  • 8/11/2019 Analogue Instruments REV 04-10

    1/86

    Analogue Instruments

    ENERGY DIVISION

  • 8/11/2019 Analogue Instruments REV 04-10

    2/86

  • 8/11/2019 Analogue Instruments REV 04-10

    3/861

    Features

    Extensive range

    A ccurate m easurem ent and display of

    electrical and electronic param eters

    W ide range of case styles and

    specifications

    M axim um reliability in harsh

    environm ents

    Benefits

    Low cost

    Local indication

    Ease of installation

    M inim al training

    Low m aintenance

    R easonable accuracy

    Applications

    Sw itchgear

    D istribution system s

    G enerator sets

    C ontrol panels

    Energy m anagem ent

    B uilding m anagem ent

    U tility pow er m onitoring

    Process control

    M otor control

    Approvals

    U L, C SA , A B S, LR S, B V, ISS eP

    Contents Page

    DIN Panel Meters 2 29A n extensive range of 48, 72, 96 and 144m m D IN style panel

    m eters. Short-scale am m eters, voltm eters and frequency m eters

    incorporate slide-in dials and term inal covers. Long-scale m eters

    are also available. M eters for pow er or energy contain in-built

    transducers and can be custom ised to suit m any different systemconfigurations and ranges.

    Instrument Selector Switches 30 31Panel m ounted selector sw itches offering a 7-position

    voltm eter sw itch and a 4-position am m eter sw itch for reading

    line-to-line or line-to-neutral voltage and phase current.

    070 Series ANSI Switchboard Meters 32 62A n extensive range of analogue and digital/analogue m eters in

    412" and 834" A N SI case styles. M eters utilise a high shock oil

    dam pened m ovem ent, and provide 1% accuracy for all R M S A C

    and D C ranges. The range offers various custom ised options and

    features. U L, C SA , A B S and ISSeP approvals.

    549 Series Panel Meters 63 65C om pact panel m eters designed to fit standard 1 732" sw itch

    knock-outs. The range offers high accuracy AC and D C am m eters

    and voltm eters, elapsed tim e m eters and im pulse counters.

    A B S approvals.

    Saxon Series Panel Indicators 66 67A range of 212", 312" and 412" surface m ount panel m eters utilising

    taut band m echanism s and offering IP54 protection. The range

    offers iron vane and m oving coil A C and D C am m eters and

    voltm eters, elapsed tim e and frequency m eters. U L approvals.

    016 Series Fiesta Panel Indicators 68 70A robust range of short-scale and long-scale 3 12" surface m ount

    panel m eters offering IP55 protection and featuring w ide

    view -contoured w indow s. The range offers iron vane and

    m oving coil A C and D C am m eters and voltm eters, elapsedtim e and frequency m eters. U L approvals.

    Challenger Series 71 75C hallenger analogue panel m eters feature a detachable low er

    fascia plate, w hich allow s either surface or w indow m ounting.

    M eters use a high torque pivot and jew el m ovem ent.

    078/080/087 Series Sealed and Ruggedised Indicators 76 80D esigned to com ply w ith industrial, m arine and m ilitary

    specifications, these 240 and 90 scale m eters m eters

    are resistant to extrem e shock, vibration, tem perature, dirt

    and hum idity. The range offers a w ide range of bezel sizes fitted

    w ith toughened glass.

    Guide to Catalogue Numbering Systems and Glossary 81 82

    Analogue Instruments

    H igh quality analogue instrum ents designed to m easure an extensive

    range of electrical and electronic param eters. This com prehensive range

    offers D IN instrum ents, A N SI sw itchboard m eters, panel indicators,

    sealed and ruggedised instrum ents, and com plem entary selector

    sw itches for line-to-line and line-to-neutral readings. Instrum ents are

    precision engineered and robust in design, ensuring accuratem easurem ent and display in the m ost dem anding of environm ents.

    A llinstrum ents are available in a range of styles, sizes and specifications

    to m eet the exacting needs of your industry.

  • 8/11/2019 Analogue Instruments REV 04-10

    4/862

    Features

    A range of the m ost popular short-scale

    m easuring instrum ents in 4 case sizes

    Shock resistant sprung pivot and jew el

    m ovem ent

    Term inal covers supplied as standard

    EM C hard frequency m eter are fully

    EM C and LVD com pliant1/4" fast onterm inals available

    Benefits

    Low cost

    Local indication

    Ease of installation

    M inim al training

    Low m aintenance

    C ustom ised options and features

    Applications

    Sw itchgear

    D istribution system s

    G enerator sets

    C ontrol panelsEnergy m anagem ent

    B uilding m anagem ent

    U tility pow er m onitoring

    Process control

    M otor control

    Approvals

    Lloyds:

    03/00055 - M oving coil m eters

    03/00056 - M oving iron m eters

    03/00057 - Frequency m eters

    DIN Panel Meters Short scale

    A range of 48, 72, 96 and 144m m D IN style panel m eters m easuring

    all electrical param eters and featuring m oving coil or m oving iron

    m ovem ents. A ll m eters incorporate slide-in dials and term inal covers as

    standard. A range of custom ised options is available.

    MovementsMoving Coil Meter

    C entre cored, self shielding m oving coil m ovem ent, using pivots, hairsprings and sprung

    jew els. Seven variations have been designed in m ovem ent ranges: all interm ediate

    ranges are achieved by shunting the next low est range. A ll D C voltm eters are 1000

    ohm s per volt, rectified product run at 900 ohm s per volt, m illivolt m eters use the 5

    m illiam p m ovem ent.

    Moving Iron Meter

    C lapper type repulsion design using pivots, hairsprings and jew el m ovem ents.

    The bottom jew el is oil filled to provide dam ping w hile the top is sprung for resilience.

    A ll voltm eters are m anufactured w ith external voltage dropper resistors to substantially

    reduce the self heating effects.

    Frequency MeterM eter uses a 100 m icroam p 4000 ohm m ovem ent driven by an EM C hard frequency

    conversion circuit.

    Dials, Scales and PointersStandard dials are w hite m atte w ith black printed scales and bar knife-edge pointers.

    B lack dials w ith w hite or yellow scales and pointers are also available. Interchangeable

    slide-in dials are used on the E242, E243, E244 and 246 90 m oving iron, m oving coil

    and frequency m eter m odels.

    G eneral options include red supplem entary pointers, red indexes (quadrant scales), red,

    green or blue lines, bands or segm ents, finely spaced divisions, m ulti-scales, special

    scales and captions to custom er' requirem ents.

    Specifications

    Type of M oving iron for M oving coil for M oving coil w ith M oving coil w ith M axim um Com bined M D Iinstrument current and current and rectifiers for built-in transducer dem and w ith m oving

    voltage voltage current and for frequency indicators iron m ovem entvoltage m easurem ent

    Format 48 x 48m m 48 x 48m m 48 x 48m m72 x 72m m 72 x 72m m 72 x 72m m 72 x 72m m 72 x 72m m96 x 96m m 96 x 96m m 96 x 96m m 96 x 96m m 96 x 96m m 96 x 96m m144 x 144m m 144 x 144m m 144 x 144m m 144 x 144m m

    Movement Sprung pivot Sprung pivot Sprung pivot Sprung pivot Sprung pivot Sprung pivottype jew el w ith silicon jew el w ith eddy jew el w ith eddy jew el w ith eddy jew el w ith silicon jew el w ith silicon

    oil dam ping current dam ping current dam ping current dam ping oil dam ping oil dam ping

    Burden 0.5VA - 15A See detailed See detailed See detailed 2.5VA 3VAthen 0.8VA specifications specifications specifications

    voltm eters 4.5V AAccuracy 1.5% to 1.5% to 2.5% to 0.5% to D IN 4 3780 3% on M D I 3% on M D I

    D IN 43780 D IN 43780 D IN 43780 1.5% am m eter

    Input type AC current or DC current or Rectified AC Frequency for all M ean RM S value M ean RM S valuevoltage voltage current or voltage ranges and m axim um and m axim um

    voltage dem and current dem and currentand instantaneouscurrent

    Measuring 6 - 600V 15m V - 600V 6 - 600V 57.7V @ 45H z 1 - 6A 1 - 6Arange 100m A -100A 25A - 100A 100A - 100m A 500V @ 44H z 8, 15 or 20 8, 15 or 20

    m inute delays m inute delays0 - 5A /6Ainstantaneous

    Dielectric 3kV AC 3KV AC 3KV AC 3KV AC 3KV AC 3KV ACvoltagewithstandtest

  • 8/11/2019 Analogue Instruments REV 04-10

    5/863

    General Specifications

    Dimensions

    Perform ance B SEN 60051

    M easuring ranges D IN 43701

    A ccuracy overload B SEN 60051

    D im ensions D IN 43700

    Scale m arking generally to D IN 43802

    M agnetic influence B SEN 60051

    Safety B SEN 61010-1

    Term inals C lam p strap M 4 for up to 25A . C lam p strap M 8 forover 25A .1/4" spade term inals available for m odels E243 and E 244

    H um idity range U p to 95% R H (non condensing)

    Test voltage @ 50H z 3kV R M S for 1 m inute

    Am m eter ranges 1.0/1.2/1.3/1.5/2.5/4/5/6/8 and decade m ultiples thereof.

    O verload AC current x 1.2 continuous x 10 for 5 seconds

    A C voltage and frequency x 1.2 continuous x 2 for 5 seconds

    Standard calibration 23C . C alibration at other tem peratures available

    on request

    O perating tem perature -20C to +60C

    D am ping tim e Less than 3 seconds

    Enclosure code IP52 as standard

    IP54 on requestC ase and base G rade U L94V0 (Lexan 500R )

    C ase D im ensions and panel cutout conform to IEC 473, D IN

    43700. C ase m ade from glass filled polycarbonate self-

    extinguishing and non drip in accordance w ith U L94 V -O .

    B ezel Slim -line D IN 43802, black as standard

    Bezel w indow Standard sheet glass, w ith zero adjusters w here

    appropriate. N on reflecting glass or polycarbonate

    shatterproof w indow s are available.

    Installation Installations in sw itchboard panel or m osaic

    arrangem ent on equipm ent or m achine w ith a panel

    thickness of up to 40m m in a horizontal or vertical plane

    Fixing on panel Sw ivel captive fasteners, w hich can be fixed

    at either corner.

    M ounting position N orm al vertical m ounting or as indicated on the scalein accordance w ith D IN 16 25 7. A de viation of 15 is perm issible

    Insulation group Insulation resistance m ore than 5M @ 500 V

    E nvironm ental M easurem ent category III IE C 1010-1

    Pollution degree 2 IEC 1010-1

    Electrical rating 600V R M S (920V peak)

    A pprovals EM C, LVD and Lloyds

    Max. panel thickness = 40mm

    Moving coil measuring range Moving iron measuring range

    6 - 60A C = 67m m 0 - 30A C = 64m m

    > 60A C = 78m m > 30A C = 67m m

    D A B

    48 x 48 45 x 45 4

    72 x 72 68 x 68 4

    96 x 96 92 x 92 4

    144 x 144 135 x 135 4

    D 53 C CA B

    DIN 16257 symbol meaning for

    calibration position

    Vertical

    Horizontal

    Inclined 60

    Inclination of dial surface.

    R equired orientation m ust alw ays be

    stated w hen ordering if other than

    vertical m ounting is required.

  • 8/11/2019 Analogue Instruments REV 04-10

    6/864

    DIN Panel Meters Short scale

    Moving Iron AC Ammeters and Voltmeters

    D esigned to m easure A C current or voltage, these m eters indicate true

    R M S values and are substantially independent of system w aveform .

    Scales are calibrated dow n to 20% , and am m eters can have overload

    scales of x2, x3, x5 or x6 for m otor start duty. A m m eters can be supplied

    for use w ith -/1A or -/5A current transform ers, w hilst voltm eters can bescaled for use w ith voltage transform ers. H eavy dam ping is available as

    an option. M eters can be used to m easure D C at reduced accuracy.

    Frequency Meters

    Frequency m eters use an integral electronic converter and a m oving coil

    indicator. These easy to read m eters are C lass 0.5 accurate.

    A ccuracy: C lass 1.5

    Frequency: 50 or 60H z, (400H z on request)

    B urden at 50H z: A m m eters: 0.5VA

    voltm eters: U p to 4.5V A m axim um

    R atings: A m m eters: 0.5 - 100A A C direct connected (40A for

    E242-75A and E246-07A ).

