PAGE : 1 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
AUP-X-400-V4 (ATX12V) Uninterrupted Switching Power Supply Technical Specification
Part No.
REVISION HISTORY
VERSION RELEASE DATE NOTES DATE
1. MAR-2011 IMPROVE THE EFFICIENCY NOT LESS THAN 80% AND COMPLAIN WITH EN60950-1:2006+A11:2009 2011/3/17
PAGE : 2 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
CONTENTS
1. INTRODUCE..………………………………………………………………………………………….. 04 1.1 SCOPE……….………………………………………………………………………………… 04 1.2 RELATED DOCUMENTS…………………………………………………………………… 04 2. IMPORTANT NOTICE BEFORE INSTALL …………………………………………………………. 04 3. APPLICABLE DOCUMENTS………………………………………………………………………… 04 4. ELECTRICAL SPECIFICATION……………………………………………………………………… 05 4.1 AC Input Voltage……………………………………………………………………………… 05 4.2 Frequency……………………………………………………………………………………… 06 4.3 Inrush Current…………………………………………………………………………………. 06 4.4 AC Input Current………………………………………………………………………………. 06 4.5 Efficiency……………………………………………………………………………….……… 06 5. Output Requirements..................................................…………………………………….……... 07 5.1 Output Regulations...........................................………………………………………..…. 07 5.2 DC Load Requirements...............................…....…………………………………….…… 07 5.3 Cross Regulation ………................................……...…………………………………..… 08 5.4 +5V Standby Voltage................................…..…....……………………………………..… 08 5.5 DC Output Voltage Ripple And Noise…............………………………………..……….… 08 5.6 Total Output Power.............…...............................…………………………………..….… 08 5.7 Remote ON/OFF Control.….................................………………………………………… 08 5.8 Power Sequence…………...................................……………………………….………… 09 5.9 Power on Time (T1)………….…………………………………………………………..….. 09 5.10 Rise Time (T2).………………………………..………………………………………………. 09 5.11 Power Good Delay Time (T3)…………………………………………………………..….. 09 5.12 Power Good Rise Time (T4).…………………………………………………………………. 09 5.13 Hold Up Time (T5)……………………………………………………………………………. 10 5.14 Power Fail Signal (T6)…..……………….……………..……………………………………. 10 5.15 USPS Timing Chat…………………………………………………………………………. 10 6. Protections........................................................................……………………………………..… 11 6.1 Over Voltage Protection.......................................…………..…………………………..… 11 6.2 Short Circuit Protection........................................………….…………………………..…. 11 6.3 Protection Reset.....................................................…………..…………………………… 11 6.4 Over Shoot.............................................................…………...………………………….. 12 6.5 Over Power Protection.......................................……………………………………..…… 12 7. MECHANICAL SPECIFICATION.........................................……………………………………..… 13 7.1 USPS MAIN BODY PHYSICAL DIMENSION.....…………..…………………………..… 13 7.2 AC INPUT CONNECTOR …………………………………………………………………… 13 7.3 DC OUTPUT CONNECTOR ………………………………………………………………… 14
PAGE : 3 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
8. BATTERY PACK MECHANICAL SPECIFICATION..............……………………………………..… 19 8.1 PHYSICAL DIMENSION.....…………..…………………………..…………………………. 19 8.2 BATTERY PACK PANEL …………………………………………………………………… 19 8.3 BATTERY PAC WIRES CONFIGURATION & CONNECTOR …………………………. 20 8.4 LED INDIACTION AND ALARM TABLE ………………………………………………….. 20 8.5 BATTERY PACK INSIDE CONNECTION…………………………………………………… 21 8.6 BATTERY SPECIFICAITON………………………………………………………………….. 21 9. COMMUNICATION PORT AND RUPS 2000 BACKUP UTILITY HARDWARE
CONFIGURATION …………………………..………………………………………………………… 22
9.1 COMMUNICATION PORT PIN ASSIGNMENT…………………………………………… 22 9.2 SELECT SUITABLE COMMUNICATE CABLE FOR YOUR PC SYSTEM’S RS-232 PORT………… 22 9.3 RUPS 2000 PACKAGE……………………………………………………………………… 23 10. USING THE UPS MONITORING PROGRAM THAT COMES WITH WINDOWS XP………. 24 11. Environment....................................................................……………………………………...…. 28 11.1 Operation/Storage Temperature Range............………….……………………………..… 28 11.2 Humidity................................................................…………………………………….….. 28 12. Safety.................................................................................……………………………….……….. 28 13. EMI Requirements..........................................................………………………………….……… 28 14. Dielectric Voltage Withstand (HI-POT).......................……………………………………..…….. 28 15. PFC.........................................................…………………………….……………………………… 28 16. Electrostatic Discharge Requirement (ESD)................………………………………….……… 28 17. EFT/Burst........................................................................…………………………………….…… 28 18. Surge.....................................…………………………………………. ……………………………… 28 19. Burn-In.............................................................................……………………………………….… 29 20. MTBF...............................................................................……………………………………….…. 29
PAGE : 4 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
1. INTRODUCE
1.1 SCOPE
THIS SPECIFICATION DESCRIBES THE PERFORMANCE CHARACTERISTICS OF AUP-X-400-V4 USPS (UNINTERRUPTED SWITCHING POWER SUPPLY) PRODUCT, WHICH IS A 400WATT, 7 OUTPUTS SWITCHING POWER SUPPLY IN EPS12V FORM FACTOR WITH BATTERY BACKUP FUNCTION. THE AUP-X-400-V4 IS BASED ON ATX / PS/2 FORM FACTOR DESIGNED TO MEET THE MOST OF INTEL AND AMD COMPUTER REQUIREMENTS.
