Arc Flash Hazard Calculations – What does it

all mean?

Robert E. Fuhr, P.E.

PowerStudies, Inc.

Page 2: Arc Flash Hazard Calculations – What does it all mean?

Why are Arc Flash Hazard Studies Needed?

� To Increase Electrical Safety at your facility!

� Required by National Electric Code (NEC) and OSHA

� To Protect You!

Page 3: Arc Flash Hazard Calculations – What does it all mean?
Page 4: Arc Flash Hazard Calculations – What does it all mean?
Page 5: Arc Flash Hazard Calculations – What does it all mean?

OSHA Requirements

� Standard 29 CFR 1910 Subpart S, 1910 to 1910.336

� Must identify all hazards above 50 Volts

� Must put safeguards in place for these hazards

� Must train employees on safe work practices

� OSHA has officially adopted NFPA 70E

Page 6: Arc Flash Hazard Calculations – What does it all mean?

� Employers must provide workers with appropriate PPE as per the OSHA 29 1910.132 (h)(1) PPE payment requirement, i.e., (PPE) used to comply with this part, shall be provided by the employer at no cost to employees. Paragraph (h) became effective February 13, 2008, and employers must implement the PPE payment requirements no later than May 15, 2008

Page 7: Arc Flash Hazard Calculations – What does it all mean?

Key References in NEC ® -2008

�110.16 Flash Protection. Switchboards, panel boards, industrial control panels, and motor control centers in other than dwelling occupancies, that are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked to warn qualified persons of potential electric arc flash hazards.

Page 8: Arc Flash Hazard Calculations – What does it all mean?

NEC 110.16 (continued)

�The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

Page 9: Arc Flash Hazard Calculations – What does it all mean?

Key References in NEC ® -2011

� FPN No. 1 : NFPA 70E-2012, Standard For Electrical Safety in the Workplace,

provides assistance in determining severity of potential exposure, planning safe work practices and selecting personal protective equipment.

Page 10: Arc Flash Hazard Calculations – What does it all mean?

NFPA 70E -Flash Hazard Analysis

� 130.3 – A flash hazard analysis shall be donein order to protect personnel from the possibility of being injured by an arc flash.

� The analysis shall determine:– Flash Protection Boundary – Personal protective equipment

� Calculate using – Formulas in 130.3.A and Table 130.7(C)(9)(a)* in

NFPA 70E– * - Use with extreme caution!!!– Equations in IEEE 1584

Page 11: Arc Flash Hazard Calculations – What does it all mean?

Industry standards and regulations:

� OSHA 29 CFR 1910 Subpart S

� NFPA 70 - The National Electrical Code (2008 Edition)

� NFPA 70E - Standard for Electrical Safety in the Workplace (2004 Edition)

Page 12: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard Analysis Key Steps

� Use NFPA 70E* Tables, IEEE 1584, or Lee Equations to Determine

– Incident energy levels

– Arc Flash hazard distance

� * Use with extreme caution!

Page 13: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard Analysis Key Steps

� Use – Calculated Incident

Energy

– NFPA 70E Table 130.7(C)(11)

– to determine

� Hazard/Risk Category

� Required PPE

Page 14: Arc Flash Hazard Calculations – What does it all mean?

Acceptable & Informative Labels

Page 15: Arc Flash Hazard Calculations – What does it all mean?

NFPA 70E Table 130.7(C)(11)

Page 16: Arc Flash Hazard Calculations – What does it all mean?

Short CircuitFault Study

Coordination (PDC)Study

Arc Flash StudyDevice Operating Time

Arcing Fault Current

3 Phase BoltedFault Current

Arc Flash Label

Energy Level

Boundaries

Required PPE

Obtain EquipmentNameplate Data

& Settings

Page 17: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Energy Calculation

� Use 85%Ia

� Determine Upstream Protective Device Clearing Times (PDC Study)

� Repeat process for 100%Ia

� Use largest energy calculation

Page 18: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard Analysis Key Steps

�Determine:–Bolted Fault Currents (Short Circuit Study)

–Arcing Fault (AF) Current

–Upstream Protective Device Clearing Times (PDC Study) using AF

Page 19: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard Analysis Key Steps

�Calculate Arc Flash Energy

�Use NFPA 70E Tables to determine:– Glove Rating Class

– Limited Approach Boundary

– Prohibited Approach Boundary

– Restricted Approach Boundary

– Required PPE

Page 20: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Hazard Analysis Key Steps

� Arc Flash Warning Labels showing the details.

Page 21: Arc Flash Hazard Calculations – What does it all mean?