    M axim um system voltage 600V AC

    Low load / high m iddle, m axim um 10A

    Voltm eters: 6 - 600V

    B ezel size m m 48 72 96 144

    Scale length m m 42 65 94 145

    Product codes

    A C am m eter E242-75A E243-02A E244-02A 246-071A

    x2 overload am m eter E242-752A E243-022A E244-022A 246-072

    x3 overload am m eter E242-753A E243-023A E244-023A 246-073

    x5 overload am m eter E242-755A E243-025A E244-025A 246-075

    x6 overload am m eter E242-756A E243-026A E244-026A 246-076

    A C voltm eter E242-75V E243-02V E244-02V 246-07V

    R atings: 100-125V A C

    200-250V A C

    380-440V A C *500V AC *

    *U se E242-013 and 253-TH Z in place of E242-41S for

    voltages over 380V

    M odels available for use w ith V Ts

    Frequency: 0.5% : 45/55H z, 55/65H z, 45/65H z, 360/440H z

    B urden: 4VA m axim um

    Product Codes

    Specifications

    B ezel size m m 48 72 96

    Scale length m m 42 65 94

    Product codes E242-41S E243-41S E244-41S

    Product Codes

    Specifications

    Connections

    AC Ammeter

    AC Voltmeter

    Connections

  • 8/11/2019 Analogue Instruments REV 04-10

    7/865

    Maximum Demand Indicators

    The therm al/tim e characteristics of M D I m eters m onitor the m ost

    econom ic use of cable, fusegear and transform ers. The directly heated

    bim etal elem ent indicates m ean R M S current over 8, 15, or 20 m inutes,

    and a red slave pointer show s the highest value reached. The reset knob

    is w ire sealable. Scales are calibrated to m atch the C T prim ary plus 20%

    overload. End values are selected from : 1.2, 1.8, 2.4, 3, 3.6, 4.8, 6, 7.2,

    9 am ps and their m ultiples of 10 and 100.

    Combined AC Ammeter and Maximum Demand Indicator

    W here m easurem ent of instantaneous and m axim um dem and currents

    are required, these instrum ents com bine both m ovem ents in one case.

    The m eter can also replace an existing A C am m eter.

    M eets the sam e specifications listed above.

    A ccuracy: C lass 3

    O ptions: 5A for use w ith separate C T

    5/5A saturating C T

    1/5A saturating C T

    B urden at 50 H z: M D I - 2.5VA , C T - 2VA

    O verload w ithstand: Standard: 5 x FL for 5 seconds, 10 x FL for 1 second.

    W ith saturating C T: 10 x FL for 3 seconds,

    20 x FL for 1 secondFrequency: 50/60H z

    A ccuracy: M oving iron am m eter: C lass 1.5

    M D I: C lass 3

    B urden at 50H z: M I - 0.5VA , M D I - 2.5VA

    saturating C T - 2V A

    B ezel size m m 72 96

    Scale length m m * 65 94

    Product codes

    8 minute time lag

    w ithout lim iting C T for use w ith 5A C T E243-16B E244-16B

    15 minute time lag

    w ithout lim iting C T for use w ith 5A C T E243-16A E244-16A

    20 minute time lag

    w ithout lim iting C T for use w ith 5A C T E243-16J E244-16J

    * S caled 0/100/120% of C T prim ary value.

    Product Codes

    Specifications

    B ezel size m m 72 96

    Scale length m m * 65 94

    Product codes

    8 minute time lag

    w ithout lim iting C T for use w ith 5A C T 3VA E244-16Q

    15 minute time lagw ithout lim iting C T for use w ith 5A C T 3V A E243-16C E244-16C

    20 minute time lag

    w ithout lim iting C T for use w ith 5A C T 3VA E244-16H

    * S caled 0/100/120% of C T prim ary value.

    Product Codes

    Specifications

    Connections

    Maximum Demand Indicators

  • 8/11/2019 Analogue Instruments REV 04-10

    8/866

    Connections

    DC Voltmeter

    DC Ammeter

    Connections

    AC Ammeter

    AC Voltmeter

    Moving Coil DC Ammeters and Voltmeters

    M oving coil m eters are suitable for all D C system s. The linear scale is

    calibrated dow n to zero and the accuracy m aintained dow n to 10% .

    H igh currents are m easured w ith separate shunts and suitably scaled

    indicators. Suppressed, centre and offset zero m odels are available.

    Moving Coil Rectified AC Ammeters and Voltmeters

    For high frequency or linear full scale A C m easurem ents, theseinstrum ents m easure average values of sinusoidal w aveform s and are

    scaled in R M S values. The high quality silicon bridge rectifier gives a

    linear scale dow n to near zero, w here som e com pression occurs.

    A ccuracy: C lass 1.5

    R atings: A m m eters: 100A -25A , (200A for long-scale m odel)

    4/20m A suppressed zero

    40A for m odel E242, E243 and E 244 up to 100A

    Voltm eters: 50m V-600V

    1/5V suppressed zero

    50, 60, 75, 100, 150m V for use w ith shunts

    Im pedance: A m m eters: 75m V internal shunt above 60m A

    Voltm eters: 1000/V above 1V

    B ezel size m m 48 72 96 144

    Scale length m m 42 65 94 145

    Product codes

    A m m eters E242-89A E243-01A E244-01A 246-10A

    A m m eters suppressed zero E242-89R E243-01R E244-01R 246-10

    Voltm eters E242-89V E243-01V E244-01V 246-10V

    Voltm eters suppressed zero E242-89S E243-01S E244-01S 246-10S

    A ccuracy: 1.5% ES

    R atings: A m m eters: 250A -1A A C

    O ver 1A via CTs

    Voltm eters: 15 - 600V A C direct connected.

    m odels available for use w ith V Ts

    Frequency: 50/60Hz, (Single frequencies 25Hz - 3kHz on request)

    Product Codes

    B ezel size m m 48 72 96 144

    Scale length m m 42 65 94 145

    Product codes

    A m m eters E242-89B E243-01B E244-01B 246-10B

    Voltm eters E242-89W E243-01W E244-01W 246-10W

    Product Codes

    Specifications

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    9/867

    Process Indicators

    M eters are used to check process functions locally or rem otely at

    centralised controls. These m oving coil instrum ents offer a w ide variety

    of electrical and m echanical readouts and are operated by transducer,

    tachogenerator, therm ocouple, resistance bulb or other D C analogue

    signals. Suppressed, centre and offset zero m odels are available on request.

    A ccuracy: C lass 1.5

    R atings: 1, 2, 5, 10, 20m A

    4/20m A suppressed zero

    B ezel size m m 48 72 96 144

    Scale length m m 42 65 94 145

    Product codes

    A C current E242-89A E243-01A E244-01A 246-10A

    A C voltage E242-89V E243-01V E244-01V 246-10V

    Speed E242-892 E243-012 E244-012 246-102

    Frequency E242-893 E243-013 E244-013 246-103

    Phase angle E242-894 E243-014 E244-014 246-104

    W atts E242-895 E243-015 E244-015 246-105

    VA r E242-896 E243-016 E244-016 246-106

    VA E242-897 E243-017 E244-017 246-107

    Product Codes

    Connections

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    10/868

    Features

    Extensive range of specialist m eters in

    four case sizes

    Shock resistant taut band suspension

    Vibration-proof H i-Q dam ping

    Slide-in dials for 90current, voltage and

    frequency on m odels 242, 243 and 244

    Term inal covers supplied as standard

    Benefits

    Low cost

    Local indication

    Ease of installation

    M inim al training

    Low m aintenance

    C ustom ised options and features

    Applications

    Sw itchgear

    D istribution system s

    G enerator sets

    C ontrol panels

    Energy m anagem ent

    B uilding m anagem ent

    U tility pow er m onitoring

    Process control

    M otor control

    Approvals

    LRS and BV

    DIN Panel Meters Long-Scale

    A n extensive range of 48, 72, 96 and 144m m D IN style panel m eters

    m easuring all electrical and electronic param eters. M eters are shock

    resistant and vibration proof and supplied w ith term inal covers.

    A selection of slide-in dials and custom ised options are available.

    MovementsIn C rom pton Instrum entspatented H i-Q taut band suspension, all the delicate parts ofthe traditional instrum ents are elim inated. There are no pivots, no jew el bearings, no

    hair-springs and no air dam ping vane. Instead, a tough platinum ribbon suspends the

    m oving elem ent betw een front and rear tension springs. Specially contoured pads are

    fitted to the ends of the spindle, and the w orking gap at each end is filled w ith a high

    quality silicon fluid. The pads, together w ith the fluid reservoir, form a system w hich

    acts as a resilient built-in shock absorber. This provides both rotational and longitudinal

    dam ping as the m oving elem ent floats on oil w ith no bearing friction and is effectively

    cushioned against shock and vibration. 360 synchroscopes and pow er factor m eters

    have robust pivot and jew el bearings w ith oil dam ping.

    Dials, Scales and Pointers

    Standard dials are w hite m atte w ith black printed scales and bar knife-edge pointers.

    B lack dials w ith w hite or yellow scales and pointers are also available. Interchangeable

    slide-in dials are used on m odel num bers 242, 243 and 244 90 m oving iron, m oving coil

    and frequency m eters.

    G eneral options include red supplem entary pointers, red indexes (quadrant scales), red,

    green or blue lines, bands or segm ents, finely spaced divisions, m ulti-scales, special

    scales and captions to custom er' requirem ents.

    Illumination

    M eters com e w ith a full range of illum ination options. Internal illum ination is available

    in the follow ing m odels:

    244 and 246 short-scale m oving coil and m oving iron vane.

    243,244 and 246 long-scale m oving coil and m oving iron vane.

    Through-dial (translucent) illum ination on 244 and 246 m odels. Edge illum ination on 243,

    244 and 246 m odels. R eplaceable 6, 12 or 24V lam ps are used on all m odels except 243

    long-scale m eters, w here the lam ps are internal.

    Perform ance B SEN 60051

    M easuring ranges D IN 43701

    A ccuracy overload B SEN 60051

    D im ensions D IN 43700

    Scale m arking generally D IN 43802

    M agnetic influence B SEN 60051

    Safety IEC 414

    Term inals C lam p strap M 4 up to 25A . C lam p strap M 8 for

    over 25A

    H um idity range U p to 95% R H (non condensing)

    Test voltage @ 50H z 2kV RM S for 1 m inute

    O verload AC current x 1.2 continuous x 10 for 5 seconds

    O verload A C voltage x 1.2 continuous x 2 for 5 seconds

    Frequency See m ain pages for other instrum ents

    Dam ping tim e Less than 3 seconds is standard. M ore heavily

    dam ped m ovem ents are available on request.

    Standard calibration 23C

    O perating tem perature -20C to -60C

    Enclosure code IP54 as standard (to BSEN 60529). For IP55 consult

    w ith factory.

    Term inals IP20B w ith term inal cover or term inal

    boots fitted

    C ase G rade U L94V0

    B ase G rade U L94V1

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    11/869

    DIN 16257 symbol meaning for

    calibration position

    Vertical

    H orizontal

    Inclined 60

    Inclination of dial surface from a

    horizontal plane, e.g. 60

    R equired orientation m ust alw ays be

    stated w hen ordering if other than

    vertical m ounting is required.

    Specifications Continued

    Dimensions

    C ase D im ensions and panel cutout conform to IEC 473,

    D IN 43700. M odels 242, 243 and 244 have injection

    m oulded cases and bezels in flam e retardant

    engineering therm oplastic, recognised by U nderw riters

    Laboratory m aterials specifications. A ll 246 m odels

    have pressed steel cases.

    B ezel Slim -line D IN 43802, black as standard

    Bezel w indow Standard sheet glass, w ith zero adjusters w hereappropriate. N on reflecting glass or polycarbonate

    shatterproof w indow s are available.

    Installation Installations in sw itchboard panel or m osaic

    arrangem ent on equipm ent or m achine w ith a panel

    thickness of up to 40m m in a horizontal or vertical

    plane. Installation C ategory III

    Fixing on panel M odels 242, 243 and 244 2 corner fixing clam ps

    and tensioning thum b screw s.

    M odel 242 available w ith a one piece push onclam p.

    M odel 246 2 side fixing spring clips.

    M ounting position N orm al vertical m ounting or as indicated on the scale

    in accordance w ith D IN 16257. A deviation of 15 is

    perm issible.