1.2 RELATED DOCUMENTS
THIS DOCUMENT IS BASED ON THE SPECIFICATIONS LIST IN BELOW TABLE, WITH EXCEPTIONS AS DESCRIBED IN THE BODY OF THIS DOCUMENT. FOLLOW INTEL ATX12V POWER SUPPLY DESIGN GUIDE TO UPDATE SPECIFICATION, SUCH AS POWER, CURRENT, EFFICIENCY, CONNECTORS …ETC. DOCUMENT TITLE ATX12V POWER SUPPLY DESIGN GUIDE
2. IMPORTANT NOTICE BEFORE INSTALL
1. TO FULLY CHARGE THE BATTERY FOR THE FIRST TIME IT IS USED, ALLOW THE POWER CORD
TO REMAIN PLUGGED IN A FULL 24 HOURS. NORMAL TIME TO RECHARGE THE BATTERY TO
ITS FULL CAPACITY IS 5 ~ 8 HOURS. 2. IF THERE IS A DEFECT IN THE BATTERY PACK, THE BATTERY BACKUP WILL NOT FUNCTION.
CONTACT YOUR SUPPLIER OR TECHNICAL ENGINEER. ( BUT, SWITCHING POWER SUPPLY
STILL CAN FUNCTION WITH AC POWER LINE. )
3. APPLICABLE DOCUMENTS
THE FOLLOWING DOCUMENTS FORM A PART OF THIS SPECIFICATION TO THE EXTEND SPECIFIED: EUROPEAN STANDARDS
EN60950-1 : 2006 + A11 : 2009 EN 62301 : 2005
EN 60065 : 2002 + A1 : 2006 EN 61347-2-13 : 2006 EN 61347-1 : 2008
BASIC AND INTERNATIONAL STANDARDS IEC 60950-1 : 2005 IEC 62301 : 2005
IEC 60065 : 2001 + A1 : 2005 IEC 61347-2-13 : 2006 IEC 61347-1 : 2007
EST STANDARDS :
EN 55022 : 2006 + A1 : 2007, CLASS B EN55024 : 1998 + A1 : 2001 + A2 : 2003 IEC 61000-4-2 :2008 EN 61000-3-2 : 2006 IEC 61000-4-3 : 2006 +A1 : 2007 IEC 61000-4-4 : 2004 EN 61000-3-3 : 1995 + A1 : 2001 +A2 : 2005 IEC 61000-4-5 : 2005 IEC 61000-4-6 “ 2003 + A1 : 2004 + A2 : 2006 IEC 61000-4-8 : 1993 + A1 : 2000 IEC 61000-4-11 : 2004
PAGE : 5 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
4. ELECTRICAL SPECIFICATION
UNLESS OTHERWISE NOTED, THE ELECTRICAL REQUIREMENTS SPECIFIED HEREIN SHALL ACCORD WITH THE ENVIRONMENTAL LIMITS FOR NORMAL OPERATION DEFINED IN SECTION 7 OF THIS DOCUMENT.
