PRODUCTS 2013MaritimeAutronica Fire and Security AS
Protecting life,
environment andproperty
-
8/12/2019 Aureonica PC2013 MAR
2/66
Autronica Fire and Security AS2n
Protecting life, environment and property
AutroSafe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Panels AutroSafe 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Panel kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Service tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Customer conguration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OPC server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Autroprime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Conguration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fire detection system accessories . . . . . . . . . . . . . . . . . . . 17Power supply units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cabinets and racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Mounting accessories for cabinets/racks. . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PLC equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Loop units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Input and output units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Manual call points and release stations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Alarm units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Flame detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Accessories for loop units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Accessories for ame detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Test/measuring equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Contents
-
8/12/2019 Aureonica PC2013 MAR
3/66
Autronica Fire and Security AS n3
Autronica products 2013
Stringent control throughout Autronica Fire and Security AS assures the excellence of our products andservices. For a complete overview of our approvals, please visit our web site www.autronicare.com.
AutroMaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Software licences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Software modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Interface modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Software hardcopies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Engineering/Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Omicron multilevel alarm systems . . . . . . . . . . . . . . . . . . . 46Level alarm system OAS 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Vapour alarm system OVS 2.1 OP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Gas sampling systems OGS 3.1 and OGS 3.11. . . . . . . . . . . . . . . . . . . . 48
Fixed gas detection system OGS 2.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Water ingress system OAS WI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Temperature calibrator OTE-T700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Pressure calibrator OTE-P202 and OTE-P300 . . . . . . . . . . . . . . . . . . . . 51
Fire suppression systems . . . . . . . . . . . . . . . . . . . . . . . . . . 52Novec 1230 Fluid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Argonite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
CO2high pressure system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Low Expansion Foam systems for Offshore Service Vessels . . . . . . . . . . . 56
Low Expansion Foam systems for Cargo Tank Deck . . . . . . . . . . . . . . . . . 57
Low expansion foam system for open or closed car deck, shuttle ferries . . 58Low expansion foam system for helicopter deck . . . . . . . . . . . . . . . . . . . . . 59
Low-pressure water mist system local protection . . . . . . . . . . . . . . . . . . . 60
Low-pressure water mist system total ooding. . . . . . . . . . . . . . . . . . . . . 61
Low-pressure water mist system accommodation . . . . . . . . . . . . . . . . . . 62
Low-pressure water mist systems and Safe Return to Port . . . . . . . . . . . . 63
http://www.autronicafire.com/http://www.autronicafire.com/ -
8/12/2019 Aureonica PC2013 MAR
4/66
-
8/12/2019 Aureonica PC2013 MAR
5/66
-
8/12/2019 Aureonica PC2013 MAR
6/66
Autronica Fire and Security AS6n
Protecting life, environment and property
Panels
The AutroSafe 4 family consists of four different panel types. These are:
n Fire alarm control panel, BS-420. BS-420 is the main panel in the AutroSafe family. It can be used as a stand-alonepanel as well as part of a network system. All operations, alarm management, indications and other functions within an
operation zone are controlled and handled by the panel. The panel is equipped with a display, light indicators, a numeric
keypad, a navigation wheel and special function buttons (e.g. Silence Alarms). Loop driver, input and output modules can be
connected. An integrated AutroFieldBus interface makes it possible to connect AutroFieldBus equipment to the panel. All
AutroSafe systems must include at least one BS-420 panel.
n Operator panel, BS-430. As for the BS-420 panel, all operations, alarm management, indications and other functions withinan operation zone are controlled and handled by the BS-430 panel. The panel is equipped with a display, light indicators,
a numeric keypad, a navigation wheel and special function buttons (eg. Silence Alarms). No loop driver, input or outputmodules can be connected to this panel.
n Controller, BC-420. The BC-420 serves as a connection unit for loop driver modules as well as input and output modules.
It is equipped with two light indicators for System Fault and Power. The panel has neither display nor operator buttons. Anintegrated AutroFieldBus interface makes it possible to connect AutroFieldBus equipment to the panel.
n Repeater panel, BU-BV-420. Physical dipswitches on the panel control the BU-BV-420 panel function. As an alarmoperation panel it can operate alarms within one or more operation zones. As an information panel no operation of alarms
are available. The information panel provides information from one or more operation zones.
In addition to the panels the power cabinet BP-405 is a part of the AutroSafe 4 family. The cabinet includes a 5 A power pack
(BPS-405) which provides six 24 VDC / 2 A outputs. The input voltage is 115 / 230 VAC and the total maximum power available
is 24 VDC / 5 A. An integrated AutroFieldBus interface makes it possible for the power pack to communicate (send fault
messages) with the BS-420 or BC-420 panel. The cabinet provides space for two 12 V / 18 Ah batteries (not included).
-
8/12/2019 Aureonica PC2013 MAR
7/66
Autronica Fire and Security AS n7
Autronica products 2013
Fire
detectionsystems
Panel kits
For engineering purposes, we have established kits to be equipped according to specications.
An AL_Com+ stack can contain up to six loop driver modules (BSD-3xx). By using AutroFieldBus, an additional AL_Com+ stack
(with up to six additional loop driver modules) can be added to the system.
NOTE! The AutroSafe panels are certied with the AL_Com+ modules mounted inside the panel cabinet.
Image Part number Description Including Options
116-KIT-BS-420MMaritime re alarm
control panel kit
Panel front BSV-420M
Cabinet UEA-400
Power supply module BSS-310A
Communication module BSL-310
Text foils E-2879/XX*
Loop driver module BSD-310
Loop driver module H.P. BSD-311
BS-100 loop driver module BSD-330Output module BSB-310A
Output module BSJ-310
Input module BSE-310
Input module BSE-320
Redundant power BS-1342
Dual power monitoring module
BSS-311
116-KIT-BC-420 Controller kit
Panel front BCV-420
Cabinet UEA-400
Power supply module BSS-310A
Communication module BSL-310
Text foils E-2880/XX*
Loop driver module BSD-310
Loop driver module H.P. BSD-311
BS-100 loop driver module BSD-330
Output module BSB-310A
Output module BSJ-310
Input module BSE-310Input module BSE-320
116-KIT-BS-430 Operator panel kit
Panel front BSV-420
Cabinet UE-1488
Text foils E-2879/XX*
116-KIT-BU-BV-420 Repeater panel kit Panel front BUV-420Cabinet UE-1489
Text foils E-2880/XX*
116-BP-405 Power cabinet 420 x 346 x 146
Includes a 5A power pack (BPS-
405) which provides six 24 VDC
/2 A outputs. The input voltage is
115/230 VAC and the total maximum
power available is 24 VDC / 5 A. An
integrated AutroFieldBus interface
makes it possible for the power
pack to communicate (send fault
messages) with the BS-420 or BC-
420 panel. Space for two 12 V / 18
Ah batteries (not included)
*Available languages, replace XX with one of the following codes:
GB-G = Maritime/Oil & Gas English, N-M = Maritime Norwegian, DK-M = Maritime Danish, D-M = Maritime German,
BR-M = Maritime Portuguese
-
8/12/2019 Aureonica PC2013 MAR
8/66
Autronica Fire and Security AS8n
Protecting life, environment and property
Switches
A network solution (AutroNet) with more than two panels demands the use of switches. Only Phoenix Ethernet switches areapproved and supported by Autronica Fire and Security AS. The type and number of switches depends on the installation/
network construction (no. of panels and distance between panels and switches)
Image Part number Description*
Currentconsumption
(max.)@ 24 VDC
RJ45ports
Fibre opticports**
Operatingtemperature
116-5151-030.2127 FL switchSFNT 5TX 120 mA 5 -40 - 75C
116-5151-030.2128 FL switchSFNT 4TX/FX 160 mA 4 1 MM (SC) -40 - 75C
116-5151-030.2129 FL switchSFNT 8TX 153 mA 8 -40 - 75C
116-5151-030.2130 FL switchSFNT 7TX/FX 175 mA 7 1 MM (SC) -40 - 70C
116-5151-030.2131 FL switchLM 5TX 150 mA 5 -40 - 70C
116-5151-030.2132 FL switchLM 4TX/FX 380 mA 4 1 MM (SC) -40 - 70C
* SFNT = Standard Function, Narrow housing, high Temperature range
LM = Lean Managed
SFNB = Standard Function, Narrow housing, Basic entry level
SFN = Standard Function, Narrow housing
** MM = Multi Mode
SM = Single Mode
SC = Square Connector
(Set and Click, Stab and Click, Standard Connector)
-
8/12/2019 Aureonica PC2013 MAR
9/66
Autronica Fire and Security AS n9
Autronica products 2013
Switches (cont.)
Image Part number Description*
Currentconsumption(max.)
@ 24 VDCRJ45ports
Fibre opticports**
Operatingtemperature
116-5151-030.2133 FL switchLM 4TX/2FX 400 mA 4 2 MM (SC) -40 - 70C
116-5151-030.2134 FL switchLM 4TX/FX SM 380 mA 4 1 SM (SC) -40 - 70C
116-5151-030.2135 FL switchLM 4TX/2FX SM 400 mA 4 2 SM (SC) -40 - 70C
116-5151-030.2142FL switch SFNB 4TX/FX
SM 20185 mA 4 1 SM (SC) 0 - 60C
* SFNT = Standard Function, Narrow housing, high Temperature range
LM = Lean Managed
SFNB = Standard Function, Narrow housing, Basic entry level
SFN = Standard Function, Narrow housing
** MM = Multi Mode
SM = Single Mode
SC = Square Connector
(Set and Click, Stab and Click, Standard Connector)
Printer
Image Part number Description
116-BUP-400 Printer unit for AutroSafe 4
116-1712-012.0001 Printer paper 57 x 46 x 13 mm / 25 m
Fire
detectionsystems
-
8/12/2019 Aureonica PC2013 MAR
10/66
Autronica Fire and Security AS10n
Protecting life, environment and property
Modules
In addition to loop driver modules BSD-310, BSD-310N and BSD-311, as well as the obligatory power supply module BSS-310Aand communication module BSL-310, AutroSafe features input and output modules for different applications (monitored alarm
loops, servicing relays and LEDs, control inputs, etc.).
