ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMNT PLANT OF HOTEL UNAKOTI, JOYHIND ROAD, DHARMANAGAR, NORTH TRIPURA Date of Received: 10.08.2020 Sl. No Parameters S-1 Standards (Into Public Sewers) 1. pH 7.67 5.5-9.0 2. Conductivity (μS/cm) 645 - 3. Turbidity (NTU) 10.6 - 4. Total Suspended Solids (mg/L) 48 600 5. Total Dissolved Solids (mg/L) 323 - 6. Bio-Chemical Oxygen Demand (mg/l) 18.5 350 7. Total Hardness (mg/l) 40.4 - 8. Chemical oxygen Demand (mg/l) 98 - 9. Chlorides (mg/l) 62.4 1000 10. Iron (mg/l) 0.12 3 11. Ammunical Nitrogen (mg/l) 4.16 50 12. Sulphide (mg/l) BDL - 13. Oil and Grease (mg/l) 7.5 20 14. Fluorides (mg/l) BDL 15 15. Arsenic (mg/l) BDL 0.2 *BDL (Below Detectable Limit) Site of collection: S-1: Treated Waste Water from Sewage Treatment Plant of Hotel Unakoti, Joyhind Road, Dharmanagar, North Tripura

Upload: others

Post on 21-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMNT PLANT OF HOTEL UNAKOTI, JOYHIND ROAD, DHARMANAGAR,

NORTH TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.67 5.5-9.0

2. Conductivity (µS/cm) 645 -

3. Turbidity (NTU) 10.6 -

4. Total Suspended Solids (mg/L) 48 600

5. Total Dissolved Solids (mg/L) 323 -

6. Bio-Chemical Oxygen Demand

(mg/l) 18.5 350

7. Total Hardness (mg/l) 40.4 -

8. Chemical oxygen Demand

(mg/l) 98 -

9. Chlorides (mg/l) 62.4 1000

10. Iron (mg/l) 0.12 3

11. Ammunical Nitrogen (mg/l) 4.16 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 7.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Hotel Unakoti, Joyhind Road,

Dharmanagar, North Tripura

Page 2: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATMENT PLANT OF P.C. CHARTTERJEE MEMORIAL EYE HOSPITAL, D.N.V

ROAD, DHARMANAGAR, NORTH TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 6.67 5.5-9.0

2. Conductivity (µS/cm) 378 -

3. Turbidity (NTU) 2.06 -

4. Total Suspended Solids (mg/L) 48 600

5. Total Dissolved Solids (mg/L) 241 -

6. Bio-Chemical Oxygen Demand

(mg/l) 10.5 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand

(mg/l) 94 -

9. Chlorides (mg/l) 49.7 1000

10. Iron (mg/l) 0.09 3

11. Ammunical Nitrogen (mg/l) 5.24 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 11.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of P.C. Chartterjee Memorial Eye

Hospital, D.N.V Road, Dharmanagar, North Tripura.

Page 3: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATMENT PLANT OF HOTEL PANCHABATI, DNV ROAD, DHARMANAGAR,

TRIPURA (N)

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.67 5.5-9.0

2. Conductivity (µS/cm) 401 -

3. Turbidity (NTU) 8.77 -

4. Total Suspended Solids (mg/L) 48 600

5. Total Dissolved Solids (mg/L) 201 -

6. Bio-Chemical Oxygen Demand

(mg/l) 8.5 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 47.3 1000

10. Iron (mg/l) 0.26 3

11. Ammunical Nitrogen (mg/l) 5.28 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 3.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Hotel Panchabati, DBV Road,

Dharmanagar, Tripura (N).

Page 4: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATEMENT PLANT OF ALLIED BLENDERS & DISTILLERES PVT. LTD.,

KUMARGHAT INDUSTRIAL ESTATE, KUMARGHAT, UNAKOTI TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.51 5.5-9.0

2. Conductivity (µS/cm) 129.1 -

3. Turbidity (NTU) 0.93 -

4. Total Suspended Solids (mg/L) 22 100

5. Total Dissolved Solids (mg/L) 64.4 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 5.5 30

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 34 250

9. Chlorides (mg/l) 28.7 1000

10. Iron (mg/l) 0.13 3

11. Ammunical Nitrogen (mg/l) 5.28 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 6.5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of Allied Blenders & distilleries Pvt. Ltd.,

Kumarghat Industrial Estate, Kumarghat, Unakoti Tripura.

