applicable controllers monitoring and control...

18
G6-76 (Monitor III Software) 6/18c Page 1 Decision-Makerr 3+ M340+ ATS Controller and PM340 Power Monitor are not illustrated. Standard Software Features and Functions D Monitor and control the power system generator sets and transfer switches from a personal computer using a single software package D Monitor and control systems through a Windowsr-based graphical user interface D View the status of all devices on one site overview screen D Password-protected data access: Guest, User, and Supervisor D Monitor and control systems over a local area network, remotely via a modem connection, or through an Ethernet connection D Connect up to 247 controller devices on a local area network D Monitor data from multiple devices on the same local area network simultaneously D Start or stop the generator set from a PC D Read and adjust trip points, time delays, and system parameter settings D Assign inputs and outputs D View ECM data for ECM-equipped engines D View system run time history D View up to 100 recent events including engine starts, faults, shutdowns, and warnings D Device data windows automatically update D Software kits include hardware for either local or remote communications Monitor III Software Monitoring and Control Software Monitor III software provides monitoring and control of Kohlerr generator sets and transfer switches equipped with the following controllers: APM402 generator set controller Decision-Makerr 6000 generator set controller Decision-Makerr 3000 generator set controller Decision-Makerr 550 generator set controller Decision-Makerr 340 generator set controller Decision-Makerr 3+ generator set controller MPACt 1500 automatic transfer switch controller MPACt 1000 automatic transfer switch controller M340 and M340+ automatic transfer switch controllers PM340 Power Monitor Decision-Makerr 340 Decision-Makerr 550 Power System Accessories Applicable Controllers MPACt 1000 Windowsr is a registered trademark of Microsoft Corporation. MPACt 1500 Decision-Makerr 6000 APM402/Decision-Makerr 3000

Upload: others

Post on 24-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 1

Decision-Makerr 3+

M340+ ATS Controller and PM340 Power Monitor are not illustrated.

Standard Software Features and FunctionsD Monitor and control the power system generator sets and transfer

switches from a personal computer using a single software packageD Monitor and control systems through a Windowsr-based graphical

user interfaceD View the status of all devices on one site overview screenD Password-protected data access: Guest, User, and SupervisorD Monitor and control systems over a local area network, remotely via

a modem connection, or through an Ethernet connectionD Connect up to 247 controller devices on a local area networkD Monitor data from multiple devices on the same local area network

simultaneouslyD Start or stop the generator set from a PCD Read and adjust trip points, time delays, and system parameter

settingsD Assign inputs and outputsD View ECM data for ECM-equipped engines

D View system run time history

D View up to 100 recent events including engine starts, faults,shutdowns, and warnings

D Device data windows automatically updateD Software kits include hardware for either local or remote

communications

Monitor III Software

Monitoring and Control SoftwareMonitor III software provides monitoring and control of Kohlerr generatorsets and transfer switches equipped with the following controllers:

APM402 generator set controller

Decision-Makerr 6000 generator set controller

Decision-Makerr 3000 generator set controller

Decision-Makerr 550 generator set controller

Decision-Makerr 340 generator set controller

Decision-Makerr 3+ generator set controller

MPACt 1500 automatic transfer switch controller

MPACt 1000 automatic transfer switch controller

M340 and M340+ automatic transfer switch controllers

PM340 Power Monitor

Decision-Makerr 340

Decision-Makerr 550

Power System Accessories

Applicable Controllers

MPACt 1000Windowsr is a registered trademark of Microsoft Corporation.

MPACt 1500

Decision-Makerr 6000

APM402/Decision-Makerr 3000

Page 2: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 2

Monitoring and Control Software

Use Monitor III software to create screens containing datawindows that display system information, controller settings, andoperating status for connected generator sets, transfer switches,and power monitors. For more information, see TP-6347,Monitor III Software Operation and Installation Manual.

D Easily select, create, arrange, or delete data windows.

D Create data windows for multiple devices in a network.

D Create and save multiple screen configurations.

D Display screens show system status and settings.

D Password-protected setup windows allow remote operationand adjustment.

Kohler publishes Modbusr data register maps for its products.Modbus protocol manual TP-6113 is available through Kohlerdistributors.

Modbusr is registered trademark of Schneider Electric.

