arc flash training
TRANSCRIPT
SM
Arc Flash Basics
TRAINING
SM
Electrical Hazards
(A) Touch Potential (B) Step Potential (C and D) Touch / Step Potential
• Shock
• Arc Flash
• Arc Blast
SM
Arc Flash & Arc Blast
• Arc Flash
– Heat
– Fire
• Arc Blast
– Pressure
– Shrapnel
– Sound
Example of an arcing fault
SM
Arc Flash
• As much as 80% of all electrical injuries are burns resulting from an arc flash and ignition of flammable clothing
• Arc temperature can reach 35,000°F - this is four times hotter than the surface of the sun
• Fatal burns can occur at distances over 10 ft
• Over 2000 people are admitted into burn centers each year with severe electrical burns
SM
Arc Blast
• An arc fault develops a “pressure wave”
• Sources of this blast include:– Copper expands 67,000 times its original volume when
vaporized
– Heat from the arc, causes rapid air expansion
• This may result in a violent explosion of circuit components and thrown shrapnel
• The blast can destroy structures, knock workers from ladders, or across the room
SM
Arcing Fault - Effects
Copper Vapor:Solid to Vapor
Expands by67,000 times
Intense Light
Hot Air-Rapid Expansion
35,000 F
Pressure Waves
Sound Waves
Molten Metal
Shrapnel
SM
Arc Flash Hazard
• Energy of Arc Flash determined by:– Arcing fault duration or time to clear
• Speed of the overcurrent protective device
– Arcing fault current magnitude• Available fault current
• Current-limitation can reduce
– Distance to Arcing Fault
SM
Test 4 Still Photo Before
SM
Test 4 Still Photo INITIAL
SM
Test 4 Still Photo DURING
SM
Test 4 Still Photo FINAL
SM
Test 4 RESULTS
• Burns
– 3rd Degree at Neck and Hands
– Shirt did not ignite and reduced to below 2nd degree burn
• Sound – 141.5 db
• Pressure – Collapsed Lungs
SM
NFPA 70E 110.8(B)(1)
– Requires an electrical hazard analysis if working on or near exposed conductors or circuit parts• Shock Hazard Analysis
– “Approach Boundaries”
• Flash Hazard Analysis – Flash Protection Boundary
– Incident Energy / PPE
NFPA70E - Electrical Hazard Analysis
SM
Shock Hazard Analysis
• NFPA 70E 130.2(A)
• A shock hazard analysis shall determine:– The voltage to which exposed
– The boundary requirements
– The personal protective equipment necessary in order to minimize the possibility of electric shock to personnel
SM
Shock Protection Boundaries
• NFPA 70E 130.2(B)
• The shock protection boundaries identified
– Limited Approach: Qualified persons and unqualified if accompanied by qualified person
– Restricted Approach: Qualified persons only
– Prohibited Approach: Qualified persons only –PPE as if in direct contact with live part
SM
NFPA 70E Table 130.2(C)
Shock Protection Boundaries
Column Number (1) (2) (3) (4) (5)
Nominal System
Voltage Range
Limited approach Boundary Restricted
Approach
Boundary
Prohibited
Approach
Boundary
Exposed
Movable
Conductor
Exposed
Fixed
Circuit Part
Includes
Inadvertent
Movement
Adder
Includes
Reduced
Inadvertent
Movement
Adder
Phase-to-Phase
Energized Part to Employee - Distance in feet - Inches
Less than 50 V Not Specified Not Specified Not Specified Not Specified
50 V to 300 V 10 ft. 0 in. 3 ft. 6 in. Avoid Contact Avoid Contact
301V to 750 V 10 ft. 0 in. 3 ft. 6 in. 1 ft. 0 in. 0 ft. 1 in.
751 V to 15 kV 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in. 0 ft. 7 in.
15.1 kV to 36 kV 10 ft. 0 in. 6 ft. 0 in. 2 ft. 7 in. 0 ft. 10 in.
Column Number (1) (2) (3) (4) (5)
Nominal System
Voltage Range
Limited approach Boundary Restricted
Approach
Boundary
Prohibited
Approach
Boundary
Exposed
Movable
Conductor
Exposed
Fixed
Circuit Part
Includes
Inadvertent
Movement
Adder
Includes
Reduced
Inadvertent
Movement
Adder
Phase-to-Phase
Energized Part to Employee - Distance in feet - Inches
Less than 50 V Not Specified Not Specified Not Specified Not Specified
50 V to 300 V 10 ft. 0 in. 3 ft. 6 in. Avoid Contact Avoid Contact
301V to 750 V 10 ft. 0 in. 3 ft. 6 in. 1 ft. 0 in. 0 ft. 1 in.
751 V to 15 kV 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in. 0 ft. 7 in.
15.1 kV to 36 kV 10 ft. 0 in. 6 ft. 0 in. 2 ft. 7 in. 0 ft. 10 in.
SM
Flash Hazard Analysis
• NFPA 70E 130.3 Flash Hazard Analysis: Flash hazard analysis shall be done in order to protect personnel from the possibility of being injured by an arc flash. …”
• What is required?
– Determine Flash Protection Boundary
– Determine the personnel protective equipment (incident energy determination)
SM
Flash Protection Boundary
Linear distance from exposed live parts within which a person could receive second degree burns (1.2 cal/cm2) resulting from an arc flash
480V
MCC
SM
Flash Hazard Analysis
Three common methods (600V or less):1) Default FPB and task-hazard/ PPE tables
• Qualifiers and limitations
2) Utilize NFPA 70E equations• Incident energy – select PPE
• FPB
3) IEEE1584: equations or calculator • Incident energy – select PPE
SM
Flash Hazard Analysis
• NFPA 70E 130.7(C)(10) Protective Clothing and Personal Protective Equipment Matrix– Determine after calculating the incident energy
of the arc
– Hazard Risk Category• HRC 0: 0-1.2 cal/cm²
• HRC 1: 1.2-4 cal/cm²
• HRC 2: 4-8 cal/cm²
• HRC 3: 8-25 cal/cm²
• HRC 4: 25-40 cal/cm²
• DANGEROUS: > 40 cal/cm²
SM
Flash Protection Boundary (FPB)
Must wear appropriate PPE
Equ
ipm
en
t
NFPA70E - Electrical Hazard Analysis
Q
U
Q
UU
Q
Q U
+
UU
LIMITEDRESTRICTEDPROHIBITED
Arc Flash PPE
Shock PPE