    A pprovals Lloyds Shipping (LR S), B ureau Veritas (B V), EM C and LV D

    Model 242 243 244 246

    B ezel A 48 x 48 72 x 72 96 x 96 144 x 144

    Panel cut-out B 45 x 45 68 x 68 92 x 92 138 x 138

    Scale length: 90 42 65 94 145

    Scale length: 240 72 112 150 230

    Maximum overall depth C:

    A m m eters and voltm eters AC and D C * 64 64 64 60A m m eters and voltm eters w ith sw itch* 64

    D ual m eters* 64

    Elapsed tim e m eter/hours run* 64 64 64

    M axim um dem and indicator* 64 64 60

    C om bined M D I and M I indicator* 64 60

    M axim um dem and indicator w ith relay* 90

    Frequency m eter 90* 64 64 64 60

    Frequency m eter 240* 120 125

    Phase angle, pow er factor m eter 90* 107

    240* 107

    M .C . indicator w ith separate transducer* 64 64 64 60

    D ynam om eter 360 synchroscope* 120 125

    D ynam om eter 360 pow er factor m eter* 120

    Phase sequence indicator* 64 64

    Position indicator* 120 125

    Speed indicator* 64 64 64 60

    Tem perature indicators* 120 125

    Q uadra m eters* 64

    Im pulse counters* 64 64 64

    W attm eter, VA rm eter 90 107 125

    W attm eter, VA rm eter 240 107 125

    M odel 244-21Y and 244-21Z 142

    LED synchroscope and synchro check relay 80

    LED 360 synchroscope 80

    Indicator only

    * If separate term inal cover is used, add 20m m to dim ension C .

    N ot available

    Panel cut-out

    M axim um panel

    thickness 10m m

    B

    B

    A

    A

    C

  • 8/11/2019 Analogue Instruments REV 04-10

    12/8610

    Connections

    AC Ammeter

    AC Voltmeter

    Moving Iron AC Ammeters and Voltmeters

    D esigned to m easure A C current or voltage, these m eters indicate true

    R M S values and are substantially independent of system w aveform .

    Scales are calibrated dow n to 20% , and am m eters can have overload

    scales x2, x3, x5 or x6 for m otor start duty. A m m eters can be supplied

    for use w ith -/1A or -/5A current transform ers, w hilst voltm eters can be

    scaled for use w ith voltage transform ers. H eavy dam ping is available as

    an option. M eters can be used to m easure D C at reduced accuracy.

    A ccuracy: C lass 1.5

    Frequency: 50 or 60H z, (400H z on request)

    B urden at 50H z: A m m eters: 1.5VA

    Voltm eters: 4.5VA m axim um

    R atings: A m m eters: 0.5 - 25A A C D C

    M axim um system voltage 720V A C Low load / high

    m iddle (m axim um 10A )Voltm eters: 6 - 600V A C

    B ezel size m m 48 72 96 144

    Scale length m m 72 112 150 230

    Product codes

    A m m eter 242-03A 243-03A 244-03A 246-03A

    x2 overload am m eters 242-032 243-032 244-032 246-032

    x3 overload am m eters 242-033 243-033 244-033 246-034

    x5 overload am m eters 242-035 243-035 244-035 246-035

    x6 overload am m eters 242-036 243-036 244-036 246-036

    Low load am m eters 243-03H 244-03H Voltm eter 242-03V 243-03V 244-03V 246-03V

    Product Codes Long Scale

    Specifications Long-Scale Meters

  • 8/11/2019 Analogue Instruments REV 04-10

    13/86

  • 8/11/2019 Analogue Instruments REV 04-10

    14/8612

    Connections

    AC Ammeter

    AC Voltmeter

    Connections

    DIN Panel Meters Long-Scale and Dual

    Moving Coil Rectified AC Ammeters and Voltmeters

    For high frequency or linear full scale A C m easurem ents, these

    instrum ents m easure average values of sinusoidal w aveform s and are

    scaled in R M S values.

    The high quality silicon bridge rectifier gives a linear scale dow n to near

    zero, w here som e com pression occurs.

    Dual Frequency Meters

    Tw o instrum ents in one case can be used to m easure a w ide range of

    frequencies. These dual instrum ents save both panel space and assem bly

    tim e. The 244-41D is an ideal com ponent in synchronising applications.

    B ezel size m m 48 72 96 144

    Scale length m m 72 112 150 230

    Product codes

    A m m eters 242-05B 243-05B 244-05B 246-05B

    Voltm eters 242-05W 243-05W 244-05W 246-05W

    Product Codes Long-Scale

    Specifications Long-Scale

    A ccuracy: 1.5-% ES

    R atings: A m m eters: 250A -1A A C . U p to 30A on m odels 244/246-05B

    Voltm eters: 15 - 600V direct connected

    M odels available for use w ith V Ts

    Frequency: 50/60H z. (Single frequencies 25Hz to 3kHz on request)

    B ezel size m m 96

    Scale length m m 65

    Product code 244-41D

    Product Code

    Specifications

    A ccuracy: C lass 0.5

    R atings: 100 - 125V A C

    200 - 250V A C

    380 - 440V A C

    500V A CM odels available for use w ith V Ts

    Frequency 0.5% : 45/55H z,

    55/65H z,

    45/65H z,

    360/440H z

    B urden: 4VA m axim um

  • 8/11/2019 Analogue Instruments REV 04-10

    15/8613

    Features

    Integral selector sw itch

    True RM S m easurem ent

    Slide-in dials

    Scaled for custom er VT or C T

    prim ary values

    D IN 72 and D IN 96 m odelsTerm inal cover as standard

    Shock resistant sprung pivot and

    jew el m ovem ent

    x2 overload am m eters

    Benefits

    Space and tim e saving

    C om petitive cost

    Local indication

    Ease of installation

    Low m aintenance

    C ustom ised options and features

    Applications

    Sw itchgear

    D istribution system s

    G enerator Sets

    C ontrol panels

    Energy m anagem ent

    B uilding m anagem ent

    Compliant with

    IEC 61010-1B 2001, EM C and LVD

    DIN Panel Meters

    Moving Iron AC Ammeters and Voltmeters

    with Selector Switch

    Crom pton Instrum ents, a business unit of Tyco Electronics, is pleased to

    add the new m oving iron AC am m eter and voltm eter w ith selector sw itch to

    its com prehensive range of panel m eters. These 96m m and 72m m unitsoffer Class 1.5 true RM S m easurem ent of three-phase A C voltage or current

    w ith various sw itch notation options. The integral selector sw itch elim inates

    the necessity for a separate selector sw itch, saving valuable panel space

    and providing installation benefits. Both am m eters and voltm eters feature a

    slide-in dial, scaled for VT or CT values to suit application prim ary values.

    These robust m oving iron m eters incorporate a clapper type repulsion

    design w hich utilises a pivot, hairspring and jew el m ovem ent. The bottom

    jew el is oil filled to provide dam ping w hile the top is sprung for resilience.

    Voltm eters are m anufactured w ith internal voltage dropper resistors.

    Product Codes AC Voltmeters with Selector Switch

    Product Codes AC Ammeters with Selector Switch

    Product Codes Options

    Code Case Full scale Switch notation 3-

    size deflection Phase

    E243-02Q -G -PM **-C 7-SW 6 72m m 0/120 V A C 0FF L1L2 L2L3 L3L1 3W

    E243-02Q -G -PZ**-C 7-SW 6 72m m 0/150 V A C 0FF L1L2 L2L3 L3L1 3W

    E243-02Q -G -PZ-PZ-C 7-SW 6 72m m 0/150 V A C 0FF L1L2 L2L3 L3L1 3W

    E243-02Q -G -R X-R X-C 7-SW 6 72m m 0/300 V A C 0FF L1L2 L2L3 L3L1 3W

    E243-02Q -G -SF-SF-C7-SW 3 72m m 0/500 V AC L1L3 L1L2 L2L3 L3N L2N L1N 4W

    E243-02Q -G -SJ-SJ-C7-SW 3 72m m 0/600V AC L1L3 L1L2 L2L3 L3N L2N L1N 4W

    E244-02Q -G -PZ**-C 7-SW 6 96m m 0/150 V A C 0FF L1L2 L2L3 L3L1 3W

    E244-02Q -G -PZ-PZ-C 7-SW 6 96m m 0/150 V A C 0FF L1L2 L2L3 L3L1 3WE244-02Q -G -R X-R X-C 7-SW 6 96m m 0/300 V A C 0FF L1L2 L2L3 L3L1 3W

    E244-02Q -G -SF-SF-C7-SW 3 96m m 0/500 V AC L1L3 L1L2 L2L3 L3N L2N L1N 4W

    E244-02Q -G -SF-SF-C7-SW 3 96m m 0/600V AC L1L3 L1L2 L2L3 L3N L2N L1N 4W

    **Insert applicable VT prim ary and secondary value, e.g. 15kV /110V .

    Description

    N on reflecting glass w indow

    Polycarbonate shatterproof w indow

    R ed supplem entary pointer, externally adjustable

    R ed index m ark (triangle)

    Please state any required options at tim e of ordering.

    Code Case Full scale Switch notation

    size deflection

    E243-02E-G -LS**-C 7-A M P3 72m m 0/5 A A C O FF L1 L2 L3

    E244-02E-G -LS**-C 7-A M P3 96m m 0/5 A A C O FF L1 L2 L3

    E243-022E-G -LS**-C 7-A M P3 72m m 0/5/10A AC O FF L1 L2 L3

    E244-022E-G -LS**-C 7-A M P3 96m m 0/5/10A AC O FF L1 L2 L3

    E243-02E-G -LA **-C 7-A M P3 72m m 0/1 A A C O FF L1 L2 L3

    E244-02E-G -LA **-C 7-A M P3 96m m 0/1 A A C O FF L1 L2 L3

    E243-022E-G -LA **-C 7-A M P3 72m m 0/1/2A A C O FF L1 L2 L3

    E244-022E-G -LA **-C 7-A M P3 96m m 0/1/2A A C O FF L1 L2 L3

    **Insert applicable C T prim ary value.

  • 8/11/2019 Analogue Instruments REV 04-10

    16/86

  • 8/11/2019 Analogue Instruments REV 04-10

    17/8615

    D isplay: 99999.99

    Voltage: 100-125V A C

    200-250V A C

    380-440V A C

    Frequency: 50 or 60H z

    B urden: 2.5VA for D C input m odels

    Voltage: 10/27V (12, 24V) D C

    38/58V (48V) D C

    90/132V (110V) D C

    Connections

    Elapsed Time/Hours Run Meters AC

    Elapsed Time/Hours Run Meters DC

    DIN Panel Meters

    ETM and Impulse Counters

    Elapsed Time or Hours Run Meters

    Elapsed tim e m eters (ETM ) or hours-run m eters m onitor "O N /R U N " tim e

    of plant and equipm ent, allow ing the user to effectively control

    production efficiency, cost estim ation and service period m onitoring for

    preventative m aintenance. Tim e is m easured in increm ents of 0.01h upto 99999.99 hours after w hich the m eter autom atically resets to zero.

    M eters are non resettable before this tim e to prevent accidental resetting.

    A ccuracy: Pulse for pulse

    D isplay: 6 digit 999999

    R atings: 110, 120, 220, 230, 240, or 415V AC 10%

    50/60H z

    12V or 24V D C 10%

    B urden: 0.75VA (110V A C )2.70VA (415V A C )

    80m W (12V DC)

    Pulse w idth: 50m s m inim um

    M ark/space ratio: 1:1

    Impulse Counters

    Im pulse counters can be used to m easure any param eter w here there isan applicable pulse that is directly proportional to the m easured param eter.

    For exam ple, the num ber of m otor starts can be recorded by using a

    com bination of Paladin transducers, kW h, am pere hour, VA hour. The

    counter registers one digit every tim e an on/off voltage pulse is applied to

    the input term inals, and is non resettable to prevent accidental resetting.

    B ezel size m m 48 72 96

    Scale length 99999.99h 99999.99h 99999.99h

    Product codes

    50H z 242-158 243-155 244-155

    60H z 242-159 243-156 244-156

    D C input 242-157 243-151 244-151

    Product Codes

    Specifications

    B ezel size m m 48 72 96

    Scale length 999999 999999 999999

    Product codes

    DC input

    12V 242-259G -M U 243-259G -M U 244-259G -M U

    24V 242-259G -B D 243-259G -B D 244-259G -B D

    AC input

    110V 242-259G -PM 243-259G -PM 244-259G -PM120V 242-259G -PQ 243-259G -PQ 244-259G -PQ

    220V 242-259G -R 4 243-259G -R 4 244-259G -R 4

    230V 242-259G -RQ 243-259G -R Q 244-259G -R Q

    240V 242-259G -R R 243-259G -R R 244-259G -R R

    380V 242-259G -R U 243-259G -R U 244-259G -R U

    415V 242-259G -SB 243-259G -SB 244-259G -SB

    Product Codes

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    18/8616

    DIN Panel Meters Quadra

    Quadra 3-in-1 and 4-in-1

    The Q uadra range of 96m m2D IN style 3-in-1 and 4-in-1 m eters offer

    reduced stock holding and savings on space, installation and

    com m issioning. Ideally suited for generator set applications, the range

    offers m easurem ent of A C and D C , current and voltage, frequency or

    elapsed tim e. O ptions include custom er logo on dial, coloured dial, panelm ounting gasket and heavily dam pened m ovem ents.