Minimum System Requirements

D 133 MHz or higher Intelr Pentiumr-compatible CPU

D 32 MB RAM

D CD-ROM drive and 75 MB hard drive space available forinstallation

D 800 x 600 or better color monitor (1024 x 768 recommended)

D MicrosoftrWindowsr 2000, Windowsr XP, Windows Vistar, orWindowsr 7 operating system

D COM port numbered between 1 and 255, capable of baud rate9600 or 19200 (for direct local connection)

D PC network interface card (NIC) (for applications usingethernet connections only)

D Adober Acrobatr or Adober Readerr (to display the Help file)

Intelr and Pentiumr are registered trademarks of Intel Corporation.Microsoftr, Windowsr, and Windows Vistar are registered trademarks of MicrosoftCorporation.Adober Acrobatr and Adober Readerr are registered trademarks of Adobe SystemsIncorporated.

Page 3: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 3

Decision-Makerr 550 and Decision-Makerr 6000 Generator Set Controllers

All of the following information is available through Decision-Makerr 550 and Decision-Makerr 6000 controller communications.Adjustments and manual operations are password-protected.

Parameter View AdjustDate and TimeDate D D

Time D D

Synchronize with computer D

Electrical Information% of rated kW D

Current, L1, L2, L3 D

Frequency D

Voltage, line-line D

Voltage, line-neutral D

Total kVA, L1, L2, and L3 D

Total kVAR, L1, L2, and L3 D

Total kW, L1, L2, and L3 D

Total power factor, L1, L2, and L3 D

Engine InfoBattery voltage (ECM) D

Coolant Level D

Coolant Pressure D

Coolant Temperature D

Engine speed (RPM) D

Fuel last run consumption D

Fuel pressure D

Fuel burn rate, liters/hr. or gal./hr. D

Fuel temperature D

Intake air filter diff. pressure D

Intake air temperature D

Oil pressure D

Oil level D

Oil temperature D

Oil crankcase pressure D

Event History (100 most recent events)Faults D

Warnings D

Shutdowns D

Input activation D

Output activiation D

Save history button D D

Time and date of each event D

Generator Info D D

Battery voltage, nominal D D

Connection, wye or delta D D

Rating, kW D D

NFPA 110 defaults, enabled or disabled D D

Phases, single or three D D

Frequency, nominal D D

Voltage, nominal D D

Operating mode, standby or prime power D D

Parameter View AdjustMaintenancekW hours * D

Last maintenance date D

Last run start date D

Last run start time D

Loaded/unloaded run time * D

Number of starts * D

Operating days D

Run time * D

Last run time, loaded and unloaded D* Total and since last maintenance

Maintenance OperationsReset maintenance records button D

Reset faults button D

System InfoAlternator part number D

Controller serial number D

Engine part number D

Final assembler’s clock number D

Final assembly date D

Generator set serial number D

Generator set model number D

Genset name (optional, user-defined) D D

Load description (optional, user-defined) D D

Location (optional, user-defined) D D

Device ID D

Specification number D

Application code version (controller) D

Time DelaysCrank on D D

Crank pause D D

Engine cooldown D D

Engine start D D

Load shed D D

Maximum crank cycles D D

Overvoltage D D

Starting aid D D

Undervoltage D D

Trip PointsHigh battery voltage D D

load shed output D D

Low battery voltage D D

Overfrequency D D

Overspeed D D

Overvoltage D D

Underfrequency D D

Undervoltage D D

Page 4: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 4

Decision-Makerr 550 and Decision-Makerr 6000 Controllers, continued

Relay Driver Outputs (RDOs), System Events, and Common AlarmsAssign up to 31 relay driver outputs (RDOs). Define any event as a common fault, except as noted.

Parameter View AdjustRelay Driver Outputs (RDOs), System Events, andCommon AlarmsHigh shutdown enable/disable D D

High warning enable/disable D D

Low shutdown enable/disable D D

Low warning enable/disable D D

Assign/remove functions: D D

AC sensing loss D D

Air damper control D D

Air damper indicator D D

Air/fuel module (AFM) remote start D D

Air temperature signal loss D D

Alternator protection shutdown D D

Analog inputs 1--7 D D

Battery charger fault D D

Breaker trip D D

Critical overvoltage D D

Defined common fault (not selectable ascommon fault)

D D

Delay engine cooldown D D

Delay engine start D D

Digital inputs 1--21 D D

EEPROM write failure D D

Emergency power system (EPS)supplying load

D D

Emergency stop D D

Fuel valve relay D D

Generator running D D

Ground fault D D

High air temperature shutdown D D

High air temperature warning D D

High battery voltage D D

High coolant temperature shutdown D D

High coolant temperature warning D D

High oil temperature shutdown D D

High oil temperature warning D D

In synch D D

Internal fault D D

Load shed kW over D D

Load shed overtemperature D D

Load shed underfrequency D D

Locked rotor D D

Parameter View AdjustLoss of ECM communications D D

Loss of field shutdown D D

Low battery voltage D D

Low coolant level D D

Low coolant temperature shutdown D D

Low coolant temperature warning D D

Low fuel D D

Master switch error D D

Master switch not in AUTO D D

Master switch off D D

Master switch open D D

Block heater control (for future MDECapplications)