Page 5: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATMENT PLANT OF HOTEL KALPATARU-INN, A. A. ROAD, KUMARGHAT,

UNAKOTI, TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 9.48 5.5-9.0

2. Conductivity (µS/cm) 186.3 -

3. Turbidity (NTU) 3.79 -

4. Total Suspended Solids (mg/L) 26 600

5. Total Dissolved Solids (mg/L) 93.3 -

6. Bio-Chemical Oxygen Demand

(mg/l) 8.5 350

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 23.7 1000

10. Iron (mg/l) 0.15 3

11. Ammunical Nitrogen (mg/l) 3.66 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 6.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Hotel Kalpataru-Inn, A. A.

Road, Kumarghat, Unakoti, Tripura.

Page 6: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST, JAIL ROAD, DHARMANAGAR,

NORTH TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 6.87 5.5-9.0

2. Conductivity (µS/cm) 3041 -

3. Turbidity (NTU) 1.4 -

4. Total Suspended Solids (mg/L) 78 600

5. Total Dissolved Solids (mg/L) 1701 -

6. Bio-Chemical Oxygen Demand

(mg/l) 13.5 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand

(mg/l) 94 -

9. Chlorides (mg/l) 23.7 1000

10. Iron (mg/l) 0.32 3

11. Ammunical Nitrogen (mg/l) 4.68 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 5.5 20

14. Fluorides (mg/l) 0.06 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Maa Sarada Trust, Jail Road,

Dharmanagar, North Tripura.

Page 7: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM EFFLUENT

TREATMENT PLANT OF RAJ AUTOMOBILES, DHARMANAGAR, TRIPURA (W).

Date of received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.62

5.5-9.0

2. Conductivity (µS/cm) 135.2

-

3. Turbidity (NTU) 1.05

-

4. Total Suspended Solids (mg/L) 16

600

5. Total Dissolved Solids (mg/L) 67.5

-

6. Bio-Chemical Oxygen Demand

(mg/l) 7.5 350

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 21.7 1000

10. Iron (mg/l) 0.16 3

11. Ammunical Nitrogen (mg/l) 4.22 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 11 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-2: Waste Water sample (Treated) collected from Sewage Treatment Plant of Raj Automobiles,

Dharmanagar, Tripura (w)

Page 8: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE

TREATEMENT PLANT OF HEALTH CURE NURSING HOME, DHARMANAGAR, TRIPURA.

Date of received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.8 5.5-9.0

2. Conductivity (µS/cm) 199.1 -

3. Turbidity (NTU) 0.85 -

4. Total Suspended Solids (mg/L) 42 600

5. Total Dissolved Solids (mg/L) 99.6 -

6. Bio-Chemical Oxygen Demand

(mg/l) 8.5 350

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 55.7 1000

10. Iron (mg/l) 1.37 3

11. Ammunical Nitrogen (mg/l) 2.68 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 9 20

14. Fluorides (mg/l) BDL 15

Page 9: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Health Cure Nursing Home,

Dharmanagar,Tripura.

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATMENT

PLANT OF P.C. CHARTTERJEE MEMORIAL EYE HOSPITAL, D.N.V ROAD, DHARMANAGAR, NORTH TRIPURA

Date of Received: 04/01/2020

Sl. No Parameters S-1 Standards (Into Public

Sewers)

1. pH 7.13 5.5-9.0

2. Conductivity (µS/cm) 603 -

3. Turbidity (NTU) 4.8 -

4. Total Suspended Solids (mg/L) 42 600

5. Total Dissolved Solids (mg/L) 302 -

6. Bio-Chemical Oxygen Demand (mg/l) 21.5 350

7. Total Hardness (mg/l) 30.3 -

8. Chemical oxygen Demand (mg/l) 186 -

9. Chlorides (mg/l) 35.7 1000

10. Iron (mg/l) 0.10 3

11. Ammunical Nitrogen (mg/l) 2.88 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 8.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of P.C. Chartterjee Memorial Eye Hospital, D.N.V

Road, Dharmanagar, North Tripura

Observation:

Page 10: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

One treated waste water sample of Sewage Treatment Plant of P.C Chatterjee Memorial Eye Hospital,

Dharmanagar, North Tripura was received from Sri. Subrata Majumder, JEE, NZOL on 04.01.2020 for the

analysis of different physical & chemical parameters. The sample was analyzed in the laboratory of TSPCB using

the standard methods given in APHA, 2012 (American Public Health Association).