The modules have the same format, mount onto the panels DIN mounting rail and plug into one another.
Important note on module capacity.Each re alarm control panel/controller contains a power supply module BSS-310A and a communication module BSL-310.
The BS-420 and BC-420 panels have space for up to 12 modules totally inside the cabinet.
An AL_Com+ stack can contain up to six loop driver modules (BSD-3xx)By using AutroFieldBus, an additional AL_Com+ stack (with up to six additional loop driver modules) can be added to the
system.
NOTE! The AutroSafe panels are certied with the AL_Com+ modules mounted inside the panel cabinet.
Image Part number Description
Monitoredinpu
ts
Monitoredoutpu
ts
Totalinpu
ts
Totaloutpu
ts
Monitorsshortcircuits
Ensuresloopcommunication
ForuseinEXzone2on
ly
Amplifedpoweroutp
ut
Max.perpan
elNotes
116-BSB-310A Output module 0 4 Requires external 24V
116-BSD-310 Loop driver module 6/12 Max. 127 loop units
116-BSD-310/N Loop driver module 6/12 Max. 127 loop units
116-BSD-311Loop driver module
H.P. 6/12
-
8/12/2019 Aureonica PC2013 MAR
11/66
Autronica Fire and Security AS n11
Autronica products 2013
Modules (cont.)
Image Part number Description
Monitoredinputs
Monitoredoutputs
Totalinputs
Totaloutputs
Monitorsshortcircuits
E
nsuresloopcommunication
ForuseinEXzone2only
Amplifedpoweroutput
Max.perpanel Notes
116-BSD-330 BS-100 loop driver 8
116-BSE-310 Input module 4 0
116-BSE-320 Input module 8 0Galvanically insulated
inputs
116-BSJ-310 Output module 0 8 Open transistor outputs
116-BSS-310A Power supply module 4 0
116-BSS-311Dual power
monitoring module4 4
116-BS-1342 Redundant power for I/O modules, kit
Fire
detectionsystems
-
8/12/2019 Aureonica PC2013 MAR
12/66
Autronica Fire and Security AS12n
Protecting life, environment and property
Communication
Image Part number Description
116-BSD-321/1
AutroFieldBus protocol converter
Interface between AutroFieldBus and AL_Com+. Enables communication between all
AL_Com+ modules in an AL_Com+ stack connected to AutroFieldBus. The module enables
AutroSafe DualSafety conguration, with both ordinary Al_Com communication and
AutroFieldBus.
116-BSL-310
AutroSafe communication module, serves as an interface for the common internal
communication line between all the different I/O modules. Part of the re alarm control panel.
116-BSL-321
Multi mode bre optic converter
Amplier for AUTROLON/AutroFieldBus networks, which acts as a bre-optic modem. The
converter ensures reliable communication for distances of up to 3000 m. Uses multi-mode
(62.5/125 m or 50/125 m) bre-optic cable. Degree of protection: IP20
116-BSL-336
Voyage data recorder (VDR) interface
Allows AutroSafe re detection system data to be logged on voyage data recording systems.
Converts standard AutroSafe AutroCom messages to NMEA-0183 standards-compliant
strings, allowing events to be written to the VDR. Degree of protection: IP20
116-BSL-337
AutroSafe BU-70 interface module
Enables the connection of BU-70/BU-100/BU-101 to AutroSafe. This is a simple, cost effective
way to upgrade BS-100 systems to AutroSafe. The RS232/20mA current loop converter BSL-
12/2 must be used to convert RS232 to 20mA current loop communication.
Degree of protection: IP20
-
8/12/2019 Aureonica PC2013 MAR
13/66
Autronica Fire and Security AS n13
Autronica products 2013
Service tools
Part number Description
116-AS-SYSUTILPAC Total licensing solution (for certied partners)
116-AS-SYSUTILCD Upgrade CD for AutroSafe
116-AS-VDRCD VDR protocol interface on CD
116-WAS-2000 AS2000, loop diagnostics hardware
116-SW-100 AS2000, loop diagnostics software
116-XJA-027Connection cable for AS2000; for connection between computer and re alarm panel
(AS-SYSUTILPAC includes this item)
116-XJA-028 Connection cable for AS LoopSim, for computer panel interconnection
116-XJA-033 Connection cable for EAU-321, for computer module interconnection
116-XGE-1/10-110 Ribbon cable for connection of BSF-310/BSA-400 to BSL-310. 110 cm. Order only.
116-XGE-1/10-200 Ribbon cable for connection of BSF-310/BSA-400 to BSL-310. 200 cm.
116-XL-073 Conversion cable from AutroSafe3 to AutroSafe 4
Customer conguration
Part number Description
116-PROG-AUTROSAFE Customer specic software for AutroSafe
116-TXT-AUTROSAFE Customer text/controls
OPC server
With the AutroSafe OPC server several re detection systems and other control systems can communicate. The solution
improves the compatibility between the AutroSafe and surveillance systems from other manufacturers.
Part number Description
116-AS-OPC-SERVER/CD1
AutroSafe OPC server CD V1.2 incl. access code for access level 1. Includes read access to all status
information for detectors, output and alarm devices. This level of license will also make it possible to send
(write) Silence, Reset and SetTime commands to the AutroSafe system. Within this level you can also
Disable/Enable detectors.
116-AS-OPC-SERVER/CD2AutroSafe OPC server CD V1.2 incl. access code for access level 2. Includes all functionality in level 1, plus
the possibility to Activate/Deactivate and Enable/Disable outputs and alarm devices via OPC write commands.
116-AS-OPC-SERVER/CD3
AutroSafe OPC server CD V1.2 incl. access code for access level 3. Includes all functionality in level 1 and 2.
This level also provides additional information for points, for example AMEAS, Temp, Smoke, Alarm limits and
Engineering values.
Fire
detectionsystems
-
8/12/2019 Aureonica PC2013 MAR
14/66
Autronica Fire and Security AS14n
Protecting life, environment and property
Autroprime is a re detection system for small-to-medium sized applications. The system features the standards-
compliant, effective and reliable features Autronica customers expect, in addition to a range of newly developed features.
Simplicity is the keyword for this brand new product. The entire process, from installation and conguration, throughoperation to service is designed with the intent that Autroprime is going to be the simplest re-detection system on the
market. Our SelfVerify technology make sure the system takes care of everyday maintenance routines by itself.
Combining safety and economy
Autronica products have always been associated with cutting-edge technologies that change the way in which peoplethink about re detection. Autroprime is no exception, the system includes many tried and tested Autronica technologies,
the revolutionary part is that these high-end features are put together in a low-end package.
Autroprime nally brings a truly integrated concept to re detection, everything is in place, and system functionality and
reliability have never been better. Low-level simplicity ensures that this re detection system exceeds expectation and
provides next-generation possibilities, all for a low life-cycle cost.
Autroprime is approved according to EN 54/2 and 4 and SOLAS.
AUTROPRIME re detection made easy
-
8/12/2019 Aureonica PC2013 MAR
15/66
Autronica Fire and Security AS n15
Autronica products 2013
Fire
detectionsystems
Panels
The Autroprime system allows for a combination of maximum 8 panels and mimic drivers on a redundant panel bus. Degree ofprotection all panels: IP32.
Image Part number DescriptionDimensions
L x W x D (mm) Notes
116-71211548Fire alarm control
panel BS-200M420 x 346 x 140
Full re detection system with 4 loop drivers
each controlling 127 devices. The operator
panel may be mounted remotely with
redundant connections both for signal and
power. With space for batteries.
116-71211549Fire alarm control
panel BS-200M420 x 346 x 140
Full re detection system with 4 loop drivers
each controlling 127 devices. The operatorpanel may be mounted remotely with
redundant connections both for signal and
power. An extra termination block is included
for simplied panel bus and RS232/-244/-485
connection. With 230 VAC main and
emergency power inputs.
116-71211550Fire alarm control
panel BS-200M420 x 346 x 140
Full re detection system with 4 loop drivers
each controlling 127 devices. The operator
panel may be mounted remotely with
redundant connections both for signal and
power. An extra termination block is included
for simplied panel bus and RS232/-244/-485
connection. With 110 VAC main and
emergency power inputs.
116-BS-211 Repeater panel 310 x 220 x 45
Helps users manage alarms and other
events.
Panel bus included
116-BU-210 Fire brigade panel 310 x 154 x 45Showing alarms only.
Panel bus included.
116-BV-210 Information panel 310 x 154 x 45
Provides all information, but does not allow
handling of events.
Panel bus included
116-71211551Mimic driver BUR-
200M181 x 125 x 40
Panel bus included. With termination blocks.