D D

Yellow alert (for future MDECapplications)

D D

Red alert (for future MDEC applications) D D

NFPA 110 fault D D

No coolant temperature signal D D

No oil pressure signal D D

Oil pressure shutdown D D

Oil pressure warning D D

Oil temperature signal loss D D

Overcrank D D

Overcurrent shutdown D D

Overcurrent warning D D

Overfrequency D D

Overpower shutdown D D

Overspeed D D

Overvoltage D D

Prelube relay D D

Protective relay common (for switchgear) D D

Reverse power shutdown (forswitchgear)

D D

Software-controlled relay driver outputs(SCRDOs) 1--4 (on/off)

D D

Speed sensor fault D D

Starting aid D D

System ready D D

Underfrequency D D

Undervoltage D D

Weak battery D D

Page 5: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 5

Decision-Makerr 550 and Decision-Makerr 6000 Controllers, continued

InputsAssign up to 7 analog inputs and 21 digital inputs.

Parameter View AdjustDigital Inputs (assign up to 21)Delay time D D

Inhibit time D D

Enable/disable D D

Assign/remove functions: D D

Warning D D

Shutdowns, type A and B D D

Voltage raise D D

Voltage lower D D

Variable PF (power factor) mode D D

Remote shutdown D D

Remote reset D D

Air damper D D

Low fuel (level or pressure) D D

Field overvoltage D D

Idle mode active (ECM only) D D

Battleswitch D D

Ground fault D D

Battery charger fault D D

High oil temperature (non-ECM) D D

Low coolant level D D

Low coolant temperature (not user-se-lectable)

D

Enable synch (not user-selectable) D

AFM (air-fuel module) shutdown [ D D

Knock shutdown [ D D

Detonation warning [ D D

Detonation shutdown [ D D

Low fuel shutdown [ D D

Breaker closed (not user-selectable) D D[ Waukesha engines only

Parameter View AdjustAnalog Inputs (assign up to 7)High shutdown value D D

High warning value D D

Inhibit time D D

Low shutdown value D D

Low warning value D D

Shutdown delay D D

Shutdown enabled D D

Warning delay D D

Warning enabled D D

Description (optional, user-defined) D D

Battery voltage D

Remote Operation (password-protected)

Manual Operation ControlGenerator set run time D

Set run time D

Start generator set D

Stop generator set D

Maintenance OperationsReset maintenance records button D

Reset faults button D

Page 6: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 6

APM402 and Decision-Makerr 3000 Generator Set Controllers

The following information for APM402 and Decision-Makerr 3000 controllers can be monitored through Monitor III.

Parameter ViewElectrical InformationTotal kVA D

Total kW D

% of Rated kW D

Voltage L1-L2 D

Voltage L2-L3 D

Voltage L3-L1 D

Voltage L1-L0 D

Voltage L2-L0 D

Voltage L3-L0 D

Current L1, A D

Current L2, A D

Current L3, A D

Frequency, Hz D

Engine Information (Analog)Engine Speed, RPM D

Coolant Temperature, _C and _F D

Oil Pressure, PSI and kPa D

Battery Voltage, VDC D

ECM Battery Voltage, VDC D

Parameter ViewGenerator InformationGenset Rating D

Nominal Voltage D

Nominal Current D

Nominal Frequency D

Nominal Battery Voltage D

Phases D

Connection D

Alarm Silence Always D

Total Energy Delivered D

System InformationGenset Model No. D

Genset Spec No. D

Genset Serial No. D

Alternator Part No. D

Engine Model No. D

Engine Part No. D

Engine Serial No. D

Software Version No. D

Page 7: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 7

Decision-Makerr 340 Generator Set Controller

All of the following information for Decision- Makert 340 generator set controllers can be monitored through Monitor III. Manualoperations are password-protected. A Modbus/KBUS converter is required for this device.