From the result table, it has been observed that, all the analyzed parameters of treated waste water sample

of the said unit is within the prescribed standards limit of CPCB (Central Pollution Control Board) for

discharge of effluents.

(Rajib Paul) (Ratan Debnath) (Rahul lodh)

JSA SLA JLA

ANALYTICAL RESULTS OF DISCHARGE WASTE WATER SAMPLE COLLECTED FROM THE NILADRI MOTOR

(TATA DIVISION), KASHIPUR, A.A. ROAD, AGARTALA, TRIPURA (W)++

Sl. No Parameters S-1 Standards (Into Public

Sewers)

1. pH 6.83 5.5-9.0

2. Conductivity (µS/cm) 332 -

3. Turbidity (NTU) 67.3 -

4. Total Suspended Solids (mg/L) 30 600

5. Total Dissolved Solids (mg/L) 166 -

6. Bio-Chemical Oxygen Demand (mg/l) 60.6 350

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand (mg/l) 286 -

9. Chlorides (mg/l) 35.7 1000

10. Iron (mg/l) 0.25 3

11. Ammunical Nitrogen (mg/l) 3.04 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 35 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Discharge Waste Water Sample from Niladri Motor (Tata Division), Kashipur, A.A. Road, Agartala,

Tripura (W)

Observation:

Page 11: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

One discharge water sample from Niladri Motor (Tata Division), Kashipur, A.A. Road, Agartala, Tripura (W)

collected by the TSPCB official (Lab. Division) on 07.03.2020 for the analysis of different physical & chemical

parameters. The sample was analyzed in the laboratory of TSPCB using the standard methods given in APHA,

2012 (American Public Health Association).

From the result table, it has been observed that, value of Oil & Grease of the discharge water sample of the

said unit is beyond the prescribed standards limit for discharge of effluents given in CPCB (Central

Pollution Control Board).

(Rajib Paul) (Tuli Chakma) (Ratan Debnath) (Rahul Lodh)

JSA JSA SLA JLA

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM THE SEWAGE

TREATMENT PLANT OF HOTEL CITY CENTRE, H.G.B ROAD, AGARTALA, TRIPURA (W)

Sl. No Parameters S-1 Standards (Into Public

Sewers)

1. pH 7.39 5.5-9.0

2. Conductivity (µS/cm) 891 -

3. Turbidity (NTU) 5.28 -

4. Total Suspended Solids (mg/L) 48 600

5. Total Dissolved Solids (mg/L) 445 -

6. Bio-Chemical Oxygen Demand (mg/l) 13.5 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand (mg/l) 102 -

9. Chlorides (mg/l) 12.8 1000

10. Iron (mg/l) 0.18 3

11. Ammunical Nitrogen (mg/l) 1.48 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 14.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Hotel City Centre, H.G.B Road, Agartala, Tripura

(W).

Observation:

Page 12: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

One treated waste water sample from the Sewage Treatment Plant of Niladri Hotel City Centre, H.G.B Road,

Agartala, Tripura (W) was collected by the TSPCB official (Lab. Division) on 07.03.2020 for the analysis of

different physical & chemical parameters. The sample was analyzed in the laboratory of TSPCB using the standard

methods given in APHA, 2012 (American Public Health Association).

From the result table, it has been observed that, all the analyzed parameters of treated waste water sample

of the said unit is within the prescribed standards limit of CPCB (Central Pollution Control Board) for

discharge of effluents.

(Rajib Paul) (Tuli Chakma) (Ratan Debnath) (Rahul Lodh)

JSA JSA SLA JLA

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM M/s

UNAKOTI NURSING CARE, KAILASAHAR, UNAKOTI TRIPURA

Date of Received: 10.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.8 5.5-9.0

2. Conductivity (µS/cm) 199.1 -

3. Turbidity (NTU) 0.85 -

4. Total Suspended Solids (mg/L) 22 600

5. Total Dissolved Solids (mg/L) 99.6 -

6. Bio-Chemical Oxygen Demand

(mg/l) 8.5 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical Oxygen Demand (mg/l) 64 -

9. Chlorides (mg/l) 38.4 1000

10. Iron (mg/l) 0.11 3

11. Ammunical Nitrogen (mg/l) 2.08 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 5.5 20

14. Fluorides (mg/l) BDL 15

Page 13: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water sample collected from M/s Unakoti Nursing Care, Kailasahar, Unakoti

Tripura.