ITEM APOLLO USPS AUP-X-400-V4 CAPACITY 400W INPUT VOLTAGE 90~260VAC AUTO VOLTAGE SELECTED INPUT FREQUENCY 60/50HZ POWER FACTOR 0.97 (ACTIVE PFC) SURGE PROTECTION YES
+12 V1 / 16A +12 V2 / 16A + 5 V / 30 A + 3.3 V / 28 A -12 V / 0.8A -5 V / 0.3A
OUTPUT DC CURRENT *1 MAX. CONTINUOUS TOTAL DC OUTPUT SHALL NOT EXCEED 350W, PEAK 400W)*2. MAX. COMBINED OUTPUT ON +5V & +3.3V SHALL NOT EXCEED 150W.
+5V STAND BY / 2.5A BATTERY CHARGER 27.6V/300MA WEIGHT 6 KGS (WITH BP5EP-2410W BATTERY PACK ) USPS MAIN BODY DIMENSION 150 X 145 X 86 MM BATTERY PACK DIMENSION AND TYPE BP-5EP 219 X 145 X 42 MM3, 3.5KGS
LEAD ACID (MAINTENANCE FREE) 24V/3AH HRL1210W / 178 X 33.6 X 64 MM3 ( PER UNIT )
DESIGNED MOSFET IC WITH COPYRIGHT HYBRIDE IC DESIGN
INRUSH CURRENT 80A FOR 230VAC, 60A FOR 115VAC OVER VOLTAGE PROTECTION YES OVER POWER PROTECTION YES >110%~150% OVER CURRENT PROTECTION 240VA OF EACH DC OUTPUT
UPS Mode / Function Specification (V4.0) CAPACITY 600VA AC INPUT VOLTAGE TRANSFER POINT ( UNDERVOLT )
FROM NORMAL TO BACKUP : 80 / 175 VAC FROM BACKUP TO NORMAL : 90 / 185 VAC
AC INPUT VOLTAGE TRANSFER POINT ( OVERVOLT )
PROTECTION BY FUSE
TRANSFER TIME 0 MS FOR DC OUTPUT(COMPUTER) SYSTEM BACKUP TIME ( BACKUP FOR A PC SYSTEM )
AT LEAST 1 MINUTES LONGER BACKUP TIME CAN USE OTHER BATTERY PACK
RECHARGE TIME 5~8 HOURS BATTERY VOLTAGE MONITORING LED DISPLAY, BUZZER BATTERY ISOLATED IF W/O AC WHEN AC POWER SOURCE IS NOT AVAILABLE, THE
RELAY WILL ISOLATED WITH DC POWER SOURCE TO AVOID THE BATTERY POWER AUTO DISCHARGE.
4.1 AC Input Voltage
The power supply shall be operated at universal input voltage defined in the following table.
lnput Voltage MIN NOM MAX
Voltage 90 100-240 264
PAGE : 6 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
4.2 Frequency
The input frequency range is from 50Hz to 60Hz.
4.3 Inrush Current
The max inrush current is 80A for 230VAC / 60A for 115VAC.
4.3.1 Cold Start
Conditions Limits
115/230VAC, full load. 25℃ ambient.
No component over stress or damage should occur to the power supply. Input fuse shall not blow.
4.3.2 Warm Start
4.4 AC Input Current
AC Input MAX Units
100~240V 7-4 AMPS
4.5 Efficiency
The power supply efficiency shall not be less than 80% at the maximum load of sec. 5.2 and 115/230Vac
input voltage.
Conditions Limits
Turn off at 132/264VAC full load for 1 sec then turn on at the peak of the input voltage cycle at 25℃ ambient.
No component over stress or damage should occur to the power supply. Input fuse shall not blow.
PAGE : 7 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
5 Output Requirements
5.1 Output Regulations
Output Voltage Range MIN Nominal MAX Units
+5V ±5% +4.75 +5.00 +5.25 Volts
+12V1 ±5% +11.40 +12.00 +12.60 Volts
+12V2 ±5% +11.40 +12.00 +12.60 Volts
-5V ±10% -4.50 -5.00 -5.50 Volts
-12V ±10% -10.80 -12.00 -13.20 Volts
+3.3V ±5% +3.14 +3.30 +3.47 Volts
+5Vsb ±5% +4.75 +5.00 +5.25 Volts
Note: 1). The above voltage range should also include ripple and noise.
2). The output voltage should be measured at the terminals of output connector.