Parameter ViewAuxiliary inputsDelay time D

Description D

Inhibit time D

Common faults (1--6) D

Date/Time D

Electrical Info D

Current, L1, L2, and L3 D

Frequency D

Power level (percent of alternator kilowatt rating) D

Power factor D

Total kilowatts D

Voltage, line-to-line for all phases D

Voltage, line-to-neutral for all phases D

Engine parametersBattery voltage D

Coolant temperature D

Engine speed D

Oil pressure D

History (since initial startup and since last maintenancerecord reset)Days of operation D

Last run time (duration) D

System startup date and time D

Energy delivered, kilowatt hours D

Last start date D

Last start time D

Number of starts D

Run time loaded D

Run time unloaded D

Shutdown history, date and description (code) D

Relay driver output assignments (1--10) D

System informationController serial number D

Generator set name D

Load description D

Location D

Model number D

Generator set serial number D

Specification number D

Parameter ViewSystem summaryGenerator set kilowatt rating D

Battery voltage (12 or 24), nominal D

Generator status (stopped/running/cranking) D

Master switch position D

Programming mode D

System status including current shutdown or warn-ing

D

System voltage (nominal) D

System frequency (nominal) D

Time delay settingsCrank on D

Crank pause D

Engine cooldown D

Engine start D

Maximum number of crank cycles D

Overvoltage D

Undervoltage D

Starting aid D

Trip point settingsLow battery voltage D

High battery voltage D

Overfrequency D

Underfrequency D

Overspeed D

Overvoltage D

Undervoltage D

Remote Operation (password-protected)

Operation ControlReset faults D

Generator set run time D

Set run time (start/stop generator set) D

Page 8: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 8

Decision-Makerr 3+ Generator Set Controller with Communications

All of the following information for Decision-Makert 3+ generator set controllers can be monitored through Monitor III. TheDecision-Makert 3+ controller with communications (red main logic board) and the Modbusr communication board are required.Manual operations are password-protected.

Parameter View

Status (on/off indicators)

Run mode D

Generator running D

System ready D

Lost ECM communications D

Common fault D

High coolant temperature D

Low coolant temperature D

Low coolant level D

Low oil pressure D

Not in auto D

Emergency stop D

Master switch error D

Overcrank D

Overspeed D

Locked rotor D

No AC voltage D

Speed sensor fault D

Intermittent speed sensor D

Air damper switch D

Low fuel D

High battery voltage D

Low battery voltage D

Battery charger D

ATS emergency on D

User input #1 D

User input #2 D

ECM red alarm D

ECM yellow alarm D

Controller application code version D

Parameter View

ECM Information *

Communication protocol, J1939, MTU, or MTU withVSG

D

DC voltage at ECM (analog) D

ECM hours of operation D

ECM fault code D

Engine Information (analog)

Engine speed, RPM D

Coolant temperature * D

Fuel temperature * D

Charge air temperature * D

Oil pressure * D

Fuel pressure * D

Charge air pressure * D

DIP Switch Settings

Overspeed: 60 or 70 Hz D

Temperature cooldown: enabled or disabled D

Crank mode: continuous or cyclic D

Engine: non-ECM, DDC/MTU, J1939, or MTU withVSG

D

* For ECM-equipped engines only

Remote Operation (password-protected)

Operation ControlStart engine D

Stop engine D

Reset faults D

Modbusr is a registered tradmark of Schneider Electric.

Page 9: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 9

MPACt 1500 Automatic Transfer Switch Controller

The following information is available for both the Normal and Emergency sources. Adjustment screens are password-protected.

Parameter View AdjustActive Time DelayTime delay name D

Time remaining, seconds D

Graphic display, time delay elapsed/remain D

End time delay button D

Common AlarmsCommon alarms, available and assigned D

Audible alarms, available and assigned D

Date/TimeDate D

Time D

Synchronize with computer button D

Daylight saving time enable/disable D

Clock ahead/behind month, week, day D

DIP Switch SettingsPassword enable/disable RO D

Maintenance/run mode RO D

Spare switch on/off (2) RO D

Event HistoryLost preferred source: last time, date, andduration

D

Events: D

Contactor position changes (transfers) D

Faults D

Input activation D

Output activation D

DIP switch position changes D

Other events as described in ATSmanual

D

Test button activation/release D

Time and date of each event D

Save history D

Clear history D

Event History ViewView events for a selected time period D D

Start date D D

End date D D

Get events D D

Save history button D

Exercise Calendar ModeEvent number D

Next start date D

Enable/disable each event D D

Start date D

Start time D D

Run time D D

Loaded/unloaded D D

Interval D D

Repeat rate (setup only) D

Parameter View AdjustI/O State (on=green, off=gray)Logic board input status D

Logic board output status D

I/O module input status D

I/O module output status D

Frequency Set Points (Source N, E)Overfrequency dropout D D

Overfrequency pickup D D

Underfrequency pickup D D

Underfrequency dropout D D

Frequency dropout time, seconds D D

Load Control (up to 9 loads)Mode, time-based or current-based foreach source

D D

Add load (amps, current-based only) D D

Remove load (amps, current-based only) D D

Loads to add (1--9) D D

Add priority (current-based only) D D

Remove priority (current-based only) D D

Add time delay (min:sec, current-based) D D

Remove time delay(min:sec, current-based)