Page 14: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

CETP, BODHJUNGNAGAR, AGARTALA

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 8.55 5.5-9.0

2. Conductivity (µS/cm) 2936 -

3. Turbidity (NTU) 188 -

4. Total Suspended Solids (mg/L) 244 100

5. Total Dissolved Solids (mg/L) 1879 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 252 30

7. Total Hardness (mg/l) 616 -

8. Chemical oxygen Demand

(mg/l) 512 250

9. Chlorides (mg/l) 28.5 1000

10. Iron (mg/l) 1.73 3

11. Ammunical Nitrogen (mg/l) 7.02 50

12. Sulphide (mg/l) 0.19 2

13. Oil and Grease (mg/l) 7 10

14. Fluorides (mg/l) 0.18 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Common Effluent Treatment Plant, Bodhjungnagar,

Agartala.

Page 15: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATEMENT PLANT OF PRAN BEVERAGE, BODJUNGNAGAR, AGARTALA

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.37 5.5-9.0

2. Conductivity (µS/cm) 321 -

3. Turbidity (NTU) 60.6 -

4. Total Suspended Solids (mg/L) 38 100

5. Total Dissolved Solids (mg/L) 160.7 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 22 30

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand

(mg/l) 140 250

9. Chlorides (mg/l) 71.5 1000

10. Iron (mg/l) 0.28 3

11. Ammunical Nitrogen (mg/l) 7.02 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 3 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of Pran Beverage,

Bodhjungnagar, Agartala.

Page 16: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATEMENT PLANT OF NEW AMBADI ESTATES, LTD, JARUL BACHAI,

SRINAGAR, TRIPURA (W).

Date of Collection: 27.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.27 5.5-9.0

2. Conductivity (µS/cm) 3079 -

3. Turbidity (NTU) 68.7 -

4. Total Suspended Solids (mg/L) 98 100

5. Total Dissolved Solids (mg/L) 1820 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 28 30

7. Total Hardness (mg/l) 389 -

8. Chemical oxygen Demand

(mg/l) 192 250

9. Chlorides (mg/l) 31.5 1000

10. Iron (mg/l) 0.41 3

11. Ammunical Nitrogen (mg/l) 6.98 50

12. Sulphide (mg/l) 0.15 2

13. Oil and Grease (mg/l) 9 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of New Ambadi Estates, Ltd, Jarul

Bachai, Srinagar, Tripura (W)

Page 17: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM ILS

HOSPITAL, AGARTALA, TRIPURA (W).

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.79 5.5-9.0

2. Conductivity (µS/cm) 813 -

3. Turbidity (NTU) 15.6 -

4. Total Suspended Solids (mg/L) 42 600

5. Total Dissolved Solids (mg/L) 352 -

6. Bio-Chemical Oxygen Demand

(mg/l) 6.5 350

7. Total Hardness (mg/l) 70.7 -

8. Chemical oxygen Demand

(mg/l) 54 -

9. Chlorides (mg/l) 114.5 1000

10. Iron (mg/l) 0.37 3

11. Ammunical Nitrogen (mg/l) 6.44 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 9.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of ILS Hospital, Agartala,Tripura

(W)

Page 18: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF LIFE LINE NURSING HOME AND RESEARCH

CENTRE, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.09 5.5-9.0

2. Conductivity (µS/cm) 512 -

3. Turbidity (NTU) 28.7 -

4. Total Suspended Solids (mg/L) 54 600

5. Total Dissolved Solids (mg/L) 327 -

6. Bio-Chemical Oxygen Demand

(mg/l) 26 350

7. Total Hardness (mg/l) 90.9 -

8. Chemical Oxygen Demand

(mg/l) 92 -

9. Chlorides (mg/l) 51.7 1000

10. Iron (mg/l) 0.21 3

11. Ammunical Nitrogen (mg/l) 6.02 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 12 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Life Line Nursing Home and

Research Centre, Agartala,Tripura (W)

Page 19: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF ORTHO CARE AND RELATED RESEARCH CENTRE,