8 in/16 out
-
8/12/2019 Aureonica PC2013 MAR
16/66
Autronica Fire and Security AS16n
Protecting life, environment and property
Printer
Image Art. nummer Beskrivelse
116-BUP-200 Printer unit for Autroprime
116-1712-012.0001 Printer paper 57 x 46 x 13 mm / 25 m
Modules
Part number Description
116-BSD-200A/PACK Autroprime loop extension pack, 2 loops
116-BSA-200A Autroprime main circuit board
Conguration
Part number Description
116-APRIME-CONFIGCD Autroprime conguration CD
-
8/12/2019 Aureonica PC2013 MAR
17/66
Autronica Fire and Security AS n17
Autronica products 2013
FIRE DETECTION SYSTEM ACCESSORIESIn order to project our re detection system to any application, we provide a wide range of accessories such as cabinets, racks,mounting equipment, batteries etc.
Power supply units
Part number Description Output voltage
116-BPS-405 Power supply unit for AutroSafe 4 24 VDC / 5 A
116-BPS-410 Power supply unit for AutroSafe 4 24 VDC / 10 A
116-BPS-410/115 Power supply unit for AutroSafe 4, 115 VAC 24 VDC / 10 A,
116-BSS-103A Power supply unit for all systems. Including housing for mounting on TS-35 rail 24 VDC / 3 A
116-BSS-103A/02 Power supply without housing. Supplied with NTC resistor 24 VDC / 3 A
116-4550-004.0001 Power supply for Autroprime SC-150 27ME 24 VDC / 5 A, 110/230 VAC
116-4550-012.2410 Power supply with fault output for all systems 24 VDC / 10 A, 110/230 VAC
116-4660-055.0001 DC/DC converter 24 VDC / 6,3 A
116-8147-015.5120 Transformer 110-130 VAC / 220 VAC, 200 VA
116-8147-038.5130 Transformer 110-130 VAC / 220 VAC, 300 VA
Batteries
Autronica Fire and Security AS offers accumulator batteries for every Autronica re detection system. Generally, 24 VDC backupis used, requiring two batteries per panel. All batteries are sealed and can be placed in cabinets.
Part number Description Voltage WeightDimensionsLxWxH (mm) Notes
116-4160-001. FIAMM FG20721 12V / 7.2 Ah 2,4 kg 79 x 56 x 106
116-4160-002. FIAMM FG21803 12V / 18 Ah 5,9 kg 181 x 76 x 167 AutroSafe
116-4160-003. FIAMM FG22703 12V / 27 Ah 8,7 kg 166 x 175 x 125 AutroSafe
116-4160-004. FIAMM FG24204 12V / 42 Ah 13,8 kg 196 x 163 x 174 AutroSafe
116-4160-005. FIAMM FG20201 12V / 2.0 Ah 0,9 kg 178 x 34 x 65
116-4160-005.0001 FIAMM FG21202 12V / 12 Ah 4,0 kg 151 x 98 x 99
116-4160-005.0003 FIAMM FG20341 12 V / 3 Ah 1,41 kg 134 x 67 x 60
116-4160-005.0005 FIAMM FG20451 12V / 4,5 Ah 1,6 kg 90 x 70 x 106 Autroprime
116-4160-006. FIAMM FG27004 12V / 70 Ah 22,0 kg 350 x 166 x 174
116-4160-006.0001 Sonnenschein A512/115 12V / 115 Ah 40,0 kg 286 x 269 x 230
116-4160-006.0003 Sonnenschein A512/85 12V / 80 Ah 31,0 kg 330 x 171 x 236
116-4160-006.0004 Sonnenschein A115/200 12V /200 Ah 70,0 kg 518 x 274 x 242
Fire
detectionsystems,fre
detectionsystemacc
essories
-
8/12/2019 Aureonica PC2013 MAR
18/66
-
8/12/2019 Aureonica PC2013 MAR
19/66
-
8/12/2019 Aureonica PC2013 MAR
20/66
-
8/12/2019 Aureonica PC2013 MAR
21/66
-
8/12/2019 Aureonica PC2013 MAR
22/66
-
8/12/2019 Aureonica PC2013 MAR
23/66
Autronica Fire and Security AS n23
Autronica products 2013
Input and output units
We offer a wide range of interactive input and output units for many different applications.The system features Exn-, Exia- and Exd approved input and output units for high risk applications.
All input and output units feature automatic addressing and short-circuit protection.
Image Part number Description
Confgurablein
put
Monitoredin
put
Monitoredoutput
Inputs/outp
uts
RequiresexternalPSU
SelfVe
rify
ForuseinEXareas
Degreeofprotection* Notes
116-BN-180 AutroKeeper 2/2 IP30
Use two units to
access one loop from
two loop controllers.
DIN rail mounting in
cabinet.
For AutroSafe only
116-BN-201 Monitoring unit 1/0IP54
IP67
116-BN-303Single monitored
input unit 1/0
IP54
IP67
Function selectable
via dip switch
116-BN-304 Input/output unit 1/1 IP54
IP67
Function selectable
via dip switch
116-BN-305Dual monitored input/
output unit 2/2
IP54
IP67
Function selectable
via dip switch
*: When two degrees of protection is given, the lowest is relevant when using membrane inlets and the highest when using PG inlets
Loopunits
-
8/12/2019 Aureonica PC2013 MAR
24/66
Autronica Fire and Security AS24n
Protecting life, environment and property
Input and output units (cont.)
Image Part number Description
Confgurableinput
Monitoredinput
Monitoredoutput
Inputs/outputs
R
equiresexternalPSU
SelfVerify
ForuseinEXareas
Degreeofprotection* Notes
116-BN-320 Interface unit 2/1 IP54
IP67
For AutroFlame
detectors
116-BN-320/D-LDoor monitoring and
control unit 2/1 IP67
Cable entries on the
back
116-BN-320/D-L2Door monitoring and
control unit 2/1 IP67
Cable entries on the
side
116-BN-320/D-XSDoor monitoring and
control unit, extra small 2/1 IP65
116-BN-320/FSSprinkler valve monitoring
and control unit 1/0 IP65
116-BN-320/GMU-XSGeneral monitoring and
control unit, extra small 2/1 IP65
116-BN-320/LLL Low location light unit 2/1 IP65
-
8/12/2019 Aureonica PC2013 MAR
25/66
Autronica Fire and Security AS n25
Autronica products 2013
Input and output units (cont.)
Image Part number Description
Confgurableinput
Monitoredinput
Inputs/outputs
R
equiresexternalPSU
SelfVerify
ForuseinEXareas
Degreeofprotection* Notes
116-BN-320/SV Standard control unit 2/1 IP67
116-BNB-330ALoop adapter unit for
conventional loops
116-BNB-331Loop adapter unit for
conventional loops 1/1 IP67
116-BN-500/EX Input unit 1/0 IP54
IP67
For interfacing external
units, clean contacts,
alarm relays, etc.
Zones 0, 1 & 2
116-BN-500/N Input unit 1/0 IP54
IP67
For interfacing external
units, clean contacts,
alarm relays, etc.
Zone 2
*When two degrees of protection is given, the lowest is relevant when using membrane inlets and the highest when using PG
inlets
Loopunits
-
8/12/2019 Aureonica PC2013 MAR
26/66
Autronica Fire and Security AS26n
Protecting life, environment and property
Detectors
We offer a wide range of interactive detectors for many different applications, with or without SelfVerify. The following series areavailable:
n 200 series, standard interactive addressable detectors.
n 300 series with SelfVerify, interactive addressable detectors.
n 500 series with SelfVerify, interactive addressable detectors for use in demanding environments.
The system also offers Exn- and Exia approved versions of detectors designed for use in high risk applications. S series smoke
detectors are specially designed for applications where high sensitivity is required.
Image Part number
Heat
Smoke
MultiSensor
Includingbase
SelfVerify
Environm
entallyprotected
Fo
ruseinEXareas
Foruse
inEXzone2only
Highsensitivity
Sealedunit
Wet/dryareas
Degreeofprotection
Notes
116-5861-033.0150 W/
DIP65 SWM-1KL 140C
116-BD-200M W IP56For steam saunas/cold stores
(-30 C)
116-BD-501 W IP56
116-BD-501/EX W IP56
116-BD-501/N W IP56
116-BDH-200 D IP44D
116-BDH-300 D IP44D
116-BDH-500 IP44D
116-BDH-500/EX IP44D
116-BDH-500/EXE IP44D RIME approved/NK
116-BDH-500/N IP44D
*: Available with the following alarm temperatures (replace XXX with F): 140 F (60 C), 160 F (70 C), 190 F (90 C), 225 F (110 C),
325 F (165 C), 360 F (180 C), and 450 F (230 C)
**: Available with the following alarm temperatures (replace XXX with F): 225 F (110 C), 275 F (135 C), 325 F (165 C), 360 F (180 C),
and 450 F (230 C)
-
8/12/2019 Aureonica PC2013 MAR
27/66
Autronica Fire and Security AS n27
Autronica products 2013
Loopunits
Detectors (cont.)