5.2 DC Load Requirements
Output Voltage MIN NOM MAX Units
+5V 2.0 15 30 AMPS
+12V1 2.0 8 16 AMPS
+12V2 2.0 8 16 AMPS
-5V 0.0 0.15 0.3 AMPS
-12V 0.0 0.4 0.8 AMPS
+3.3V 2.0 15 28 AMPS
+5Vsb 0.5 1 2.5 AMPS
Note : 1). The maximum continuous total DC output power shall not exceed 400 Watts.
2). The maximum continuous combined load on +5V and +3.3V outputs shall not
exceed 150 Watts. Combined load on +12V1 and +12V2 outputs shall not
exceed 360(30A) Watts.
3). The maximum continuous combined load on +5V, +3.3V and +12V1,+12V2
outputs shall not exceed 380 Watts. –5V and -12V outputs shall not exceed
9.6Watt.
PAGE : 8 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
5.3 Cross Regulation
The DC loads shall remain within the ranges specified in 5-2 DC Load Requirements and the DC output
voltages also shall remain within the regulation ranges specified in 5-1 Output Regulation when
measured at the load end of the output connectors.
5.4 +5V standby voltage
The +5Vsb is on whenever the AC power is present.
5.5 DC Output Voltage Ripple and Noise
Output Voltage Ripple & Noise Max Units
+5V 50 mV
+12V1 120 mV
+12V2 120 mV
-5V 100 mV
-12V 120 mV
+3.3V 50 mV
+5Vsb 50 mV
Note : 1)The measurements should be made by crossing a 10uF/ electrolytic and a 0.1uF ceramic
disk capacitors at each output with measuring bandwidth from DC to 20 MHz. If ambient
temperature is under 20℃ or over 30℃, the AC input should be nominal input.
5.6 Total Output Power
MAX Units
400 Watts
5.7 Remote ON/OFF Control
The power supply outputs shall be enabled with an active-low TTL signal.
When TTL signal is low, the DC outputs are to be enabled.
PAGE : 9 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
When TTL signal is high or open circuited, the DC outputs are to be disabled.
Electronic means or a mechanical switch may activate the TTL signal.
After the TTL signal is active high, must wait for 3 seconds before active low again.
5.8 Power Sequence
On Off AC IN T1 T5 PS_ON
95% +12V 10% +5V O/P’s +3.3V T2
T3 PG#
T4
T6
5.9 Power On Time (T1)
5.10 Rise Time (T2)
5.11 Power Good Delay Time (T3)
MIN. MAX. Units
100 500 ms
The test environment is 25℃ condition @ nominal input.
5.12 Power Good Rise Time (T4)
MAX Units
500 ms
Min. MAX. Units
0.5 20 ms
MAX Units
10 ms
PAGE : 10 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
5.13 Hold Up Time (T5)
The test environment is 25℃ & full load condition @ nominal input.
5.14 Power Fail Signal (T6)
Power good signal shall go to a down level 1ms before +5V output voltage falls below the regulation
limits during PS-ON signal pull high.
5.15 USPS TIMING CHAT
(A) 2 TURN ON COMPUTER POWER SYSTEM, THE CONDITIONS OF EACH POINT ARE AS BELOW:
1 AC LINE NORMAL
MIN. Units
16 ms
MIN. Units
1.0 ms
PAGE : 11 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
3 BATTERY / DC SUPPORT NORMAL
4 5VSB OUTPUT NORMAL
6 REMOTE ON/OFF STAY IN HI CONDITION, IT’S ALSO IN STANDBY MODE.
WHEN ACTIVE REMOTE ON, 5 DC O/P WILL UP AND 8 PG DELAY FOR 200~350MS THEN IT ALSO UP, THEN THE
COMPUTER GO INTO NORMAL OPERATION.
(B) IF THE AC LINE HAS ANY CHANGING, BUT TIMING SHORTER THAN 20MS. THEN, IT WON’T EFFECT TO DC
OUTPUTS AND ALL SIGNALS ARE AS NORMAL.
(C) IF THE AC LINE BROWN OUT THAN 20MS, THEN ALL POINTS WILL BE AFFECTED. (FOR RED LINE SHOWS WITHOUT
UPS BACKUP) 568 UPS MONITORING SIGNAL WILL SEND AC FAIL, HI TO PC SYSTEM THROUGH RS-232
PORT, MEANWHILE ALL OF DC OUTPUTS ARE BACKUP BY BATTERY PACK TO KEEP STABILE OUTPUTS FOR PC
SYSTEM WITHOUT ANY INTERRUPTED.
(D) IF THE AC RECOVER, THEN ALL SIGNALS WILL BE RECOVER TO NORMAL, TOO.
