authority for electricity regulation, oman electric …summer).pdf · the authority for electricity...
TRANSCRIPT
Electromagnetic Field Measurements
Authority for Electricity Regulation, Oman
Electric and Magnetic Field Measurements- summer
measurements
September 2009
Electromagnetic Field Measurements
2 | P a g e
Sultan Qaboos University
College of Engineering Department of Electrical & Computer Engineering
ELECTROMAGNETIC FIELD MEASUREMENTS
A Consultancy Project For the
September 2009
Authority for Electricity Regulation: Eng. Ibrahim Al-Harthi ([email protected]) : Eng. Hilal Al Ghaithi ([email protected]) SQU Team: Principal Investigator: Dr. Abdullah Al-Badi [email protected] Co-Investigator: Dr. Amer Al-Hinai and Engr. Salem Al-Hinai
[email protected] and [email protected]
Department of Electrical & Computer Engineering College of Engineering, Sultan Qaboos University P.O. 33, Al-Khod, Muscat-123 Sultanate of Oman Tel: +968-24141324 GSM: +968-99217654 Fax: +968-24413454
Electromagnetic Field Measurements
3 | P a g e
Table of Contents
Executive Summary ........................................................................................................................................... 4 1. Introduction ................................................................................................................................................ 7 2. STANDARDS ............................................................................................................................................ 7 3. Results of The Measurements ................................................................................................................. 7
3.1 Location 1 – Customer 1 .................................................................................................................. 8 3.2 Location 2 – Customer 2 ................................................................................................................ 10 3.3 Location 3 – Customer 3 ................................................................................................................ 12 3.4 Location 4 – Bid- Bid ...................................................................................................................... 15 3.5 Location 5 – Fanja .......................................................................................................................... 18 3.6 Location 6 – Al Farfarh ................................................................................................................... 21 3.7 Location 7 – Royal Camp Suwiaq ................................................................................................. 22 3.8 Location 8 – Royal Camp Sohar ................................................................................................... 24 3.9 Location 9 – Royal Camp Buryami ................................................................................................ 26 3.10 Location 10 – LDC-SQU (Mawalleh) ............................................................................................. 28 3.11 Location 11 – (M-Grid) Al Khoud ................................................................................................... 30 3.12 Location 12– Customer 4 ............................................................................................................... 33 3.13 Location 13– Al Gubrah ................................................................................................................. 35 3.14 Location 14– MSQ grid station ...................................................................................................... 38 3.15 Location 15– MSQ 220 kV ............................................................................................................. 42 3.16 Location 16 – Wadi Adai ................................................................................................................ 43 3.17 Location 17– Al Qurm primary ....................................................................................................... 52 3.18 Location 18– Al Qurm .................................................................................................................... 57 3.19 Location 19– Al Amerate area, near Al Shabiah ......................................................................... 60 3.20 Location 20– Customer 5 .............................................................................................................. 63
4 Results compared to winter measurements and ICNIRP standards ................................................... 66 5 Conclusions ............................................................................................................................................. 69 6 References .............................................................................................................................................. 70 Appendix A Measurement Devices ................................................................................................................. 71 Appendix B Calibration Certificates ................................................................................................................. 72
Electromagnetic Field Measurements
4 | P a g e
EXECUTIVE SUMMARY
The Authority for Electricity Regulation, Oman commissioned a study for the introduction of electromagnetic field regulation for the Sultanate of Oman. As part of the study, electric and magnetic field measurements at specified locations had been performed by KEMA. The measurements were performed in several high voltage environments which included different types of electricity infrastructure (including overhead lines, underground cables, and substations).
The original measurements performed by KEMA were done during the winter period which is the off peak period for the electricity system in the Sultanate of Oman. In the “KEMA measurements report” it was recommended that the measurements be repeated in the summer peak season when loads are highest.
The Authority commissioned Sultan Qaboos University to repeat the measurements of electric and magnetic fields for the same locations following the same profile. SQU performed the measurements during the period from 10 to 19 August 2009. The measurements were taken around 3 PM (from 2 PM to 5 PM) to capture the peak loads. This report should be read and interpreted in conjunction with the KEMA measurements report. There was an expected increase in the measured values of the magnetic fields when compared to the winter measurement values because of the differences in the current magnitudes. However, since the electric field is related mainly to the voltage of the transmission and distribution lines small differences in the electric field values were found between the two measurement reports.
To facilitate comparison between the two measurements, similar profiles were taken and the locations are presented using the same sequence used in KEMA measurement report.
The reference values chosen for these measurements are the values recommended by the international Commission on Non-Ionizing Radiation Protection (ICNIRP), see Table A. These values are supported by the World Health Organization (WHO)
Table A: ICNIRP Standards ICNIRP levels for 50 Hz Electic field strength (V/m) Magnetic flux density (µT) General public 5000 100 Occupational exposure 10000 500
The measured values for the electric and magnetic field strength were compared to the ICNIRP standards for both General Public Exposure (for locations accessible by Public) and Occupational exposure (operational location where no public access is allowed)
Figures A and B present a summary of the maximum measured values for electric and magnetic fields in Public locations for both winter and summer measurements referenced against the Public exposure limits of ICNIRP
Electromagnetic Field Measurements
5 | P a g e
0
20
40
60
80
100
Ham
oud
Al-J
abri
Ras
hid
Al-B
alus
hi
Ray
a Al
-Kha
rusi
Bid-
Bid
Fanj
a
Al-F
arfa
rh
Roy
al C
am S
uwia
q
Roy
al C
amp
Soha
r
Roy
al C
am B
urya
mi
LDC
-SQ
U (M
awal
leh)
(M-G
rid) A
l-Kho
ud
Shei
ka
Al-G
uhbr
ah
MSQ
grid
sta
tion
MSQ
220
kV
Al-Q
urm
Al-A
mer
at a
rea
Abdu
llah
Al-Z
akw
ani
Stre
ngth
of M
easu
red
Mag
natic
Fie
ld (µ
T)
Locations of Measurements
Maximum magnatic field values vs ICNIRP reference value for Genral Public exposure (100 µT)
Summer Measurements
Winter Measurements
ICNIRP Standard (100 uT
Figure A: summary of the maximum measured values for magnetic fields referenced against General Public exposure limits of the ICNIRP
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Ham
oud
Al-J
abri
Rash
id A
l-Bal
ushi
Ray
a Al
-Kha
rusi
Bid-
Bid
Fanj
a
Al-F
arfa
rh
Roy
al C
am S
uwia
q
Roy
al C
amp
Soh
ar
Roya
l Cam
Bur
yam
i
LDC
-SQ
U (M
awal
leh)
(M-G
rid) A
l-Kho
ud
She
ika
Al-G
uhbr
ah
MS
Q g
rid s
tatio
n
MSQ
220
kV
Al-Q
urm
Al-A
mer
at a
rea
Abdu
llah
Al-Z
akw
ani
Stre
ngth
of M
easu
red
Elec
tric
Fie
ld S
teng
th (V
/m)
Locations of Measurements
Maximum Electric field values vs ICNIRP reference value for for Genral Public exposure (5000 V/m)
Summer Measurements
Winter Measurements
ICNIRP Standard (10000 V/m)
Figure B: summary of the maximum measured values for electric fields referenced against General Public exposure limits of the ICNIRP
Electromagnetic Field Measurements
6 | P a g e
Figures C and D present a summary of the maximum measured values for electric and magnetic fields in operational location for both winter and summer measurements referenced against the Occupational exposure limits of the ICNIRP
Figure C: summary of the maximum measured values for magnetic fields referenced against the Occupational exposure limits of the ICNIRP
Figure D: summary of the maximum measured values for electric fields referenced against the Occupational exposure limits of the ICNIRP
From the measurement results for magnetic and electric fields taken during summer time, it can be concluded that:
a) the levels of the electric and magnetic fields on general public are lower than the permissible limit recommended by the International Commission on Non-Ionizing Radiation Protection (ICNIRP);
b) the levels of electric and magnetic fields to which electricity industry employees could be exposed to are below the permissible limits recommended by the ICNIRP.