D D

Disconnect before transfer time delay,N to E and E to N

D D

Reconnect after transfer time delay,N to E and E to N (time-based only)

D D

Maintenance HistoryTime not in preferred * D

Time in standby * D

Operation time * D

Switch transfers * D

Lost preferred source * D

Failures to transfer * D

System start date D D

Last maintenance reset date D

Transfer time, N to E, mS D

Transfer time, E to N, mS D

Transfer time, N to open, mS [ D

Transfer time, E to open, mS [ D

Transfer time, N to close, mS [ D

Transfer time, E to close, mS [ D

Close transfer parallel time(closed-transition)

D

Reset maintenance records button D* Total and since reset[ Service entrance models

Page 10: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 10

MPACt 1500 Automatic Transfer Switch Controller, continued

Parameter View AdjustProgrammable InputsForced transfer to off D D

Peak shave mode D D

Inhibit transfer D D

Remote end time delay D D

Remote test D D

Low battery voltage D D

Remote common alarm D D

Bypass contactor disable D D

3 source system disable D D

Remotely monitored inputs #1--4 D D

Programmable OutputsAlarm silenced D D

Audible alarm D D

Preferred source available D D

Standby source available D D

Battery backup low D D

Contactor in preferred poistion D D

Contactor in standby position D D

Contactor in off position D D

Contactor in source N position D D

Contactor in source E position D D

Maintenance mode D D

Not in auto D D

Load control active D D

Low battery on standby source D D

Exerciser active D D

Test mode active D D

Peak shave active D D

Non-emergency transfer D D

Load bank bank active D D

Start source N generator D D

Start source E generator D D

In phase monitor synching D D

Common alarm (1--2) D D

Undervoltage, N and E D D

Overvoltage, N and E D D

Voltage unbalance D D

Loss of phase, N and E D D

Phase rotation error, N and E D D

Overfrequency, N and E D D

Underfrequency, N and E D D

Failure to acquire standby D D

Failure to acquire preferred D D

Failure to transfer D D

I/O module lost comms D D

Aux. switch fault D D

Aux. switch open D D

Load control outputs 1--9 D D

Software-controlled RDO 1--4 D D

3 source system disable D D

Parameter View AdjustRemote I/O (Input/Output)Software-controlled relay outputs on/offtoggle

D D

Remote monitored inputs status D

I/O descriptions D D

Source Information, Normal and EmergencyVoltage, line-to-line D

Voltage, line-to-neutral D

Frequency D

Phases, single or three D D

Selected rotation (ABC/CBA/none) D D

Actual rotation (ABC or CBA) D

System voltage (nominal) D D

System frequency (nominal) D D

Line current (accessory required) D

System InformationDesignation (optional, user-defined) D D

Location (optional, user-defined) D D

Load branch (optional, user-defined) D D

Load description (optional, user-defined) D D

ATS serial number (factory-set) D

Contactor serial number (factory-set) D

Controller serial number (factory-set) D

Software version numbers (controller) D

Device ID D

MAC address D

System SummarySystem state D

Contactor position D

Preferred source, N/E D

Mode of operation, gen/utility, gen/gen,utility/utility, or utility/gen/gen

D D

Transition mode, open/programmed/closed D D

Preferred source available D

Standby source available D

Extended engine start time delay,enable/disable

D

Commit to transfer, enable/disable D D

Peak shave delay bypass, enable/disable D D

In phase monitor, enable/disable D D

Phase angle D

Rated current D D

Loaded remote test, enable/disable D D

Supervised transfer, mode and switchposition

D

Service entrance type, none/ICCB/MCCB D D

Closed-transition program override mode,auto/manual (password-protected)

D D

Synchronous closed transition:Voltage phase angle (deg.) D D

Voltage differential (%) D D

Frequency differential (Hz) D D

Page 11: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 11

MPACt 1500 Automatic Transfer Switch Controller, continued

Parameter View AdjustTime DelaysSource N engine start D D

Source E engine start D D

Source N engine cooldown D D

Source E engine cooldown D D

Preferred to standby D D

Standby to preferred D D

Fail to acquire standby D D

In phase transfer failure D D

Off-to-standby (programmed-transition) D D

Off-to-preferred, (programmed-transition) D D

Voltage Set Points (Source N, E)Overvoltage dropout D D

Overvoltage pickup D D

Undervoltage pickup D D

Undervoltage dropout D D

Unbalanced voltage enable/disable D

Unbalanced voltage dropout D D

Unbalanced voltage pickup D D

Debounce time, seconds D D

Remote Operation (password-protected)

