Environment: 32-125°F (0-50°C), 20-95%RH, non-condensing, Type 1 (dry / indoor environment)
CertificationsUL Listed, UL916 Standard for Energy Management Equipment, US/CanadaFCC Part 15CEC Title 24 Electronics meet or exceed IEC Level 3
WarrantyTwo (2) year limited manufacturer warranty from date of shipment (extended warranty optional).
Firmware Specifications (Controller Board)Platform: Aperio Open Control Platform Time Clock: Real-time clock with BACnet time syncSchedule: BACnet Schedule, Monday – Sunday, Holidays, and ExceptionsNon-Volatile Memory: 16MB total, 2MB for trend data (15min trend requires 2K per day)RAM: 2MB total, data stored in non-volatile memory upon power loss Configuration: Tech Kit 2.0 (see data sheet for details)Configuration Connection: Micro-B USB or Bluetooth Wireless
Low Voltage Specifications (Controller Board)Power In: 24VAC +/-10%, 30VA, 50-60 Hz Auxiliary Out: 24VAC, 800mA (devices with full wave rectified power supply only)Universal Input (UI) Power Out: 24VDC, 200mA totalUniversal Input: 24 two-wire inputs Universal Input Software Configuration:
Digital Input (DI)Analog Input (AI): 0-5VDC, 0-10VDC, or 4-20mA
Universal Input Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / 500’(152m)
BAS Network SpecificationsProtocol: BACnet MS/TPBaud Rate: DIP switch selectable 9.6K, 19.2K, 38.4K, 76.8K, or 115.2KDevice Profile: BACnet Advance Application Controller (AAC)Address Range: 1 – 99 selectable with rotary dialsUnit Load: 1/8 unit loadTopology: RS-485, half duplex, daisy chain wiringWire Requirement / Maximum Length: CL3P, 22AWG, 2 conductor, shielded, low cap / 4000’(1216m)Points: See PIC Statement
Transformer SpecificationsType: 30VA Inherently LimitedPrimary: Dual Tap 120 or 277VAC +/-10%, 30VA, 50-60 HzSecondary: 24VAC +/-10% Inherently LimitedWire Requirement: 18AWG Minimum (Solid or Stranded)
LTR SpecificationsType:
UL ListedSPST latching with manual override leverElectrically operated mechanically held, pulse drivenShort Circuit Current Rating (SCCR) 30,000A @ 277 VAC
Maximum Ratings: Tungsten 20A @ 347VAC / Ballast 30A @ 347VAC / Resistive 20A @ 347VAC / 1.5HP @ 120VACLoad Terminal: Universal screw terminal, box type clamp Terminal Capacity (per side): (2) 14-10AWG or (1) 8AWG (Solid or Stranded copper wire)
Optional Equipment SpecificationsSee Relay Panel Optional Equipment Data Sheet
Data Sheet : Catalog Page 21
www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2014 Blue Ridge Technologies International, LLC All Rights Reserved. RP32Basic-DS-V14.05
Relay Panel 32 Basic
General Architecture
BAS Router
Relay Panel (RP)
Internet
Field DevicesField Devices Field Devices Field Devices
Retrofit Interior (RI) Retrofit Kit (RK)
IP
BACnet MS/TP
LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)
LVS OCC LS
Field Devices
Zone Control (ZC)
General Architecture
BAS Router
Internet
Field DevicesField Devices Field Devices Field Devices
Retrofit Interior (RI) Retrofit Kit (RK)
IP
BACnet MS/TP
LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)
LVS OCC LS
Field Devices
Zone Control (ZC) Relay Panel (RP)
General Architecture
BAS Router
Internet
Field DevicesField Devices Field Devices Field Devices
Retrofit Interior (RI) Retrofit Kit (RK)
IP
BACnet MS/TP
LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)
LVS OCC LS
Field Devices
Zone Control (ZC) Relay Panel (RP)
General Architecture
BAS Router
Internet
Field DevicesField Devices Field Devices Field Devices
Retrofit Interior (RI) Retrofit Kit (RK)
IP
BACnet MS/TP
LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)
LVS OCC LS
Field Devices
Zone Control (ZC) Relay Panel (RP)
* See Price List for Recessed (Flush) door panels.