Electromagnetic Field Measurements
7 | P a g e
1. INTRODUCTION
The Authority for Electricity Regulation, Oman commissioned a study for the introduction of electromagnetic field regulation for the Sultanate of Oman. As part of the study, electric and magnetic field measurements at specified locations had been performed by KEMA. The measurements were performed in several high voltage environments which included different types of electricity infrastructure (including overhead lines, underground cables, and substation) The original measurements performed by KEMA were taken during the winter period which is the off peak period for the electricity system in the Sultanate of Oman. In the “KEMA measurements report” it was recommended that the measurements be repeated in the summer peak season when loads are highest. SQU has conducted several studies on the effect of electromagnetic fields on humans as well as on pipelines [7-10]. SQU has both qualified personnel capable of conducting the required measurements as well as has calibrated standard electromagnetic field measurement equipment. The Authority commissioned Sultan Qaboos University to repeat the measurements of electric and magnetic fields for the same locations as those in the KEMA study. SQU performed the measurements during the period from 10 to 19 August 2009. The measurements were taken around 3 PM (from 2 PM to 5 PM) to capture the peak loads. This report should be read and interpreted in conjunction with the KEMA measurements report
2. STANDARDS
Different existing standards such as Institute of Electrical and Electronics Engineers (IEEE) [11], Australian [12] and International Commission on Non-Ionizing Radiation Protection (ICNIRP) [13] which specify the maximum permissible exposure values for electomagnetic field for Occupational exposure and exposure to General public. The ICNIRP standards (See Table 1. Reference standards for 50 Hz frequency) were used as reference in the KEMA measurement report.
Table 1: ICNIRP Reference Standards for 50 Hz
Electric field strength (V/m) Magnetic flux density (µT)
General public 5000 100
Occupational exposure 10000 500
3. RESULTS OF THE MEASUREMENTS
Locations of the Measurements Table 2 shows the meaurement locations, the sources of the electromagnetic fields, and the day and time of the measurements.. The locations are presented in the same chronological order as the KEMA measurements report. All measurements were taken at 1 m height above ground level. The specified profiles used by KEMA were followed during the measurement.
Electromagnetic Field Measurements
8 | P a g e
Table 2: Measurement locations and source of electromagnetic field Day Location Sources Date & Time
# Name/description 1 1 Customer 1 11kV, 415V Monday 10th August (3-5)pm
2 Customer 2 11kV cable 3 Customer 3 Substation
2 4 Bid-Bid 132kV Monday 17th August (3-5)pm
5 Fanja 11kV, 415V 6 Al Farfarh 33kV
3 7 Royal Camp Suwiaq 220kV, 132kV, 11kV Saturday 15th August (3-3:45)pm
8 Royal Camp Sohar 220kV Saturday 15th August (4:30-5:15)pm
4 9 Royal Camp Buryami 132kV Sunday 16th August (2-3)pm
5 10 LDC-SQU (Mawalleh) 132kV, 33kV Wednesday 19th August (3-5)pm
11 (M-Grid) Al Khoud 132kV, 33kV, 11kV, 415V, cables
12 Customer 4 11kV, substation 6 13 Al Guhbrah 132kV, 33kV Wednesday 12th August (3-5)pm
14 MSQ grid station Transformers, cables 15 MSQ 220kV 220kV
7 16 Wadi ADI, 220KV grid station
220kV, transformers, cables
Tuesday 18th August (3-5)pm
17 Al Qurm primary 33kV & 11kV, transformers, cables
18 Al Qurm Cables 33kV & 11kV 8 19 Al Amerat area 33 kV Tuesday 11th August (3-5)pm
20 Customer 5 11kV, transformer
3.1 Location 1 – Customer 1
Table 3 shows the current per phase in 11 kV overhead lines before and after the transformer feeder, the
current through 415 V service lines are also presented.
Table 3: Measured Currents
Blue [A] Yellow [A] Red [A] Neutral [A]
11 kV-1 212 225 209 -
11 kV- 2 178 188.5 189 -
415 V -1 134.3 196 206 82
415 V- 1 47.5 27.8 45.6 22.6
Electromagnetic Field Measurements
9 | P a g e
Figure 1: Schematic overview of location 1
The profiles for the electric fields were the same as the previous report, where as substantial differences
were obtained in the magnetic field profiles due to the differences in the currents that flow through the
different circuits. The maximum value of measured magnetic field is 2.3 µT. This value was obtained at the
beginning of profile 1 near the fence of the neighbor. The profiles of magnetic fields are presented in the
Figures 2 to 4.
0
0.5
1
1.5
2
2.5
0 10 20 30 40 50 60
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 2: Profile 1, magnetic field
Profile 1
Profile 2
Profile 3 Profile
3
11kV 415 V
Measurement profile415 V cable
12m
10m
2m
15m 20m
Electromagnetic Field Measurements
10 | P a g e
0
0.1
0.2
0.3
0.4
0.5
0.6
0 5 10 15 20
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 3: Profile 2, magnetic field
0
0.2
0.4
0.6
0.8
1
1.2
0 5 10 15 20 25
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 4: Profile 3, magnetic field
3.2 Location 2 – Customer 2
Table 4 shows the current per phase in 11 kV overhead line and the current through 415 V service lines
Table 4: Measured Currents
Blue [A] Yellow [A] Red [A] Neutral [A]
11 kV 225 233 233 -
415V 34.8 16 49.3 31.7
Electromagnetic Field Measurements
11 | P a g e
Figure 5: Schematic overview of location 2
The profiles for the electric fields were the same as the previous report; the two profiles of magnetic fields are
presented in Figures 6 and 7. The maximum value of the measured magnetic field is 0.125 µT along profile
1 near the house fuse box.