How a Short Circuit Study is Performed

� Obtain distribution system nameplate data for:

– Transformers

– Motors

– Circuit breakers, fuses, relays

– Switchgear

– Motor Control Centers

– Conductor sizes and lengths

Page 22: Arc Flash Hazard Calculations – What does it all mean?

How a Short Circuit Study is Performed

� Enter data into the computer program.

� Simulate short circuit at each location and calculate the fault current.

� Compare calculated fault current to equipment short circuit rating.

Page 23: Arc Flash Hazard Calculations – What does it all mean?

What is Protective Device Coordination (PDC) Study?

� Determines:

– fuse sizes

– Settings for relays and circuit breakers

– Device operating time

� The study has 2conflicting goals

Page 24: Arc Flash Hazard Calculations – What does it all mean?

Goal #1 - Maximum Selective Coordination Between Equipment

� Correct fuse sizes and settings will allow the device closest to a fault to trip.

� If the first device fails to operate, then the next upstream device will trip.

� Longer device trip delays = increased device coordination= greater incident energy

Page 25: Arc Flash Hazard Calculations – What does it all mean?

Selective Coordination 3-MSWBD MAIN

SWBD

XFMR-UTILSS

P 2- XFMR-UTILS

5-Fdr to ATS-E

6-PNL-A MAIN

PNL-A - 250 A

E N

ATS 260 Amp

1

2

3

Page 26: Arc Flash Hazard Calculations – What does it all mean?

Goal #2 - Maximum Equipment Protection and Reduction in Arc

Flash Energy� Correct fuse sizes and device settings will

quickly interrupt the fault current for a short circuit downstream.

� Shorter device delays = decreasedequipment damage = less Incident Energy

Page 27: Arc Flash Hazard Calculations – What does it all mean?

Maximum Equipment Protection

� (No Selective Coordination)

3-MSWBD MAIN

SWBD

XFMR-UTILSS

P 2- XFMR-UTILS

5-Fdr to ATS-E

6-PNL-A MAIN

PNL-A - 250 A

E N

ATS 260 Amp

1

1

1

Page 28: Arc Flash Hazard Calculations – What does it all mean?

� Must balance these two conflicting goals based upon the type of facility.

Page 29: Arc Flash Hazard Calculations – What does it all mean?

PDC Vocabulary

� Time Current Curve (TCC)

� Log-log graph of time versus current

� Every breaker, fuse, and relay has a time current characteristic curve.

Page 30: Arc Flash Hazard Calculations – What does it all mean?

PDC Vocabulary

� Selective Device Coordination

– The devices plotted on the time current curves are coordinated for all levels of fault current and time.

Page 31: Arc Flash Hazard Calculations – What does it all mean?
Page 32: Arc Flash Hazard Calculations – What does it all mean?

Fuse TCC

3-6 Sec

5 kA

@15 kA

This Fuse is Current Limiting –Clearing time is 0.004 seconds

Page 33: Arc Flash Hazard Calculations – What does it all mean?
Page 34: Arc Flash Hazard Calculations – What does it all mean?

Thermal Magnetic Trip Unit

� Thermal Unit is Fixed

� Instant-aneous

– Fixed

– Adjustable

Page 35: Arc Flash Hazard Calculations – What does it all mean?

Thermal Magnetic Breaker

20 kA0.01-0.025 Sec

4 kA

20-50 Sec

Page 36: Arc Flash Hazard Calculations – What does it all mean?
Page 37: Arc Flash Hazard Calculations – What does it all mean?
Page 38: Arc Flash Hazard Calculations – What does it all mean?

Solid State Trip

Unit

� SQ D NW 40H

� 4000 Amp

� Micrologic

Current Sensors

Rating Plugs

Current Setting

Page 39: Arc Flash Hazard Calculations – What does it all mean?

Solid State Trip

Unit

� Varies for each Trip Unit!

� Some Functions are Not Adjustable!

Long Time Pickup (LTPU)

Long Time Delay (LTD)

Short Time Pickup (STPU)

Short Time Delay (STD)

Instantaneous (I)

Short Time

Delay I2T-IN

(I2T)

Page 40: Arc Flash Hazard Calculations – What does it all mean?

Solid State Trip

� SQ D NW 40H

� 4000 Amp

� Micrologic

100 kA

0.01-0.06 Sec

6 kA

0.08-0.12 Sec 30 kA

170-210 Sec

Page 41: Arc Flash Hazard Calculations – What does it all mean?

Time Current Curves

� An example of a TCC with Coordinated Devices

Current in Amperes X 100

Page 42: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Energy Calculations

� Incident Energy Levels are dependent on: – Level of arcing fault current

– Upstream device clearing time.