Operation ControlPeak shave start/stop D

Unloaded test start/stop (remote start/stop) D

Unloaded sync check start/stop (closed-transition) D

Loaded test start/stop (remote start/stop) D

Auto-loaded test start/stop (remote start/stop) D

Auto test time (1--60 min.) D

Programmed-transition transfer to OFF/resumenormal operation

D

Prime power start/stop D

Source 1 and source 2 duration (view)Source 1 and source 2 countdown (view)

End time delay (active time delay window) D

Software-controlled relay outputs on/off D

Page 12: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 12

MPACt 1000 Automatic Transfer Switch Controller

The following information is available for both the Normal and Emergency sources. Adjustment screens are password-protected.

Parameter View AdjustActive Time DelayTime delay name D

Time remaining, seconds D

Graphic display, time delay elapsed/remain D

End time delay button D

Common AlarmsCommon alarms, available and assigned D

Audible alarms, available and assigned D

Date/TimeDate D

Time D

Synch with system clock D

Automatic daylight saving time D

DIP Switch SettingsTransfer inhibited/permitted D

Test loaded/unloaded D

Exercise inhibited/permitted D

Manual exercise 1 week/2 week D

Exercise loaded/unloaded D

Commit/no commit to transfer D

Phase rotation ABC/CBA D

Event HistoryLost preferred source: last time, date, andduration

D

Events: D

Contactor position changes (transfers) D

Faults D

Input activation D

Output activation D

DIP switch position changes D

Other events as described in ATSmanual

D

Test button activation/release D

Time and date of each event D

Save history button D

Event History ViewView events for a selected time period D D

Start date D D

End date D D

Get events D D

Save history button D

ExerciserMode: manual, calendar, or calendar w/manual override

D D

Next exercise start date D D

Next exercise start time D D

Manual exercise period D D

Loaded/unloaded D D

Run time D D

Manual exercise disable button (setup only) D D

Manual exercise set/end button (setup only) D D

Exercise time remaining D D

Parameter View AdjustExercise Calendar ModeEvent number D D

Next start date D D

Enable/disable each event D D

Start time D D

Run time D D

Loaded/unloaded D D

Interval D D

Repeat rate (setup only) D

Frequency Set Points, (Source N, E)Overfrequency dropout D D

Overfrequency pickup D D

Underfrequency pickup D D

Underfrequency dropout D D

Frequency dropout time, seconds D D

Voltage Set Points, (Source N, E)Overvoltage dropout D D

Overvoltage pickup D D

Undervoltage pickup D D

Undervoltage dropout D D

Debounce time, seconds D D

Load Control Time Delays (up to 9 loads)Disconnect before transfer time delay,N to E and E to N

D D

Reconnect after transfer time delay,N to E and E to N

D D

Maintenance RecordsTime not in preferred * D

Time in standby * D

Operation time * D

Switch transfers * D

Lost preferred source * D

Failures to transfer * D

System start date D D

Last maintenance reset date D

Transfer time, N to E, mS D

Transfer time, E to N, mS D* Total and since resetSource Information, Normal and EmergencyVoltage, line-to-line RO D