(E) AND (F) ARE REPEAT ABOVE PROCEDURES.
IF 3 DC INPUT ( BATTERY PACK ) VOLTAGE DROP TO 21.5 ± 0.5V, THEN WILL SEND A SIGNAL ”BATTERY
LOW” TO PC SYSTEM.
IF 3 DC INPUT VOLTAGE DROP TO 18.5 ± 0.5V, THEN WILL SEND A SIGNAL 7 ”SHUT DOWN” TO PC
SYSTEM
6. Protections
6.1 Over Voltage Protection
When the DC outputs (+5V, +12V1,+12V2, +3.3V) have over voltage condition, the power supply shall
provide latch mode over voltage protection.
DC output Max Unit
+12V1,+12V2 15.5 V
+5V 6.5 V
+3.3V 4.6 V
6.2 Short Circuit Protection
A short circuit placed to ground shall cause no damage or power supply shall be shutdown. (The contact
resistance is 0.05 ohm when the outputs short circuit.)
6.3 Protection Reset
When the power supply latches into shutdown condition due to a fault on an+5V,+3.3V,+12V1,+12V2
output(OCP, OVP, UVP), the protection shall reset after the fault has been removed, use remote on/off
control or recycle the AC power again for a typical of 5 seconds.
PAGE : 12 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
6.4 Over Shoot
Any output overshoot at turn on shall be less than 15% of the nominal output value (with resistive load)
as described in sec. 5.1.
6.5 Over Power Protection
At 115/230Vac input the power supply will shut down all DC output within 110% to 150% of full load.
PAGE : 13 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7. MECHANICAL SPECIFICATION
7.1 USPS MAIN BODY PHYSICAL DIMENSION
W150*H86*D140 (MM)
7.2 AC INPUT CONNECTOR
THE AC INPUT RECEPTACLE SHALL BE AN IEC 320 C14 TYPE OR EQUIVALENT.
PAGE : 14 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7.3 DC CONNECTOR
7.3.1 EPS12V/ AX 12V MAIN POWER CONNECTOR: MAIN POWER CONNECTOR (P1) / CABLE (L1) :
CONNECTOR: MOLEX 39-01-2200 OR EQUIVALENT (MATING MOTHERBOARD CONNECTOR IS MOLEX 39-29-9202 OR EQUIVALENT)
PIN COLOR SIGNAL AWG PIN COLOR SIGNAL AWGORANGE +3.3VDC 16
1 ORANGE +3.3VDC 16 13 BROWN +3.3VS. 20 2 ORANGE +3.3VDC 16 14 BLUE -12VDC 18 3 BLACK COM 16 15 BLACK COM 16 4 RED +5VDC 16 16 GREEN PS_ON# 22 5 BLACK COM 16 17 BLACK COM 16 6 RED +5VDC 16 18 BLACK COM 16 7 BLACK COM 16 19 BLACK COM 16 8 GRAY PWR_OK 16 20 N/C ------ -- 9 PURPLE +5VSB 18 21 RED +5VDC 16
+12V1DC 16 +5VDC 16 10 YELLOW
+12VS. 20 22 RED
+5VS. 20 11 YELLOW +12V1DC 16 23 RED +5VDC 16 12 ORANGE +3.3VDC 16 24 BLACK COM 16
Cable L1: 550+/-20mm
VS. : REMOTE SENSE SIGNAL DOUBLE CRIMPED WITH DC OUTPUT VOLTAGECONTACT. FOR ATX12V PLEASE USE 20 PIN CONNECTOR. FOR EPS12V PLEASE USE 24 PIN CONNECTOR.
7.3.2 PROCESSOR POWER CONNECTOR (P14) / CABLE (L14)
CONNECTOR: 8 PIN MOLEX 39-01-2080 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 BLACK COM 16
2 BLACK COM 16 3 BLACK COM 16 4 BLACK COM 16 5 YELLOW/BLACK +12V2DC 16
6 YELLOW/BLACK +12V2DC 16 7 YELLOW/BLACK +12V2DC 16
8 YELLOW/BLACK +12V2DC 16
L14 (UL1007)550 +/-10
MM
PAGE : 15 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7.3.3 PROCESSOR POWER CONNECTOR (P15) / CABLE (L15)
CONNECTOR: 6 PIN MOLEX 39-01-2060 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 YELLOW/BLACK +12V2DC 16
2 YELLOW/BLACK +12V2DC 16 3 YELLOW/BLACK +12V2DC 16 4 BLACK COM 16 5 BLACK COM 16 6 BLACK COM 16
L14 (UL1007)550 +/-10
MM
7.3.4 +12V1 POWER CONNECTOR (P11) / CABLE (L11)
CONNECTOR: MOLEX 39-01-2040 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 BLACK COM 16
2 BLACK COM 16
3 YELLOW/BLACK +12V2DC 16
4 YELLOW/BLACK +12V2DC 16
L11 (UL1007)
550 +/- 10 MM
7.3.5 PERIPHERAL CONNECTOR(S) P2 / CABLE (L2)
CONNECTOR: AMP 1-480424-0 OR MOLEX 8981-04P OR EQUIVALENT.