Line Voltage Bay Options with Dead Front Cover (Top of Panel)
XX = Blank None
H1 9” Bay
HA 9” Bay + (1) 4 Pole 30A Electrically Held Lighting Contactor, 120V Coil
HB 9” Bay + (2) 4 Pole 30A Electrically Held Lighting Contactor, 120V Coil
HC 9” Bay + (4) 4 Pole 30A Electrically Held Lighting Contactor, 120V Coil
HD 9” Bay + (1) 4 Pole 30A Electrically Held Lighting Contactor, 277V Coil
HE 9” Bay + (2) 4 Pole 30A Electrically Held Lighting Contactor, 277V Coil
HF 9” Bay + (4) 4 Pole 30A Electrically Held Lighting Contactor, 277V Coil
Low Voltage Bay Options (Bottom of Panel)
XX = Blank None
L1 9” Bay
LA 9” Bay + (1) 2.5A 24VDC Power Supply
LB 9” Bay + (2) 2.5A 24VDC Power Supply
LC 9” Bay + (1) BACnet IP Router
LD 9” Bay + (1) BACnet IP Router + (1) 2.5A 24VDC Power Supply
LE 9” Bay + (1) BACnet IP Router + (2) 2.5A 24VDC Power Supply
Power Options
X = 0 120 / 277VAC Transformer
1 347VAC Transformer
2 120 / 277VAC Transformer + 120 / 277VAC Auxiliary Transformer
3 347VAC Transformer + 347VAC Auxiliary Transformer
Special Options
XX = 00 None
X1 UL924 Emergency Bypass (Relays 17-32 only)
Quantity of Relays Installed
XX = 01 thru 32 Up to 32 Relays Installed
Ordering Information*RPSB32 - XX - X - XX - XX - XX
Transformer Terminations Transformer Terminations
120VAC Black
Neutral WhiteEarth Ground
277VAC Brown
347 Transformer Terminations
Neutral BlackEarth Ground
H2
H1
347VAC Brown
Earth Ground
208V Red
120V White
Neutral Black
277V Brown240V Orange
LTR Terminations
Line In
Relay Output
Wire Strip Length IndicatorManual Override Lever
Relay Terminations
PT3 Terminations
RE
DB
LUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Original RR8*, RR9, 2R9, or HDR5P Relay / Wiring*The yellow wire (RIB connector Pin 2) is capped when using RR8 relays.
Pin 1Pin 2Pin 3Pin 4Pin 5
Original RR7 or 2R7 Relay / WiringPT3
RIB Connector IDC
IDC
PT5 Terminations
PT5
RIB Connector
Pin 1Pin 2Pin 3Pin 4Pin 5
Pin 1Pin 2
Yellow
BlackRedBlue
Yellow*
BlackRedBlue
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
RO 1 RO 2
Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 17 RO 18
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
RO 2
RO 1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 18
RO 17Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16RO 1
RO 2
RO 17
RO 181
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
Relays 17-32
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
16-20pinRibbon Cable
20pinRibbon Cable
20pinRibbon Cable
16pinRibbon Cable
Controller Board Terminations
16-20pinRibbon Cable
ExistingRibbon Cable
16-20pinRibbon Cable
ExistingRibbon Cable Relays 1-32
Relays 33-64
UI (Universal Input) / GND (Ground) / RO (Relay Output)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output)
Power LEDRun LED
Power Switch
Controller Board Terminations
UI (
Uni
vers
al In
put)
/ GN
D (G
roun
d)
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
Relays 1-32
Relays 33-64
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
Transformer Terminations Transformer Terminations
120VAC Black
Neutral WhiteEarth Ground
277VAC Brown
347 Transformer Terminations
Neutral BlackEarth Ground
H2
H1
347VAC Brown
Earth Ground
208V Red
120V White
Neutral Black
277V Brown240V Orange
LTR Terminations
Line In
Relay Output
Wire Strip Length IndicatorManual Override Lever
Relay Terminations
PT3 Terminations
RE
DB
LUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Original RR8*, RR9, 2R9, or HDR5P Relay / Wiring*The yellow wire (RIB connector Pin 2) is capped when using RR8 relays.
