TI390F/24/ae
Technical Information
Micropilot M FMR250
Level-Radar
Smart Transmitter for continuous and non-contact level
measurement in solids.
Cost-effective 4 to 20 mA 2-wire technology.
Application
The Micropilot M performs continuous, non-contact
level measurement especially in powdery to granular
bulk solids. Additionally it can be used in liquids as well.
Dust, filling noises, temperature layers and gas
stratification do not affect measurement.
Typical areas of application are:
• Level measurement in tall silos with extremely dusty
bulk solids e.g. cement, raw meal or animal feed.
• Applications with high temperature requirements up
to 200 °C (392 °F), e.g. clinker or fly ash.
• Applications with highly abrasive bulk solids e.g.
ferrite.
The FMR250 with DN80 or DN100 horn antenna for all
standard applications, particularly also for small nozzle
sizes.
The FMR250 with DN200 parabolic antenna offers high
beam focussing of 4° and is thus ideal for applications
with many installations.
Your benefits
• 2-wire technology, low price:
2-wire technology reduces wiring costs and allows
easy implementation into existing systems.
• Non-contact measurement:
Measurement is almost independent from product
properties.
• Easy on-site operation via menu-driven alphanumeric
display.
• Easy commissioning, documentation and diagnostics
via Endress+Hauser operating software.
• Integrated air purge connection for extremely dusty
conditions or media tending to create build-up.
• Max. measuring range 70 m (229 ft).
• Suitable for process temperatures up to 200 °C
(392 °F).
• HART® or PROFIBUS® PA respectively
FOUNDATION™ Fieldbus protocol.
• Optional remote display and operation.
Micropilot M FMR250
2 Endress+Hauser
Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Equipment architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measuring conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operating frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Transmitting power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Data of the FOUNDATION Fieldbus interface . . . . . . . . . . . . . . . . 9
Auxiliary energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Load HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Ripple HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Max. noise HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Overvoltage protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Performance characteristics. . . . . . . . . . . . . . . . . . . . 15
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Reaction time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Influence of ambiente temperature . . . . . . . . . . . . . . . . . . . . . . . 15
Operating conditions: Installation . . . . . . . . . . . . . . . 16
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Beam angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation in vessel FMR250 . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
FMR250 with top target positioner . . . . . . . . . . . . . . . . . . . . . . . 21
Integrated air purge connection . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operating conditions: Environment. . . . . . . . . . . . . . 22
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cleaning of the antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Electromagnetic compatibility (EMC). . . . . . . . . . . . . . . . . . . . . . 22
Operating conditions: Process . . . . . . . . . . . . . . . . . . 23
Process temperature range / Process pressure limits . . . . . . . . . . 23
Dielectric constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 24
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
E+H UNI flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Process connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operation concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 35
CE approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
External standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . 35
RF approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 36
Micropilot M FMR250 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Remote display FHX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Commubox FXA191 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Commubox FXA195 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Commubox FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ToF Adapter FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Micropilot M FMR250
Endress+Hauser 3
Function and system design
Measuring principle The Micropilot is a "downward-looking" measuring system, operating based on the time-of-flight method. It
measures the distance from the reference point (process connection) to the product surface. Radar impulses are
emitted by an antenna, reflected off the product surface and received again by the radar system.
L00-FMR250xx-15-00-00-en-001
Input
The reflected radar impulses are received by the antenna and transmitted into the electronics. A microprocessor
evaluates the signal and identifies the level echo caused by the reflection of the radar impulse at the product
surface. The unambiguous signal identification is accomplished by the PulseMaster® software, based on many
years of experience with time-of-flight technology.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2,
with c being the speed of light.
Based on the known empty distance E, the level L is calculated:
L = E – D
Refer to the above figure for the reference point for "E".
The Micropilot is equipped with functions to suppress interference echoes. The user can activate these
functions. They ensure that interference echoes (i.e. from internals and struts) are not interpreted as level echo.
Output
The Micropilot is commissioned by entering an empty distance E (=zero), a full distance F (=span) and an
application parameter. The application parameter automatically adapts the instrument to the process
conditions. The data points “E” and “F” correspond with 4mA and 20mA for instruments with current output.
They correspond with 0 % and 100 % for digital outputs and the display module.
A linearization with max. 32 points, based on a table entered either manually or semi-automatically, can be
activated locally or remotely. This function provides a measurement in engineering units and a linear output
signal for spheres, horizontal cylindrical tanks and vessels with conical outlet.
20mA
100%
4mA
0%
D
L
F
E
Flange:reference point ofmeasurement
Flange:reference point ofmeasurement
Threadedconnection1-½ (R 1-
:reference point ofmeasurement
BSPT ½”)or 1-½” NPT
Micropilot M FMR250
4 Endress+Hauser
Equipment architecture Stand-alone
The instrument provides a 4 to 20 mA output with HART protocol, or PROFIBUS PA respectively
FOUNDATION Fieldbus communication.
4 to 20 mA output with HART protocol.
The complete measuring system consists of:
L00-FMR2xxxx-14-00-06-en-001
Local operation
• with display and operating module VU331,
• with a Personal Computer, FXA193 and the operating software "ToF Tool - FieldTool Package" respectively
"FieldCare". The ToF Tool is a graphical operating software for instruments from Endress+Hauser that
operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with
commissioning, securing data, signal analysis and documentation of the measuring point.