PIN COLOR SIGNAL AWG CABLE
1 YELLOW +12V1DC 18
2 BLACK COM 18
3 BLACK COM 18
4 RED +5VDC 18
L2 (UL1007) 550 +/-10 MM L2+(UL1007)
150 MM
7.3.6 FLOPPY DRIVE CONNECTOR P3 / CABLE (L3)
CONNECTOR: AMP 171822-4 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 RED +5VDC 20
2 BLACK COM 20
3 BLACK COM 20
4 YELLOW +12V2DC 20
L3 (UL1007)
150MM
7.3.7 SERIAL ATA POWER CONNECTOR (P13) / CABLE (L13)
CONNECTOR: MOLEX 88751 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 YELLOW +12V1DC 18
2 BLACK COM 18
3 RED +5VDC 18
4 BLACK COM 18
5 ORANGE +3.3VDC 18
L13 (UL1007)550 +/-10 MM
L13+(UL1007)
200MM
PAGE : 16 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7.1.1 BACKUP DC INPUT CONNECTOR (P4) / CABLE (L4)
CONNECTOR: TKP H7619P-02 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 RED BAT + VE 16
2 BLACK BAT -VE 16
L4 150MM UL1007
7.3.8 LED DISPLAY CONNECTOR (P5) / CABLE (L5)
CONNECTOR: TKP 7755-05 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 YELLOW LED1 22
2 ORANGE LED2 22
3 RED LED3 22
4 ------ ------- ------
5 BLACK COM 22
L5 150MM
(UL1007)
7.3.9 COMMUNICATE PORT CONNECTOR (P7) / CABLE (L7) CONNECTOR: TKP 7755-06 OR EQUIVALENT
PIN COLOR SIGNAL AWG CABLE
1 YELLOW BAT. LOW 22
2 ORANGE GND 22
3 RED SHUTDOWN 22
4 BROWN GND 22
5 GREEN AC FAIL 22
6 ------ ------ ----
L7 150MM
(UL1007)
7.3.10 COMMUNICATE PORT CONNECTION CABLE (P7+ TO DB9)
P7+ CONNECTOR: TKP 7755-6P OR EQUIVALENT / CABLE : L7+ TO DB9 , 450MM (UL1007)
DB9 PIN COLOR SIGNAL AWG P7+ PIN P7+
1 BROWN BAT. LOW 22 1
3 RED GND 22 2
4 ORANGE SHUTDOWN 22 3
7 YELLOW GND 22 4
8 GREEN AC FAIL 22 5
DB9
------ ------- 6
PAGE : 17 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7.3.11 COMMUNICATE PORT CONNECTION CABLE (P7+ TO IDE A) (OPTION)
P7+ CONNECTOR: TKP 7755-6P OR EQUIVALENT / CABLE : L7+ TO IDE A , 450MM (UL1007)
IDE A PIN COLOR SIGNAL AWG P7+ PIN P7+
1 BROWN BAT. LOW 22 1
3 RED GND 22 2
4 ORANGE SHUTDOWN 22 3
7 YELLOW GND 22 4
8 GREEN AC FAIL 22 5
------ ------- 6
7.3.12 COMMUNICATE PORT CONNECTION CABLE (P7+ TO IDE B) (OPTION)
P7+ CONNECTOR: TKP 7755-6P OR EQUIVALENT / CABLE : L7+ TO IDE B , 450MM (UL1007)
IDE B PIN COLOR SIGNAL AWG P7+ PIN P7+
1 BROWN BAT. LOW 22 1
3 RED GND 22 2
4 ORANGE SHUTDOWN 22 3
7 YELLOW GND 22 4
8 GREEN AC FAIL 22 5
------ ------- 6
PAGE : 18 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
7.3.13 COMMUNICATE PORT CONNECTION CABLE (P7+ TO CN1 OF INTERFACE BOARD) (OPTION)
P7+ CONNECTOR: TKP 7755-6P OR EQUIVALENT / CABLE : L7+ TO H110-5, 2.00, 450MM (UL1007)
5 PIN COLOR SIGNAL AWG P7+ PIN P7+
1 BROWN BAT. LOW 22 1 2 RED GND 22 2 3 ORANGE SHUTDOWN 22 3 4 YELLOW GND 22 4 5 GREEN AC FAIL 22 5
------ ------- 6
7.3.14 INTERFACE BOARD FOR USB B TYPE PORT
PAGE : 19 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
8. BATTERY PACK MECHANICAL SPECIFICATION 8.1 PHYSICAL DIMENSION : L219 X W145 X H41.5 (MM)
8.2 BATTERY PACK PANEL
8.2.1 THE L6+ CABLE OF USPS MAIN BODY HAS A MAIN SWITCH. THIS MAIN
SWITCH SHOULD INSTALL AT SUITABLE PLACE OF PC CHASSIS AND THE PC
SYSTEM HAS A TURN ON/OFF SWITCH ON THE CHASSIS FRONT PANEL.