    Product Codes

    Specifications

    Product Codes

    V oltm eter: 110, 120, 200, 230, 240, 380, 400, 415, 440, 480V A C

    nom inal. M axim um end scale 600 volts

    Frequency m eter inputs: 45/55H z, 55/65H z, 45/65H z, 360/440H z

    Voltage inputs: Sam e as voltm eter inputs above

    A m m eter inputs: 10m A A C 1 or 5A input (internal C T)

    H o urs run: 110, 120, 220, 230, 240, 380, 400, 415, 440 volts

    50 or 60H z

    H our run counting range: 99999.99 hours

    D C current: 250A - 1A D C including 1, 5, 10, 20 and 4-20m AD C for transducer inputs

    D C volts: 50m V to 600V D C including 50, 60, 75 and 150m V

    for shunt inputs

    B urden: C urrent: 0.75VA per phase

    H ours run: 2.5V A

    LC D hours run: 0.5V A

    Voltage: 0.5VA

    Frequency: 4V A

    Code Description

    244-80C A C V + D CI + A C A + D C A

    244-80D 3 x D C I + D C ETM (LC D )

    244-80G 3 x A C A

    244-80H 3 x A C V + FR Q

    244-80I 3 x A C A + ETM

    244-80J 3 x A C A + ETM (LC D )

    244-80K FR Q + A C V + D C I

    244-80N A C A + A C V + FR Q + ETM

    244-80P 3 x A C V

    244-80Q A C V // FRQ // ETM + A C A

    244-80R A C V // ETM + 2 x A C V

    244-80S 2 x A C V + 2 x A C A

    244-80T FR Q // ETM + A C V

    244-80U 3 x A C A + A C V244-80W ETM // FR Q + D C I + A C V

    244-80X 4 x D C I

    244-80Y ETM // FR Q + D C I

    244-80Z A C V + A C A + FR Q // ETM

    244-802 2 x A C V + A C A + ETM

    244-803 A C V + FR Q + 2 x A C A

    244-804 3 x A C A + D C I

    244-806 3 x A C V + A C A

    244-807 V, H z, ETM + SW ITC H

    A C V = R ectified A C voltm eter

    A C A = R ectified A C am m eter

    D C A = D C am m eter

    D C I = D C indicator

    ETM = Elapsed tim e m eter

    ETM (LC D ) = LC D elapsed tim e m eter

    FR Q = Frequency m eter

    // = In parallel w ith

    W hen ordering please specify the inputs for each param eter and the scaling required.

  • 8/11/2019 Analogue Instruments REV 04-10

    19/86

  • 8/11/2019 Analogue Instruments REV 04-10

    20/8618

    Connections

    DC Ammeter

    DC Voltmeter

    Connections

    Dual DC Ammeter

    Dual DC Voltmeter

    DIN Panel Meters

    Moving Coil DC Ammeters and Voltmeters

    M oving coil m eters are suitable for all D C system s. The linear scale is

    calibrated dow n to zero and accuracy m aintained dow n to 10% .

    H igh currents are m easured w ith separate shunts and suitably scaled

    indicators. Suppressed, centre and offset-zero m odels are available.

    Moving Coil Dual DC Ammeters and Voltmeters

    D ual instrum ents can be used to m easure a w ide range of currents and

    voltages, and save both space and tim e by requiring only one panel

    cut-out. The 244-80M allow s for independent m easurem ent of tw o D C

    currents in one case. The 244-80E allow s for independent m easurem ent

    of tw o D C voltages in one case.

    A ccuracy: C lass 1.5

    R atings: A m m eters: 100A -25A , (200A for 05 m odel)

    4/20m A suppressed zero

    40A for m odel 243/244-01A

    Voltm eters: 50m V-600V

    1/5V suppressed zero

    50, 60, 75, 100, 150m V for use w ith shunts

    Im pedance: A m m eters: 75m V internal shunt above 60m A

    Voltm eters: 1000/V above 1V

    A ccuracy: C lass 1.5

    R atings: D C C urrent: 100A -25A direct connected

    4/20m A suppressed zero.

    D C volts: 50m V-600V

    1/5 volt suppressed zero50, 60, 75, 150m V for use w ith shunts.

    B ezel size m m 96

    Scale length m m 94

    Product codes

    A m m eters 244-80M

    Voltm eters 244-80E

    B ezel size m m 48 72 96 144

    Scale length m m 72 112 150 230

    Product codes

    A m m eter 242-05A 243-05A 244-05A 246-05A

    A m m eters suppressed zero 242-05R 243-05R 244-05R 246-05R

    Voltm eters 242-05V 243-05V 244-05V 246-05V

    Voltm eters suppressed zero 242-05S 243-05S 244-05S 246-05S

    Product Codes Long-Scale

    Specifications

    Product Codes Long-Scale

    Specifications

    Further details available on request.

  • 8/11/2019 Analogue Instruments REV 04-10

    21/8619

    DIN Panel Meters

    Temperature and Process Indicators

    Temperature Indicators

    Long-scale indicators are used to read tem perature values, usually

    rem otely w ith R TD or therm ocouple sensors supplied by the custom er.

    R TD (R esistance Tem perature D etector) indicators m easure the change

    in the sensor resistance. A 2- or 3-w ire system m ay be used.

    Therm ocouple indicators accept standard m illivolt input signals. C old

    junction com pensation is provided and therm ocouple break indication is

    incorporated into the instrum ent.

    Process Indicators

    Instrum ents used to check process functions both locally or rem otely at

    centralised controls. These m oving coil instrum ents offer a w ide variety

    of electrical and m echanical readouts operated by transducer,

    tachogenerator, therm ocouple, resistance bulb or other D C analogue

    signals. Suppressed, centre and offset zero m odels are available on request.

    B ezel size m m 96 144

    Scale length m m 150 230

    Product codes

    R TD 244-45R 246-45R

    Therm ocouple 244-45T 246-45T

    Product Codes

    Specifications

    Connections

    Thermocouple Indicators -45TG

    RTD Indicators -45RG

    Connections

    Accuracy: Class 1.5 - indicator only. RTD indicator suitable for

    10 copper 100 platinum , 100 and 120 nickel

    sensors. Pow er in R TD is around 100W .

    Therm ocouple indicator suitable for J (0-700C),

    K (0-1200C). 50 m axim um circuit resistance.

    Auxiliary supply: M odel 45R: from 63.5-480V AC at 50/60H z.

    M odel 45T: 110, 115, 220, 240, 380, 400, 480V A C

    and 12, 24, 48, 110, 125V D C .

    B urden: -45R 2VA , -45T 3VA

    Accuracy: C lass 1.5Ratings: 1, 2, 5, 10 and 20m A. 4/20m A suppressed zero

    Burden: See technical data sheet T118

    B ezel size m m 48 72 96 144

    Scale length m m 72 112 150 230

    Product codes

    A C current 242-05A 243-05A 244-05A 246-05A

    A C voltage 242-05V 243-05V 244-05V 246-05V

    Speed 242-052 243-052 244-052 246-052

    Frequency 242-053 243-053 244-053 246-053

    Phase angle 242-054 243-054 244-054 246-054W atts 242-055 243-055 244-055 246-055

    VA r 242-056 243-056 244-056 246-056

    VA 242-057 243-057 244-057 246-057

    Product Codes Long-Scale Models

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    22/8620

    Connections

    Tap position indicator with self-contained power source

    Connections

    Phase Sequence Indicators

    DIN Panel Meters

    Tap Position and Phase Sequence

    Moving Coil Tap Position Indicators

    Long-scale position indicators are used to m onitor transform er tap, hoist

    or valve positions. They em ploy a 3-w ire system and 11 to 18 positions

    can be provided using 400 steps. The m easuring system is m ade upofa m oving coil indicator, stabilised pow er supply and transducer.

    Indicators can accept user-supplied rem ote potentiom eter or resistance

    therm om eter sensors.

    Phase Sequence Indicators

    Electronic phase sequence indicators ensure correct phase rotation andthe presence of all 3-phase supplies. Incorrect or loss of phase can cause

    serious dam age in a w ide range of electrical m achines. Ship-to-shore

    supplies, m obile generators and rem ote installations are particularly

    vulnerable to this problem .

    B ezel size m m 96 144

    Scale length m m 150 230

    Product codes

    Position indicator 244-45P 246-45P

    Product Codes

    Specifications

    A ccuracy: C lass 1.5

    Auxiliary supply: AC 50, 110, 220, 240V, 50/60Hz

    D C 50, 110, 125, 220V, 15%

    B urden: 2VA

    B ezel size m m 72 96

    Product codes

    Phase sequence indicator 243-12P 244-12P

    Product Codes

    Specifications

    Voltage: 151/300V, 301/500V

    100/150V (M odel 244-12P only)

    Frequency: 50/60H z

    B urden: 2.5VA /phase

  • 8/11/2019 Analogue Instruments REV 04-10

    23/8621

    DIN Panel Meters Phase Angle Meters

    Electronic Phase Angle Meters

    Phase angle m eters indicate the phase displacem ent betw een current

    and voltage. They are used in applications w here the phase angle m ust

    be m onitored, for exam ple w ith tariffs having VA r penalties, or to

    optim ise generator pow er delivery.

    The m easuring system includes a m oving coil indicator and a phase angle

    transducer. The 244 and 246 m odels are self contained.

    A ccuracy: C lass 2.5 (2 electrical)

    R atings: C urrent: 1A or 5A for C Ts.

    Voltage: 100/130V, 200-250V and 380-450V,

    100-110 for VT use.

    Frequency: 50H z, 60H z, 400H z.B urden at 50H z: C urrent: 1VA

    Voltage: 4V A per phase

    C urrent range: 20-125%

    B ezel size m m 72 96 144

    Scale length m m 65 94 145

    Product codes

    Single phase E243-014-G -FA + 244-42B 246-425

    256-TPS

    3-phase 3/4 w ire E243-014-G -FA + 244-42A 246-42A

    balanced load 256-TPT

    Product Codes Short-Scale Models

    Specifications

    B ezel size m m 72 96 144

    Scale length m m 112 150 230

    Product codes

    Single phase 243-054G -FA + 244-425 246-425

    256-TPS

    3-phase 3/4 w ire 244-427 246-427

    balanced load

    Product Codes Long-Scale Models

    Connections

    Single Phase Systems

    3-Phase, 3-4-Wire Balanced Systems

  • 8/11/2019 Analogue Instruments REV 04-10

    24/8622

    DIN Panel Meters

    360 Power Factor Indicator

    360 Dynamometer Power Factor Indicators

    Pow er factor indicators are suitable for generators or supplies operating

    in parallel. The four quadrant 360 scale calibrated cos 0-1-0-1-0

    indicates forw ard (export) and reverse (im port) pow er flow for inductiveand capacitive loads.

    A ccuracy: C lass 2.5 (2 electrical)

    R atings: C urrent: -/1A or -/5A for C Ts

    Voltage: 60-600V , 100/110 for VT use.

    Frequency: 50H z or 60H z

    B urden: C urrent: 2VA per coil @ 50H z

    Voltage: 4V A per coil @ 50H z (7.5V A > 250V)

    B ezel size m m 96 144

    Scale length 360 360

    Product codes

    Single phase 244-137 246-137

    3-phase 3- or 4-w ire 3-currents + 1 voltage 244-131 246-131

    3-phase 3- or 4-w ire 1-current + 3 voltages 244-132 246-132

    3-phase 3- or 4-w ire, unbalanced load 244-136 246-136

    Product Codes

    Specifications

    ConnectionsSingle Phase

    3-phase 3- or 4-wire 1-current 3-voltages, balanced load

    3-phase 3- or 4-wire, unbalanced load

    3-phase 3- or 4-wire 3-voltage, balanced load

    3-phase 3-wire using two CTs, unbalanced load

  • 8/11/2019 Analogue Instruments REV 04-10

    25/8623

    DIN Panel Meters Synchscope

    360 Dynamometer Synchroscope

    W here m anual parallelling of tw o A C system s is necessary, the

    frequency of both system s can be m onitored by a synchroscope.

    The system s are synchronised w hen the pointer is stationary in the

    12 o'clock position. The instrum ent uses silicon oil dam ping and is rated

    for continuous operation and connection.

    A ccuracy: C lass 2.5 (2 electrical)

    Ratings voltage: 100-125V, 200-250V, 380-450V*

    * U se transform er box 855-954 100-110V for VT use

    Frequency: 50H z, 60H z, 50/60H z, 400H z

    B urden at 50H z: 5VA m axim um .