Remote operation
• with HART handheld DXR375,
• with a Personal Computer, Commubox FXA191/195 and the operating software "ToF Tool - FieldTool
Package" respectively "FieldCare".
ENDRESS + HAUSER
E+–
%
ENDRESS + HAUSERRMA 422
1# % &
Copy
G H I
P Q R S
, ( ) ‘
A B C
Paste
PageOn
PageUp
DeleteBksp
Insert
J K L
T U V
_ < >
D E F
Hot Key
+ Hot Key
M N O
W X Y Z
+ * /
4
7
.
2
5
8
0
375FIELD COMMUNICATOR
3
6
9
-
9 6
DELTABAR: * * * * * * * *ONLINE
1 QUICK SETUP2 OPERATING MENU
4 SV 0 °C3 PV 352 mbar
HELP SAVE
dsdmdmdf das.
asdas faasas la.
1# % &
Copy
G H I
P Q R S
, ( ) ‘
A B C
Paste
PageOn
PageUp
DeleteBksp
Insert
J K L
T U V
_ < >
D E F
Hot Key
+ Hot Key
M N O
W X Y Z
+ * /
4
7
.
2
5
8
0
375FIELD COMMUNICATOR
3
6
9
-
9 6
DELTABAR: * * * * * * * *ONLINE
1 QUICK SETUP2 OPERATING MENU
4 SV 0 °C3 PV 352 mbar
HELP SAVE
dsdmdmdf das.
asdas faasas la.
- FieldCare- ToF Tool - FieldToolPackage
- FieldCare- ToF Tool - FieldToolPackage
HART handheldDXR375FXA191/195
orDXR375
Transmitter powersupply unitRMA422or RN221N(communication resistorincluded)
PLC
CommuboxFXA191/195
Operating anddisplay moduleVU331
Service adapterFXA193
Micropilot M FMR250
Endress+Hauser 5
System integration via PROFIBUS PA
A maximum of 32 transmitters (8 if mounted in an explosion hazardous location EEx ia IIC according to
FISCO-model) can be connected to the bus. The segment coupler provides the operating voltage to the bus.
Both on-site as well as remote operation are possible.The complete measuring system consists of:
L00-FMxxxxxx-14-00-06-en-001
System integration via FOUNDATION Fieldbus
A maximum of 32 transmitters (standard, EEx em or EEx d) can be connected to the bus. For protection class
EEx ia IIC: the max. number of transmitters depends on the established rules and standards for intrinsically
safe circuits (EN 60079-14), proof of intrinsically safety. Both on-site as well as remote operation are possible.
The complete measuring system consists of:
L00-FMxxxxxx-14-00-06-en-003
ENDRESS + HAUSER
Service adapter
FXA291/ToF Adapter FXA291
FSA193
�
�
Micropilot MProsonic M
Levelflex M
ENDRESS + HAUSER
E+–
%
T
PROFIBUS DP
PROFIBUS PA
ToF Tool - FieldTool Package
Personal computer e.g. withToF Tool - FieldToolPackage andProfibard resp. Proficard
Segment coupler
PLC
Operating anddisplay moduleVU331
MoreFunctions(valves etc)
T TFF link
Levelflex M
ENDRESS + HAUSER
E+–
%
Prosonic MMicropilot M
ToF Tool -FieldToolPackageFieldCare
Personal computere.g. withNI-FBUS configurator
Operating anddisplay moduleVU331
power supply
power conditioner
power supply
power conditioner
Additionalfunctions(valves etc.)
Service adapter• FXA291/ToF Adapter FXA291• FXA193
Micropilot M FMR250
6 Endress+Hauser
System integration via Fieldgate
Vendor Managed Inventory
By using Fieldgates to interrogate tank or silo levels remotely, suppliers of raw materials can provide their
regular customers with information about the current supplies at any time and, for example, account for them
in their own production planning. For their part, the Fieldgates monitor the configured level limits and, if
required, automatically activate the next supply. The spectrum of options here ranges from a simple purchasing
requisition via e-mail through to fully automatic order administration by coupling XML data into the planning
systems on both sides.
Remote maintenance of measuring equipment
Fieldgates not only transfer the current measured values, they also alert the responsible standby personnel, if
required, via e-mail or SMS. In the event of an alarm or also when performing routine checks, service
technicians can diagnose and configure connected HART devices remotely. All that is required for this is the
corresponding HART operating software (e.g. ToF Tool - FieldTool Package, FieldCare, ...) for the connected
device. Fieldgate passes on the information transparently, so that all options for the respective operating
software are available remotely. Some on-site service operations can be avoided by using remote diagnosis and
remote configuration and all others can at least be better planned and prepared.
L00-FXA520xx-14-00-06-en-009
Note!
The number of instruments which can be connected in mutidrop mode can be calculated by the "FieldNetCalc"
program. A description of this program can be found in Technical Information TI 400F (Multidrop Conncector
FXN520). The program is available form your Endress+Hauser sales organisation or in the internet at:
"www.endress.com � Download" (Text Search = "Fieldnetcalc").
-
FieldgateFXA520
ENDRESS+HAUSERRN 221N
ENDRESS+HAUSERRN 221N
.
FieldgateFXA520 20 to 45 VDC
FX
N5
20
FX
N5
20
Multidrop-ConnectorFXN520
HTTP scriptWeb browser…
AnalogEthernet
GSM
e.g. 2 x RN221N-B …
Channel 1
Hazardous AreaNon-hazardous Area
Channel 2
Via HART Client:- ToF Tool - FieldToolPackage
- FieldCare. . .