8.2.2 PLEASE SWITCH THIS MAIN SWITCH TO “ I “ POSITION.
8.2.3 PUSH THE TURN ON/OFF SWITCH, THEN THE PC SYSTEM WILL START TO
WORK.
PAGE : 20 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
8.3 BP-5EP BATTERY PACK WIRES CONFIGURATION & CONNECTOR
8.3.1 BACKUP DC INPUT CONNECTOR (P4+) / CABLE (L4+) CONNECTOR: TKP H7619R-02 OR EQUIVALENT
CONNECTOR: CABLE
SIGNAL COLOR AWG
UL1007
1 BAT +VE RED 16 150MM
2 BAT -VE BLACK 16 150MM
8.3.2 LED DISPLAY CONNECTOR (P5+) / CABLE (L5+)
CONNECTOR: TKP 7755P-05 OR EQUIVALENT
PIN SIGNAL COLOR AWG CABLE 1 LED1 YELLOW 22
2 LED2 ORANGE 22
3 LED3 RED 22
4
5 COM BLACK 22
L5 150MM
(UL1007)
8.4 LED INDICATION AND ALARM TABLE
UTILITY STATES LED INDUCTOR STATE BUZZER STATE
NORMAL
BLACKOUT, UPS ON (24~21.5V)
BEEP.. BEEP.. BEEP .. ( 3 SECONDS INTERVAL )
BATTERY LOW (21.5~18.5V)
BEEP………… ( SOUNDS QUICKLY AND
SHORT )
AC NORMAL / BATTERY FAIL
PAGE : 21 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
8.5 BATTERY PACK INSIDE CONNECTION
8.6 BATTERY SPECIFICATION
PAGE : 22 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
9 COMMUNICATION PORT AND RUPS 2000 BACKUP UTILITY HARDWARE
CONFIGURATION 9.1 COMMUNICATION PORT PIN ASSIGNMENT
PIN RS-232 USPS 1 DCD BATTERY LOW
3 TXD GND
4 DTR SHUTDOWN
7 RTS GND
8 CTS AC FAIL
9.2 SELECT SUITABLE COMMUNICATE CABLE FOR YOUR PC SYSTEM’S RS-232 PORT
USPS OFFER THREE CABLES FOR INTERNAL AND EXTERNAL TYPE RS-232, YOU ONLY NEED
TO CHOICE ONE OF THEM FOR YOUR PC SYSTEM.
FOR DB9 PORT, PLEASE CONNECT THE DB9 PIN TO PIN CABLE TO CONNECT WITH EXTERNAL
RS-232 PORT!
PAGE : 23 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
9.3 RUPS 2000 PACKAGE : 1. DB9 PORT PIN TO PIN CABLE 2. USB-B TO USB-A CABLE 3. RS-232 TO USB INTERFACE BOARD 4. CD DISKETTE WITH SOFTWARE BACKUP UTILITY FOR WINDOWS SERIES, DOS, LINUX,
NOVELL... 5. USER MANUAL
FOR MORE DETAIL OF RUPS 2000, PLEASE REFER THE USER MANUAL!