Pin 1Pin 2Pin 3Pin 4Pin 5
Original RR7 or 2R7 Relay / WiringPT3
RIB Connector IDC
IDC
PT5 Terminations
PT5
RIB Connector
Pin 1Pin 2Pin 3Pin 4Pin 5
Pin 1Pin 2
Yellow
BlackRedBlue
Yellow*
BlackRedBlue
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
RO 1 RO 2
Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 17 RO 18
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
RO 2
RO 1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 18
RO 17Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16RO 1
RO 2
RO 17
RO 181
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
Relays 17-32
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
16-20pinRibbon Cable
20pinRibbon Cable
20pinRibbon Cable
16pinRibbon Cable
Controller Board Terminations
16-20pinRibbon Cable
ExistingRibbon Cable
16-20pinRibbon Cable
ExistingRibbon Cable Relays 1-32
Relays 33-64
UI (Universal Input) / GND (Ground) / RO (Relay Output)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output)
Power LEDRun LED
Power Switch
Controller Board Terminations
UI (
Uni
vers
al In
put)
/ GN
D (G
roun
d)
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
Relays 1-32
Relays 33-64
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
Transformer Terminations Transformer Terminations
120VAC Black
Neutral WhiteEarth Ground
277VAC Brown
347 Transformer Terminations
Neutral BlackEarth Ground
H2
H1
347VAC Brown
Earth Ground
208V Red
120V White
Neutral Black
277V Brown240V Orange
LTR Terminations
Line In
Relay Output
Wire Strip Length IndicatorManual Override Lever
Relay Terminations
PT3 Terminations
RE
DB
LUE
OFF
Original WR-6(XXX) Relay / WiringRIB Terminal Block
Red
Blue
Original RR8*, RR9, 2R9, or HDR5P Relay / Wiring*The yellow wire (RIB connector Pin 2) is capped when using RR8 relays.
Pin 1Pin 2Pin 3Pin 4Pin 5
Original RR7 or 2R7 Relay / WiringPT3
RIB Connector IDC
IDC
PT5 Terminations
PT5
RIB Connector
Pin 1Pin 2Pin 3Pin 4Pin 5
Pin 1Pin 2
Yellow
BlackRedBlue
Yellow*
BlackRedBlue
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
RO 1 RO 2
Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 17 RO 18
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16
RO 2
RO 1
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
RO 18
RO 17Relays 17-32
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
1
Controller Board Terminations RIB-A Terminations RIB-B Terminations
Relays 1-16RO 1
RO 2
RO 17
RO 181
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
CN
2
Relays 17-32
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
RIB-A / RIB-BRelays 33-64
16-20pinRibbon Cable
20pinRibbon Cable
20pinRibbon Cable
16pinRibbon Cable
Controller Board Terminations
16-20pinRibbon Cable
ExistingRibbon Cable
16-20pinRibbon Cable
ExistingRibbon Cable Relays 1-32
Relays 33-64
UI (Universal Input) / GND (Ground) / RO (Relay Output)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output) / IDC (Insulation Displacement Connector)
UI (Universal Input) / GND (Ground) / RO (Relay Output)
Power LEDRun LED
Power Switch
Controller Board Terminations
UI (
Uni
vers
al In
put)
/ GN
D (G
roun
d)
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
24VAC Power In
24VAC Auxiliary Out
Relays 1-32
Relays 33-64
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
Power LEDRun LED
Power Switch
SW3
J3J1
1’s10’s
TEST
RELAY 33-64
LEXP
Bluetooth
SN
/DD
N
Term
OU
TIN
RELAY 1-32
1
ON
2 3 4 5 6 7 8
Bluetooth Plug
UI 1UI 2
24VDCGNDUI 3UI 4
24VDCGNDUI 5UI 6
24VDCGNDUI 7UI 8
24VDCGNDUI 9
UI 1024VDC
GND
UI 1
7U
I 18
24VD
CG
ND
UI 1
9U
I 20
24VD
CG
ND
UI 2
1U
I 22
24VD
CG
ND
UI 2
3U
I 24
24VD
CG
ND
5VD
CG
ND
UI 11UI 12
24VDCGNDUI 13UI 14
24VDCGNDUI 15UI 16
24VDCGND
BT485 Terminator Plug(if applicable)
Shield In/OutBACnet(-) In/OutBACnet(+) In/Out
Baud Rate Dip Switch Network Address Rotary Switch 10’sNetwork Address Rotary Switch 1’s
Test Button
PWR
PWR SW
RUN
0 1 2 3 4 5 6 7 8
9 0 1 2 3 4 5 6 7 8
9Micro-B USB Port
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S
CO
MM
BN+ BN- S