� Multiple Sources

Page 43: Arc Flash Hazard Calculations – What does it all mean?

Typical Assumptions for an Analysis

� Trip time is determined by the upstream protective device settings.

� Worker is stationary.

� The maximum time that a worker will be exposed to the arc flash is 2.0 seconds. (Depends upon location!!!)

Page 44: Arc Flash Hazard Calculations – What does it all mean?

Current Vs Energy LevelsFault Current vs. Incident Energy

(Time Constant @ 0.025 Sec)

0 0 0

1 1 1 1 1 1 1

0

1

2

3

4

0 20 40 60 80 100

Fault Current

Inc

ide

nt

En

erg

y

Energy PPE Class

Page 45: Arc Flash Hazard Calculations – What does it all mean?

Time Vs Energy LevelsTime vs. Incident Energy

(Fault Current Constant @ 30 kA)

1 1 1 2 2 3 3 3 40

10

20

30

0 0.1 0.2 0.3 0.4 0.5 0.6

Device Operating Time

Inc

ide

nt

En

erg

y

Incident Energy PPE Class

Page 46: Arc Flash Hazard Calculations – What does it all mean?

Distance Vs Energy LevelsDistance vs. Incident Energy

(Time Constant @ 0.5 Sec & Fault = 60 kA)

0

124+ 34

0

10

20

30

40

50

0 50 100 150 200 250

Distance (Inches)

Inc

ide

nt

En

erg

y

Energy Class

Page 47: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Warning Labels

� What does it mean?

Page 48: Arc Flash Hazard Calculations – What does it all mean?

Limited Approach Boundary:

� An approach limit at a distance from an exposed live part within which a shock hazard exists. This value is determined by NFPA 70E (2004) Table 130.2(B).

� Qualified Persons

� Unqualified if accompanied by a Qualified Persons

� PPE not required if AF Boundary is not in Limited Approach Boundary

Page 49: Arc Flash Hazard Calculations – What does it all mean?

Restricted Approach Boundary

� An approach limit at a distance from an exposed live part within which there is an increased risk of shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the live part.

� Determined by NFPA 70E (2004) Table 130.2(B)

Page 50: Arc Flash Hazard Calculations – What does it all mean?

Restricted Approach Boundary

� Qualified Persons Only

� Must wear PPE

Page 51: Arc Flash Hazard Calculations – What does it all mean?

Prohibited Approach Boundary

� An approach limit at a distance from an exposed live part within which work is considered the same as making contact with the live part.

� Determined by NFPA 70E (2004) Table 130.2(B).

� Qualified Persons Only

� PPE Required as if in direct contact

Page 52: Arc Flash Hazard Calculations – What does it all mean?

Flash Protection Range

Qualified Persons Only

PPE Required if Flash Protection Boundary is Crossed

FPB dependent on:

Voltage Level

Fault level

Trip Time of Protective Device

Eq

uip

men

t

Prohibited RangeLimited Approach Range Restricted Range

Limited Approach Range: Qualified or unqualified persons*

*Only if accompanied by Qualified Person

Restricted Boundary: Qualified Persons Only, PPE required

Prohibited Boundary: Qualified Persons Only. PPE required as if direct contact with

energized part

Limited Approach

Boundary

(Fixed by Voltage)

Restricted Boundary

(Fixed by Voltage)

Prohibited Boundary

(Fixed by Voltage)

FlashProtectionBoundary

BoundaryVaries

Page 53: Arc Flash Hazard Calculations – What does it all mean?
Page 54: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Label Installation

� Always clean the surface with detergent to remove all grease and dirt. Wipe surface dry before applying the label.

� Some locations will have a Line Side Label. They should be installed at locations where maintenance staff could be exposed to energized parts on the line side of a fuse or circuit breaker. Examples of this are Main Breakers in Switchboards and Switchgear.

Page 55: Arc Flash Hazard Calculations – What does it all mean?

Arc Flash Label Installation

� Transformer Labels are for small distribution transformers (480/208 V) where both the 480 and 208 Volts terminals are exposed.

� Locations where the label will be exposed to direct sun light should be brought to the attention of PowerStudies, Inc. We will provide labels with a special UV protective covering to protect the label from fading.

Page 56: Arc Flash Hazard Calculations – What does it all mean?

Line Side vs Bus AF Labels

Page 57: Arc Flash Hazard Calculations – What does it all mean?

Need more Information

� www.powerstudies.com– Articles

– Links

– Specifications for Power System Studies� Short Circuit

� Protective Device Coordination

� Arc Flash Hazard