PAGE : 24 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
10 Using the UPS Monitoring Program That Comes With Windows XP
( For Window 7, please use RUPS 2000 V4.2 version )
10.1 WITH THE COMPUTER AND THE USPS OFF, CONNECT THE SERIAL PORT CONNECTION CABLE BETWEEN USPS
MAIN BODY DB9 PORT AND AN OPEN RS-232 SERIAL PORT ON THE COMPUTER.
10.2 TURN THE USPS ON AND START THE COMPUTER.
10.3 ONCE THE COMPUTER HAS STARTED, CLICK ON START, THEN CONTROL PANEL.
10.4 IN THE CONTROL PANEL, DOUBLE-CLICK ON POWER OPTIONS.
10.5 CLICK THE UPS TAB.
PAGE : 25 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
10.6 CLICK THE SELECT BUTTON
10.7 SET THE MANUFACTURER TO GENERIC.
10.8 SELECT THE COM PORT THAT THE USPS IS CONNECTED TO.
10.9 CLICK ON CUSTOM SO IT IS HIGHLIGHTED.
10.10 LICK THE NEXT BUTTON.
PAGE : 26 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
10.11 ET THE UPS SIGNAL POLARITY AS SHOWN BELOW.
10.12 LICK THE FINISH BUTTON
10.13 LICK THE CONFIGURE BUTTON.
PAGE : 27 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
10.14 ECONDS BETWEEN POWER FAILURE AND FIRST NOTIFICATION - THIS IS THE TIME BETWEEN WHEN THE
POWER FAILS AND THE UPS STARTS BEEPING. SECONDS BETWEEN SUBSEQUENT POWER FAILURE
NOTIFICATIONS - THIS IS THE TIME BETWEEN BEEPS DURING A POWER FAILURE
10.15 INUTES ON BATTERY BEFORE CRITICAL ALARM - THIS DETERMINES HOW LONG THE UPS WILL RUN
BEFORE THE OPERATING SYSTEM STARTS TO SHUT DOWN. IF LEFT BLANK, THE UNIT WILL RUN UNTIL THERE IS
APPROXIMATELY 2 MINUTES OF BACKUP TIME REMAINING, THEN THE OPERATING SYSTEM WILL START TO SHUT
DOWN.
10.16 EXT, INSTRUCT THE COMPUTER TO: - LEAVE AS "SHUT DOWN".
10.17 INALLY, TURN OFF THE UPS. - IF CHECKED, THIS WILL ALLOW THE UPS TO BE TURNED OFF
AUTOMATICALLY ONCE THE OPERATING SYSTEM IS SHUT DOWN.
10.18 LICK THE OK BUTTON
10.19 LICK THE APPLY BUTTON
PAGE : 28 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
11. Environment
11.1 Operation/Storage Temperature Range
Operation : 5℃ to 50℃(nominal input)
Storage : -40℃ to 70℃
Humidity (none condensing)
Operation: 20% to 85% RH(nominal input)
Storage : 10% to 95% RH
12. Safety
UL60950-1
CE EN 60950 : 2006, + A11:2009
13. EMI REQUIREMENTS
CE
FCC part 15 sub part J class B at system load
CISPR 22 CLASS B
14. Dielectric Voltage Withstand (HI-POT) The power supply shall withstand for 3 seconds minute without breakdown the application of an
1800Vac-supply voltage applied between both input line and chassis (10mA AC Cutoff current). Isolating
transformers shall similarly withstand 4242Vdc applied between both primary and secondary windings for
a minimum of one minute.
15. PFC Active Power Factor Correction, complies with EN 61000-3-2: 1995+A1+A2:1998, Class D.
16. Electrostatic Discharge (ESD) Comply with IEC 61000-4-2.
17. EFT/ Burst Comply with IEC 61000-4-4.
18. Surge Comply with IEC 61000-4-5.
LOAD100%80%
50℃ 40℃
PAGE : 29 / 29 AUP-X-400-V4 (BP-5EP) ATX12V 2011.03
19. Burn-In Applying 115 Vac ± 10 % or 230 Vac ± 10% input voltage and maximum load (80%) for this product in 45 ±
5 ℃ chamber.
20. M.T.B.F. The power supply shall have a minimum mean time between failure greater than 100,000 hours at
continuous operation of 100% load and an ambient temperature of 25℃ .
21. Label
Label 1 : USPS Main Body Main Label
Label 2 : USPS Main Body Label for Serial No.
Label 3 : Battery Pack Label, Same as Label 2 format.
REMARK : ALL OF INFORMATION ARE ONLY FOR REFERENCE, THE CORRECT INFORMATION WILL BE CONFIRM AGAIN WITH