Image Part number
Heat
Smoke
MultiSensor
Includingbase
SelfVerify
E
nvironmentallyprotected
ForuseinEXareas
ForuseinEXzone2only
Highsensitivity
Sealedunit
Wet/dryareas
Degreeofprotection
Notes
116-BHH-200 IP44D
116-BHH-300 IP44D
116-BHH-500 IP44D
116-BHH-500/EX IP44D
116-BHH-500/EXE IP44D RIME approved/NK
116-BHH-500/N IP44D
116-BHH-500/S IP44D
116-BHH-500/S/Ex IP44D
116-BHH-500/S/N IP44D
116-BHH-220 IP44D
116-BHH-320 IP44D
116-BHH-520 IP44D
116-BHH-520/EX IP44D
116-BHH-520/EXE IP44D RIME approved NK
116-BHH-520/N IP44D
-
8/12/2019 Aureonica PC2013 MAR
28/66
Autronica Fire and Security AS28n
Protecting life, environment and property
Manual call points and release stations
We offer a wide range of interactive manual call points for different applications, every unit features SelfVerify. Two main seriesare available:
n 300 series with SelfVerify, interactive addressable manual call points.
n 500 series with SelfVerify, interactive addressable manual call points for use in demanding environments.
The system features Exn- and Exia approved versions for high risk applications.
Image Part number Description
ForuseinEXareas
Forusein
EXzone2only
Watertight/outdoormodel
Extremeenvironments
LEDindicator
Metalconnectionbox
Gla
ssnotincluded
Degreeofprotection
Notes
116-BF-300V2 Manual call point
IP42D
w/o
cover
IP44D
w cover
116-BF-510WP-H Manual call point
IP52
w/o
cover
IP55
w cover
116-BF-300M/EXE Manual call point IP44D*NK
RIME approved
116-BF-300M/N Manual call point IP44D*
116-BF-500V2/EX Manual call point IP44D*
116-BF-500/N Manual call point IP66
*: Degree of protection, inner housing.
-
8/12/2019 Aureonica PC2013 MAR
29/66
-
8/12/2019 Aureonica PC2013 MAR
30/66
Autronica Fire and Security AS30n
Protecting life, environment and property
Alarm units
We offer a wide range of alarm units for connection to detection loops or dedicated alarm outputs.
Image Part number Description
Alarmoutputmounting
Loopmounting
Electronic
Signalpresets
Confgurable
Watertight
Sound
Light
Soundoutput(dBA/1m)
Lightoutput(c/j)*
Degreeofprotection
Notes
116-BBL-100 Beacon 2 c IP32C
Supported by
Autroprime
and AutroSafe
version 4.3
116-BBL-100/IP Beacon 2 c IP65
Supported by
Autroprime
and AutroSafe
version 4.3
116-BBR-7M Alarm bell 6 93 IP55
116-BBR-24 Alarm bell 6 91 IP42
116-BBR-110 Base sounder 86 IP42
Combined
detector
base and
addressable
sounder
*: Candela (c), Joule (j)
-
8/12/2019 Aureonica PC2013 MAR
31/66
Autronica Fire and Security AS n31
Autronica products 2013
Alarm units (cont.)
Image Part number Description
Alarmoutputmounting
Loopmounting
Electronic
Signalpresets
Confgurable
Watertight
Sound
Light
S
oundoutput(dBA/1m)
Lightoutput(c/j)*
Degreeofprotection
Notes
116-BBR-130 Base sounder 90 IP32C
Combined
detector base
and addressable
sounder.
Supported byAutroprime
and AutroSafe
version 4.3
116-BBR-200 Sounder 100 IP42
116-BBR-200/IP Sounder 100 IP66
116-BBR-200/W Sounder 100 IP42
116-BBR-230 Sounder 100 IP32C
Supported by
Autroprime
and AutroSafe
version 4.3
116-BBR-230/IP Sounder 100 IP65
Supported by
Autroprime
and AutroSafe
version 4.3
*: Candela (c), Joule (j)
Loopunits
-
8/12/2019 Aureonica PC2013 MAR
32/66
Autronica Fire and Security AS32n
Protecting life, environment and property
Alarm units (cont.)
Image Part number Description
Alarmoutputmounting
Loopmounting
Electronic
Signalpresets
Confgurable
Watertight
Sound
Light
S
oundoutput(dBA/1m)
Lightoutput(c/j)*
Degreeofprotection
Notes
116-BBQ-130Base sounder
w/beacon 90 2 c IP21C
Combined
detector base
and addressable
sounder/beacon.
Supported byAutroprime
and AutroSafe
version 4.3
116-BBQ-230 Sounder/beacon 100 2 c IP32C
Supported by
Autroprime
and AutroSafe
version 4.3
116-BBQ-230/IP Sounder/beacon 100 2 c IP65
Supported byAutroprime
and AutroSafe
version 4.3
116-BU-46 Alarm indicator IP30 With LED
116-4340-006.0201 Xenon beacon IP55
116-4340-006.0924Solex beacon,
shallow base
2,5
cIP54
*: Candela (c), Joule (j)
-
8/12/2019 Aureonica PC2013 MAR
33/66
Autronica Fire and Security AS n33
Autronica products 2013
Alarm units (cont.)
Image Part number Description
Alarmoutputmounting
Loopmounting
Electronic
Signalpresets
Confgurable
Watertight
Sound
Light
S
oundoutput(dBA/1m)
Lightoutput(c/j)*
Degreeofprotection
Notes
116-4340-006.0925Solex beacon,
deep base
2,5
cIP54
116-4340-006.0926Solex beacon,
shallow base
2,5
cIP54
116-7770-009.0002Roshni LP,
shallow base 102 IP54
116-7770-009.0004Roshni LP,
shallow base 102 IP54
116-7770-009.0005Roshni, deep
base 102 IP65
116-7780-004.0001Flashni, shallow
base 101 0,7 j IP54
*: Candela (c), Joule (j)
Loopunits
-
8/12/2019 Aureonica PC2013 MAR
34/66
Autronica Fire and Security AS34n
Protecting life, environment and property
Alarm units (cont.)
Image Part number Description
Alarmoutputmounting
Loopmounting
Electronic
Signalpresets
Confgurable
Watertight
Sound
Light
S
oundoutput(dBA/1m)
Lightoutput(c/j)*
Degreeofprotection
Notes
116-7780-004.0002Flashni, deep
base 101 0,7 j IP65
116-7780-005.2301Sounder and
beacon AL112 112 5 j IP55
116-7780-005.2401Sounder and
beacon AL121 121 5 j IP55
116-7780-006. Air typhoon 141 IP65 0.6-1.0 Mpa
116-7780-006.0002 Air typhoon 141 IP65 2.5-3.0 Mpa
*: Candela (c), Joule (j)
-
8/12/2019 Aureonica PC2013 MAR
35/66
Autronica Fire and Security AS n35
Autronica products 2013
Flame detectors
NEW! The AutroFlame IR Flame Detector is a point ame detector for detection of res involving combustion of carbonaceousmaterials. It has a high IP rating making it suitable for the harshest environments.
The dual IR ame detector is used in various applications in which risk to personnel is high and where re might result in alarge loss of equipment. Beyond critical life-safety concerns, the advanced signal processing and DYFI+ intelligence ensure
that the detector has a high immunity to any nuisance alarm source and makes this detector the obvious choice for demanding
applications.
All AutroFlame X detectors have 4 x M25 cable entries. Swivel mount, glands and blind plugs are not included.
All AutroFlame X detectors have an ambient temperature range of -55 C to + 60 C for T6 and -55 C to + 75 C for T5.For interfacing AutroFlame X detectors to AutroSafe, use 116-BN-304.
Image Part number Description
Housing
De
greeofprotection
Notes
116-BG-201 AutroFlame Dual IR interactive PCBIP66/
67
116-BG-21 AutroFlame Dual IR conventional PCBIP66/
67
116-5861-011.4310 AutroFlame X33AF multispectrum IR SS IP66
Available with HART protocol on
request (X3301S4M23W1)
Combination unit with camera available
116-5861-011.4320 AutroFlame X33AF multispectrum IR Alu IP66
Available with HART protocol on
request (X3301S4M23W1)
Combination unit with camera available
116-5861-011.4340 AutroFlame X33AF multispectrum IR SS IP66 For areas with high temperatures
116-5861-011.4360 AutroFlame X33AF multispectrum IR Alu IP66 For areas with high temperatures
116-5861-011.4341 AutroFlame X33AF multispectrum IR SS IP66 Built-in BNB-300
116-5861-011.4361 AutroFlame X33AF multispectrum IR Alu IP66 Built-in BNB-300
116-5861-011.3980 AutroFlame X98 single IR SS IP66
116-5861-011.3981 AutroFlame X98 single IR Alu IP66
116-5861-010.1001 UV ame detector NS-DUV ACS IP55
116-5861-010.2010 601FEX-M IR FR110 IP20Ambient temperature range:
-20 C +70 C
Loopunits
-
8/12/2019 Aureonica PC2013 MAR
36/66
Autronica Fire and Security AS36n
Protecting life, environment and property
Accessories for loop units
Image Part number Description
116-BWA-100 Detector base for AuroSafe detectors
116-BWB-110 Base adapter for analogue addressable detectors mounted on interactive loops
116-BWP-100/20 Drip proof conduit box with M20 glands
116-BWP-100/20/PG16 Drip proof conduit box with M20 glands (PG16)
116-BWP-100/25 Drip proof conduit box with holes for M25 glands
116-WBJ-140 Mounting/demounting tool for AutroSafe detectors mounted on base BWA-100
116-WBW-100 Bypass unit for BWA-100
116-WBW-101 Mounting plate for false ceilings
116-BZ-500
Galvanic barrier for Exia approved detectors.
If power to the unit is supplied from the panel, a 24 V DC/DC converter,
e.g. 116-4660-055.0001 (p. 19) must be used to regulate the power.
-
8/12/2019 Aureonica PC2013 MAR
37/66
Autronica Fire and Security AS n37
Autronica products 2013
Loopunits
Accessories for loop units (cont.)