KALYANI, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.11 5.5-9.0

2. Conductivity (µS/cm) 792 -

3. Turbidity (NTU) 15.7 -

4. Total Suspended Solids (mg/L) 78 600

5. Total Dissolved Solids (mg/L) 396 -

6. Bio-Chemical Oxygen Demand

(mg/l) 38 350

7. Total Hardness (mg/l) 255 -

8. Chemical oxygen Demand

(mg/l) 118 -

9. Chlorides (mg/l) 118.9 1000

10. Iron (mg/l) 0.55 3

11. Ammunical Nitrogen (mg/l) 6.12 50

12. Sulphide (mg/l) 0.27 -

13. Oil and Grease (mg/l) 6.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Ortho Care and Related

Research Centre, Agartala,Tripura (W)

Page 20: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATMENT PLANT OF THE CARE AND CURE POLYCLINIC & MEDICAL

RESEARCH CENTRE, PALACE COMPOUND, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.55 5.5-9.0

2. Conductivity (µS/cm) 719 -

3. Turbidity (NTU) 41.9 -

4. Total Suspended Solids (mg/L) 70 600

5. Total Dissolved Solids (mg/L) 316 -

6. Bio-Chemical Oxygen Demand

(mg/l) 33.5 350

7. Total Hardness (mg/l) 80.8 -

8. Chemical oxygen Demand

(mg/l) 124 -

9. Chlorides (mg/l) 77.3 1000

10. Iron (mg/l) 0.27 3

11. Ammunical Nitrogen (mg/l) 4.22 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 11.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of The Care and Cure Polyclinic &

Medical Research Centre, Palace Compound, Tripura (W)

Page 21: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF TROPICAL ORTHOPEDICS & RELATED RESEARCH

CENTRE, KAMARPUKURPAR, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 8.11 5.5-9.0

2. Conductivity (µS/cm) 669 -

3. Turbidity (NTU) 5.22 -

4. Total Suspended Solids (mg/L) 78 600

5. Total Dissolved Solids (mg/L) 396 -

6. Bio-Chemical Oxygen Demand

(mg/l) 19 350

7. Total Hardness (mg/l) 60.6 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 35.7 1000

10. Iron (mg/l) 0.29 3

11. Ammunical Nitrogen (mg/l) 6.62 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 9.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Tropical orthopaedics &

Related Research Centre, Kamarpukurpar, Agartala, Tripura (W)

Page 22: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF AGARTALA NURSING HOSPITAL & RESEARCH

CENTRE PVT. LTD, POST OFFICE CHOWMUHANI, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.55 5.5-9.0

2. Conductivity (µS/cm) 1551 -

3. Turbidity (NTU) 9.62 -

4. Total Suspended Solids (mg/L) 68 600

5. Total Dissolved Solids (mg/L) 714 -

6. Bio-Chemical Oxygen Demand

(mg/l) 32 350

7. Total Hardness (mg/l) 70.7 -

8. Chemical oxygen Demand

(mg/l) 88 -

9. Chlorides (mg/l) 118.5 1000

10. Iron (mg/l) 0.25 3

11. Ammunical Nitrogen (mg/l) 4.88 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 11 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Agartala Nursing Hospital &

Research Centre Pvt. Ltd, Post Office Chowmuhani, Agartala, Tripura (W)

Page 23: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF BHAUMIK POLYCLINIC & NURSING HOME, A. A.

ROAD, DHALESWAR, AGARTALA, TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.06 5.5-9.0

2. Conductivity (µS/cm) 940 -

3. Turbidity (NTU) 42.7 -

4. Total Suspended Solids (mg/L) 88 600

5. Total Dissolved Solids (mg/L) 470 -

6. Bio-Chemical Oxygen Demand

(mg/l) 19 350

7. Total Hardness (mg/l) 101.01 -

8. Chemical oxygen Demand

(mg/l) 98 -

9. Chlorides (mg/l) 61.5 1000

10. Iron (mg/l) 0.27 3

11. Ammunical Nitrogen (mg/l) 6.22 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 15.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Bhaumik Polyclinic & Nursing

Home, A. A. Road, Dhaleswar, Agartala, Tripura (W)

Page 24: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF HOTEL GINGER, KHEJURBAGAN, AGARTALA,

TRIPURA (W).

Date of Collection: 25.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.95 5.5-9.0

2. Conductivity (µS/cm) 235 -

3. Turbidity (NTU) 2.37 -

4. Total Suspended Solids (mg/L) 34 600

5. Total Dissolved Solids (mg/L) 150 -

6. Bio-Chemical Oxygen Demand

(mg/l) 9.5 350

7. Total Hardness (mg/l) 60.7 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 32.7 1000

10. Iron (mg/l) 0.29 3

11. Ammunical Nitrogen (mg/l) 6.42 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 8 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Hotel Ginger, Khejurbagan,

Agartala, Tripura (W)

Page 25: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF AMC, BHUBANBAN, TRIPURA (W).