Voltage, line-to-neutral RO D

Frequency RO D

Phases, single or three RW D D

Selected rotation (ABC or CBA) RW D D

Actual rotation (ABC or CBA) RO D

System voltage (nominal) RW D D

System frequency (nominal) RW D D

Page 13: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 13

MPACt 1000 Automatic Transfer Switch Controller, continued

Parameter View AdjustSystem InformationDesignation (optional, user-defined) D D

Location (optional, user-defined) D D

Load branch (optional, user-defined) D D

Load description (optional, user-defined) D D

ATS serial number (factory-set) D

Contactor serial number (factory-set) D

Controller serial number (factory-set) D

Software version numbers D

System SummarySystem state D

Contactor position D

Preferred source, N/E D

Mode of operation,gen-utility/gen-gen/utility-utility

D

Transition mode, open/progammed D

Extended engine start time delay,enabled/disabled

D

Preferred source available D

Standby source available D

Supervised transfer mode D

Supervised transfer switch position D

Commit to transfer, enabled/disabled D

Peak shave delay bypass, enabled/disabled D

In phase monitor, enabled/disabled D

Rated current D

I/O modules expected D

Time DelaysSource N engine start D D

Source E engine start D D

Source N engine cooldown D D

Source E engine cooldown D D

Preferred to standby D D

Standby to preferred D D

Acquire standby source D D

In phase monitor synch D D

Off-to-standby (programmed-transition) D D

Off-to-preferred, (programmed-transition) D D

Programmable InputsForced transfer to off D D

Peak shave mode D D

Inhibit transfer D D

Remote end time delay D D

Remote test D D

Low battery voltage D D

Remote common alarm D D

Bypass contactor disable D D

3 source system disable D D

Parameter View AdjustProgrammable OutputsPreferred source available D D

Standby source available D D

Contactor in preferred poistion D D

Contactor in standby position D D

Contactor in off position D D

Contactor in source N position D D

Contactor in source E position D D

Maintenance mode D D

Not in auto D D

Load control active D D

Low battery on standby source D D

Exerciser started D D

Test mode active D D

Peak shave active D D

Non-emergency transfer D D

Load bank bank active D D

Start source N generator D D

Start source E generator D D

In phase monitor waiting for synch D D

Common alarm (1--2) D D

Undervoltage, N and E D D

Overvoltage, N and E D D

Loss of phase, N and E D D

Phase rotation error, N and E D D

Overfrequency, N and E D D

Underfrequency, N and E D D

Failure to acquire standby D D

Failure to transfer D D

I/O module lost comms D D

I/O module not found D D

Aux. switch fault D D

Aux. switch open D D

Load control outputs 0--8 D D

Software-controlled RDO 1--4 D D

3 source system disable D D

Remote Operation (password-protected)

Operation ControlPeak shave start/stop D

System test start/stop (Remote Start/Stop) D

Programmed transition transfer to OFF/resumenormal operation

D

End time delay (active time delay window) D

Modbus-controlled relay outputs D

Page 14: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 14

M340 and M340+ Transfer Switch Controllers

All of the following information for M340 and M340+ transfer switch controllers can be viewed through Monitor III. A Modbus/KBUSconverter is required for this device.

Parameter ViewDate/TimeDate D

Time D

Frequency Setpoints (Source N, E)Overfrequency dropout D

Overfrequency pickup D

Underfrequency pickup D

Underfrequency dropout D

Voltage Setpoints (Source N, E)Overvoltage dropout D

Overvoltage pickup D

Undervoltage pickup D

Undervoltage dropout D

Maintenance HistoryTime not in normal position * D

Time in emergency * D

Days of operation * D

Number of transfers * D

Last maintenance date D

System start date D

Exercise time remaining D

Last exercise date D

Last outage date D

Last outage time D

Last outage duration D* Total and since last maintenance D

Source Info for Source N and Source ELine-to-line voltage D

Frequency D

System voltage D

System frequency D

Parameter ViewSystem InfoATS name D

Location D

Load description D

Branch D

ATS serial number D

Controller serial number D

Number of phases D

Switch size D

System SummaryAlert code D

Switch position D

Programming mode D

System status messages D

Time DelaysEngine start D

Normal to emergency D

Emergency to normal D

Engine cooldown D

Before emergency D

After emergency D

Sequence to emergency D

Return to emergency D

Before normal D

After normal D

Sequence to normal D

Return to normal D

Remote Operation (password-protected)

Operation ControlEngine run time D

Set run time (starts engine) D

Page 15: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 15

PM340 Power Monitor

The following information for the Power Monitor can be viewed through Monitor III software. A Modbus/KBUS converter is requiredfor this device.

Parameter ViewAnalog InputsAnalog input reading, (2) D

Auxiliary InputsDescription D

Inhibit time D

Date/TimeDate D

Time D

Electrical InfoVoltage, line-to-line D

Voltage, line-to-neutral D

Current, L1, L2, L3 D

Frequency D

Total kW D

Total kVAR D

Power factor D

Power supply voltage, VDC D

System InfoGenerator set name D

Location D

Load description D

Model number D

Specification number D

Generator set serial number D

Controller serial number D

Parameter ViewSystem SummarySystem status D

Switch position D

Contactor position D

Programming mode D

Test mode timed D

Test mode active D

ATS rating D

Nominal voltage D

Nominal frequency D

Phases D

Connection type D

HistoryRun time, normal D

Run time, emergency D

Run time, off D

Event history, date and event description (code) D

Remote Operation (password-protected)

Operation ControlEngine run time D

Set run time (starts engine) D

Page 16: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 16

Connection TypesA personal computer (PC) can communicate with generator setcontrollers, transfer switch controllers, and power monitors usinglocal, remote modem, or remote network (Ethernet) connections.

Connection Notes:

D A device in the following diagrams is any generator setcontroller, transfer switch controller, or power monitor listed onpage 1 of this document. All devices must be configured forModbus communication.