Part number Description
116-CXBZ Bezel for manual call points. Only for 116-BF-300V2.
116-4860-011.0100 Polycarbonate cover for manual call points.
116-4860-011.9901 Test key for manual call point 116-BF-300V2 (10 pack).
116-4890-021.0001 Lift ap in polycarbonate for manual call point 116-BF-502, all versions
116-4890-021.0010 Lift ap in stainless steel for manual call point 116-BF-502, all versions
116-4890-022.0001 Lift ap in polycarbonate for manual call point 116-BF-501, all versions
116-4890-022.0010 Lift ap in stainless steel for manual call point 116-BF-501, all versions
116-6550-125.0075 Spacer for open installation of base sounder BBR-110
116-BW-240 Deep mounting plate for base sounders
116-7770-009.0008 Power base 230 V for Roshni
Accessories for ame detectors
Part number Description116-6571-071.2500 Cable gland M25, polyamid, Eexe, degree of protection: IP67
116-6332-032.1925 Blind plug M25, polyamid, Eexe, degree of protection: IP67
116-6571-016.2520 Cable gland adapter M20/M25
116-6530-030.0020 Blind plug M20, brass, nickel plated. Exd/Exe, degree of protection: IP66/68
116-6530-030.0025 Blind plug M25, brass, nickel plated. Exd/Exe, degree of protection: IP66/68
116-001680-001 K1003A1006 Window cleaner for ame detectors (6 pcs.)
116-5861-011.9050 Q9033B Swivel mount for AutroFlame detectors, stainless steel
116-5861-011.9051 Q9033A Swivel mount for AutroFlame detectors, aluminium
116-007338-010 Q2033A10R 10 degree eld-of-view limiter
116-007338-020 Q2033A20R 20 degree eld-of-view limiter
116-007338-030 Q2033A30R 30 degree eld-of-view limiter/Weather shield (maintains standard eld of view)
116-007240-001 Q1116A air shield assembly
116-009199-001 Q1198A dual air shield/ange mount assembly
116-5861-010.1002 UV detector base, IP55
116-5861-010.2013 Ex detector base for 601FEX-M
116-5861-010.2014 Deckhead mounting kit for series 601
-
8/12/2019 Aureonica PC2013 MAR
38/66
-
8/12/2019 Aureonica PC2013 MAR
39/66
-
8/12/2019 Aureonica PC2013 MAR
40/66
Autronica Fire and Security AS40n
Protecting life, environment and property
AutroMaster ISEMS is an Integrated Safety and Emergency Management System combining the strengths of a powerful
re detection system with control and monitoring functions dedicated to make sure you are in control in case of an
emergency.
Graphical user interfaceThe AutroMaster provides an intuitive control and monitoring interface built to save valuable time when every second
counts. Status information is displayed in real-time with easy-to-understand graphical representation. Navigation is
fast and instinctual and the powerful zoom functions allow you to monitor all areas in great detail. AutroMaster displays
values for gas density, smoke and heat in dynamic colours, making it easy to perform the necessary actions duringemergencies.
InteroperabilityControl and monitoring of third party systems can easily be performed via serial protocols or network interfaces. They
provide connection to basically any source network time servers, telephone systems for text messaging, public address
systems for automated voice messaging, emergency lights, access control systems, CCTV, automation systems and soon.
Logging and reportingThe AutroMaster keeps track of all events in the system and has a built-in report generator. This provides a cost-effective
system log for maintenance and documentation purposes.
Decision-making toolsIn high-risk environments around the world, a seemingly innocuous re can quickly escalate into an emergency
of large proportions. When disaster strikes and you only have seconds to make the proper decisions,
the right safety and emergency management system is an invaluable asset. The AutroMaster
includes a Decision Support System (DSS) that will help you make the rightdecisions at the right time.
AUTROMASTER a fully integrated safety and emergency management system
Easy to use,provides full overview
and saves valuable time
-
8/12/2019 Aureonica PC2013 MAR
41/66
Autronica Fire and Security AS n41
Autronica products 2013
Autr
oMasterIntegratedSafetyandEmergencyManagementSystem
AutroMaster editionsAutroMaster ISEMS is the complete AutroMaster edition, including all functionality. In addition, we offer a market specic edition
with the modules most relevant for the maritime market
Modules/functions
Basic functionality
Fire management basic functions
MultiSensor control
Report generator
Control and monitoring of emergency lights/LLL
Extended functionality
AutroSafe IFG unit support NA
Touch screen support
Decision support system/incident manager
Electronic plotting table
Training/simulation module
Event record and replay module
Video module (live video support CCTV)
Remote connect function
Message Center module
Interfaces
Hernis CCTV interface
System-S interface
NMEA interface
Saia PLC support
VDR output
Siemens S7 PLC support
MODBUS interface
ESPA 4.4.4 interface
-
8/12/2019 Aureonica PC2013 MAR
42/66
Autronica Fire and Security AS42n
Protecting life, environment and property
Software licences
Part number Description
116-PROG-AUTROMASTER-MARAutroMaster Maritime Edition For the maritime market the AutroMaster Maritime Edition is specially
designed to meet the IMO/SOLAS requirements and regulatory demands.
116-PROG-AUTROMASTERISEMS
AutroMaster ISEMS Provides the full range of functionality every possible add-on module is
included in this package, making it the perfect choice for demanding applications and professional
customers.
116-PROG-AM-UPGRADE
Upgrade of AutroMaster to most recent version Existing AutroMaster customers can upgrade their
license to the most recent version of AutroMaster. Requires change of AutroMaster conguration
data.
Software modules
Part number Description
116-PROG-AM-MOD-DSS
Decision Support System (DSS) An interactive incident management system for AutroMaster.
The DSS gives operators access to customer-specied checklists. The checklists are organized as
checkpoints with one or more action items that can be used to manage operations, and these can be
marked off as actions are completed.
116-PROG-AM-MOD-EPTABLEElectronic re control plotting table gives you a dynamic plotting table to keep track of actorsevents during an emergency or drill. All EPT activity is logged in the Decision Support System and is
available for later reviews.
116-PROG-AM-MOD-TSIM
Training/Simulation module A tool to simulate pre-congured events. During a simulation it is
possible to pause, stop/end, and continue the simulation. Running the simulation tool is similar to
running a live event, alarms and faults are acknowledgeable and resettable. Every event is logged,
and after a simulation (or a stop), a full log can created and it is possible to replay the simulation
using the Event record/replay module.
116-PROG-AM-MOD-EVENT
Event Record/Replay module Offers a screenshot-based replay of incidents on AutroMaster and
can be congured to start recording manually or on pre-congured events as pre-warning, alarm or
simulation. Recordings are available for replay, and under replay the operator can start, stop, pause,
fast-forward and fast backwards. It is possible to export stored events.
116-PROG-AM-MOD-VIDEO Video interface module Includes display of live video in AutroMaster from IP based video cameras.
116-PROG-AM-MOD-REMOTERemote Connect function The Remote Connect Module enables a remote connection to
AutroMaster from any location using a server/client technology.
116-PROG-AM-MOD-MC
Message Centre module In the Message Centre the user can send text messages to telephone
systems and other AutroMaster PCs. The user can also send pre-recorded voice messages to PA
systems. Requires ESPA 4.4.4. interface.
-
8/12/2019 Aureonica PC2013 MAR
43/66
Autronica Fire and Security AS n43
Autronica products 2013
Autr
oMasterIntegratedSafetyandEmergencyManagementSystem
Interface modules
Part number Description
116-PROG-AM-MOD-HERNISHernis CCTV interface Interface enables use of AutroMaster together with video cameras and
servers from Hernis.
116-PROG-AM-MOD-NMEA
NMEA interface A protocol used for interface in between maritime electronic equipment, and
AutroMaster has built-in support for this in the NMEA interface module. Interface towards GPS is the
most common application.
116-PROG-AM-MOD-SAIAPLCSaia PLC support With the Saia PLC support, the AutroMaster can interface towards PLCs using
Saia as protocol.
116-PROG-AM-MOD-VDROUTPUTVDR output Used in maritime applications for giving output to the Voyage Data Recorder.
Conguration of which data and status messages to send to the VDR is done by project engineering.
116-PROG-AM-MOD-S7PLCSiemens S7 PLC support With the Siemens S7 PLC support, the AutroMaster can interface towards
PLCs using S7 as protocol.
116-PROG-AM-MOD-MODBUSMODBUS interface With the MODBUS interface AutroMaster can be connected to almost any kind
of electronic equipment for monitoring and control.
116-PROG-AM-MOD-ESPA444
ESPA 4.4.4 interface Offers a serial protocol intended for the interconnection of paging equipment
with telephone exchanges or computer systems. The protocol used is message-based and is built
upon the ISO1745 transport specication. Required if Message Centre module is used.
Software hardcopies
Part number Description
116-PROG-AUTROMASTER-CD CD containing AutroMaster software required for installation
116-AUTROMASTER-MAR-CD AutroMaster MAR back-up CD without license
116-AUTROMASTERISEMS-CD AutroMaster ISEMS back-up CD without license
Engineering/Conguration
Part number Description
116-AM-CONFIG General conguration work on setup of AutroMaster
116-AM-CHANGE Change of AutroMaster conguration
116-PROSJAMB Conversion of drawings into AutroMaster format
116-PROSJAMD Adding of detectors to drawings
116-PROSJAMDF Adding of color ll for analog values
-
8/12/2019 Aureonica PC2013 MAR
44/66
Autronica Fire and Security AS44n
Protecting life, environment and property
Hardware
Part number Description
116-AUTROMASTER-PC-10M PC, maritime standard. Model subject to change without prior notice.