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.13 5.5-9.0

2. Conductivity (µS/cm) 445 -

3. Turbidity (NTU) 7.9 -

4. Total Suspended Solids (mg/L) 52 600

5. Total Dissolved Solids (mg/L) 284 -

6. Bio-Chemical Oxygen Demand

(mg/l) 15 350

7. Total Hardness (mg/l) 112 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 47.3 1000

10. Iron (mg/l) 0.08 3

11. Ammunical Nitrogen (mg/l) 5.02 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 5.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of AMC, Bhubanban, Tripura (W)

Page 26: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF HOTEL SHANKAR, AGARTALA, TRIPURA (W).

Date of Collection: 21.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 8.11 5.5-9.0

2. Conductivity (µS/cm) 3033 -

3. Turbidity (NTU) 55.8 -

4. Total Suspended Solids (mg/L) 208 600

5. Total Dissolved Solids (mg/L) 1941 -

6. Bio-Chemical Oxygen Demand

(mg/l) 38.2 350

7. Total Hardness (mg/l) 305.9 -

8. Chemical oxygen Demand

(mg/l) 122 -

9. Chlorides (mg/l) 27.2 1000

10. Iron (mg/l) 0.27 3

11. Ammunical Nitrogen (mg/l) 5.22 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 13.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water, from Sewage Treatment Plant of Hotel Shankar, Agartala, Tripura

(W)

Page 27: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF ASHA CHILDCARE & NURSING HOME & RESEARCH

CENTRE, AGARTALA, TRIPURA.

Date of Collection: 27.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.11 5.5-9.0

2. Conductivity (µS/cm) 411 -

3. Turbidity (NTU) 1.25 -

4. Total Suspended Solids (mg/L) 38 600

5. Total Dissolved Solids (mg/L) 263 -

6. Bio-Chemical Oxygen Demand

(mg/l) 15 350

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 51.9 1000

10. Iron (mg/l) 0.13 3

11. Ammunical Nitrogen (mg/l) 3.88 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 11 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Asha childcare & Nursing

Home Research Centre, Agartala, Tripura.

Page 28: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF SARKAR CLINIC & NURSING HOME, AGARTALA,

TRIPURA.

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.22 5.5-9.0

2. Conductivity (µS/cm) 145 -

3. Turbidity (NTU) 2.77 -

4. Total Suspended Solids (mg/L) 18 600

5. Total Dissolved Solids (mg/L) 92 -

6. Bio-Chemical Oxygen Demand

(mg/l) 5 350

7. Total Hardness (mg/l) 49.3 -

8. Chemical oxygen Demand

(mg/l) 34 -

9. Chlorides (mg/l) 23.7 1000

10. Iron (mg/l) 0.09 3

11. Ammunical Nitrogen (mg/l) 4.66 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 6.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Sarkar Clinic & Nursing Home,

Agartala, Tripura.

Page 29: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATMENT PLANT OF GOMATI MILK PRODUCER’S CO-OPERATIVE UNION,

INDRANAGAR, AGARTALA, TRIPURA.

Date of Collection: 21.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 8.85 5.5-9.0

2. Conductivity (µS/cm) 284 -

3. Turbidity (NTU) 23 -

4. Total Suspended Solids (mg/L) 44 100

5. Total Dissolved Solids (mg/L) 141 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 3 30

7. Total Hardness (mg/l) 50.5 -

8. Chemical oxygen Demand

(mg/l) 34 250

9. Chlorides (mg/l) 29.7 1000

10. Iron (mg/l) 0.12 3

11. Ammunical Nitrogen (mg/l) 4.22 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 14 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of Gomati Milk Producer’s Co-

operative Union, Indranagar, Agartala, Tripura.

Page 30: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF DISHA NURSING HOME, PALACE COMPOUND,

AGARTALA, TRIPURA (W).

Date of Collection: 21.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.89 5.5-9.0

2. Conductivity (µS/cm) 233 -

3. Turbidity (NTU) 0.41 -

4. Total Suspended Solids (mg/L) 22 600

5. Total Dissolved Solids (mg/L) 149 -

6. Bio-Chemical Oxygen Demand

(mg/l) 10 350

7. Total Hardness (mg/l) 40.4 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 21.3 1000

10. Iron (mg/l) 0.11 3

11. Ammunical Nitrogen (mg/l) 4.36 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 3.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Disha Nursing Home, Palace

Compound, Agartala, Tripura (W).