0
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0 5 10 15 20 25
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 6: Profile 1, magnetic field
Profile 1 Profile 2
11kV cable415 VMeasurement profile
Fuse box
0.5m
2m
Electromagnetic Field Measurements
12 | P a g e
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
0 1 2 3 4 5 6 7 8
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 7: Profile 2, magnetic field
3.3 Location 3 – Customer 3
The measurement profiles and the spot measurement for the electric fields are the same as the results
presented in the KEMA report. The maximum value of the magnetic field that was measured is 135 µT. This
value was measured inside the substation (Spot number 4) between the switch box and the transformer. The
maximum measured value of the magnetic field outside the substation was 16.1 µT along profile 2 near the
switch box. The maximum measured value near the fence of the house (along profile 1) is 6 µT. The
magnetic field profiles are shown in Figures 9 to 13.
Profile 2
Pro
file
1
Pro
file
4
Prof
ile 3
Transformer
Switch Box
0.25m
5m
Spot 6
Spot 5
Spot 4 Spot 1
Spot 3
Spot 7 Spot 2
Figure 8: Schematic overview of location 3
Electromagnetic Field Measurements
13 | P a g e
0
1
2
3
4
5
6
7
0 5 10 15 20
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 9: Profile 1, magnetic field
0
2
4
6
8
10
12
14
16
18
0 1 2 3 4 5 6
Mag
netic
Fie
ld (u
T)
Distance (m
Figure 10: Profile 2, magnetic field
Electromagnetic Field Measurements
14 | P a g e
Figure 11: Profile 3, magnetic field
0
0.5
1
1.5
2
2.5
3
0 5 10 15 20 25
Mag
netic
Fie
ld (u
T)
Distance (m)
Figure 12: Profile 4, magnetic field
Electromagnetic Field Measurements
15 | P a g e
0
20
40
60
80
100
120
0 1 2 3 4 5 6 7 8
Mag
netic
Fie
ld (u
T)
Spot Number
Figure 13: Spot measurement, magnetic field
3.4 Location 4 – Bid- Bid
The magnetic and electric field profiles are depicted in Figures 15 to 20, it should be noted that the direction
of the profiles during the measurements were taken opposite to what is given in KEMA report. The
maximum values of the measured electric and magnetic fields are 0.6 kV/m and 1.03 µT respectively.
These values were measured directly underneath the 132 kV transmission lines. The measured values for
the electric and magnetic fields near the houses were very small, 0.006 kV/m and 0.05 µT respectively.
Figure 12: Schematic overview of location 4
Profile
2
Profile
1
Profile
3
20m 20m
132kV
Measurement profile
11kV415V
Electromagnetic Field Measurements
16 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - 4 - p r o f ile 1 + 2 . m b k
Figure 15: Profile 1, magnetic field
0
0.01
0.02
0.03
0.04
0.05
0.06
0 10 20 30 40 50 60
Distance (m)
Electric Field (kV/m)
Figure 16: Profile 1, Electric Field
Electromagnetic Field Measurements
17 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - 4 - p r o f ile 1 + 2 . m b k
Figure 17: Profile 2, magnetic field
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0 10 20 30 40 50 60
Distance (m)
Electric Field (kV/m)
Figure 18: Profile 2, Electric Field
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
10 20 30 40 50 60 70
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - 4 - p r o f ile 3 . m b k
Figure 19: Profile 3, magnetic field
Electromagnetic Field Measurements
18 | P a g e
0
0.1
0.2
0.3
0.4
0.5
0 20 40 60 80
Distance (m)
Electric Field (kV/m)
Figure 20: Profile 3, Electric Field
Table 5 presents the current for the 132 kV and 11 kV overhead lines.
Table 5: Measured Currents Circuit 1 [A] Circuit 2 [A] 132kV - profile 1 213 214 132kV - profile 2 213 214 132kV - profile 3 287 287 11kV 95 -
3.5 Location 5 – Fanja
The maximum value of the measured electric field was 0.07 kV/m, under the 11 kV over head lines. The
maximum value of the measured magnetic field was 0.5 µT along profile 2. The profiles of the electric and
magnetic fields are illustrated in Figures 22 to 25.
Profile 2
Prof
ile 1
Figure 21: Schematic overview of location 5
11kV 415V Measurement profile
Electromagnetic Field Measurements
19 | P a g e
0.0
0.1
0.2
0.3
0.4
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t M a g n e t ic F ie ld \ M e a s u r e m e n t s R e s u lt s \ m e a u r e m e n t s R e s u lt s m a g n e t ic F ie ld \ lo c a t io n - 5 . m b k
Figure 22: Profile 1, magnetic field
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0 10 20 30 40 50
Distance (m)
Electric Field (kV/m)
Figure 23: Profile 1, Electric Field
Electromagnetic Field Measurements
20 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
10 20 30 40 50 60 70 80
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t M a g n e t ic F ie ld \ M e a s u r e m e n t s R e s u lt s \ m e a u r e m e n t s R e s u lt s m a g n e t ic F ie ld \ lo c a t io n - 5 . m b k
Figure 24: Profile 2, magnetic field
0
0.005
0.01
0.015
0.02
0.025
0.03
0.035
0 10 20 30 40
Distance (m)
Electric Field (kV/m)
Figure 25: Profile 2, Electric Field
Table 5 presents the current for the 11 kV and 415 overhead lines.
Table 6: Measured Currents
Blue [A] Yellow [A] Red [A] Neutral [A] 11kV 38 38 40 - 415V_line1 226 160 150 45.5
415V_line2 133.2 132.5 168.2 29.4 415V_line3 27.3 13.2 12.4 17.8 415V_line4 81.2 62.8 32.4 31.2
Electromagnetic Field Measurements
21 | P a g e
3.6 Location 6 – Al Farfarh
The maximum values of the electric and magnetic fields are 0.075 kV/m and 1.25 µT respectively. The
profiles of the magnetic and electric fields are presented in Figures 27 and 28 respectively.