116-AUTROMASTER-RACKPC 19" rack mount PC
116-5151-019.2250 Maritime desktop mounting kit for standard PC (MS2250 / DC8200)
116-5151-019.2260 Maritime minitower mounting kit for standard PC (MS2260 / DC8200)
116-5151-020.1951 19 standard LCD monitor
116-5151-020.2405 24 widescreen LCD monitor
116-5760-050.2003 Laser printer, colour, network and USB
116-5151-200.0023 20 monitor, console mounted, JH20T17 MMD
116-5151-017.0002 Keyboard - UK/English character set
116-5151-020.0400 Mouse - USB - 3 buttons
116-5151-017.0010 PC loudspeakers for desktop use
116-5151-017.0011 PC loudspeakers for internal mount (in 5.25" bay on PC)
116-5151-020.0731 Network card 10/100 MBPS, 1 port
116-5151-020.2027 Serial/Parallel port extension card, 4 serial ports / 1 parallel port
116-7190-011.0030 USB printer cable, 3 meters
116-7190-010.0030 Parallel cable (Centronics), 3 meters
116-7190-060.0050 Cat5 patch cable 5 meters, straight
116-7190-060.5050 Cat5 patch cable 5 meters, crossed
-
8/12/2019 Aureonica PC2013 MAR
45/66
Autronica Fire and Security AS n45
Autronica products 2013
Autr
oMasterIntegratedSafetyandEmergencyManagementSystem
-
8/12/2019 Aureonica PC2013 MAR
46/66
Autronica Fire and Security AS46n
Protecting life, environment and property
The Omicron multilevel alarm systems by Autronica include high level/overll alarm systems, gas detection systems,
tank and vapour pressure systems, temperature alarms and calibration equipment. Since delivery of the rst generation
independent high level system in 1989, we have developed a range of high-tech systems for the shipping and offshore
industry. More than 5000 vessels are using Omicron equipment.
The systems are designed to attract minimum maintenance overheads. We deliver reliable, service-friendly systems
to meet owners and regulatory requirements. The systems full IMO, IACS, EC, USCG and classication societies
regulations.
The Omicron systems are based largely on tailor made solutions for FPSOs, LNGs, LPGs, shuttle tankers and storage
tankers. Therefore, we give you a short description of the complete systems rather than a description on part number
level. Please contact us for more information.
OMICRON MULTILEVEL ALARM SYSTEMS solutions you can trust
-
8/12/2019 Aureonica PC2013 MAR
47/66
Autronica Fire and Security AS n47
Autronica products 2013
Level alarm system OAS 5
Vapour alarm system OVS 2.1 OP
For high level and overll
Omicron level alarm system OAS 5 with sensors, is a complete
level alarm system required either as an independent Overll
or High level and Overll system on all type of tankers.When delivered as a dual point system it is approved as two
independent systems as required in the regulations.
Sensor
Type HL-8903 for one level and type HHL-8903 for two levels.
Special models for LNG/LPG vessels with more than two levels.This oat type sensor works on a permanent magnet - reed
switch principle.
Features:
n Does not require a specialist engineer for installation or start
up
n Proven to be very reliable
n Two years guarantee
n Cover all types of vessels
(E.g. LNG,LPG, Chem, CT, PT etc.)
n Type approved by all major classication societies
n Extensive reference list
n Short delivery times
For vapour return lines on tankers
Omicron vapour alarm system OVS 2.1 OP monitors the
oxygen content and the pressure in the waste vapour line(s)
during loading of tank vessels. It consists of a detector cabinet
mounted on deck with Eex ia approved oxygen and pressure
sensors, ow fail initiator, manifold selector, test and purgefacility. The electronic cabinet mounted in the cargo control
room with alarm panel has individual LED displays and alarm
status LEDs.
Different models cover all congurations of manifolds and
vapour lines.
Omicronmultilevelalarms
ystems
-
8/12/2019 Aureonica PC2013 MAR
48/66
Autronica Fire and Security AS48n
Protecting life, environment and property
Gas sampling systems OGS 3.1 and OGS 3.11
For total solutions in gas sampling
Omicron gas sampling system OGS 3.1 is our advance model
for special requirements. Different models and options covermost applications you will nd on board any kind of tankers with
special needs. All delivered parts are completely assembled
ready for interconnection to on-site application. OGS 3.1 is
based on a scanning method, which means that sample points
are being connected to sensor(s) in a cyclic sequence. Theoperator panel has LCD display and individual LED lamps
indicating each measuring point status. To minimize scanning
cycle time and guarantee fresh samples at all times, the system
has two vacuum pumps. One main pump, continuously sucking
from all sample points and a smaller sample pump takingsamples from the actual point according to the sequence. Thisinsures quick response if gas is detected. Purging of sample
line is done immediately after each sampling is nished.
New design of the well known OGS 3.1 gas samplingsystem (smaller and more compact).
Gas sampling systems can be used in all spaces where gas
detection is requested, and they can handle several gasses
simultaneously. Our systems have the unique automatic blow
back feature, which together with two sampling pumps create arapid and clean sampling cycle. Hence for Gas tankers we are
able to handle more points and still maintain the 30 minute ruleof IMO Gas Code.
Standard features:n Infrared hydrocarbon sensor with range 0 - 100 % L.E.L
n Low and high gas alarms
n Flame arrestor and shut-off valve for each sampling tube
n Automatic and sequential purging of each sampling tube
n Manual disconnection of sampling points not in use
(e.g. when water in ballast tanks)
n Two vacuum pumps (main and sample)
n Non-return valves mounted on deck for ballast tanks inorder to avoid liquid entering into the system
n Extensive hardware and software system monitoring
Optional features:n Up to 5 additional units with control transfer function.
Multiple operating panel
n
Remote alarm unit. Simple alarm status panel with LEDsand buzzer (e.g. for Bridge)
n Aux. relay outputs. Up to 32 relay outputs, freely
congurable to any sample point
n Standby pump with manual switch over
n Dual purge supply (E.g. Nitrogen and instrument air)
n Multi-gas detection. Up to 3 different gas sensors can be installed
n Alarm printer
n Bulkhead penetrations
n Automatic disconnection of sample line when sample
point is manually disconnected from scanning cyclen RS485/-422MODBUSRTU serial line output to external
computer
n Custom made systems on request
-
8/12/2019 Aureonica PC2013 MAR
49/66
-
8/12/2019 Aureonica PC2013 MAR
50/66
Autronica Fire and Security AS50n
Protecting life, environment and property
Water ingress system OAS WI
For high level and overll
The Omicron water ingress system has been specially designed and
manufactured for detecting the presence of water in the inner bottom in
any holds reaching a height of 0,5 m and another height of not less than
15 % of the depth of hold but not more than 2 m. Furthermore, also holdslocated partially or totally forward of the foremost cargo hold, and ballast
tanks located forward of the foremost cargo hold, collision bulkhead of Bulk
carrier, in conformity with SOLAS regulation XII/ 12 rule requirement
The system consists of a main alarm panel with cabinet and level sensor
operated by detecting the conductivity in a liquid when present. The sensorand the alarm panel are connected together with an intrinsically safe
barrier. When the presence of water has reached the detecting points (ref.
rule requirement) of level sensor installed at the preset level in the cargohold or other space, the electric signals which are activated on the level
switches are transmitted to the main alarm panel. At the same time, the
audible and visual alarms are activated on the main alarm panel.
The system has also all necessary functions like loop monitoring of
sensors and power failure. An overriding device ensures that the alarm can
be deactivated or reactivated for the detector installed in the tank and holds
used for carriage of water ballast according to the SOLAS regulation XIII12.1. The main power and standby power are prepared in such way that if
the main power fails, the standby power will provide continuous power to
the alarm panel, and an alarm will be given.
The sensor:
Type WI-22 designed for various locations onboard abulk carrier. The construction is unique with the following
advantages:
n Complete unit in stainless steel.
n Non movable parts due to conductivity principle.
n Classied as simple apparatus
n IP68/ 2.5 bar with 35 m signal cable and mounting bracket
included.
n Tested working temperature -25 to 120 C.
n Easy to function test.
n Designed without any active electronic components on
deck.
n Can operate in all sorts of bulk cargoes.
The alarm cabinet:
Type OAS is a complete signal monitoring and alarm unitwhich is delivered for three alarm sensors per cargo hold. The
third channel (free of charge ) can be used for alarm sensor
on top of the cargo for covering water penetration through
hatch covers.
n Intrinsically safe connections to sensors.
n Potential free contacts for common external alarms and
light & horn.
n All normal alarm functions.
n Optional RS485/-422 serial line communication with host
computer.
n The Alarm Panel can either be mounted in the front door
of the alarm cabinet or in a common console.
n Power supply: 115/230 VAC, Emergency power supply 24
VDC
-
8/12/2019 Aureonica PC2013 MAR
51/66
Autronica Fire and Security AS n51
Autronica products 2013
Pressure calibrator OTE-P202 and OTE-P300
The temperature calibrator is intended for testing of temperaturesensors, indicators, switches and safety equipment. The heating
medium is hot air. This makes it clean to use and it has quick
temperature change response. Temperature range is about 10
degrees above ambient to + 700 C with digital readout of the
measured temperature.