Page 31: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATEMENT PLANT OF RAMKRISHNA RUBBER INDUSTRY.

BODJUNGNAGAR, AGARTALA

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.18 5.5-9.0

2. Conductivity (µS/cm) 940 -

3. Turbidity (NTU) 91.8 -

4. Total Suspended Solids (mg/L) 72 100

5. Total Dissolved Solids (mg/L) 470 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 20 30

7. Total Hardness (mg/l) 135 -

8. Chemical oxygen Demand

(mg/l) 160 250

9. Chlorides (mg/l) 22.7 1000

10. Iron (mg/l) 0.15 3

11. Ammunical Nitrogen (mg/l) 5.68 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 9.5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of Ramkrishna Rubber Industry,

Bodhjungnagar, Agartala.

Page 32: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

EFFLUENT TREATMENT PLANT OF PROGRESSIVE AUTOMOBILES PVT. LTD,

NAGICHERRA, AGARTALA, TRIPURA

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.39 5.5-9.0

2. Conductivity (µS/cm) 155 -

3. Turbidity (NTU) 1.27 -

4. Total Suspended Solids (mg/L) 22 100

5. Total Dissolved Solids (mg/L) 99 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 11 30

7. Total Hardness (mg/l) 40.4 -

8. Chemical oxygen Demand

(mg/l) 64 250

9. Chlorides (mg/l) 23.9 1000

10. Iron (mg/l) 0.15 3

11. Ammunical Nitrogen (mg/l) 5.62 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 4.5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Effluent Treatment Plant of Progressive Automobiles Pvt.

Ltd, Nagicherra, Agartala, Tripura.

Page 33: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM EFFLUENT

TREATMENT PLANT OF SRI RAMKRISHNA ENGINEERING WORKS (UNIT-II), SOUTH

RAMNAGAR, TRIPURA (W).

Date of Collection: 14.08.2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.27 5.5-9.0

2. Conductivity (µS/cm) 168 -

3. Turbidity (NTU) 19.7 -

4. Total Suspended Solids (mg/L) 34 100

5. Total Dissolved Solids (mg/L) 108 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 9.5 30

7. Total Hardness (mg/l) 70.7 -

8. Chemical oxygen Demand

(mg/l) 64 250

9. Chlorides (mg/l) 18.7 1000

10. Iron (mg/l) 0.17 3

11. Ammunical Nitrogen (mg/l) 4.78 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 5.5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-2: Waste Water sample (Treated) collected from Sewage Treatment Plant of Sri Ramkrishna

Engineering works (Unit-II), South Ramnagar, Tripura (W).

Page 34: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM

SEWAGE TREATEMENT PLANT OF SANJEEVANI NURSHING HOME & RESEARCH

CENTRE, LALBAHADUR CHOWMUHANI, BANAMALIPUR, AGARTALA, TRIPURA (W)

Date of Collection: 21.08.2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 6.87 5.5-9.0

2. Conductivity (µS/cm) 457 -

3. Turbidity (NTU) 4.68 -

4. Total Suspended Solids (mg/L) 32 600

5. Total Dissolved Solids (mg/L) 292 -

6. Bio-Chemical Oxygen Demand

(mg/l) 8 350

7. Total Hardness (mg/l) 113 -

8. Chemical oxygen Demand

(mg/l) 64 -

9. Chlorides (mg/l) 69.2 1000

10. Iron (mg/l) 0.13 3

11. Ammunical Nitrogen (mg/l) 4.12 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 8.5 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water from Sewage Treatment Plant of Sanjeevani Nursing Home &

Research Centre, Agartala, Tripura (w).

Page 35: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM EFFLUENT

TREATMENT PLANT OF TARASANKAR MOTOR PVT. LTD, WEST CHINAIHANI, AIRPORT ROAD,

AGARTALA, TRIPURA (W).