D RS-232 connects up to 15.2 m (50 ft.) from PC’s serial port.

D RS-485 connects up to 247 devices with amaximum total cablelength of 1220 m (4000 ft.). Use a terminating resistor on thelast device in the network. See EIA standards.

D The 550 controller can act as an RS-232 to RS-485 portconverter when the controller is located within 15 m (50 ft.) ofthe PC.

D The Decision-Makert 3+ and MPACt 1000 controllers mustuse RS-485 connections for Monitor III communications.

D The Decision-Makert 340, M340, M340+, and PM340 PowerMonitor require Modbus/KBUS converters.

D The MPACt 1500 ATS controller uses RS-485 and Ethernetconnections.

D A Modbus/Ethernet converter is required for remote network(Ethernet) connections to all devices except the MPACt 1500ATS controller.

Local Connections

A PC connects directly to a device or network of devices with anRS-232 cable or an RS-485 cable.

RS-232 *

RS-232 to RS-485port converter

RS-485

RS-232

Device *

Device

PC

PC

RS-232 to RS-485port converter

RS-232

Device

Additionaldevices

RS-485

RS-485

RS-485

PC

Device

Terminatingresistor

* Some devices can use RS-232 connections. See ConnectionTypes.

Page 17: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

G6-76 (Monitor III Software) 6/18c Page 17

Remote Modem Connections

The PC and device(s) are connected by modems. The PC communicates with the device or device network via a telephone network,and the PC can be located anywhere a telephone line can be accessed.

Telephonelines

Device modemRS-232 *

Telephone linefrom modem

Device *

PCw/modem

Telephonelines

Telephone linefrom modem RS-485

RS-485

RS-485

PCw/modem

Device modem

RS-232

Device

Device

RS-232 to RS-485port converter

DeviceTerminatingresistor* Some devices can use RS-232 connections. See Connection Types.

Remote Network Connection (Ethernet)

A PC with a network interface card is connected to the Ethernet network. The 1500 ATS controller has an RJ-45 connector for directEthernet connection. Other devices can connect together using RS-485 connections and connect to the Ethernet network through aModbusr/Ethernet converter. The PC can be located anywhere the site’s Ethernet network can be accessed.

PC with networkinterface card

Device

Additionaldevices

RS-485

Modbusr RTU

Converter,Modbusr/Ethernet RS-485

ModbusrTCP/IP

Modbusr TCP/IPModbusrTCP/IP

EthernetNetwork

PC with networkinterface card

RS-485

Category 5

Terminatingresistor

Device

Modbusr TCP/IPCategory 5

1500 ATSController

Page 18: Applicable Controllers Monitoring and Control Softwareresources.kohler.com/power/kohler/industrial/pdf/g6076.pdfDefine any event as a common fault, except as noted. Parameter View

KOHLER CO., Kohler, Wisconsin 53044 USAPhone 920-457-4441, Fax 920-459-1646For the nearest sales and service outlet in theUS and Canada, phone 1-800-544-2444KOHLERPower.com

2005, 2006, 2011, 2018 by Kohler Co. All rights reserved.

Availability is subject to change without notice. Kohler Co. reserves theright to change the design or specificationswithout notice andwithout anyobligation or liability whatsoever. Contact your local Kohlerr generatordistributor for availability.

DISTRIBUTED BY:

Network Communication Products and Accessories- Monitor III software kit with hardware key. Includes:

d Software CD-ROMd Null modem cabled Network termination resistord Operation manual and connection instructions

- Monitor III software kit with hardware key and devicemodem for remote connections. Includes:d Software CD-ROMd AT modem cabled Device modem, 120VAC/60Hz, 19.2k baudd Optical isolatord Converter, RS-232/RS-485d Connector, 9-pin/25-pind Null modem, 25-pind Network termination resistord Operation manual and connection instructions

- Device modem kit, 50Hz, 19.2k baud

- Modbusr/Ethernet converter kit. Includes DC adapterwith universal AC plug. (RS-485/RJ-45 connectors;required for TCP/IP connections. Not required for theMPACt 1500 ATS controller).

- Modbusr/KBUS converter kit for the following devices(required for Monitor III or other Modbusrcommunication):- Decision-Makert 340 generator set controller- M340 and M340+ transfer switch controller- PM340 power monitor

- Modbusr communication board for Decision-Makert 3+generator set controllers (required for Monitor III or otherModbusr communication)

- RS-232/RS-485 port converter

- Null modem cable, 9-pin/9-pin

G6-76 (Monitor III Software) 6/18c Page 18