Prof
ile 1
33kVMeasurement profile
3m
3m
Figure 23: Schematic overview of location 6
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
10 20 30 40 50 60 70 80 90
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - 6 . m b k
Figure 27: Profile 1, magnetic field
Electromagnetic Field Measurements
22 | P a g e
0
0.01
0.02
0.030.04
0.05
0.06
0.07
0.08
0 20 40 60 80
Distance (m)
Electric Field (kV/m)
Figure 28: Profile 1, Electric Field
Table 7 presents the current for the 33 kV and 415 V overhead lines.
Table 7: Measured Currents
Blue [A] Yellow [A] Red [A] Neutral [A] 33kV 121 121 121 - 415 V 95 85 102 25
3.7 Location 7 – Royal Camp Suwiaq
The maximum measured value of the electric field was 3 kV/m and was recorded underneath the 220 kV
overhead line, whereas a value of 2.7 kV/m was measuerd underneath 132 kV overhead line. The value
measured at the reference points 1 and 2 were 0.005 kV/m and 0 kV/m respectively.
The maximum measured value for the magnetic field was 1.75 µT. The measurement at reference points 1
and 2 were 0.01 µT and 0 µT respectively. The profiles of the magnetic and electric fields are presented in
Figures 30 and 31 respectively.
Table 8 presents the current for the different overhead lines.
Table 8: Measured Currents
Circuit 1 [A] Circuit 2 [A]220kV 200 200 132kV 155 155 33kV 238 -
Electromagnetic Field Measurements
23 | P a g e
±300m
±600m
His Majesty’s Camp
132kV33kVMeasurement profile
220kV
Reference point 1
Reference point 2
Figure 29: Schematic overview of location 7
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
100 200 300
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t M a g n e t ic F ie ld \ M e a s u r e m e n t s R e s u lt s \ m e a u r e m e n t s R e s u lt s m a g n e t ic F ie ld \ lo c a t io n - 7 . m b k
Figure 30: Profile 1, magnetic field
Electromagnetic Field Measurements
24 | P a g e
‐0.5
0
0.5
1
1.5
2
2.5
3
3.5
0 100 200 300 400
Distance (m)
Electric Field (kV/m)
Figure 31: Profile 1, Electric Field
3.8 Location 8 – Royal Camp Sohar
The maximum measured value of electric field was 2.7 kV/m and it was recorded underneath the 132kV
overhead line. The values of the electric fields at the two reference points were 0 kV/m.
The maximum measured value of the magnetic field was 4.3 µT. The values for the magnetic fields at the
two reference points were 0.01 µT. The profiles of the magnetic and electric fields are illustrated Figures 33
and 34 respectively.
±1200m
±700m
132kVMeasurement profile
His Majesty’s Camp
Reference point 1
Reference point 2
Figure 32: Schematic overview of location
Electromagnetic Field Measurements
25 | P a g e
The following table presents the current for the 220 kV overhead lines.
Table 9: Measured Currents
Circuit 1 [A] Circuit 2 [A]220kV 530 530
0
1
2
3
4
5
100 200 300 400 500 600 700
Mag
netic
Fie
ld (u
T)
Distance (m)C : \ P r o g r a m F ile s \ E n e r t e c h C o n s u lt a n t s \ E M C A L C 2 0 0 7 \ D a t a \ m e a u r e m e n t s \ lo c a t io n - 8 b . m b k
Figure 33: Profile 1, magnetic field (starts between two towers)
Figure 34: Profile 1, Electric Field
Electromagnetic Field Measurements
26 | P a g e
3.9 Location 9 – Royal Camp Buryami
The maximum measured values of electric fields were 2.8 kV/m and 1.4 kV/m for profiles 2 and 1 respectively. It should be noted that there were other overhead transmission lines run in parallel with 132 kV lines near profile 2. The values of the electric fields at the two reference points were 0 kV/m.
Profile 1
132kVMeasurement profile
His Majesty’s Camp
Reference point 1
Reference point 2
±300m
±1100m
Figure 35: Schematic overview of location 9
Table 10 presents the current for the 132 kV overhead lines.
Table 10: Measured Currents Circuit 1 [A] 132kV 170 132kV 170 The maximum measured values of the magnetic field were 4.3 µT and 3.8 µT for profiles 1 and 2 respectively. The values for the magnetic fields at the two reference points 1 and 2 were 0.01 µT and 0.02 µT respectively. The profiles of the electric and magnetic fields are presented in the Figures 36 to 39.
Electromagnetic Field Measurements
27 | P a g e
0
1
2
3
4
5
100 200 300 400
Mag
netic
Fie
ld (u
T)
Distance (m)
C : \ P r o g r a m F ile s \ E n e r t e c h C o n s u lt a n t s \ E M C A L C 2 0 0 7 \ D a t a \ m e a u r e m e n t s \ lo c a t io n - 9 - p r o f ile 1 . m b k Figure 36: Profile 1, magnetic field
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 10 20 30 40 50 60
Distance (m)
Electric Field (kV/m)
Figure 37: Profile 1, Electric Field
Electromagnetic Field Measurements
28 | P a g e
0
1
2
3
4
20 40 60 80 100 120 140 160 180
Mag
netic
Fie
ld (u
T)
Distance (m)C : \ P r o g r a m F ile s \ E n e r t e c h C o n s u lt a n t s \ E M C A L C 2 0 0 7 \ D a t a \ m e a u r e m e n t s \ lo c a t io n - 9 - p r o f ile 2 . m b k
Figure 38: Profile 2, magnetic field
0
0.5
1
1.5
2
2.5
3
0 20 40 60 80 100 120 140
Distance (m)
Electric Field (kV/m)
Figure 39: Profile 2, Electric Field
3.10 Location 10 – LDC-SQU (Mawalleh)
The maximum value of the electric field was 1.8 kV/m, measured underneath the overhead transmission
line. The value measured at the reference point was 0.006 kV/m.
Electromagnetic Field Measurements
29 | P a g e
School
132kV33kVMeasurement profile
±80m
±20m
20m
Figure 40: Schematic overview of location 10
The currents are given in the Table 11.
Table 11: Measured Currents
Circuit 1 [A] Circuit 2 [A]
132kV - 1 88 88
132kV - 2 472 472
33kV - 1 - -
33kV - 2 - -
33kV - 3 - -
The maximum measured value of the magnetic field is 5.5 µT. The value measured at the reference point
was 0.85 µT. The profiles for the magnetic and electric fields are shown in the Figures 41 and 42
respectively.