Date of Collection: 21/08/2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 6.41 5.5-9.0

2. Conductivity (µS/cm) 236 -

3. Turbidity (NTU) 0.78 -

4. Total Suspended Solids (mg/L) 26 100

5. Total Dissolved Solids (mg/L) 117 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 7.5 30

7. Total Hardness (mg/l) 30.3 -

8. Chemical oxygen Demand

(mg/l) 64 250

9. Chlorides (mg/l) 16.9 1000

10. Iron (mg/l) 0.12 3

11. Ammunical Nitrogen (mg/l) 4.62 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Waste Water sample (Treated) collected from Sewage Treatment Plant of Tarasankar Motor

Pvt. Ltd, West Chinaihani, Airport Road, Agartala, Tripura (W)

Page 36: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM EFFLUENT

TREATMENT PLANT OF JAIN UDYOG (AUTOMOBILE DIVISION) A.D.NAGAR, AGARTALA,

TRIPURA (W).

Date of received: 21/08/2020

Sl. No Parameters S-1 Standards

(Into inland surface water)

1. pH 7.11 5.5-9.0

2. Conductivity (µS/cm) 61.9 -

3. Turbidity (NTU) 0.87 -

4. Total Suspended Solids (mg/L) 8 100

5. Total Dissolved Solids (mg/L) 32 2100

6. Bio-Chemical Oxygen Demand

(mg/l) 3.5 30

7. Total Hardness (mg/l) 40.4 -

8. Chemical oxygen Demand

(mg/l) 34 250

9. Chlorides (mg/l) 17.8 1000

10. Iron (mg/l) 0.12 3

11. Ammunical Nitrogen (mg/l) 3.08 50

12. Sulphide (mg/l) BDL 2

13. Oil and Grease (mg/l) 4.5 10

14. Fluorides (mg/l) BDL 2

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)

Site of collection:

S-1: Treated Waste Water sample collected from Sewage Treatment Plant of Jain Udyog

(Automobile Division) A.D.Nagar, Agartala, Tripura (W).

Page 37: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF INLET AND OUTLET WASTE WATER SAMPLES COLLECTED FROM THE EFFLUENT TREATMENT PLANT OF VIRGIN RUBBER PVT. LTD, SIMNA, KALIBARI, TRIPURA (W).

Date of Collection: 18/08/2020

Sl. No Parameters S-2

Standards, CPCB (Disposal on

land)

1. pH 4.66 5.5-8.0

2. Conductivity (µS/cm) 8044 -

3. Turbidity (NTU) 321 -

4. Total Suspended Solids (mg/L) 398 200

5. Total Dissolved Solids (mg/L) 4022 2100

6. Bio-Chemical Oxygen Demand (mg/l) 280 10

7. Total Hardness (mg/l) 808 -

8. Chemical oxygen Demand (mg/l) 1280 250

9. Chlorides (mg/l) 24.2 -

10. Iron (mg/l) 0.47 -

11. Ammunical Nitrogen (mg/l) 6.86 -

12. Sulphide (mg/l) 0.39 -

13. Oil and Grease (mg/l) 25 10

14. Fluorides (mg/l) BDL -

15. Arsenic (mg/l) BDL -

*BDL (Below Detectable Limit)

Site of collection:

Outlet waste water sample collected from the Effluent Treatment Plant of Virgin Rubber Pvt. Ltd, Simna, Kalibari, Tripura (W).

Page 38: ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE … · 2021. 1. 4. · ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM SEWAGE TREATEMENT PLANT OF MAA SARADA TRUST,

ANALYTICAL RESULTS OF TREATED WASTE WATER SAMPLE COLLECTED FROM ROYAL GUEST

HOUSE, PALACE COMPOUND, AGARTALA, TRIPURA (W).

Date of Collection: 05/08/2020

Sl. No Parameters S-1 Standards

(Into Public Sewers)

1. pH 7.49 5.5-9.0

2. Conductivity (µS/cm) 666 -

3. Turbidity (NTU) 25.1 -

4. Total Suspended Solids (mg/L) 58 600

5. Total Dissolved Solids (mg/L) 333 -

6. Bio-Chemical Oxygen Demand (mg/l) 10 350

7. Total Hardness (mg/l) 242.4 -

8. Chemical oxygen Demand (mg/l) 32 -

9. Chlorides (mg/l) 62.9 1000

10. Iron (mg/l) 0.10 3

11. Ammunical Nitrogen (mg/l) 3.66 50

12. Sulphide (mg/l) BDL -

13. Oil and Grease (mg/l) 18 20

14. Fluorides (mg/l) BDL 15

15. Arsenic (mg/l) BDL 0.2

*BDL (Below Detectable Limit)