Remote monitoringRemote confoguration/diagnosis
Micropilot M FMR250
Endress+Hauser 7
Input
Measured variable The measured variable is the distance between a reference point (refer to fig. on page 2) and a reflective surface
(i.e. medium surface).
The level is calculated based on the vessel height entered.The level can be converted into other units (volume,
mass) by means of a linearization (32 points).
Measuring range The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the mounting
location and eventual interference reflections. The maximum configurable range is 70 m (229 ft) for
Micropilot M FMR250.
Reduction of the max. possible measuring range through:
• Media with poor reflection properties (= small DC). For examples refer to table 1.
• Angle of repose.
• Extremely loose surfaces of bulk solids, e.g. bulk solids with low bulk weight for pneumatic filling.
• Build-up, above all of moist products.
Table 1:
The following table describes the media groups and the dielectric constant εr.
The respective lower group applies for very loose or loosened bulk solids.
Antenna selection
Media group DC (εr) Examples Signal attenuation
A 1.6 to 1.9
– Plastic granulate
– White lime, special cement
– Sugar
19 to 16 dB
B 1.9 to 2.5 – Portland cement, plaster 16 to 13 dB
C 2.5 to 4
– Grain, seeds
– Ground stones
– Sand
13 to 10 dB
D 4 to 7– Naturally moist (ground) stones, ores
– Salt10 to 7 dB
E > 7
– Metallic powder
– Carbon black
– Coal
< 7 dB
Antenna type Application
FMR250-*4*... 3" (DN80)
FMR250-*5*... 4" (DN100)
The FMR250 with 3" (DN80) or 4" (DN100) horn antenna for all standard applications,
particularly also for small nozzle sizes.
To achieve an optimised signal strength it is recommended to use an antenna with as
large as possible diameter.
In small tanks in particular, an antenna extension should not be used wherever possible
to optimize dynamics at close range.
FMR250-*6*... 8"(DN200) The FMR250 with 8" (DN200) parabolic antenna offers high beam focussing of 4° and is
thus ideal for applications with many installations.
Micropilot M FMR250
8 Endress+Hauser
Measuring conditions • The measuring range begins, where the beam hits the vessel bottom. Particularly with dish bottoms or
conical outlets the level cannot be detected below this point.
The maximum measuring range can be increased in such applications by using a top target positioner
(see Page 16).
• In case of media with a low dielectric constant (groups A and B), the vessel bottom can be visible through
the medium at low levels. In order to guarantee the required accuracy in these cases, it is recommended to
position the zero-point at a distance C = 2" to 6" (50...150 mm) above the vessel bottom (see Fig.).
• In principle it is possible to measure up to the tip of the antenna with FMR250. However, due to
considerations regarding abrasion and build-up, the end of the measuring range should not be chosen any
closer than A=16" (400 mm, see Fig.) to the tip of the antenna.
L00-FMR250xx-17-00-00-en-001
Operating frequency • FMR250: K-band
Transmitting power Average energy density in beam direction:
100%
0%
A
C
Measuring range
DistanceAverage energy density
measuring range = 70 m (229 ft)
3 ft (1 m) < 64 nW/cm2
16 ft (5 m) < 2.5 nW/cm2
Micropilot M FMR250
Endress+Hauser 9
Output
Output signal • 4 to 20 mA with HART protocol
• PROFIBUS PA
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
• FOUNDATION Fieldbus (H1)
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
Signal on alarm Error information can be accessed via the following interfaces:
• Local display:
– Error symbol
– Plain text display
• Current output
• Digital interface
Linearization The linearization function of the Micropilot M allows the conversion of the measured value into any unit of
length or volume. Linearization tables for calculating the volume in cylindrical vessels are pre-programmed.
Other tables of up to 32 value pairs can be entered manually or semi-automatically.
Data of the FOUNDATION
Fieldbus interface
Basic Data
Virtual communication references (VCRs)
Link Settings
Device Type 100F (hex)
Device Revision 05 (hex)
DD Revision 01 (hex)
CFF Revision 01 (hex)
ITK Version 5.0
ITK-Certification Driver-No. IT042000
Link Master (LAS) cabable yes
Link Master / Basic Device selectable yes; Default: Basic Device
Number VCRs 24
Number of Link-Objects in VFD 24
Permanent Entries 1
Client VCRs 0
Server VCRs 24
Source VCRs 23
Sink VCRs 0
Subscriber VCRs 23
Publisher VCRs 23
Slot time 4
Min. Inter PDU delay 4
Max. response delay 10
Micropilot M FMR250
10 Endress+Hauser
Transducer Blocks
Function Blocks
Block Content Output values
Sensor Block contains all parameters related to the mesurement • level or volume1) (channel 1)
• distance (channel 2)
1) depends on sensor block configuration
Diagnsotic Block contains diagnostic information no output values
Display Block contains parameters to configure the local display no output values
Block Content Execution time Functionality
Resource Block The Resource Block contains all the data that uniquely
identifies the field device. It is an electronic version of a
nameplate of the device.
enhanced
Analog Input
Block 1
Analog Input
Block 2
The AI block takes the manufacturer's input data,
selected by channel number, and makes it available to
other function blocks at its output.
30 ms standard
PID Block The PID block serves as proportional-integral-derivative
controller and is used almost universally to do closed-
loop-control in the field including cascade and feedfor-
ward.