Electromagnetic Field Measurements
30 | P a g e
0
1
2
3
4
5
6
20 40 60 80 100 120 140 160
Mag
netic
Fie
ld (u
T)
Distance (m)D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - w e d n e s d a y 1 9 - 2 . m b k
Figure 41: Profile 1, magnetic field
00.20.40.60.81
1.21.41.61.82
0 50 100 150 200 250
Distance (m)
Electric Field (kV/m)
Figure 42: Profile 1, Electric Field
3.11 Location 11 – (M-Grid) Al Khoud
The maximum measured value of the magnetic field was 1.85 µT. The maximum measured value of the
electric field was 0.85 kV/m. This value was measured underneath the 132kV overhead transmission line.
The profiles for the magnetic and electric fields are depicted in Figures 44 and 45 respectively.
Electromagnetic Field Measurements
31 | P a g e
Figure 43: Schematic overview of location 11
The currents that passes through the different circuits are given in Tables 12 and 13.
Table 12: Measured Currents Circuit 1 [A] Circuit 2 [A] 132kV 175 175 33kV - 1 174 - 33kV - 2 100 - 33kV - 3 154 - Cable 1 182 Cable 2 172 Cable 3 123 Cable 4 54 Cable 5 115 Cable 6 115 Cable 7 167
Table 13: Measured Currents
Blue [A] Yellow [A] Red [A] Neutral 11kV 128.2 147.2 138.8 - 415V - 1 61.6 36.1 60.4 28.8 415V - 2 23.3 32 27.4 16.7
132kV
415V Measurement profile
11kV 33kV
14m 8m 12m 16m ±30m
Electromagnetic Field Measurements
32 | P a g e
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
10 20 30 40 50 60 70 80 90 100 110
Mag
netic
Fie
ld (u
T)
Distance (m)F : \ m e a u r e m e n t s \ lo c a t io n - w e d n e s d a y 1 9 - 3 . m b k
Figure 44: Profile 1, magnetic field
00.10.20.30.40.50.60.70.80.9
0 20 40 60 80 100 120
Distance (m)
Electric Field (kV/m)
Figure 45: Profile 1, Electric Field
Electromagnetic Field Measurements
33 | P a g e
3.12 Location 12– Customer 4
The maximum measured value of the magnetic field is 5.5 µT along profile 1. This value was measured next
to the substation. The maximum measured value of the magnetic field of profile 2 is 9 µT. This value was
measured close to the transformer.
Pole mounted Transformer
Measurement profile11kV
Substation
2m
Figure 46: Schematic overview of location 12
The current is given in Table 14.
Table 14: Measured Currents Blue [A] Yellow [A] Red [A] 11kV 20.3 21.9 15.8
The maximum measured value of the electric field is 0.0375 kV/m. This value was measured underneath
11kV overhead line. The electric field along profile 2 was very small.
The profiles for the electric and magnetic fields are illustrated in Figures 47 to 49.
Electromagnetic Field Measurements
34 | P a g e
0
1
2
3
4
5
6
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)F : \ m e a u r e m e n t s \ lo c a t io n - w e d n e s d a y 1 9 - 1 . m b k
Figure 47: Profile 1, magnetic field
0
0.0050.01
0.015
0.02
0.0250.03
0.035
0.04
0 10 20 30 40
Distance (m)
Electric Field (kV/m)
Figure 48: Profile 1, Electric Field
Electromagnetic Field Measurements
35 | P a g e
0
1
2
3
4
5
6
7
8
9
2 4 6 8 10 12 14 16 18 20 22 24
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - w e d n e s d a y 1 9 - 1 . m b k Figure 49: Profile 2, magnetic field
3.13 Location 13– Al Gubrah
The maximum measured value of the magnetic field of profile 1 is 4.5 µT. This value was measured almost
underneath the middle of 132 kV overhead transmission line. At profile 2, the measurement is almost
constant with an average of 0.21 µT, because the profile was taken in parallel with overhead transmission
lines. The maximum value near the building was 0.2 µT.
The maximum measured values of the electric field of profile 1 are 0.94 kV/m, 0.48 kV/m and 0.42 kV/m.
These values were measured underneath the overhead transmission lines. The maximum measured value
of profile 2 is 0.12 kV/m. The maximum value near the building was 0.13 kV/m. The profiles for the electric
and magnetic fields are presented in Figures 51 to 54.
The current per circuit is shown in Table 15.
Table 15: Measured Currents Circuit 1 [A] Circuit 2 [A]132kV - 1 348.9 352.4 132kV - 2 231 232.6 132kV - 3 227 227 33kV 350 336
Electromagnetic Field Measurements
36 | P a g e
Profile 1
Pro
file
2
Office
132kV
Measurement profile33kV
Figure 50: Schematic overview of location 13
0
1
2
3
4
5
20 40 60 80 100 120 140 160 180
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 3 . m b k Figure 51: Profile 1, magnetic field
Electromagnetic Field Measurements
37 | P a g e
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0 20 40 60 80 100 120 140 160
Distance (m)
Electric Field (kV/m)
Figure 52: Profile 1, Electric Field
0.00
0.05
0.10
0.15
0.20
0.25
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 3 . m b k Figure 53: Profile 2, magnetic field
Electromagnetic Field Measurements
38 | P a g e
0
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0 10 20 30 40 50 60
Distance (m)
Electric Field (kV/m
)
Figure 54: Profile 2, Electric Field
3.14 Location 14– MSQ grid station
The maximum measured value of the magnetic field of profile 1 is 0.55 µT. This point was near the
transformers. At profile 2, the maximum measured value is 2 µT. This point was very close to 220kV
overhead transmission line near the fence. The maximum value measured along profile 3 was 0.78 µT.
The maximum measured value of the electric field is 0.4 kV/m. This value was measured underneath the
overhead transmission line along profile 2.
The profiles for the electric and magnetic fields are presented in Figures 56 to 61. The values of the current
that passes through 220 kV circuits at the time of the measurements were presented in Table 16.
