Application of Large-
Capacity Transmission
Techniques
Wang yimin State Grid Corporation of China
Washington DC
May 30, 2013
2 State Grid Corporation Of China. All rights reserved.@2013
1. Overview of UHV AC & DC Transmission projects
Project Construction
Time
Operation
Time
Jindongnan-Nanyang-Jingmen 12/2006 01/2009
Huian-Shanghai 10/2011 12/2013
Zhebei-Fuzhou 04/2013 03/2015
Yunnan-Guangdong 12/2006 06/2010
Xiangjiaba-Shanghai 12/2007 07/2010
Jinping-Sunan 12/2009 12/2012
Hami-Zhengzhou 05/2012 09/2014
Xiluodu-Zhexi 07/2012 12/2014
Hami
Zhengzhou
Jindongnan
Nanyang
Jingmen Jinping
Xiangjiaba
Xiluodu
Huinan Shanghai
Zhebei
Fuzhou
Sunan
Shanghai
Zhexi
8000MW/2210km
7200MW/2059km 6400MW/1907km
8000MW/1680km
2*3000MVA
640km
2×3000MVA
2×656km
2×3000MVA
2×603km
Legend
1000kV AC,Commercial operation
1000kV AC,Under construction
±800kV DC,Commercial operation
±800kV DC, Under construction
5000MW/1373km Yunnan
Guangdong
3 State Grid Corporation Of China. All rights reserved.@2013
Why choose AC 1000kV ?
Based on economical analysis and other methods, 1000kV is more economical than
500kV when the transmission capacity is more than 4000MW and transmission
distance is longer than 500km
2. Application
500kV 1000kV
4 State Grid Corporation Of China. All rights reserved.@2013
DC Transmission Selection
The critical economical transmission distances are determined using the unit
capacity annual cost method
2. Application
±1100
±800
±500
kV
4500km 800 2300
Capacity :8000MW
Current :5000A
Conductor Cross Section :6×1000
Power Loss rate :3.1%~5.5%
Capacity :10000MW
Current :5000A
Conductor Cross Section :8×900
Power Loss rate :3.7%~6.3%
Capacity:3500MW
Current:3500A
Conductor Cross Section:4×1000
Power Loss rate: <3.6%
±660
Capacity :4600MW
Current :3500A
Conductor Cross Section :4×1000
Power Loss rate :3.0%~3.7%
1100
Economical Transmission Distance and Line Loss for the four voltages
5 State Grid Corporation Of China. All rights reserved.@2013
AC or DC ? who applicable ?
AC or DC are determined considering the different transmission characteristics
and the impact factors such as economic, security, reliability, environmental etc
2. Application
AC
500kV
AC
1000kV
DC
± 1100kV
DC
± 800kV
DC
± 500kV
Tra
nsm
issi
on C
apac
ity(MW
)
Transmission Distance(km)
400 800 1200 1600 2000 2400 2800 32003000
4000
5000
6000
7000
8000
9000
10000
3600 40000
DC
±660kV
6 State Grid Corporation Of China. All rights reserved.@2013
Southern
power grid
Northwest
power grid
Northeast
power grid
Legend 1000kV AC
Back to back
DC
±800kV DC
±660kV DC
±500kV DC
±400kV DC
Tibet power
grid
3. Development goal
Increase capacity
Raise the DC current up
to 6250A and the voltage
up to ±1100kV
2015 grid
" T wo vertical and two
horizontal" AC pathways
and seven DC lines
F orm the North-China
Central-China East-China
UHV synchronous grid
North China-Central China
-East China power grid.
7 State Grid Corporation Of China. All rights reserved.@2013
4. Research
Overview of ±1100kV DC development
Completed project conceptual system design and
released technical specifications.
Proposed the mode of UHVDC hierarchical
connection to 500kV and 1000kV AC system.
Raise the current of UHVDC to 6.25kA
Completed the manufacture of the Model prototype
of converter transformer and valve. both passed the
test evaluation.
Completed the development of DC field switches
including disconnector, earthing switch , transfer
switch and the manufacture of the prototypes, most of
switches passed the test evaluation.
8 State Grid Corporation Of China. All rights reserved.@2013
4. Research
DC transmission capacity:
with 5 inches thyristor current 3kA
±500kV capacity=2x500kVx3kA=3000MW
±800kV capacity=2x800kVx3kA=4800MW
4kA 4.5kA 5kA 6.25kA
800kV 6400MW 7200MW 8000MW 10GW
1100kV 11GW 13.75GW
with 6 inches thyristor
■ research in progress
9 State Grid Corporation Of China. All rights reserved.@2013
The design scheme of ±1100kV DC
4. Research
DC hierarchical connection
for capacity 10GW and above
10 State Grid Corporation Of China. All rights reserved.@2013
4. Research
To raise DC current to 6.25kA
Research shows no critical equipment problem.
Converter transformer, valve and thyristor, smoothing reactor, and DC
field equipments are OK.
But the valve side bushing is a key problem. (ABB,ALSTOM 5kA OK)
Converter transformer transportation is more difficult. the way to resolve
is modular transportation and on-site assembly .
11 State Grid Corporation Of China. All rights reserved.@2013
±800kV ±1100kV
62t、63m
112 t、78m
4. Research
±1100kV DC Tower
Based on the research result on
electromagnetic environment, 8
×1000mm2 conductor recom
mended
12 State Grid Corporation Of China. All rights reserved.@2013
The wall bushing ( 25.5m , 6.6t )
4. Research
±1100kV DC Bushing
The converter transformer valve side bushing (15.6m, 7.9t )
13 State Grid Corporation Of China. All rights reserved.@2013
±1100kV DC transformer
Converter transformer model prototype 1
Converter transformer model prototype 2
4. Research
Estimated size:
14000(length)×4050(width)
×5050(height):
Total weight: 450t
Estimated size:
12000(length)×4800(width)
×5900(height)
Total weight: 650t.
14 State Grid Corporation Of China. All rights reserved.@2013
XD-valve prototype XJ-valve prototype C-EPRI-valve prototype
4. Research
±1100kV DC Valve
Three manufacturers completed the design and manufacture of the
±1100kV valve prototype, all passed the test evaluation
15 State Grid Corporation Of China. All rights reserved.@2013
XD-disconnector test Pinggao-earthing
switch test
Pinggao-disconnector test
4. Research
±1100kV DC Switches Completed the development of DC field switches, most of which
passed the test evaluation
16 State Grid Corporation Of China. All rights reserved.@2013