    B ezel size m m 96 144

    Scale length 360 360

    Product codes

    50H z 244-145 246-145

    60H z 244-146 246-146

    50/60H z 244-147 246-147

    400H z 244-144 246-144

    Product Codes

    Specifications

    Connections

  • 8/11/2019 Analogue Instruments REV 04-10

    26/8624

    Connections360 LED Synchroscope

    360 LED Synchroscope and Synchro

    Check Relay

    DIN Panel Meters LED Synchroscope

    360 LED Synchroscope and Synchro Check Relay

    W here m anual parallelling of tw o A C system s is desired, the frequency

    of both system s can be m onitored by an LED synchroscope.The system s

    are synchronised w hen the green LED is lit in the 12 oclock position.

    The instrum ent is rated for continuous operation and connection. For the

    sem i-autom atic parallelling of tw o A C system s, the voltage, phase

    displacem ent and the frequency of both system s can be m onitored by

    this LED synchroscope and synchro check relay. C ontrols for voltage,

    phase angle, and tim e delay are provided. The system s are synchronised

    w hen the green triangular LE D s are lit together w ith the G EN /B U S green

    LED s. A dead bus option is also available.

    R atings voltage: 63.5, 110, 120, 220, 230, 240, 380, 400, 415, 440, 480V

    110/120V (115V nom inal)

    220/240V (230V nom inal)

    380/480V (430V nom inal)Volts A C or via VT

    Frequency: 40/65H z

    B urden at 50H z: 4VA m axim um

    Suitable for single or three phase system s

    S afety: IE C1010-1 (300V A C RM S installation degree 2)

    D ielectric: 4kV rm s for 1 m inute

    Isolation: B U S/G EN /R ELA Y

    Vibration: To Lloyds shipping specification

    *Phase difference: +0-20, +/-1

    *Voltage difference: +0-20% , +/-2%

    0-10% for m odels G and H

    *Tim e delay: 0-2.5 seconds +10%

    *A ccuracy: S ynchronisation at T.D C is + 1

    *O nly for the 360 LED synchroscope and synchro check relay.

    B ezel size m m 96 96 96

    Scale length m m 360 LED 360 LED 360 LED

    3- or 4-w ire Synchroscope Synchroscope Synchroscope

    40-65H z and synchro check and synchro

    check relay

    relay (dead bus)

    Product codes

    110/120V 244-14G G -PO B X 244-14H G -PO B X

    220/240V 244-14G G -R 5B X 244-14H G -R 5B X

    380/480V 244-14G G -R U B X 244-14H G -R U B X

    63.5V 244-14A G -N XYY 244-14LG -N XB X 244-14D G -N XB X

    110V 244-14A G -PM Y Y 244-14LG -PM B X 244-14D G -PM B X

    220V 244-14A G -R 4YY 244-14LG -R 4B X 244-14D G -R 4B X

    230V 244-14A G -R Q YY 244-14LG -R Q B X 244-14D G -R Q B X

    240V 244-14A G -R R YY 244-14LG -R RB X 244-14D G -R R B X

    380V 244-14A G -R U YY 244-14LG -R U B X 244-14D G -R U B X

    400V 244-14A G -SC YY 244-14LG -SC B X 244-14D G -SC B X

    415V 244-14A G -SB YY 244-14LG -SB B X 244-14D G -SB B X

    440V 244-14A G -SH YY 244-14LG -SH B X 244-14D G -SH B X

    480V 244-14A G -SEYY 244-14LG -SEB X 244-14D G -SEB X

    For the 244-14L and 244-14D m odels, the generator voltage is com pared to thenom inal input (bus) voltage specified at tim e of ordering. For the 244-14G and

    244-14H m odels, the generator voltage is com pared to the m easured bus voltage.

    Product Codes

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    27/8625

    DIN Panel Meters Power

    Wattmeters and VArmeters

    The 244/246 m odels are self contained and able to m easure active and

    reactive pow er in both balanced and unbalanced, single and 3-phase

    3-or 4-w ire system s. W attm eters are ideal for clear precise analogue

    indication of pow er in applications such as pow er generation, industrial

    control panels and pow er distribution.

    B ezel size m m 72 96 144

    Scale length m m 65 95 145

    Wattmeters product code

    Single phase E243-015-G -FA + 256-TW K 244-210 246-210

    3-phase 3-w ire balanced load E243-015-G -FA+256-TW L 244-211 246-211

    3-phase 4-w ire balanced load E243-015-G-FA+256-TW H 244-21C 246-21C3-phase 3-w ire unbalanced load E243-015-G -FA+256-TW M 244-213 246-213

    3-phase 4-w ire unbal. star CT E243-015-G -FA+256-TW N 244-214 246-214

    3-phase 4-w ire unbal. delta CT E243-015-G -FA+256-TW J 244-21E 246-21E

    3-phase 4-w ire 3-elem ent E 243-015-G -FA + 256-X W W 244-21Y 246-21Y

    VArmeters product codes

    3-phase 3- or 4-w ire balanced load E243-016-G-FA+256-TXG 244-310 246-310

    3-phase 3-w ire unbalanced load E243-016-G -FA+256-TXM 244-31S 246-31S

    3-phase 4-w ire unbal. star CT E243-016-G -FA+256-TXN 244-314 246-314

    3-phase 4-w ire unbal. delta CT E243-016-G -FA+256-TXJ 244-31E 246-31E

    Product Codes Short-Scale Models

    Specifications

    B ezel size m m 72 96 144Scale length m m 112 150 230

    Wattmeters product code

    Single phase 243-055G -FA +256-TW K 244-215 246-215

    3-phase 3-w ire balanced load 243-055G-FA+256-TW L 244-216 246-216

    3-phase 4-w ire balanced load 243-055G-FA+256-TW H 244-21D 246-21D

    3-phase 3-w ire unbalanced load 243-055G-FA+256-TW M 244-218 246-218

    3-phase 4-w ire unbal. star CT 243-055G-FA+256-TW N 244-219 246-219

    3-phase 4-w ire unbal. delta CT 243-055G-FA+256-TW J 244-21F 246-21F

    3-phase 4 -w ire 3 -elem ent 243-055G -FA + 256-X W W 244-21Z 246-21Z

    VArmeters product codes

    3-phase 3- or 4-w ire b alanced load 243-056G-FA+256-TXG 244-315 246-315

    3-phase 3-w ire unbalanced load 243-056G-FA+256-TXM 244-31L 246-31L

    3-phase 4-w ire unbal. star CT 243-056G-FA+256-TXN 244-319 246-3193-phase 4-w ire unbal. delta CT 243-056G-FA+256-TXJ 244-31F 246-31F

    M odels E243-015, E243-016, E243-055 and E 243-056 use a separate transducer.

    C rom pton transducers are ideal for this application. O ur product code reference

    assum es a 1m A output. O ther outputs of 5, 10, 20 or 4/20m A can also be used.

    Product Codes Long-Scale Models

    Accuracy: Short-scale: Class 2.5 Long-scale: Class 1.5

    M easuring ranges: V oltage: 94-106%

    C urrent: 0-120%

    Frequency influence: 0.4% H z

    R ating: C urrent: 0.2-5A , direct connected 1A -5A for CTs.

    Voltages: 57.7-480V

    O verload: 120% of nom inal continuous voltage up to 600V m axim um

    M axim um input: 600V

    Frequency: 50H z or 60H zPow er factor: Unity pow er factor assum ed range 0.5/1/0.5

    B urden: C urrent: 1VA per phase

    Voltage: 1V A per phase

    W arm -up tim e: < 15 m inutes

  • 8/11/2019 Analogue Instruments REV 04-10

    28/8626

    Wattmeter Connection Diagrams

    Single Phase

    224-210, 244-215, 246-210, 246-215

    3-phase 4-wire balanced load

    244-21C, 246-21C, 244-21D, 246-21D

    3-phase 3-wire balanced load

    244-211, 246-211, 244-216, 246-216

    3-phase 3-wire unbalanced load 2-element

    244-213, 246-213, 244-218, 246-218

    DIN Panel Meters Power

  • 8/11/2019 Analogue Instruments REV 04-10

    29/8627

    Wattmeter Connection Diagrams

    3-phase 4-wire unbalanced load star connected CTs 21/2-element

    244-214, 246-214, 244-219, 246-219

    3-phase 4-wire unbalanced load delta connected CTs

    244-21E, 246-21E, 244-21F, 246-21F

    3-phase 4-wire unbalanced load star connected CTs 3-element

    244-21Y, 246-21Y, 244-21Z, 246-21Z

  • 8/11/2019 Analogue Instruments REV 04-10

    30/86

  • 8/11/2019 Analogue Instruments REV 04-10

    31/8629

    Loading capacity: SO1 and SO2: 20A, 500V. SO3: 12A/480V

    Sw itching capacity: 3kW at 220V, 5kW at 380V, 5.5kW at 500V

    Isolating voltage: SO1 and SO 2: 500V AC. SO 3: 480V AC

    O perating tem perature: -20C to + 70C

    M ounting installation: Tw o point front fixing

    D im ensions: 48m m x 48m m

    Panel cut out: 3 drilled holes

    C om pliant w ith: LVD and EM C

    IP protection: SO 1 and SO 2: IP65. SO 3: IP54

    SO1 Three hole fixing 20A

    SO 1-SA B 4-position am m eter sw itch, L1-L2-L3-0

    SO 1-SA A 4-position am m eter sw itch, R -Y-B -O

    S O 1-S VE 7-position voltm eter sw itch, R Y-Y B-R B -0-R N -Y N -B N

    SO 1-SVD 7-position voltm eter sw itch, L1L2-L2L3-L3L1-0-L1N -L2N -L3N

    SO2 Single hole mount 20A

    SO 2-SA B 4-position am m eter sw itch, L1-L2-L3-0

    SO 2-SA A 4-position am m eter sw itch, R -Y-B -O

    S O 2-S VE 7-position voltm eter sw itch, R Y-Y B-R B -0-R N -Y N -B N

    SO 2-SVD 7-position voltm eter sw itch, L1L2-L2L3-L3L1-0-L1N -L2N -L3N

    SO3 Three hole fixing 12A

    SO 3-SA B 4-position am m eter sw itch, L1-L2-L3-0

    SO 3-SVD 7-position voltm eter sw itch, L1L2-L2L3-L3L1-0-L1N -L2N -L3N

    Connections

    Voltmeter Change-over Switches

    For m easuring 3-interconnected voltages

    and 3-phase voltage against N .

    SO1 and SO2

    SO3

    Ammeter-Change-over Switches

    SO1 and SO2

    SO3

    Product Codes

    Dimensions

    SO1 Three Hole Fixing 20 Amp

    Sw itch insert Front view Face plate Panel drilling

    SO2 Single Hole Fixing 20 Amp

    Sw itch insert Front view Face plate Panel drilling

    SO3 Three Hole Fixing 12 Amp

    Sw itch insert Face plate Panel drilling

    Instrument Selector Switches

    Panel m ounted selector sw itches offer a 7-position voltm eter sw itch and a

    4-position am m eter sw itch for reading line-to-line or line-to-neutral voltage

    and phase current. Each sw itch can be supplied w ith either num bered or

    coloured annotation.

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    32/8630

    070 S eries A NSI Sw itchbo ard Meters

    H igh quality range of sw itchboard instrum ents w ith C lass 1 accuracy and

    w hich com plies w ith A m erican A N SI-C 39.1 (1981) specifications. A vailable

    in 41/2" and 83/4" case sizes, their rugged design characteristics m eet the

    needs of the m ost dem anding environm ental applications. This extensive

    range of analogue and digital/analogue m eters utilises high shock oil

    dam pened m ovem ents and provides 1% accuracy for all R M S A C and D Cranges. The range offers various custom ised options and features.

    Description070 series offers tw o case sizes, 41/2" (M odels 075, 077 and 078) and 83/4" (M odel 079).

    M odel 078 is high shock herm etically sealed and all m odels have heavy gauge pressed

    steel cases. M ounting is by four integral studs.

    M odels 075 and 077 are a one piece flam e retardant polycarbonate m oulding w ith a

    black m atte finished bezel area, and a specially contoured w indow to m inim ise reflection

    from adjacent light sources. M odel 079 has a black pressed steel bezel w ith a

    toughened glass w indow , and M odel 078 has a die-cast bezel and a projecting m oulded

    toughened glass w indow , w hich incorporates a gas tight zero adjuster.

    Scales are 240 m oving iron and 250 m oving coil w ith parallax error-free platform dials.

    Standard dials are w hite m atte w ith black printed scales and bar knife-edge pointers.

    B lack dials w ith w hite or yellow scales and pointers are also available.

    G eneral options include supplem entary red pointer (075 and 077), slave pointer,

    calibration for non standard am bient tem peratures, special scales, trim potentiom eters,

    and Illum inated dials w ith w hite or red light sources.