80 ms standard
Arithmetic Block This block is designed to permit simple use of popular
measurement math functions. The user does not have to
know how to write equations. The math algorithm is
selected by name, chosen by the user for the function to
be done.
50 ms standard
Input Selector
Block
The input selector block provides selection of up to four
inputs and generates an output based on the configured
action. This block normally receives its inputs from AI
blocks. The block performs maximum, minimum, middle,
average and ‘first good’ signal selection.
30 ms standard
Signal Charac-
terizer Block
The signal characterizer block has two sections, each
with an output that is a non-linear function of the respec-
tive input. The non-linear function is determined by a sin-
gle look-up table with 21 arbitrary x-y pairs.
40 ms standard
Integrator Block The Integrator Function Block integrates a variable as a
function of the time or accumulates the counts from a
Pulse Input block. The block may be used as a totalizer
that counts up until reset or as a batch totalizer that has a
setpoint, where the integrated or accumulated value is
compared to pre-trip and trip settings, generating discrete
signals when these settings are reached.
60 ms standard
Micropilot M FMR250
Endress+Hauser 11
Auxiliary energy
Electrical connection Terminal compartment
Three housings are available:
• Aluminium housing F12 with additionally sealed terminal compartment for:
– standard,
– Intrinsically safe (EEx ia),
– Dust ignition proof (EEx ia with dust Ex).
• Aluminium housing T12 with separate terminal compartment for:
– standard,
– Explosion proof (EEx d),
– Intrinsically safe (EEx ia), with overvoltage protection,
– Dust ignition proof (dust Ex).
• 316L housing F23 for:
– standard,
– Intrinsically safe (EEx ia),
– Dust ignition proof (EEx ia with dust Ex).
The electronics and current output are galvanically isolated from the antenna circuit.
L00-FMR2xxxx-04-00-00-en-019
Cable gland
Terminals For wire cross-sections 16 to 18 AWG (0.5 to 2.5 mm2)
1 12 23 34 41 2 3 4
sealed terminalcompartment
F12 housing F23 housingT12 housing
Type Clamping area
Standard, Intrinsically safe, EEx ia Plastic M20x1.5 5 to 10 mm
EEx em, EEx nA Metal M20x1.5 7 to 10.5 mm
All Metal, threaded 1/2" NPT
Micropilot M FMR250
12 Endress+Hauser
Terminal assignment
Load HART Minimum load for HART communication: 250 Ω
2-wire, 4 to 20 mA with HART
The 2-wire cable is connected to the screw terminals
in the terminal compartment.
Cable specification:
• A standard installation cable is sufficient if only the
analog signal is used. Use a shielded cable when
working with a superimposed communications
signal (HART).
Note!
Protective circuitry against reverse polarity, RFI, and
over-voltage peaks is built into the device (refer to
TI241F »basics for EMC-tests«).
Note!
See TI402F/00/en for connection to Tank Side
Monitor NRF590.
L00-FMxxxxxx-04-00-00-en-015
3 4I+ I-
1 2L- L+
4 to 20 mA
CommuboxFXA 191/195DXR 375
Alternatively
Plantground
Test sockets for testingof the signal current
Power
PROFIBUS PA
The digital communication signal is transmitted to the
bus via a 2-wire connection. The bus also provides the
auxiliary energy.
For further information on the network structure and
earthing and for further bus system components such
as bus cables, see the relevant documentation, e.g.
Operating Instructions BA034S "Guidelines for
planning and commissioning PROFIBUS DP/PA" and
the PNO Guideline.
Cable specification:
• Use a twisted, shielded two-wire cable, preferably
cable type A
L00-FMxxxxxx-04-00-00-en-022
Note!
For further information on the cable specifications, see Operating Instructions BA034S "Guidelines for planning
and commissioning PROFIBUS DP/PA", PNO Guideline 2.092 "PROFIBUS PA User and Installation Guideline"
and IEC 61158-2 (MBP).
3 41 2+–
Plantground
- +
FOUNDATION Fieldbus
The digital communication signal is transmitted to the
bus via a 2-wire connection. The bus also provides
the auxiliary energy.
For further information on the network structure and
earthing and for further bus system components such
as bus cables, see the relevant documentation, e.g.
Operating Instructions BA013S "FOUNDATION
Fieldbus Overview" and the FONDATION Fieldbus
Guideline.
Cable specification:
• Use a twisted, shielded two-wire cable, preferably
cable type A
L00-FMxxxxxx-04-00-00-en-022
Note!
For further information on the cable specifications, see Operating Instructions BA013S "FOUNDATION
Fieldbus Overview", FONDATION Fieldbus Guideline and IEC 61158-2 (MBP).
3 41 2+–
Plantground
- +
Micropilot M FMR250
Endress+Hauser 13
Supply voltage HART
The following values are the voltages across the terminals directly at the instrument:
FOUNDATION Fieldbus
Cable entry • Cable gland: M20x1.5 (for EEx d: cable entry)
• Cable entry: G ½ or ½" NPT
Power consumption min. 60 mW, max. 900 mW
Current consumption HART
3.6 to 22 mA. For HART Multidrop: start up current is 11 mA.
PROFIBUS PA
Max. 13 mA.