Electromagnetic Field Measurements
39 | P a g e
Figure 55: Schematic overview of location 14
0.0
0.1
0.2
0.3
0.4
0.5
0.6
20 40 60 80 100 120 140 160
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 4 . m b k Figure 56: Profile 1, magnetic field
Profile 1
Profile
2
Profile
3
220kV Substation
Measurement profile220 kV
Electromagnetic Field Measurements
40 | P a g e
0
0.005
0.01
0.015
0.02
0.025
0.03
0.035
0.04
0.045
0.05
0 50 100 150 200
Distance (m)
Electric Field (kV/m)
Figure 57: Profile 1, Electric Field
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
10 20 30 40 50 60 70 80 90 100
Mag
netic
Fie
ld (u
T)
Distance (m)F : \ m e a u r e m e n t s \ lo c a t io n - 1 4 . m b k
Figure 58: Profile 2, magnetic field
Electromagnetic Field Measurements
41 | P a g e
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0 20 40 60 80 100 120
Distance (m)
Electric Field (kV/m)
Figure 59: Profile 2, Electric Field
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
10 20 30 40 50 60 70 80 90 100 110 120 130
Mag
netic
Fie
ld (u
T)
Distance (m)F : \ m e a u r e m e n t s \ lo c a t io n - 1 4 . m b k
Figure 60: Profile 3, magnetic field
Electromagnetic Field Measurements
42 | P a g e
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0 20 40 60 80 100 120 140
Distance (m)
Electric Field (kV/m)
Figure 61: Profile 3, Electric Field
Table 16: Measured Currents Circuit 1 [A] 220kV - 1 406 220kV - 2 412
3.15 Location 15– MSQ 220 kV
The maximum value of the magnetic field was 0.458 µT and the maximum value of the electric filed was
0.24 kV/m. The profiles for the magnetic and electric fields are presented in Figures 63 and 64 respectively.
Measurement profile220kV
220kV Substation
Figure 62: Schematic overview of location 15
Electromagnetic Field Measurements
43 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
10 20 30 40 50 60 70 80 90 100 110 120
Mag
netic
Fie
ld (u
T)
Distance (m)
D : \ t o r u s \ R e s e a r c h - P r o je c t \ E x t e r n a ly - F u n d e d \ M e a s u r e m e n t _ M a g n e t ic _ F ie ld \ M e a s u r e m e n t s _ R e s u lt s \ m e a u r e m e n t s _ R e s u lt s _ m a g n e t ic _ F ie ld \ lo c a t io n - 1 5 . m b k Figure 63: Profile 1, magnetic field
0
0.05
0.1
0.15
0.2
0.25
0.3
0 20 40 60 80 100 120
Distance (m)
Electric Field (kV/m)
Figure 64: Profile 1, Electric Field
3.16 Location 16 – Wadi Adai
The maximum measured value of the magnetic field near the boarders of the grid station was 7.3 µT along
profile 1. The maximum measured value inside the grid station (excluding the control rooms) was 17.25 µT
along profile 5 near transformers. The maximum measured value inside the control room (profiles 7a and
7b) was 7.5 µT along profile 7a, whereas the maximum measured value exceeds 180 µT inside the large
Electromagnetic Field Measurements
44 | P a g e
control room along profile 8a. This can be explained by the fact that very high current was following through
the busbar inside the large control room. The profiles for the electric and magnetic fields are presented in
Figures 66 to 80. The values of the currents that passes through the different circuits are presented in Tables
17 and 18.
Profile 7a Profile 1
Profile 3
Profile 2
Profile 4
Profile 5
Profile 6
Profile 8a
Profile 7b
Profile 8b
C-Bank
Control room
Control room
Figure 65: Schematic overview of location 16
0
1
2
3
4
5
6
7
8
10 20 30 40 50 60 70 80
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k
Cable Measurement profile
132kV OHL
Transformer
Electromagnetic Field Measurements
45 | P a g e
Figure 66: Profile 1, magnetic field
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0 20 40 60 80 100
Distance (m)
Electric Field (kV/m)
Figure 67: Profile 1, Electric Field
0
1
2
3
4
10 20 30 40 50 60 70 80
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 68: Profile 2, magnetic field
Electromagnetic Field Measurements
46 | P a g e
0
0.2
0.4
0.6
0.8
1
1.2
0 20 40 60 80 100
Distance (m)
Electric Field (kV/m)
Figure 69: Profile 2, Electric Field
0
1
2
3
4
10 20 30 40 50 60 70 80 90 100
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 70: Profile 3, magnetic field
Electromagnetic Field Measurements
47 | P a g e
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0 20 40 60 80 100 120
Distacne (m)
Electric Field (kV/m)
Figure 71: Profile 3, Electric Field
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
10 20 30 40 50 60 70 80 90
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 72: Profile 4, magnetic field
Electromagnetic Field Measurements
48 | P a g e
‐0.05
0
0.05
0.1
0.15
0.2
0 20 40 60 80 100 120
Distance (m)
Electric Field (k
V/m)
Figure 73: Profile 4, Electric Field
0
2
4
6
8
10
12
14
16
18
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 74: Profile 5, magnetic field
Electromagnetic Field Measurements
49 | P a g e
0
1
2
3
4
5
6
7
8
9
10 20 30 40 50 60
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 75: Profile 6, magnetic field
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0 10 20 30 40 50 60 70
Distance (m)
Electric Field (kV/m)
Figure 76: Profile 6, Electric Field
Electromagnetic Field Measurements
50 | P a g e
0
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8 9 10
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 77: Profile 7a, magnetic field
0
1
2
3
4
5
1 2 3 4 5 6 7 8 9 10
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 78: Profile 7b, magnetic field
Electromagnetic Field Measurements
51 | P a g e
0
20
40
60
80
100
120
140
160
180
200
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 79: Profile 8a, magnetic field
0
10
20
30
40
50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 2 0 . m b k Figure 80: Profile 8b, magnetic field
Electromagnetic Field Measurements
52 | P a g e
Table 17: Measured Currents Circuit 1 [A] Circuit 2 [A] 132kV - 1 860 560 132kV - 2 Rusial 175.4 175.8 132kV - 3 al fliaj 260 248 132kV - 4 Wadi 210 260 132 kV Transformer 2 – bus 1 240 - 132 kV Transformer 2 – bus 2 265 - 11kV - Transformer 1 461 - 11kV - Transformer 2 542 - Table 18: Measured Currents Circuit [A] 33kV cable 1 91 33kV cable 2 160 33kV cable 3 171 33kV cable 4 178 33kV cable 5 90 33kV cable 6 76 33kV cable 7 175 33kV cable 8 60 33kV cable 9 91
3.17 Location 17– Al Qurm primary
The maximum measured value of the magnetic field is 13.5 µT along profile 6. There were no noticeable
electric field present in this area; this can be explained by the fact that the grounded parts shield all the high
voltage components. The profiles for the magnetic field are depicted in Figures 82 to 89. Table 19 presents
the measured currents through different circuits.