    Perform ance: A N SI C 39.1 (1981)

    A ccuracy: C lass 1

    Term inals: 10-32 U N F term inals (M 5 screw clam p term inal for

    M odel 075)

    D ielectric voltage: W ithstand test 2.3kV for 1 m inute

    Response tim e: Approxim ately 2.5 seconds to full scale (077 and 078)

    and 3.5 seconds (079)

    O vershoot: 33% m axim um

    Standard calibration: 23C

    O perating tem perature: 0C to + 40C . M odel 078: -40C to + 70C .

    Storage tem perature: -10C to +50C

    Extrem e tem p range: -20C -to +65C

    Enclosure integrity: M odels 075/077/079 to IP54(N EM A 3S) splash proof,

    IP55 (N EM A 4) hoseproof is an optional extra

    M odel 078 to IP67 (N EM A 6 and 6P)

    Fixing on panel: 4 integral1/4 -28 U N F fixing studs

    A pprovals: EM C and LVD , U L and A B S

    Dimensions

    D im ension E varies w ith m easured param eter - see product code table overleaf.

    1 4 Fixing holes 8m m . 2 1/4-28 U N F fixing studs. 3 10-32 U N F Term inals (M 5

    screw clam p term inal on m odel 075).

    Model Panel cut-out Rear

    view

    Dia A B C D E F G

    075 103 86 43 110 17 - 30 101

    077 103 86 43 110 17 - 30 101

    078 103 86 43 110 17 - 30 101

    079 229 86 43 229 17 - 30 101

    Features

    R ugged H i-Q taut band suspension

    C lass 1 accuracy

    JIS dim ensioned product available

    on request

    Benefits

    M eets all the requirem ents of

    A N SI-C 39.1 (1981)

    Parallax error-free platform dials

    B um p, shock and vibration proof

    C ustom ised options and features

    Applications

    Sw itchgear

    D istribution system s

    G enerator sets

    C ontrol panels

    Energy m anagem ent

    B uilding m anagem ent

    U tility pow er m onitoring

    Process control

    M otor control

    Approvals

    U L approved file no. E203000

    A B S (A m erican B ureau of Shipping)

    93-LD 17806-X

    Specifications

  • 8/11/2019 Analogue Instruments REV 04-10

    33/8631

    Product Codes

    Case codes

    Type of instrument Ranges 075 077 078 079 Product codes

    A C am m eter m oving iron 0.5-10A 56 56 - - 075/077-08A

    A C am m eter m oving iron 0.5-10A - - 86 86 078/079-08A

    A C am m eter m oving iron 10.1-30A - 86 86 86 077/078/079-08A

    Slave pointer am m eter 1 or 5A 86 077-08D

    6 x overload A C am m eter 5/30A - 30/180A - 86 86 86 077/078/079-086A C voltm eter m oving iron 30-800V - 86 86 86 077/078/079-08V

    A C rectified am m eter 1-30A 56 56 86 56 075/077/078/079-05B

    A C rectified voltm eter 30-800V 56 56 86 56 075/077/078/079-05W

    A C voltm eter expanded scale 110-130V - 86 86 86 077/078/079-05Y

    A C R M S am m eter 1-30A 56 56 86 56 075/077/078/079-05F

    A C R M S voltm eter 150-750V 56 56 86 56 075/077/078/079-05G

    Slave pointer voltm eter 50-300V 86 077-05X

    E lapsed tim e m eter (99999.99) 50 or 60H z / 100-440V * and D C - 56 56 - 077/078-155/156/077-151

    Frequency m eter 50, 60

    400H z/100-440V** 86 86 86 86 075/077/078/079-41L

    A C w attm eter or VA rm eter 0.2-10A /100-440V* - 132 132 132 077/078/079-21 or 31

    360 rotary pow er factor m eter 0.2-10A /100-600V - 132 132 132 077/078/079-13

    360 rotary synchroscope 100/125V, 200/250, 380/450*** - 132 132 132 077/078/079-14LED synchroscope only 63.5-480V**** - 86 - - 077-14A

    LED synchroscope and

    synchro check relay 63.5-480V**** - 86 - - 077-14

    A C m eter relay A C 6V-500V, - 86 - - 077-30

    100A -1A , 5A via C T (see M eter R elay section)

    Phase sequence indicator 100-150, 151-300, 301-500V - 56 - - 077-12P

    M axim um dem and Indicator 1 or 5A - 86 - - 077-16

    Tap position indicator 1-18 steps. 400 - 86 - - 077-45P

    Transducer operated indicator 1, 5, 10, 20, or 4/20m A 56 56 56 56 075/077/078/079-05

    D C am m eter m oving coil 200A - 30A 56 56 56 56 075/077/078/079-05A

    D C voltm eter m oving coil 50m V-600V 56 56 56 56 075/077/078/079-05V

    D C m eter relay 100m V-500V, 10A -15A - 86 - - 077-30

    (see M eter Relay section)Tem perature indicator R TD - 86 86 86 077/078/079-45R

    Tem perature indicator Therm ocouple - 86 86 86 077/078/079-45T

    240 phase angle 1 or 5A , 100-400V

    /pow er factor 50, 60 or 400H z - 132 132 132 077/078/079-42

    Watt/hour indicators:

    W att/hour indicator 1 or 5A / 69-277V**** - 132 - - 077-KH

    Transducer operated 1, 5, 10, 20, or 4/20m A - 132 132 - 077-KH

    Analogue/LED digital indicators

    A C am m eter 1m A - 10A - 86 - - 077-D IB

    A C voltm eter 200m V - 600V - 86 - - 077-D IW

    A C w attm eter 69V/5A , 120V/5A , 50 or 60H z - 86 - - 077-D W

    A C VA rm eter 120V/5A , 208V/5A, 50 or 60H z - 86 - - 077-D X

    Phase angle m eter 69V/5A , 120V/5A, 50 or 60H z - 86 - - 077-D P

    Frequency m eter 110/130V, 50 or 60H z - 86 - - 077-D Z

    D C am m eter 1m A - 1A - 86 - - 077-D IA

    D C voltm eter 20m V - 600V - 86 - - 077-D IV

    Transducer indicator D C m A - 86 - - 077-D IT

    Tachom eter A C or D C rated - 86 - - 077-D I2

    * 100-440V = (100/125, 200/250, 380/440)

    ** 100-440V = (100/125, 200/250, 380/440). Frequencies 45/55, 55/65, 45/65, 47/53, 57/63, 360/440.

    *** U sing transform er box 855-954

    **** N om inal voltage to be specified

    For specification and connection diagram s, please refer to equivalent m odels in 240 Series D IN Panel M eter section.

    R eplace 244 w ith 077 etc., e.g. 244-210 becom es 077-210.

  • 8/11/2019 Analogue Instruments REV 04-10

    34/8632

    AC and DC Ammeters, Voltmetersand Frequency Meters

    This range of self contained, H i-Q , taut band m oving coil m eters feature

    250 linear scale and oil dam pened m echanism s for superior perform ance

    in high vibration situations. A C instrum ents are available w ith true R M S

    converting circuit or R M S com pensated rectifier. W hile types of

    frequency m eters can be dam aged by transient supply voltage spike.

    C rom pton 077-41 frequency m eters can w ithstand, w ithout dam age,10 successive transient spikes of 1250 volts. The range offers U L and

    C SA approvals. JIS dim ensioned products are available on request.

    A ccuracy: 1% full scale at 23C (73F)

    Scale arc: 250 full scale deflection

    Scale length: 077 and 078: 175.2 m m (6.9")

    079: 353 m m (13.9")

    Scale plate: 2 piece, platform type

    Response tim e: 077 and 078: Approxim ately 2.5 seconds to full scal079: Approxim ately 3.5 seconds to full scale

    O perating tem perature: 0 to 40C (32 to 104F)

    Storage tem perature: -10 to +50C (14 to 122F)

    Extrem e tem p range: -20 to +65C (-4 to 149F)

    Term inals: S tandard 10-32 U N F stud. M 5 screw clam p is optional.

    Position: Vertical (scale)

    D ielectric w ithstand: 2300V A C for 1 m inute betw een electrical circuit

    and case

    O vershoot: 33% m axim um

    Enclosure code: 077 and 079: IP54, optional IP55

    078: IP67

    A pprovals: EM C and LVD . U L approved file no. E203000

    O verload rating: AC am m eters - 2 x continuous, 50 x for 1 second

    A C voltm eters and frequency m eters - 1.2 x continuous

    D C am m eters - 2 x continuous 10 x for 1 second

    D C voltm eters - 1.2 x continuous

    Frequency range: A C calibration 60H z 20%

    Specifications Ammeters and Voltmeters

    R esponse tim e: 3 seconds m axim um

    External tem perature 0.6 tim es accuracy m axim um w ith 10C

    influence: from reference tem perature

    External field influence: 2.0 tim es accuracy m axim um w ith 0.5m T field

    A cceptable input U p to 30% distortion

    harm onic content:

    Specifications Frequency Meters

    Maximum frequency Center scale Error in

    Hz Hz Hz

    45-55 50 0.15

    46-54 50 0.15

    45-65 55 0.25

    50-70 60 0.25

    55-65 60 0.15

    56-64 60 0.15

    58-62 60 0.08

    350-450 400 1.30

    360-440 400 1.25

    380-420 400 0.80

    Specifications General

    M anufactured in accordance w ith A m erican N ational Standards A N SI C39.1, (1981)

  • 8/11/2019 Analogue Instruments REV 04-10

    35/8633

    Product Codes Transformer Rated 40/70Hz - Burden 0.3VA***

    Product Code AC Overload Ammeters - True RMS Reading***Self Contained 40/70Hz (Accuracy 1%)

    Product Codes Self Contained 40/70Hz (Accuracy 1%, 60Hz)***

    Moving Iron AC Ammeters

    412" square flange 834" square flange

    Rating Scaling*Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    1A0-1A /+077-08AA -LALA -C6 078-08AJ-LALA -C6 079-08AA -LALA -C6

    1.5A 0-1.5A /+077-08AA -LCLC -C 6 078-08AJ-LCLC -C6 079-08AA -LC LC-C62A0-2A /+077-08AA -LELE-C6 078-08AJ-LELE-C6 079-08AA -LELE-C6

    3A0-3A /+077-08AA -LJLJ-C6 078-08AJ-LJLJ-C6 079-08AA -LJLJ-C6

    5A0-5A /+077-08AA -LSLS-C6 078-08AJ-LSLS-C6 079-08AA -LSLS-C6

    7.5A 0-7.5A /+077-08A A -M FM F-C 6 078-08A J-M FM F-C 6 079-08A A -M FM F-C 6

    10A 0-10A /+077-08A A -M TM T-C 6 078-08A J-M TM T-C 6 079-08A A -M TM T-C 6

    15A 0-15A /+077-08A A -N D N D -C 6 078-08A J-N D N D -C 6 079-08A A -N D N D -C6

    20A 0-20A /+077-08A A -N G N G -C 6 078-08A J-N G N G -C 6 079-08A A -N G N G -C6

    30A 0-30A /+077-08AA -N LN L-C 6 078-08AJ-N LN L-C 6 079-08AA -N LN L-C 6

    5A 0-10A /+077-08AA -LSM T-C 6 078-08AJ-LSM T-C 6 079-08AA -LSM T-C 6

    5A 0-15A /+077-08AA -LSN D -C 6 078-08AJ-LSN D -C 6 079-08AA -LSN D -C 65A 0-20A /+077-08AA -LSN G -C 6 078-08AJ-LSN G -C 6 079-08AA -LSN G -C 6