FOUNDATION Fieldbus
CommunicationCurrent
consumption
Terminal voltage
minimal maximal
HARTstandard
4 mA 16 V 36 V
20 mA 7.5 V 36 V
Intrinsically Safe
(EEx ia)
4 mA 16 V 30 V
20 mA 7.5 V 30 V
Explosion proof
(EEx d)
4 mA 16 V 30 V
20 mA 11 V 30 V
Dust explosion
proof (dust Ex)
4 mA 16 V 30 V
20 mA 11 V 30 V
Fixed current, adjustable
e.g. for solar power
operation (measured
value transferred at
HART)
standard 11 mA 10 V 36 V
Intrinsically Safe
(EEx ia)11 mA 10 V 30 V
Fixed current for HART
Multidrop mode
standard 4 mA1))
1) Start up current 11 mA.
16 V 36 V
Intrinsically Safe
(EEx ia)4 mA1) 16 V 30 V
Supply voltage 9 V to 32 V 1)
1) There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in the
appropriate safety instructions (XA).
Lift-off voltage 9 V
Basic current 15 mA
In-rush current ≤ 15 mA
Error current 0 mA
FISCO/FNICO compliant yes
Polarity sensitive no
Micropilot M FMR250
14 Endress+Hauser
FISCO
Ripple HART 47 to 125 Hz: Uss = 200 mV (at 500 Ω)
Max. noise HART 500 Hz to 10 kHz: Ueff = 2.2 mV (at 500 Ω)
Overvoltage protector The level transmitter Micropilot M with T12-housing (housing version "D", see ordering information on page
36-38) is equipped with an internal overvoltage protector (600 V surge arrester). Connect the metallic housing
of the Micropilot M to the vessel wall or shield directly with an electrically conductive lead to ensure reliable
potential matching.
Ui 17.5 V
Ii 500 mA; with surge arrester 273 mA
Pi 5.5 W; with surge arrester1, 2 W
Ci 5 nF
Li 0.01 mH
Micropilot M FMR250
Endress+Hauser 15
Performance characteristics
Reference operating
conditions
• temperature = +20 °C (68 °F) ±5 °C (9 °F)
• pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi)
• relative humidity (air) = 65 % ±20%
• ideal reflector
• no major interference reflections inside the signal beam
Maximum measured error Typical statements for reference conditions, include linearity, repeatability, and hysteresis:
• up to 3 ft (1 m): ±1.18" (30 mm)
• above 3 ft (1 m): ±0.60" (15 mm), or 0.04% of measuring range, whatever is larger
Resolution Digital / analog in % 4 to 20 mA
• FMR250: 0.04" (1mm) / 0.03 % of measuring range
Reaction time The reaction time depends on the parameter settings (min. 1 s). In case of fast level changes, the instrument
needs the reaction time to indicate the new value.
Influence of ambiente
temperature
The measurements are carried out in accordance with EN 61298-3:
• digital output (HART, PROFIBUS PA, FOUNDATION Fieldbus):
– FMR250
average TK: 0.20"/10 K (5 mm/10 K), max. 0.60" (15 mm) over the entire temperature
range -40 to +176°F (-40 to +80°C)
• Current output (additional error, in reference to the span of 16 mA):
– Zero point (4 mA)
average TK: 0.03 %/10 K, max. 0.45 % over the entire temperature range
-40 to +176°F (-40 to +80°C)
– Span (20 mA)
average TK: 0.09 %/10 K, max. 0.95 % over the entire temperature range
-40 to +176°F (-40 to +80°C)
Micropilot M FMR250
16 Endress+Hauser
Operating conditions: Installation
Installation instructions Orientation
• Recommended distance (1) wall – outer edge of
nozzle: ~1/6 of vessel diameter. However, the
device should not, under any circumstances, be
mounted less than 20 cm (8") from the vessel wall.
Note!
If the tank wall is not smooth (corrugated metal,
welding seams, irregularities etc.) the distance from
the wall should be kept as large as possible. If
necessary, use a top target positioner to prevent
interference reflections from the tank wall.
• Not in the centre (3), interference can cause signal
loss.
• Not above the fill stream (4).
• It is recommended to use a weather protection
cover (2) in order to protect the transmitter from
direct sun or rain. Assembly and disassembly is
simply done by means of a tension clamp (see
Accessorieson page 39).
• In extremely dusty applications, the integrated air
purge connection can prevent clogging of the
antenna.
L00-FMR250xx-17-00-00-xx-003
1
2 3 4
Vessel installations
• Avoid any installations (1), like limit switches,
struts, etc., inside the signal beam (see Beam angle
on Page 17).
• Symmetrical installations (2), i.e. reinforcing rings,
heating coils, etc., can also interfere with the
measurement.
Optimization options
• Antenna size: the bigger the antenna, the smaller
the beam angle, the less interference echoes.
• Mapping: the measurement can be optimized by
means of electronic suppression of interference
echoes.
• Antenna alignment: refer to "Optimum mounting
position"
• In devices with top target positioner, the sensor can
be optimally aimed within the vessel, and/or
interference reflections can be avoided.
The max. angle β is ±15°.
• In particular, sensor alignment serves to:
– prevent interference reflections
– extend the maximum possible measuring range
in conical outlets.
• Metallic screens (3) mounted at a slope spread the
radar signals and can, therefore, reduce
interference echoes.
Please contact Endress+Hauser for further
information.
L00-FMR250xx-17-00-00-xx-002
2
3
1
Micropilot M FMR250
Endress+Hauser 17
Measurement in a plastic tank
If the outer wall of the tank is made of a non-conductive material (e.g. GRP), microwaves can also be reflected
off interfering installations outside the signal beam (e.g. metallic pipes (1), ladders (2), grates (3), …). Therefore,
avoid such interfering installations in the signal beam.