The pressure calibrator is intended for testing of pressure
sensors, indicators, switches and safety equipment. The
pressure medium is oil. It has ne adjustment of the pressure,
and an overpressure relief valve. The digital readout can be
selected to Bar or PSI. Pressure range is 0 - 200 bar / 0 - 300
bar. The unit can also be delivered in Eex version.
Technical specications:
n Measuring range: ~30 - 700 C
n Heating medium: Air
n Display: 15 mm 3,5 Digit LCD.
n Dimensions: 410 x 140 x 160 mm.
n Weight: 4 kg
n Power: 120 V - 50/60 Hz - 2700 W, 230 V - 50/60 Hz - 2300 Wn Accuracy up to 100 C: +/- 1 C, 101-400 C: +/- 1 % FS, 401-700 C: +/- 2 % FS
Technical specications:
n Measuring range: 0-200 Bar / 0-1999 PSI // 0-300 Bar 0-4350 PSI
n Pressure medium: Oil
n Display: 15 mm 3,5 Digit LCD.
n Dimensions: 310 x 115 x 135 mm.
n Weight: 5 kgn Hose length: 1,5 m with quick connector and 40 mm test cock
n Power: 1 pc. 9V battery
n Accuracy 0-10 Bar: +/- 0.2 Bar 11-200 Bar: +/- 0.25 % F.s.
11-300 Bar: +/- 0.25 % F.s.
Temperature calibrator OTE-T700Omicronmultilevelalarms
ystems
-
8/12/2019 Aureonica PC2013 MAR
52/66
Autronica Fire and Security AS52n
Protecting life, environment and property
Integration of re-safety equipment ensures that the correct response is made automatically; the integration of re
detection and suppression is a logical step. It can be difcult to get equipment made by two different suppliers to work
together in a satisfactory way, and costs and installation time increase accordingly. That is why Autronica offers the total
safety solution for maritime applications.
Autronicas re suppression systems provide reliable, low-maintenance performance that distracts attention away
from every-day activities as far as possible. They are hard-wearing enough to face the challenges of environments
characterized by pollutants, corrosive chemicals and constant activity, as well as being sensitive enough to respond
correctly in an emergency situation.
The Autronica re suppression systems are based largely on tailor made solutions. Therefore, we give you a short
description of the complete systems rather than a description on part number level. Please contact us for more
information.
FIRE SUPPRESSION SYSTEMS real-world safety solutions
-
8/12/2019 Aureonica PC2013 MAR
53/66
Autronica Fire and Security AS n53
Autronica products 2013
Fire
suppressionsystems
Novec 1230 Fluid
Novec 1230 Engineered Fire Suppression System is the newgeneration in gaseous re suppression technology. Designedto protect human life and high value assets from re, it meets
the marine industrys concerns for safety, performance and theenvironment.
Novec 1230 uid is a uorinated ketone that is stored as a liquid and
discharged as a gas. It distributes uniformly throughout the hazard
zone, and suppresses re by a combination of heat absorption and
chemical interference with the ame.
EnvironmentWith a zero ozone depletion potential (ODP), a global warming
potential (GWP) of just one, and an atmospheric lifetime (ALT) of
only 5 days, Novec 1230 uid has virtually no measurable impacton climate change. When used in a re event, the uid mitigates the
effect of an uncontrolled re. At the end of the lifetime of the system,
the uid can be readily recovered and recycled.
Clean
Novec 1230 uid discharges as a colourless, electrically non-conductive and noncorrosive gas that does not damage sensitiveequipment. There is no post-discharge residue, no costly clean-up operations are required, and down-time is kept to a minimum.
Cost-effectiveBy using its tried and trusted range of 25 bar equipment, Autronica can offer a cost-effective Novec 1230 re suppression
system.
Efcient
Small and large-scale tests have proven that Novec 1230 uid puts res out quickly, before they can do any serious damage.It does this by reaching extinguishing concentrations in ten seconds or less. It is effective on a wide range of Class A, B and
electrical res.
SafetyThe US EPA Signicant New Alternatives Program (SNAP) classies Novec 1230 uid as acceptable for use as a total ooding
agent in occupied spaces. A low design concentration of 4 to 6% in combination with a high No Observable Adverse Effect Level
(NOAEL) of 10% means it provides a safety margin of up to 100%. This is by far the largest safety margin of any clean agent
currently available. In addition, there is no risk of human asphyxiation with Novec 1230 uid since it does not act by oxygen
depletion in the hazard zone.
System designThe Autronica Engineered Fire Suppression System comprises Novec 1230 uid stored in cylinders connected to distribution
pipework and specially designed discharge nozzles.
Novec 1230 uid is stored as a liquid in nitrogen-pressurised steel cylinders. This ensures minimal storage space and weightrequirements compared to all other viable gaseous agents. It also enables rells to be transported in unpressurised cylinders
without the restrictions on gaseous alternatives.
The range of cylinders, valves and related components has been
specially selected for use with Novec 1230 uid and has been
subjected to stringent testing procedures. Flexibility, quality andreliability make the Novec 1230 range the worlds nest in re safety.
Engineered systems are designed using FM Global and UL veried
software and guidelines, and offer optimum designs for the dened
risks with reduced pipe sizes, unbalanced ows and common room and
void protection possible.
ApplicationsNovec 1230 systems are ideally suited to the protection of machinery
spaces and cargo pump rooms in a wide range of vessel types.
-
8/12/2019 Aureonica PC2013 MAR
54/66
-
8/12/2019 Aureonica PC2013 MAR
55/66
Autronica Fire and Security AS n55
Autronica products 2013
CO2high pressure system
Total ooding system for protection of engine rooms and other types ofmachinery spaces.
Local protection of cargo spaces (combined with smoke detector systemSDA) for paint locker, computer cabinets etc.Carbon dioxide re extinguishing systems are useful to extinguish res in specic
hazards or equipment, and in occupancies where an inert electrically non-
conductive medium is essential or desirable, when cleaning up of other media
presents to a problem, or where there are more economical to install than systems
using other media.
Liqueed CO2is available in almost every port in the world. Carbon Dioxide is a
non-ammable, colourless, odourless, slightly acid gas.
With the required concentration for re extinguishing on board it extinguishessurface- and deep seated res.
CO2protects the following hazards:
n Flammable liquid materials
n Electrical hazards, such as transformers, oil switches and circuit breakers,
rotating equipment and electronic equipmentn Engines utilising gasoline and other ammable liquids
n Ordinary combustibles such as paper, wood and textiles
n Hazardous solids
CO2high pressure system advantages:
n Fast and effective extinguishingn Manual release
n No damages on protected equipmentn Minimum breakdown after re
n Low installation- and maintenance costs
Installationn Autronica offers complete installation and delivery of necessary pipes and ttings.
Typical layout CO2
Fire
suppressionsystems
-
8/12/2019 Aureonica PC2013 MAR
56/66
Autronica Fire and Security AS56n
Protecting life, environment and property
Low Expansion Foam systems for Offshore Service Vessels
A foam deluge system designed for the protection of the cargo area as dened by IMO Resolution A.673(16). Otherrequirements may apply depending on the class and ag, such as DnV Pt. 5 Ch.7 SECTION 10 Offshore Service Vessels for
Transportation of Low Flashpoint Liquids.
Cargo area is that part of the offshore support vessel where cargo and cargo vapors are likely to be present and includes cargo
tanks, cargo pump-rooms, hold spaces in which independent tanks are located, cofferdams surrounding integral tanks and the
following deck areas:
n within 3 m of a cargo tank installed on deck;
n within 3 m of a cargo tank outlet in case of independent tanks installed below deck;
n within 3 m of a cargo tank outlet in case of integral tanks installed below deck and separated from the weather deck by acofferdam;
n the deck area above an integral tank without an overlaying cofferdam plus the deck area extending transversely and
longitudinally for a distance of 3 m beyond each side of the tank;
n within 3 m of any cargo liquid or vapor pipe, ange, cargo valve, gas or vapor outlet, or entrance or ventilation opening to a
cargo pump-room.
The foam liquid capacity shall be designed for 30 minutes operation based on the ow required by the capacity calculation. A
mixture of 97% water and 3% of a alcohol resistant lm forming foam liquid produce the foam, with an expansion ratio below 1:12.
Alcohol-Resistant Concentrate (AR / ARC / ATC) produces foam that is effective on fuels such as methyl alcohol, ethyl alcohol
and acetone which have appreciable water solubility or miscibility. Standard foam agents are mixtures of chemical (natural orsynthetic) whose bubbles collapse when applied to water-soluble fuels. These fuels are said to be foam destructive.
The most current Alcohol-resistant concentrates are based on AFFF concentrates to which a water-soluble polymer
(polysaccharide) has been added. When these foam agents are applied to water-soluble fuel such as methyl alcohol, a
polymeric membrane is formed between the foam and the water-soluble fuel. When this foam agent is used on a conventional
(water insoluble) hydrocarbon fuel, it functions as an AFFF foam by forming an aqueous lm at the fuel/air interface. Since thepolymer is a natural occurring chemical, small amounts of an antimicrobial agent are added to prevent biological degradation.
The solution of foam liquid and water are distributed to the various areas through a piping system. The piping system for foam solution
(foam liquid and water) should be galvanised steel and foam liquid line should be acid proof stainless steel. The control of the system
is by manual means. The system can either be started from the foam pump starter cabinet, if this is located outside of the cargo area,adjacent to the accommodation spaces and readily accessible and operable in the event of res in the areas protected.