Table 19: Measured Currents Current high
voltage side [A] 33kV - 1 87.5 33kV - 2 81.7 11kV - 1 258 11kV - 2 245 11kV – 415V Transformer
1
Electromagnetic Field Measurements
53 | P a g e
Profile 1
Profile 3
Profile 5
Profile 2
Profile 6
Profile 8
Profile 7
Profile 4Measurement profile
Control building
Transformer
Transformer
Transformer
C-banks
Figure 81: Schematic overview of location 17
0
1
2
3
4
5
6
10 20 30 40
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 82: Profile 1, magnetic field
Electromagnetic Field Measurements
54 | P a g e
0
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 83: Profile 2, magnetic field
0
1
2
3
4
5
6
7
8
9
10
11
10 20 30 40
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 84: Profile3, magnetic field
Electromagnetic Field Measurements
55 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 85: Profile 4, magnetic field
0.0
0.1
0.2
0.3
0.4
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 86: Profile 5, magnetic field
Electromagnetic Field Measurements
56 | P a g e
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 87: Profile 6, magnetic field
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
2 3 4 5 6 7 8 9 10 11 12
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 88: Profile 7, magnetic field
Electromagnetic Field Measurements
57 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 6 . m b k Figure 89: Profile 8, magnetic field
3.18 Location 18– Al Qurm
The maximum value of the magnetic field was 0.12 µT along profile 3. There was no noticeable electric field
found in that area. The profiles for the magnetic field are presented in Figures 91 to 94.
Electromagnetic Field Measurements
58 | P a g e
Profile 1
Profile 2
Profile 3
Profile 4
Cable
Measurement profile
Substation
13m
5m 5m
5m
Figure 90: Schematic overview of location 18
0.00
0.01
0.02
0.03
0.04
10 20 30 40 50
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 7 . m b k Figure 91: Profile 1, magnetic field
Electromagnetic Field Measurements
59 | P a g e
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
10 20 30 40
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 7 . m b k Figure 92: Profile 2, magnetic field
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 7 . m b k Figure 93: Profile 3, magnetic field
Electromagnetic Field Measurements
60 | P a g e
0.00
0.01
0.02
0.03
0.04
0.05
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 7 . m b k Figure 94: Profile 4, magnetic field
3.19 Location 19– Al Amerate area, near Al Shabiah
The maximum value of the magnetic field was 1.2 µT along profile 1b. The profiles for the magnetic fields
are presented in Figures 96 and 97. The measured current values are shown in Table 20.
Table 20: Measured Currents Circuit 1 [A] Circuit 2 [A]
33kV - 1 0 0 33kV - 2 0 0
Electromagnetic Field Measurements
61 | P a g e
Profile 1aProfile 1b
Measurement profile33kVFuse box
6m
2m
Figure 95: Schematic overview of location 19
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 8 . m b k Figure 96: Profile 1a, magnetic field
Electromagnetic Field Measurements
62 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 8 . m b k Figure 97: Profile 1b, magnetic field
Electromagnetic Field Measurements
63 | P a g e
3.20 Location 20– Customer 5
The maximum measured value of the magnetic field is 3.75 µT along profile 4. This value was measured
next to the pole mounted transformer. The profiles for the magnetic fields are illustrated in Figures 99 to
102. The values of the current at the time of the measurements are presented in Table 21.
Figure 98: Schematic overview of location 20
Profile 1
Profile 2
Profile
3
Profile
4
Pole mounted transformer
17m
Measurement profile
11kV 415V
3m
Electromagnetic Field Measurements
64 | P a g e
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 9 . m b k Figure 99: Profile 1, magnetic field
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
10 20 30
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 9 . m b k Figure 100: Profile 2, magnetic field
Electromagnetic Field Measurements
65 | P a g e
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 9 . m b k Figure 101: Profile 3, magnetic field
0
1
2
3
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Mag
netic
Fie
ld (u
T)
Distance (m)
F : \ m e a u r e m e n t s \ lo c a t io n - 1 9 . m b k Figure 102: Profile 4, magnetic field
The following Table gives the current per phase:
Table 21: Measured Currents Blue [A] Yellow [A] Red [A] Neutral [A] 11kV 4 5.6 6.4 - 415V 108.7 78 182.3 88.9
Electromagnetic Field Measurements
66 | P a g e
4 RESULTS COMPARED TO WINTER MEASUREMENTS AND ICNIRP STANDARDS
The measurements are a replication of the same profiles and locations of the KEMA measurements report that were taken during the winter off-peak season. In order to ensure the completeness of electromagnetic field study results it was decided by the Authority to take electric and magnetic field measurements during the peak period in order to verify the findings based on the winter measurements.
The 2009 system peak for the Main interconnected system in Oman was recorded in June 2009 (3614 MW). The loads dropped but system load remained high during the month of August with daily peaks around (3200 MW) at the peak time around 3 PM every day which is almost 90% of the yearly peak. The measurements in this report (summer measurements) were taken between 2 and 5 PM to try to capture the peak loads. It would be reasonable to assume that the maximum values of the electromagnetic fields will not increase more than 10% of the measured values.
The measured values for the electric and magnetic field strength were compared to the ICNIRP standards for both General Public Exposure (for locations accessible by Public) and Occupational exposure (operational location where no public access is allowed)
Out of the 20 locations where measurements were taken only 2 locations were considered to be operational sites which are locations 16 and 17 (Wadi Adai Grid station and Al Qurum Primary). Also, profile 3 for location 3 was taken inside a distribution substation which is considered to inaccessible to public. For those locations the reference standard would be the occupational exposure which is 10 kV/m and 500 µT.
Figure 83 and 84 present a summary of the maximum measured values for electric and magnetic fields in Public locations for both winter and summer measurements referenced against the Public exposure limits of ICNIRP
0
20
40
60
80
100
Ham
oud
Al-J
abri
Ras
hid
Al-B
alus
hi
Ray
a Al
-Kha
rusi
Bid-
Bid
Fanj
a
Al-F
arfa
rh
Roy
al C
am S
uwia
q
Roy
al C
amp
Soha
r
Roy
al C
am B
urya
mi
LDC
-SQ
U (M
awal
leh)
(M-G
rid) A
l-Kho
ud
Shei
ka
Al-G
uhbr
ah
MSQ
grid
sta
tion
MSQ
220
kV
Al-Q
urm
Al-A
mer
at a
rea
Abdu
llah
Al-Z
akw
ani
Stre
ngth
of M
easu
red
Mag
natic
Fie
ld (µ
T)
Locations of Measurements
Maximum magnatic field values vs ICNIRP reference value for Genral Public exposure (100 µT)
Summer Measurements
Winter Measurements
ICNIRP Standard (100 uT
Figure 103: summary of the maximum measured values for magnetic fields referenced against General Public exposure limits of the ICNIRP
Electromagnetic Field Measurements
67 | P a g e
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Ham
oud
Al-J
abri
Ras
hid
Al-B
alus
hi
Ray
a A
l-Kha
rusi
Bid-
Bid
Fanj
a
Al-F
arfa
rh
Roy
al C
am S
uwia
q
Roy
al C
amp
Soh
ar
Roy
al C
am B
urya
mi
LDC
-SQ
U (M
awal
leh)
(M-G
rid) A
l-Kho
ud
Shei
ka
Al-G
uhbr
ah
MSQ
grid
sta
tion
MS
Q 2
20kV
Al-Q
urm
Al-A
mer
at a
rea
Abd
ulla
h A
l-Zak
wan
i
Stre
ngth
of M
easu
red
Elec
tric
Fie
ld S
teng
th (V
/m)
Locations of Measurements
Maximum Electric field values vs ICNIRP reference value for for Genral Public exposure (5000 V/m)
Summer Measurements
Winter Measurements
ICNIRP Standard (10000 V/m)
Figure 104: summary of the maximum measured values for electric fields referenced against General Public exposure limits of the ICNIRP
Figures 105 and 106 present a summary of the maximum measured values for electric and magnetic fields in operational location for both winter and summer measurements referenced against the Occupational exposure limits of the ICNIRP.