    5A 0-25A /+077-08AA -LSN J-C6 078-08AJ-LSN J-C6 079-08AA -LSN J-C 6

    5A 0-30A /+077-08AA -LSN L-C6 078-08AJ-LSN L-C6 079-08AA -LSN L-C6

    5A 0-40A /+077-08AA -LSN P-C 6 078-08AJ-LSN P-C 6 079-08AA -LSN P-C6

    5A 0-50A /+077-08AA -LSN T-C6 078-08AJ-LSN T-C6 079-08AA -LSN T-C6

    5A 0-75A /+077-08AA -LSPB -C6 078-08AJ-LSPB -C6 079-08AA -LSPB -C6

    5A 0-100A /+077-08AA -LSPK -C6 078-08AJ-LSPK -C6 079-08AA -LSPK -C 6

    5A 0-150A /+077-08AA -LSPZ-C 6 078-08AJ-LSPZ-C 6 079-08AA -LSPZ-C 6

    5A 0-200A /+077-08AA -LSR L-C6 078-08AJ-LSR L-C6 079-08AA -LSR L-C 6

    5A 0-250A /+077-08AA -LSR S-C6 078-08AJ-LSR S-C6 079-08AA -LSR S-C6

    5A 0-300A /+077-08AA -LSR X-C6 078-08AJ-LSR X-C6 079-08AA -LSR X-C6

    5A 0-400A /+077-08AA -LSSC -C6 078-08AJ-LSSC -C6 079-08AA -LSSC -C6

    5A 0-500A /+077-08AA -LSSF-C 6 078-08AJ-LSSF-C 6 079-08AA -LSSF-C 6

    5A 0-600A /+077-08AA -LSSJ-C 6 078-08AJ-LSSJ-C 6 079-08AA -LSSJ-C 6

    5A 0-800A /+077-08AA -LSSN -C 6 078-08AJ-LSSN -C 6 079-08AA -LSSN -C6

    5A 0-1000A /+077-08AA -LSSS -C6 078-08AJ-LSSS -C6 079-08AA -LSSS -C 6

    5A 0-1200A /+077-08A A -LSS U -C 6 078-08A J-LSS U -C 6 079-08A A -LSS U -C6

    5A 0-1500A /+077-08AA -LSTC -C6 078-08AJ-LSTC -C6 079-08AA -LSTC -C 6

    5A 0-1600A /+077-08AA -LSTE-C 6 078-08AJ-LSTE-C 6 079-08AA -LSTE-C 6

    5A 0-2000A /+077-08A A -LSTM -C 6 078-08A J-LSTM -C 6 079-08A A -LSTM -C 6

    5A 0-2500A /+077-08A A -LSTU -C6 078-08A J-LSTU -C6 079-08A A -LSTU -C6

    5A 0-3000A /+077-08A A -LSU A-C 6 078-08A J-LSU A -C 6 079-08A A -LSU A -C 6

    5A 0-4000A /+077-08A A -LSU E-C 6 078-08A J-LSU E-C 6 079-08A A -LSU E-C6

    5A 0-5000A /+077-08A A -LSU J-C6 078-08A J-LSU J-C6 079-08A A -LSU J-C 6

    5A 0-6000A /+077-08A A -LSU P-C 6 078-08A J-LSU P-C 6 079-08A A -LSU P-C65A 0-7000A /+077-08A A -LSU S-C 6 078-08A J-LSU S-C 6 079-08A A -LSU S-C6

    5A 0-8000A /+077-08AA -LSUW -C6 078-08A J-LSU W -C 6 079-08A A -LSUW -C6

    5/30A To suit 077-086A-LS**-C6 078-086J-LS**-C6 079-086A-LS**-C6

    R ated 5A for standard CTs w ith 6 x full scale. * O ther scales are available

    O verload portion of the scale is not subject to ** Specify scale required

    the accuracy guarantee. *** For case types 077/078/079 use

    U L approved file no. E 203000 10-32 U N F term inals. For M 5 screw

    clam p term inals, use case type 075

    077 m oving iron am m eters available as listed above.

    AC Overload Ammeters

  • 8/11/2019 Analogue Instruments REV 04-10

    36/8634

    Product Codes Self Contained 60Hz 20% (Accuracy 1%)***

    Moving Iron AC Voltmeters

    412" square flange 834" square flange

    Rating Scaling*Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    150V 0-150V /+077-08VA -PZPZ-C 6 078-08VJ-PZPZ-C 6 079-08VA -PZPZ-C6

    250V 0-250V /+077-08VA -R SR S-C 6 078-08VJ-R SR S-C6 079-08VA -R SR S-C 6300V 0-300V /+077-08VA -R XR X-C 6 078-08VJ-R XR X-C6 079-08VA -R XR X-C 6

    500V 0-500V /+077-08VA -SFSF-C 6 078-08VJ-SFSF-C 6 079-08VA -SFSF-C6

    600V 0-600V /+077-08VA -SJSJ-C 6 078-08VJ-SJSJ-C6 079-08VA -SJSJ-C 6

    750V 0-750V 077-08VA -SM SM -C 6 078-08VJ-SM SM -C 6 079-08VA -S M S M -C 6

    Product Codes Transformer Rated 50/60HZ (Accuracy 1%)0.8VA @150V***

    150V 0-300V /+077-08VA -PZR X-C6 078-08VJ-PZR X-C 6 079-08VA -PZR X-C 6

    150V 0-600V /+077-08VA -PZSJ-C 6 078-08VJ-PZSJ-C 6 079-08VA -PZSJ-C6

    150V 0-750V /+077-08VA -PZS M -C 6 078-08VJ-PZS M -C 6 079-08VA -PZS M -C6

    150V 0-3000V /+077-08VA -PZU A -C 6 078-08VJ-PZU A -C6 079-08VA -PZU A -C 6

    150V 0-5250V /+077-08VA -PZU L-C6 078-08VJ-PZU L-C 6 079-08VA -PZU L-C 6

    150V 0-6000V /+077-08VA -PZU P-C6 078-08VJ-PZU P-C 6 079-08VA -PZU P-C 6

    150V 0-9000V /+077-08VA -PZU Y-C6 078-08VJ-PZU Y-C 6 079-08VA -PZU Y-C 6

    150V 0-15KV /+077-08VA -PZW C -C6 078-08VJ-PZW C -C 6 079-08VA -PZW C -C 6

    150V 0-18KV /+077-08VA -PZW D -C6 078-08VJ-PZW D -C 6 079-08VA -PZW D -C 6

    150V 0-45KV /+077-08VA -PZW J-C 6 078-08VJ-PZW J-C 6 079-08VA -PZW J-C6

    250V 0-600V /+077-08VA -R SSJ-C 6 078-08VJ-R SSJ-C 6 079-08VA -R SSJ-C 6

    U L approved file no. E203000 * O ther scales are available

    *** For case types 077/078/079 use

    10-32 U N F term inals. For M 5 screw

    clam p term inals, use case type 075

    AC Voltmeter

  • 8/11/2019 Analogue Instruments REV 04-10

    37/8635

    Product Codes Self Contained 40/70Hz (Accuracy 1%, 60Hz)***

    RMS Reading AC Ammeters

    412" square flange 834" square flange

    Rating Scaling*Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    1A 0-1A /+ 077-05FA -LA LA -C 6 078-05FJ-LA LA -C 6 079-05FA -LA LA -C 6

    1.5A 0-1.5A /+077-05FA-LCLC-C6 078-05FJ-LCLC-C6 079-05FA-LCLC-C62A 0-2A /+ 077-05FA -LE LE -C 6 078-05FJ-LE LE -C 6 079-05FA -LE LE -C 6

    3A 0-3A /+ 077-05FA -LJLJ-C 6 078-05FJ-LJLJ-C 6 079-05FA -LJLJ-C 6

    5A 0-5A /+ 077-05FA -LS LS -C 6 078-05FJ-LS LS -C 6 079-05FA -LS LS -C 6

    7.5A 0-7.5A /+077-05FA-M FM F-C6 078-05FJ-M FM F-C6 079-05FA-M FM F-C6

    10A 0-10A /+ 077-05FA -M TM T-C 6 078-05FJ-M TM T-C 6 079-05FA -M TM T-C 6

    15A 0-15A /+ 077-05FA -N D N D -C 6 078-05FJ-N D N D -C 6 079-05FA -N D N D -C 6

    20A 0-20A /+ 077-05FA -N G N G -C 6 078-05FJ-N G N G -C 6 079-05FA -N G N G -C 6

    30A 0-30A /+ 077-05FA -N L N L-C 6 078-05FJ-N L N L-C 6 079-05FA -N L N L-C 6

    Product Codes Transformer Rated 40/70Hz - Burden 0.3VA***150V 0-300V /+077-08VA-PZRX -C6 078-08VJ-PZRX -C6 079-08VA-PZR X-C6

    5A 0-10A /+077-05FA-LSM T-C6 078-05FJ-LSM T-C6 079-05FA-LSM T-C6

    5A 0-15A /+077-05FA-LSN D -C6 078-05FJ-LSN D -C6 079-05FA-LSN D -C6

    5A 0-20A /+077-05FA-LSN G -C6 078-05FJ-LSN G -C6 079-05FA-LSN G -C6

    5A 0-25A /+077-05FA-LSN J-C6 078-05FJ-LSN J-C6 079-05FA-LSN J-C6

    5A 0-30A /+077-05FA-LSN L-C6 078-05FJ-LSN L-C6 079-05FA-LSN L-C6

    5A 0-40A /+077-05FA-LSN P-C6 078-05FJ-LSN P-C6 079-05FA-LSN P-C6

    5A 0-50A /+077-05FA-LSN T-C6 078-05FJ-LSN T-C6 079-05FA-LSN T-C6

    5A 0-75A /+077-05FA-LSPB-C6 078-05FJ-LSPB-C6 079-05FA-LSPB-C6

    5A 0-100A /+077-05FA-LSPK-C6 078-05FJ-LSPK-C6 079-05FA-LSPK-C6

    5A 0-150A /+077-05FA-LSPZ-C6 078-05FJ-LSPZ-C6 079-05FA-LSPZ-C6

    5A 0-200A /+077-05FA-LSRL-C6 078-05FJ-LSRL-C6 079-05FA-LSR L-C6

    5A 0-250A /+077-05FA-LSRS -C6 078-05FJ-LSRS -C6 079-05FA-LSR S-C6

    5A 0-300A /+077-05FA-LSRX -C6 078-05FJ-LSRX -C6 079-05FA-LSR X-C6

    5A 0-400A /+077-05FA-LSSC -C6 078-05FJ-LSSC -C6 079-05FA-LSSC -C6

    5A 0-500A /+077-05FA-LSSF-C6 078-05FJ-LSSF-C6 079-05FA-LSSF-C6

    5A 0-600A /+077-05FA-LSSJ-C6 078-05FJ-LSSJ-C6 079-05FA-LSSJ-C6

    5A 0-800A /+077-05FA-LSSN -C6 078-05FJ-LSSN -C6 079-05FA-LSSN -C6

    5A 0-1000A /+077-05FA-LSSS-C6 078-05FJ-LSSS-C6 079-05FA-LSSS-C6

    5A 0-1200A /+077-05FA-LSSU -C 6 078-05FJ-LSSU -C 6 079-05FA-LSS U -C 6

    5A 0-1500A /+077-05FA-LSTC-C6 078-05FJ-LSTC-C6 079-05FA-LSTC-C6

    5A 0-1600A /+077-05FA-LSTE-C6 078-05FJ-LSTE-C6 079-05FA-LSTE-C6

    5A 0-2000A /+077-05FA-LSTM -C 6 078-05FJ-LSTM -C 6 079-05FA-LSTM -C 6

    5A 0-2500A /+077-05FA-LSTU -C 6 078-05FJ-LSTU -C 6 079-05FA-LSTU -C 6

    5A 0-3000A /+077-05FA-LSU A-C6 078-05FJ-LSU A-C6 079-05FA-LSU A-C6

    5A 0-4000A /+077-05FA-LSU E-C 6 078-05FJ-LSU E-C 6 079-05FA-LSU E-C 6

    5A 0-5000A /+077-05FA-LSU J-C 6 078-05FJ-LSU J-C 6 079-05FA-LSU J-C 6

    5A 0-6000A /+077-05FA-LSU P-C 6 078-05FJ-LSU P-C 6 079-05FA-LSU P-C 6

    5A 0-7000A /+077-05FA-LSU S-C 6 078-05FJ-LSU S-C 6 079-05FA-LSU S-C 6

    5A 0-8000A /+077-05FA-LSU W -C 6 078-05FJ-LSU W -C 6 079-05FA-LSU W -C 6

    R ated 5 A for standard C Ts w ith 6 x full scale. * O ther scales are available

    O verload portion of the scale is no t sub ject ** Specify scale required

    to the accuracy guarantee. *** For case types 077/078/079 use

    U L approved file no. E 203000 10-32 U N F term inals. For M 5 screw

    clam p term inals, use case type 075

    AC Ammeter

    For A C rectified non-R M S com pensated m eter, please replace the -05F in the product

    code w ith -05B .

    For A C rectified non-R M S com pensated m eter, please replace the -05F in the product

    code w ith -05B .

  • 8/11/2019 Analogue Instruments REV 04-10

    38/8636

    AC Voltmeter

    AC Voltmeter Expanded Scale

    Product Codes Self Contained 60Hz 20% (Accuracy 1%)***

    RMS Reading AC Voltmeters

    412" square flange 834" square flange

    Rating Scaling*Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    150V 0-150V /+ 077-05G A-PZP Z-C 6 078-05G J-PZP Z-C 6 079-05G A -PZP Z-C 6

    250V 0-250V /+ 077-05G A-R SR S-C 6 078-05G J-R SR S-C 6 079-05G A -R SR S-C6300V 0-300V /+ 077-05G A-R XR X-C 6 078-05G J-R XR X-C 6 079-05G A -R XR X-C6

    500V 0-500V /+ 077-05G A-SFS F-C 6 078-05G J-SFS F-C 6 079-05G A -SFS F-C 6

    600V 0-600V /+ 077-05G A-SJSJ-C 6 078-05G J-SJSJ-C6 079-05G A -SJSJ-C6

    750V 0-750V 077-05G A -SM SM -C6 078-05G J-SM SM -C 6 079-05G A -S M S M -C 6

    For A C rectified non-R M S com pensated m eter, please replace the -05G in the

    productcode w ith -05W .