L00-FMR250xx-17-00-00-xx-014
Please contact Endress+Hauser for further information.
Beam angle The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value of
the maximum energy density (3dB-width). Microwaves are also emitted outside the signal beam and can be
reflected off interfering installations. Beam diameter W as function of antenna type (beam angle α) and
measuring distance D:
VH
00
VH
00
Endress+Hauser
Endress+Hauser
- + V H
ENDRESS+HAUSERMICROPILOT II
IP 65
Order Code:Ser.-No.:
MessbereichMeasuring rangeU 16...36 V DC4...20 mA
max. 20 m
Mad
e in
Ger
man
y
M
aulb
urg
Mad
e in
Ger
man
y
M
aulb
urg
T >70°C :At >85°C
VH
00
VH
00
Endress+Hauser
Endress+Hauser
- + V H
ENDRESS+HAUSERMICROPILOT II
IP 65
Order Code:Ser.-No.:
MessbereichMeasuring rangeU 16...36 V DC4...20 mA
max. 20 m
Mad
e in
Ger
man
y
M
aulb
urg
Mad
e in
Ger
man
y
M
aulb
urg
T >70°C :At >85°C
1
32
VH
00
VH
00
Endress+Hauser
Endress+Hauser
- + V H
ENDRESS+HAUSERMICROPILOT II
IP 65
Order Code:Ser.-No.:
MessbereichMeasuring rangeU 16...36 V DC4...20 mA
max. 20 m
Mad
e in
Ger
man
y
M
aulb
urg
Mad
e in
Ger
man
y
M
aulb
urg
T >70°C :At >85°C
Antenna size
FMR250
Horn antenna Parabolic antenna
L00-FMR2xxxx-14-00-06-de-027
80 mm / 3" 100 mm / 4" 200 mm / 8"
Beam angle α 10° 8° 4°
Measuring
distance (D)
Beamwidth diameter (W)
80 mm / 3" 100 mm / 4" 200 mm / 8"
5 m / 16 ft 0.87 m / 2.80 ft 0.70 m / 2.24 ft 0.35 m / 1.12 ft
10 m / 32 ft 1.75 m / 5.60 ft 1.40 m / 4.48 ft 0.70 m / 2.23 ft
15 m / 49 ft 2.62 m / 8.57 ft 2.10 m / 6.85 ft 1.05 m / 3.42 ft
20 m / 65 ft 3.50 m / 11.37 ft 2.80 m / 9.09 ft 1.40 m / 4.54 ft
30 m / 98 ft 5.25 m / 17.15 ft 4.20 m / 13.71 ft 2.10 m / 6.84 ft
40 m / 131 ft 7.00 m / 22.92 ft 5.59 m / 18.32 ft 2.79 m / 9.15 ft
50 m / 164 ft 8.75 m / 28.70 ft 6.99 m / 22.94 ft 3.50 m / 11.45 ft
D
W
D _=2
2 . . tanW
Micropilot M FMR250
18 Endress+Hauser
Installation in vessel FMR250 Optimum mounting position
L00-FMR250xx-17-00-00-en-009
90°
90°
90°
90°
90°90°
1-½” NPT or1-½” BSPT (R 1-½”)
ANIS 3” to 8”(DN 80 to 200)
Marker at instrumentflange or threaded boss 1)
1) at version with top target positioner, the marker is at the housing adapter(opposite the air purge connection)
Standard installation FMR250 with horn
antenna
• Observe installation instructions on Page 16.
• Marker is aligned towards vessel wall.
• The marker is always exactly in the middle
between two bolt-holes in the flange.
• After mounting, the housing can be turned 350° in
order to simplify access to the display and the
terminal compartment.
• The horn antenna should protrude from the nozzle.
If this is not possible for mechanical reasons, larger
nozzle heights can be accepted.
Note!
Please contact Endress+Hauser for application with
higher nozzle.
• Vertical horn antenna.
Ideally, the horn antenna should be installed
vertically.
To avoid interference reflections or for optimum
alignment within the vessel, the FMR250 with
optional top target positioner can be swiveled by
15° in all directions.L00-FMR250xx-17-00-00-en-004
H
Ø D
Antenna size 80 mm / 3" 100 mm / 4"
D [mm / inch] 75 / 3 95 / 3.7
H [mm / inch]
(without antenna extension)< 260 / < 10.2 < 330 / < 12.9 1))
1) from 28.11.2005: H < 480 mm / 18.8 inch
Micropilot M FMR250
Endress+Hauser 19
Standard installation FMR250 with parabolic
antenna
• Observe installation instructions on Page 16.
• Marker is aligned towards vessel wall.
• The marker is always exactly in the middle
between two bolt-holes in the flange.
• After mounting, the housing can be turned 350° in
order to simplify access to the display and the
terminal compartment.
• Ideally the parabolic antenna should protrude from
the nozzle (1).
Particularly when using the top target positioner,
please ensure that the parabolic reflector is
protruding from the nozzle/roof so as not to inhibit
alignment.
Note!
For application with higher nozzle install parabolic
antenna completely in the nozzle (2), including
RF-wave guide (3).
• Vertical parabolic antenna.
Ideally, the parabolic antenna should be installed
vertically.