Figure 105: summary of the maximum measured values for magnetic fields referenced against Occupational exposure limits of the ICNIRP
Electromagnetic Field Measurements
68 | P a g e
Figure 106: summary of the maximum measured values for electric fields referenced against Occupational exposure limits of the ICNIRP
From the measurement results for magnetic and electric fields taken during summer time, it can be concluded that the levels of the fields on general public are lower than the permissible limit recommended by the International Commission on Non-Ionizing Radiation Protection (ICNIRP).
Electromagnetic Field Measurements
69 | P a g e
5 CONCLUSIONS
Electric and magnetic fields were measured at several locations determined by the Authority for
Electricity Regulation, Oman. The measurements were performed in several high voltage
environments (including 220 kV, 132 kV, 11 kV, and 415 V), as well as near several types of
electricity infrastructure (including substations, overhead lines and underground cables).
All measured values of electric and magnetic fields are lower than the recommended values
provided by ICNIRP.
The maximum values for electric fields were measured underneath 220 kV overhead line,
however the values are lower than the recommended limit (5 kV/m)
The highest values for magnetic fields were measured inside the grid stations and substation, with
values exceeding 180 µT in some places. However, since these locations are not accessible to
general public, the suggested value for occupational exposure can be applied (500 µT).
The highest values for magnetic fields in areas where members of the general public would be
exposed to the fields were at the boundaries of substations, with a maximum value of 16µT being
measured. This is significantly lower than the maximum value recommended by the ICNIRP.
There was a large increase in the measured values of the magnetic fields when compared to the
winter measurement values, due to the higher currents being carried by electrical equipment.
However, since the electric field is related to the voltage of the transmission and distribution lines
small differences in the electric field values were found between the winter and summer
measurements.
Electromagnetic Field Measurements
70 | P a g e
6 REFERENCES
1 L. Kheifets, J. Swanson and S. Greenland,” Childhood Leukemia, Electric and Magnetic Fields, and Temoral Trends", Bioelectromagnetics 27, 2006, , pp. 545-552.
2 A.Ahlbom, N. Day, M. Feychting, “A pooled analysis of magnetic fields and childhood leukaemia”, Br J Cancer, 83, 2000, pp. 692-698.
3 A. Sheppared. W. Kaune, C. Poole, M. Kelsh,” A pooled analysis of magnetic fields, wire codes, and childhood leukaemia. Epidemiol 11, 2000, pp. 624-634.
4 L. Kheifets, and R. Shimkhada,” Childhood Leukemia, , and EMF: Review of epidemiologic evidance", Bioelectromagnetics supply 17, 2005, , pp. S51-S59.
5 G.J. Draper, T. Vincent, M.E. Kroll and J. Swanson,” Childhood cancer in relation to distance from high-voltage power lines in England and Wales: a case-control study”, BMJ (2005).
6 http://www.hpa.org.uk/hpa/news/articles/press_releases/2005/050603_childhood_cancer_voltage.htm.
7 IARC, “Non-ionizing radiation, part 1, static and extremly low-frequency (ELF)
electric and magnetic field”, Lyon, France, 2002, P. 429.
8 A.H. Al-Badi, Issa Al-Zidi, Fahad Al-Amri, Humoud Al-Salmi and Ali AlMaamari,” Estimation of Population Exposure to Transmission Line Magnetic Field”, Industrial Applications of Energy Systems ( I A E S 2 0 0 8 ), Sohar University, Sultanate of Oman, April 1-2, 2008, pp. 35-40.
9 A. Al-Badi "Guidelines for pipeline installation close to overhead transmission
lines", Final Report, Petroleum Development Oman (PDO), Muscat, Sultanate of Oman, February 2006.
10 A. Al-Badi "Safe separation distance between power line and pipeline", Final
Report, Petroleum Development Oman (PDO), Muscat, Sultanate of Oman, March 2005.
11 A. Al-Badi “132 kV Power Connection from national grid to Oman India
Fertilizer Company S.A.O.C. (OMIFCO)-Mitigation of effects on buried pipeline located close to 132kV overhead line/ cable" Final Report, Petroleum Development Oman (PDO), Muscat, Sultanate of Oman, Dec. 2004.
12 IEEE Standard for Safety Levels with Respect to Human Exposure to Electromagnetic Fields, 0–3 kHz,IEEE Std C95.6™�2002.
13 Australian Radiation Protection and Nuclear Safety Agency, Radiation
Protection Standard Exposure Limits for Electric & Magnetic Fields (0 Hz to 3 kHz) Public Consultation Draft7 December 2006.
14 International commission on non-ionizing radiation protection (ICNIRP guidelines),” Guidelines For Limiting Exposure To Time-Varying Electric, Magnetic, and Electromagnetic Fields (up to 300 GHZ)” 1998
Electromagnetic Field Measurements
71 | P a g e
APPENDIX A MEASUREMENT DEVICES
The following standard devices was used to measure the magnetic and electric fields as shown in Figures 1 and 2. All these devices are calibrated.
Figure A-1: EMDEX II 50Hz Magnetic Field Meter 512K Memory, Standard 0.001μT - 100 μT Range EMDEX II is a powerful magnetic field measurement system based on EPRI's original power frequency recording magnetic field exposure meter.
Figure A-2: EMDEX II 50Hz Electric Field Probe
The EMDEX II Electric Field Probe, or E-Probe for short, allows an EMDEX II meter to measure and display power frequency (50 and 60Hz) electric fields using the 'AUX' jack on the side of the instrument.
Electromagnetic Field Measurements
72 | P a g e
APPENDIX B CALIBRATION CERTIFICATES