    Product Codes Transformer Rated 50/60HZ (Accuracy 1%)0.8VA @150V***

    150V 0-300V /+077-05G A -PZR X-C6 078-05G J-PZR X-C 6 079-05G A -PZR X-C 6

    150V 0-600V /+077-05G A -PZS J-C 6 078-05G J-PZS J-C6 079-05G A -PZS J-C 6

    150V 0-750V /+077-05G A -PZS M -C 6 078-05G J-PZS M -C 6 079-05G A -PZS M -C 6

    150V 0-3000V /+077-05G A -PZU A -C 6 078-05G J-PZU A -C 6 079-05G A -PZU A -C6

    150V 0-5250V /+077-05G A -PZU L-C6 078-05G J-PZU L-C 6 079-05G A -PZU L-C 6

    150V 0-6000V /+077-05G A -PZU P-C6 078-05G J-PZU P-C 6 079-05G A -PZU P-C 6

    150V 0-9000V /+077-05G A -PZU Y-C6 078-05G J-PZU Y-C 6 079-05G A -PZU Y-C 6

    150V 0-15KV /+077-05G A -PZW C -C6 078-05G J-PZW C-C 6 079-05G A -PZW C -C 6

    150V 0-18K V /+077-05G A -PZW D -C6 078-05G J-PZW D -C 6 079-05G A -PZW D -C 6

    150V 0-45K V /+077-05G A -PZW J-C 6 078-05G J-PZW J-C6 079-05G A -PZW J-C 6

    250V 0-600V /+077-05G A -RSS J-C 6 078-05G J-R SS J-C 6 079-05G A -R SS J-C 6

    For A C rectified non-R M S com pensated m eter, please replace the -05G in the product

    code w ith -05W .

    077 m oving iron am m eters and voltm eters available as listed above.

    Product Codes Expanded Scale - Moving Coil Zener Diode***(Accuracy 0.3% of Mid-scale Value) Self Contained, 20-1000Hz

    110-130V 110-130V 077-05YA -PN PN -C 6 078-05YJ-PN PN -C 6 079-05YA -PN PN -C 6

    110-130V To suit PT 077-05YA -PN **-C 6 078-05YJ-PN **-C 6 079-05YA -PN **-C6

    Product Codes Instantaneous AC Voltmeter***with Instantaneous Maximum Reading Slave Pointer

    150V To suit PT 077-05XA -PZ**-C 6

    250V To suit PT 077-05XA -R S**-C 6

    300V To suit PT 077-05XA -R X**-C 6

    U L approved file no. E203000 * O ther scales are available

    ** Specify scale required

    *** For case types 077/078/079 use 10-32

    U N F term inals. For M 5 screw clam p

    term inals, use case type 075

  • 8/11/2019 Analogue Instruments REV 04-10

    39/8637

    DC Ammeter

    Product Codes Self Contained (Accuracy 1%)****

    DC Ammeters

    412" square flange 834" square flange

    Rating Scaling* Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    0-200A 0-200A /+077-05AA-EAEA 078-05AJ-EAEA 079-05AA-EAEA

    0-300A 0-300A /+077-05AA -EEEE 078-05AJ-EEEE 079-05AA -EEEE0-500A 0-500A /+077-05AA -EM EM 078-05AJ-EM EM 079-05AA -EM EM

    0-800A 0-800A /+077-05AA -EW EW 078-05AJ-EW EW 079-05AA -EW EW

    0-1m A 0-1m A /+077-05AA-FAFA 078-05AJ-FAFA 079-05AA-FAFA

    0-2m A 0-2m A /+077-05AA-FG FG 078-05AJ-FG FG 079-05AA-FG FG

    0-5m A 0-5m A /+077-05AA-FXFX 078-05AJ-FXFX 079-05AA-FXFX

    0-10m A 0-10m A /+077-05AA -H AH A 078-05AJ-H AH A 079-05AA -H AH A

    0-20m A 0-20m A /+077-05AA -H FH F 078-05AJ-H FH F 079-05AA -H FH F

    0-30m A 0-30m A /+ 077-05AA -H M H M 078-05AJ-H M H M 079-05AA -H M H M

    0-50m A 0-50m A /+077-05AA -H XH Y 078-05AJ-H XH Y 079-05AA -H XH Y

    0-100m A 0-100m A /+077-05AA -JRJR 078-05AJ-JRJR 079-05AA -JRJR

    0-200m A 0-200m A /+077-05AA -KA KA 078-05AJ-KA KA 079-05AA -KA KA

    0-300m A 0-300m A /+ 077-05AA -KG KG 078-05AJ-KG KG 079-05AA -KG KG

    0-500m A 0-500m A /+ 077-05AA -KM KM 078-05AJ-KM KM 079-05AA -KM KM

    0-800m A 0-800m A /+ 077-05AA -KW KW 078-05AJ-KW KW 079-05AA -KW KW

    0-1A 0-1A /+077-05AA-LALA 078-05AJ-LALA 079-05AA-LALA

    0-5A 0-5A /+077-05AA-LSLS 078-05AJ-LSLS 079-05AA-LSLS

    0-10A 0-10A /+077-05AA -M TM T 078-05AJ-M TM T 079-05AA -M TM T

    0-15A 0-15A /+077-05AA -N D N D 078-05AJ-N D N D 079-05AA -N D N D

    0-20A 0-20A /+077-05AA -N G N G 078-05AJ-N G N G 079-05AA -N G N G

    0-30A 0-30A /+077-05AA-N LN L 078-05AJ-N LN L 079-05AA-N LN L

    Intrinsically safe milliammeters

    (accuracy 1%)

    ISSEP certified

    Rating Standard case

    catalogue no.

    1m A D C 077-11AF-FA**

    5m A D C 077-11AF-FX**

    10m A D C 077-11AF-H A**

    20m A D C 077-11AF-H F**

    4/20m A D C 077-11RFH G **

    ** State scale m arking as required

    Product Codes Milliammeters - Suppressed Zero,No Zero Set Unless Specified****

    1/5m A To Suit /+077-05RA -G M ** 078-05RJ-G M ** 079-05RA -G M **

    4/20m A To Suit /+077-05RA -H G ** 078-05RJ-H G ** 079-05RA -H G **

    10/50m A To Suit /+077-05RA -H Z** 078-05RJ-H Z** 079-05RA -H Z**

    Product Codes Shunt Rated (Accuracy 1%)****

    50m V (4m A) To suit /+077-05AA-EY** 078-05AJ-EY** 079-05AA-EY**

    50 -0-50 m V shunt /+077-05CA-G B** 078-05CJ-G B** 079-05CA-G B**

    100m V (4m A) rating /+077-05AA-G B** 078-05AJ-G B** 079-05AA-G B**

    100 -0-100 m V /+ 077-05CA -G M ** 078-05CJ-G M ** 079-05CA -G M **

    Product Codes Zero Left For Use With 50mV Shunts and0.05 Ohm Shunt Leads*** and ****

    50m V 0-15A /+077-05AA-EYN D 078-05AJ-EYN D 079-05AA-EYN D

    50m V 0-20A /+077-05AA-EYN G 078-05AJ-EYN G 079-05AA-EYN G

    50m V 0-30A /+077-05AA-EYN L 078-05AJ-EYN L 079-05AA-EYN L

    50m V 0-40A /+077-05AA-EYN P 078-05AJ-EYN P 079-05AA-EYN P

    50m V 0-75A /+077-05AA-EYPB 078-05AJ-EYPB 079-05AA-EYPB

    50m V 0-100A /+077-05AA-EYPK 078-05AJ-EYPK 079-05AA-EYPK

    50m V 0-150A /+077-05AA-EYPZ 078-05AJ-EYPZ 079-05AA-EYPZ

    50m V 0-200A /+077-05AA-EYRL 078-05AJ-EYRL 079-05AA-EYRL

    50m V 0-300A /+077-05AA-EYRX 078-05AJ-EYRX 079-05AA-EYRX

    50m V 0-400A /+077-05AA-EYSC 078-05AJ-EYSC 079-05AA-EYSC

    50m V 0-500A /+077-05AA-EYSF 078-05AJ-EYSF 079-05AA-EYSF

    50m V 0-750A /+077-05AA-EYSM 078-05AJ-EYSM 079-05AA-EYSM

    50m V 0-1000A /+077-05AA-EYSS 078-05AJ-EYSS 079-05AA-EYSS

    50m V 0-1200A /+077-05AA-EYSU 078-05AJ-EYSU 079-05AA-EYSU50m V 0-1500A /+077-05AA-EYTC 078-05AJ-EYTC 079-05AA-EYTC

    50m V 0-2000A /+077-05AA-EYTM 078-05AJ-EYTM 079-05AA-EYTM

    50m V 0-3000A /+077-05AA-EYU A 078-05AJ-EYU A 079-05AA-EYU A

    U L approved file no. E203000

    Specify shunt lead resistance valueif in excess of 0.05 ohm s for

    calibration purposes.

    D C shunt rated am m eters have

    therm istor circuit am bient

    tem perature com pensation.

    Separate shunt and shunt leads are

    not included.

    * O ther scales are available

    ** Specify scale required.

    *** O ther m V ratings and scale

    options available upon

    request.

    **** For case types 077/078/079

    use 10-32 U N F term inals.For M 5 screw clam p

    term inals, use case type 075.

    To suit

    shunt

    rating

  • 8/11/2019 Analogue Instruments REV 04-10

    40/8638

    Product Codes Sensitivity 1000 Ohms / Volt (Accuracy 1%)***

    DC Voltmeters

    412" square flange 834" square flange

    Rating Scaling* Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    50m V-800V To suit /+077-05VA-** 078-05VJ-** 079-05VA-**

    0-15V 0-15V /+077-05VA-N D N D 078-05VJ-N D N D 079-05VA-N D N D0-30V 0-30V /+077-05VA-N LN L 078-05VJ-N LN L 079-05VA-N LN L

    0-50V 0-50V /+077-05VA-N TN T 078-05VJ-N TN T 079-05VA-N TN T

    0-75V 0-75V /+077-05VA-PBPB 078-05VJ-PBPB 079-05VA-PBPB

    0-150V 0-150V /+077-05VA-PZPZ 078-05VJ-PZPZ 079-05VA-PZPZ

    0-300V 0-300V /+077-05VA-RXRX 078-05VJ-RXRX 079-05VA-RXRX

    0-400V 0-400V /+077-05VA-SCSC 078-05VJ-SCSC 079-05VA-SCSC

    0-500V 0-500V /+077-05VA-SFSF 078-05VJ-SFSF 079-05VA-SFSF

    0-600V 0-600V /+077-05VA-SJSJ 078-05VJ-SJSJ 079-05VA-SJSJ

    0-750V 0-750V 077-05VA-SM SM 078-05VJ-SM SM 079-05VA-SM SM

    0-800V 0-800V 077-05VA-SN SN 078-05VJ-SN SN 079-05VA-SN SN

    Product Codes 120V Self Contained***

    Frequency Meters

    412" square flange 834" square flange

    Rating Scaling*Standard case Sealed case hi-shock Standard case

    catalogue no. catalogue no. catalogue no.

    50 H z+/-0.1545-55H z /+077-41LA -PN AG -A G 078-41LJ-PN AG -A G 079-41LA -PN A G -A G

    50 H z+/-0.1546-54H z /+077-41LA -PN AH -A H 078-41LJ-PN AH -A H 079-41LA -PN A H -A H

    50 H z+/-0.25 45-65H z /+077-41LA -PN AJ-A J 078-41LJ-PN A J-A J 079-41LA -PN A J-A J

    60 H z+/-0.25 50-70H z /+077-41LA -PN AL-A L 078-41LJ-PN AL-A L 079-41LA -PN A L-A L

    60 H z+/-0.1555-65H z /+077-41LA -PN AN -A N 078-41LJ-PN AN -A N 079-41LA -PN A N -A N

    60 H z+/-0.1556-64H z /+077-41LA -PN AO -A O 078-41LJ-PN AO -A O 079-41LA -PN A O -A O

    60 H z+/-0.0858-62H z /+077-41LA -PN AT-A G 078-41LJ-PN AG -A G 079-41LA -PN A G -A G

    40 0H z+ /-1.3 350-450 H z /+077-41LA-PN BH -B H 078-41LJ-PN BH -B H 079-41LA-PN B H -B H

    400H z+/-1.25 360-440H z /+07