To avoid interference reflections or for optimum
alignment within the vessel, the FMR250 with
optional top target positioner can be swiveled by
15° in all directions.L00-FMR250xx-17-00-00-en-005
H
1
2
3
Ø D
Antenna size 200 mm / 8"
D [mm / inch] 197 / 7.75
H [mm / inch]
(without antenna extension)< 50 / < 1.96
Micropilot M FMR250
20 Endress+Hauser
Examples for installation with small flange (< parabolic reflector)
L00-FMR250xx-17-00-00-en-007
H
D
D inches (mm)
Antenna size 8” (200 mm)
7.76 (197)
< 1.97 (50)H inches (mm) 1)
For installationin nozzle, youcan dismantlethe parabolic reflector
Caution!
When installing on hinged flanges, the length of the antennamust be taken into account. Ensure the nozzle/opening iswide enough to accommodate the antenna tip.
4 bolts
Nozzle
1) without antenna extension
Standard installation
Micropilot M FMR250
Endress+Hauser 21
FMR250 with top target
positioner
Optimum mounting position
Using the top target positioner it is possible to tilt the antenna axis by up to 15° in all directions. The top target
positioner is used for the optimum alignment of the radar beam with the bulk solids surface.
L00-FMR250xx-17-00-00-de-008
Align antenna axis:
1. Loosen screws.
2. Align antenna axis (here this is possible up to max. ±15° in all directions).
3. Tighten screws.
Integrated air purge
connection
±15° ±15°
In extremely dusty applications, the integrated air
purge connection can prevent clogging of the
antenna. Pulsed operation is recommended.
• Pulsed operation:
max. pressure of purge air: 87 psi (6 bar abs.)
• Permanent operation:
recommended pressure range of the purge air: 2.9
to 7.3 psi (200 to 500 mbar).
Caution!
Make sure to use dry purge air.
L00-FMR250xx-17-00-00-en-010
Air purge connection:NPT
orG (max. torque
2.6 lbf ft / 3.5 Nm)
¼”
¼
Micropilot M FMR250
22 Endress+Hauser
Operating conditions: Environment
Ambient temperature range Ambient temperature for the transmitter: -40 to +80°C (-40 to +176°F), -50°C (-58°F) on request.
The functionality of the LCD display may be limited for temperatures Ta<4°F (-20°C) and Ta>+140°F (+60°C).
A weather protection cover should be used for outdoor operation if the instrument is exposed to direct sunlight.
Storage temperature -40 to +80°C (-40 to +176°F), -50°C (-58°F) on request.
Climate class DIN EN 60068-2-38 (test Z/AD)
Degree of protection • housing: IP 65, NEMA 4X (open housing and pulled out display: IP20, NEMA 1)
• antenna: IP 68 (NEMA 6P)
Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20 to 2000 Hz, 1 (m/s2)2/Hz
Cleaning of the antenna The antenna can get contaminated, depending on the application. The emission and reception of microwaves
can eventually be hindered. The degree of contamination leading to an error depends on the medium and the
reflectivity, mainly determined by the dielectric constant εr. If the medium tends to cause contamination and
deposits, cleaning on a regular basis is recommended. Care has to be taken not to damage the antenna in the
process of a mechanical or hose-down cleaning (eventually air purge connection). The material compatibility
has to be considered if cleaning agents are used!
The maximum permitted temperature at the flange should not be exceeded.
Electromagnetic compatibility
(EMC)
• Electromagnetic compatibility to EN 61326 and NAMUR recommendation EMC (NE 21). For details refer
to the declaration of conformity.
• A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable when
working with a superimposed communications signal (HART).
Micropilot M FMR250
Endress+Hauser 23
Operating conditions: Process
Process temperature range /
Process pressure limits
Note!
The specified rage may be reduced by the selected process connection. The pressure rating (PN) specified on
the nameplate refers to a reference temperature of 20°C, for ASME flanges to 100°F. Observe pressure-
temperature dependency.
The pressure values permitted at higher temperatures can be found in the following standards:
• EN 1092-1: 2001 Tab. 18
With regard to its stability property, the material 1.4435 is identical to 1.4404 which is grouped under 13EO
in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
Optional top target positioner: ±15°, seal: FMK Viton GLT
Dielectric constant • In free space: εr ≥ 1.6 (for horizontal, even product surfaces: εr ≥ 1.4)
Type of antenna Seal Temperature Pressure Wetted parts
FMR250 E Standard FKM Viton GLT -40 to +200 °C
(-40 to +392°F)
-1 to 16 bar 1)
(-14.5 to 232 psi 1)
1) E+H UNI flange: -1 to 1 bar (-14.5 to 14.5 psi)
PEEK, seal,
316L SS/1.4404/1.4435
↑
Ordering information see Page 36
Micropilot M FMR250
24 Endress+Hauser
Mechanical construction
Design, dimensions Housing dimensions
Dimensions for process connection and type of antenna see Page 25.
L00-F12xxxx-06-00-00-en-001
L00-T12xxxx-06-00-00-en-001
L00-F23xxxx-06-00-00-en-001
ENDRESS+HAUSER
2.56”(65)
3.07”(78)
max. 4.33”(110)
3.35”(85)
5.91”(150)
Ø 5.08”(129)
(Aluminum)
F12 housing
ENDRESS+HAUSER
3.70”(94)
(Aluminum)
T12 housing
2.56”(65)
3.07”(78)
max. 4.33”(110)
3.35”(85)
5.91”(150)
Ø 5.08”(129)
max. 3.70”(94)
4.09”(104)
Ø 5.08”(129) 5.91”
(150)
1.57”(40)
(316L SS)
F23 housing
Micropilot M FMR250
Endress+Hauser 25
Micropilot M FMR250 - process connection, type of antenna
Housing dimensions see Page 24.