A remote start may also be installed to activate the system from a remote position. All valves except the foam liquid valve are
manually operated.
-
8/12/2019 Aureonica PC2013 MAR
57/66
Autronica Fire and Security AS n57
Autronica products 2013
Low Expansion Foam systems for Cargo Tank Deck
A foam deluge system designed for the protection of thecargo area as dened in the IBC Code, 11.3.5.
The rate of supply of foam solution shall be not less thanthe greatest of the following:
n .1. 2 l/min per square meter of the cargo tanks deck
area, where cargo tanks deck area means the maximum
breadth of the ship times the total longitudinal extent of
the cargo tank spaces;
n .2. 20 l/min per square meter of the horizontal sectional
area of the single tank having the largest such area;
n .3. 10 l/min per square meter of the area protected by
the largest monitor, such area being entirely forward of the
monitor, but not less than 1,250 l/min. For ships less than4,000 tones deadweight, the minimum capacity of themonitor shall be to the satisfaction of the Administration.
The foam liquid capacity shall be designed for 30 minutes operation based on the ow required by the capacity calculation.
A mixture of 97% water and 3% of a lm forming foam liquid produce the foam, with an expansion ratio below 1:12. If the cargo
is alcohol based such as methyl alcohol, ethyl alcohol and acetone, alcohol resistant foam liquid has to be used.
The solution of foam liquid and water are distributed to the various areas through a piping system. The piping system for foam
solution (foam liquid and water) should be galvanized steel and foam liquid line should be acid proof stainless steel.
The control of the system is by manual means. The system can either be started from the foam pump starter cabinet, if this is
located outside of the cargo area, adjacent to the accommodation spaces and readily accessible and operable in the event of
res in the areas protected.
A remote start may also be installed to activate the system from a remote position. All valves except the foam liquid valve are
manually operated.
Fire
suppressionsystems
-
8/12/2019 Aureonica PC2013 MAR
58/66
Autronica Fire and Security AS58n
Protecting life, environment and property
Low expansion foam system for open or closed car deck, shuttle ferries
A foam deluge system designed for the protection of the car deck. The deck is divided into zones with a minimum length of 20meter for passenger vehicles and 15 meter for trucks carrying dangerous goods.
The capacity of the system is calculated based on minimum 6,5 l/m2/min for the area dedicated for passenger vehicles and 10l/m2/min for the area dedicated for trucks carrying dangerous goods. The capacity of the pump is designed for the zone having
the greatest demand including the adjacent zones or the zone having the greatest demand including foam curtain aft and
forward of the zone. The foam curtain shall have an additional coverage equal to 35% of the required capacity of the adjacent
zones.
Dedicated seawater pump(s) for the system shall be installed. The pump shall have separate feeders from main and emergencysource of power supply. The sea water pumps are supplied by the yard and/or owner and are not within the scope.
The foam liquid capacity shall be designed for 30 minutes operation based on the ow required by the pump.
A mixture of 97% water and 3% of a alcohol resistant lm forming foam liquid produce the foam, with an expansion ratio below
1:12.
Alcohol-Resistant Concentrate (AR / ARC / ATC) produces a foam that is effective on fuels such as methyl alcohol, ethyl alcohol
and acetone which have appreciable water solubility or miscibility. Standard foam agents are mixtures of chemical (natural or
synthetic) whose bubbles collapse when applied to water-soluble fuels. These fuels are said to be foam destructive.
The most current Alcohol-resistant concentrates are based on AFFF concentrates to which a water-soluble polymer
(polysaccharide) has been added. When these foam agents are applied to water-soluble fuel such as methyl alcohol, apolymeric membrane is formed between the foam and the water-soluble fuel. When this foam agent is used on a conventional
(water insoluble) hydrocarbon fuel, it functions as an AFFF foam by forming an aqueous lm at the fuel/air interface. Since the
polymer is a natural occurring chemical, small amounts of an antimicrobial agent are added to prevent biological degradation.
The solution of foam liquid and water are distributed to the various areas through a piping system. The piping system for foam
solution (foam liquid and water) should be galvanised steel and foam liquid line should be acid proof stainless steel.
The control of the system is from a common control panel including start and stop of each zone, indicating lamps for systemactivated, pump started and mains power on. In addition the system can be controlled from local push buttons.
The control panel is programmed in a way that the required zone valves are activated based on which zone is on re, i.e. if zone2 is on re and foam curtain is required to be activated fore and aft, this action is done automatically by the panel.
-
8/12/2019 Aureonica PC2013 MAR
59/66
-
8/12/2019 Aureonica PC2013 MAR
60/66
Autronica Fire and Security AS60n
Protecting life, environment and property
Low-pressure water mist system local protection
Local protection in accordance with IMO MSC/Circ. 913Low-pressure water mist re-ghting system provided for local re suppression inareas, as specied in SOLAS II-2/10.5.6 for category A machinery space, such as
top of main engine, top of auxiliary engines, boiler fronts, incinerators and fuel oilseparators.
The system may be released locally by use of manual release button within the
protected space and from manned station or automatic by re detectors for ships
with unattended machinery space.
The central operating panel should always be located in the manned station
Control systemsn Option 1
With integrated AutroSafe I/O for interconnection with the
ships AutroSafe re detection system. The advantage is
saving cables as one of the AutroSafe loops are routed
through the local protection control panel.
n Option 2
For integration with any type of ships re detection system.Voltage free outputs from the ships re detection system is
required.
n Option 3
Touch screen operated system with integrated re detector
loops for conventional re detectors. Automatic activation
based on any two detectors on the loop covering one
object.
Advantages:n Tested in accordance with IMO MSC/circ. 913n Low water consumption, 1,1 1,6 l/min./m2
n Low power consumption, 1,5 5,5 kW
n Height 0,5 8 meters, operating pressure, 4 bar
n Height 8 14,5 meters, operating pressure, 9 bar
n Small pipe size,
n Low weight piping, PN10 and PN16n Type approved by all major classication societies
n Holding wheel mark certicate, Module B and D
Low pressure water mist local protection integrated with AutroSafe interactive re detection system Typical
layout
-
8/12/2019 Aureonica PC2013 MAR
61/66
Autronica Fire and Security AS n61
Autronica products 2013
Fire
suppressionsystems
Low-pressure water mist system total ooding
For Machinery Spaces cat. A and cargo pump room in accordance with IMOMSC/Circ. 1165Low-pressure water mist re-ghting system provided for total ooding in areas,
as specied in the FSS Code chapter 7 section 2.2 for category A machineryspace and cargo pump room. The system can be supplied to any vessel with
machinery spaces volume up to 3348 m3 . FlexiFOGcan protect up to 10.1
meters height with one single grid. The bilge is also protected by FlexiFOG. No
additional nozzles required to full IMO MSC/Circ. 913 for protection of high risk
areas.
The system may be released locally within the protected space and from manned
station. The control panel will always monitor and indicate status of the system.
Automatic release possibility for local protection when unmanned engine room
condition.
Common control system with local protection and accommodation.
Galvanised steel pipes can be used.
Advantages:
n Tested and approved in accordance with IMO MSC/circ. 1165n No need for tank for rst minutes operation
n No need for doorway manifolds
n Low water consumption, 1,71 l/min./m2
n Low power consumption, 15-60 kW
n Low pressure, 10,45 bar
n Height up to 10,1 meters, single leveln Low weight piping, PN16
n For manual electric operationn Type approved by all major classication societies
n Holding wheel mark certicate, Module B and D
Low-pressure water mist total ooding: Typical layout according to IMO MSC/Circ. 1165
combined with local protection according to IMO MSC/Circ. 913
-
8/12/2019 Aureonica PC2013 MAR
62/66
-
8/12/2019 Aureonica PC2013 MAR
63/66
Autronica Fire and Security AS n63
Autronica products 2013
Fire
suppressionsystems
Low-pressure water mist systems and Safe Return to Port
Safe Return to PortThe Safe Return to Port amendment to the IMO SOLAS regulations was madeeffective from 1 July 2010. The goal is that a vessel remains functional even in
the case of re or ooding in one compartment and is able to return safely to portwithout the need to abandon ship.
The regulations are mandatory for passenger ships having a length of 120 metres or more or having three or more main vertical
zones. These vessels have to be able to return to port after a casualty case, not exceeding a dened ooding or re casualty
threshold, and provide all persons on board basic services in so-called safe areas. For re casualty cases exceeding the
casualty threshold but not exceeding one main vertical re zone, systems for supporting orderly evacuation have to be availablefor 3 hours.
The low-pressure water mist solution
The control system consists of two CPUs, each with its own program. Machinery space systems are hardwired with redundantzone valves. Manual release buttons have inputs to both CPUs.
Accommodation system zone monitoring is connected to the Ethernet ring via IE/As-I link modules.
Operation / Indication are carried out by minimum two touch screens connected to the Ethernet ring. In normal operation, the
main CPU is controlled. Change-over to the back-up CPU is carried out automatically or manually from either of the touchscreens.
Each of the pump packages has a 100% capacity and is connected to its own dedicated sea chest. The pump package is
common for both accommodation and machinery space systems, i.e. it is not necessary to have separate pumps for each of the
applications. The pump units is located in the foremost and aftmost main vertical zone.
Zone valves for machinery space protection have 100% redundancy and should be located at the pump station. Zone valves for
accommodation are normally located outside the protected re zone within a dedicated A0 enclosure, i.e. duplicate zone valvesare not required. If located outside A0 enclosure, the zone valves has to be duplicated..