L00-FMR250xx-06-00-00-en-005
Ø d
Ø d
1.06”(27)
1.06”(27)
Ø d
2.95”(75)
2.95”(75)
L
LL
L
1.97”(50)
1.97”(50)
1.97”(50)
1.97”(50)
9.84”/17.7”(250/450)
9.84”/17.7”(250/450)
5.31”(135)
5.31”(135)
5.31”(135)
5.31”(135)
1.57”(40)
1.57”(40)
0.31”(8)
0.31”(8)
b
0.91”(23)
1.69”(43)
Ø d
2.95 (75)
8.31 (211)
3” (80 mm) 8” (200 mm)
3.74 (95) 7.76 (197)
11.1 (282) 1) 7.68 (195)
4” (100 mm)
b
3”
0.94”
7.50”
L in (mm) L in (mm)
d in (mm) d in (mm)D 9.0”
0.94”
4”
Ø D Ø 13.4”(340)
Ø 8.86” (4” / DN100)
Dn200)Ø 13.4” (8” /
Ø 2.36”(60)
Ø 2.36”(60)
Ø 2.36”(60)
Ø 2.36”(60)
Parabolic antennaHorn antenna
for Class 150
NOTE: Other process connections (DIN, JIS) are available,please contact Endress+Hauser.
Flange
Flange to ANSI B16.5
1) 16.9” (430 mm) as of November 28, 2005
Antenna size Antenna size
Horn antenna Parabolic antenna
F12 / T12 / F23 housing
Threaded connection
BSPT (R 1 ½”)1-½” NPT or
1 ½”
Flange, 3” or 4”(DN 80 to 100)or equivalent
E+H UNI flange8” (DN 200)
Alignment unit withE+H UNI flange, 4” / 8”
( DN 100/200)
Micropilot M FMR250
26 Endress+Hauser
E+H UNI flange Installation hints
The number of bolts has sometimes been reduced. The bolt-holes have been enlarged for adaption of
dimensions, therefore, the flange needs to be properly aligned to the counterflange before the bolts are
tightened. Dimensions are in inches (mm).
L00-FMR250xx-06-00-00-en-006
Top target positioner with E+H UNI flange
L00-FMR250xx-06-00-00-en-007
6.89”(175)
4x90°
4x90°
8.86”(225)
Ø 0.75”(19)
Ø 0.91”(23)
0.31”(80)
13.4”(340)
4x90°
6x60
°
Ø 1.02”(26)
Ø 1.02”(26)
7.30”(185.5)
11.6”(294.5)
Material: 316L
M80x1.5
A-A
AA
AA
E+H UNI flange 4” (DN100)
compatible with- ANSI 4” Class 150- DN100 PN10/16- JIS 10K 100A
E+H UNI flange 8” (DN200)
compatible with- ANSI 8” Class 150- DN200 PN10/16- JIS 10K 200A
±15°
0.31”(8)
1.57”(40)
Ø 3.35”(85)
A-A
AA
E+H UNI flange4”/8” (DN100/DN200)
Clamping screw3 x M8 shifted at 120°
Viton seal
Micropilot M FMR250
Endress+Hauser 27
Weight
Material • Housing:
– housing F12/T12: aluminum (AlSi10Mg), seawater-resistant, powder-coated
– housing F23: 316L SS, corrosion-resistant steel
• Sight window: glass
Process connection See "Ordering information" on Page 36-38.
Seal See "Ordering information" on Page 36-38.
Antenna See "Ordering information" on Page 36-38.
Micropilot M FMR250
Weight for F12 or
T12 housing
Approx. 13 lb (6 kg)
+
weight of flange
Weight for F23
housing
Approx. 21 lb (9.4 kg)
+
weight of flange
Micropilot M FMR250
28 Endress+Hauser
Human interface
Operation concept The display of the process value and the configuration of the Micropilot occur locally by means of a large 4-line
alphanumeric display with plain text information. The guided menu system with integrated help texts ensures
a quick and safe commissioning.
To access the display the cover of the electronic compartment may be removed even in hazardous area (IS and
XP).
Remote commissioning, including documentation of the measuring point and in-depth analysis functions, is
supported via the ToF Tool, the graphical operating software for E+H time-of-flight systems.
Display elements Liquid crystal display (LCD):
Four lines with 20 characters each. Display contrast adjustable through key combination.
L00-FMxxxxxx-07-00-00-en-001
The VU331 LCD display can be removed to ease operation by simply pressing the snap-fit (see graphic above).
It is connected to the device by means of a 20" (500 mm) cable.
The following table describes the symbols that appear on the liquid crystal display:
ENDRESS + HAUSER
E+–
ENDRESS+HAUSER
MICROPILOT II
ENDRESS+HAUSER
MICROPILOT II
IP 65IP 65
Order Code:Ser.-No.:
Order Code:Ser.-No.:
MessbereichMeasuring range
MessbereichMeasuring rangeU 16...36 V DC
4...20 mA
U 16...36 V DC4...20 mA
max. 20 m
max. 20 m
Made in
Germ
any
M
aulb
urg
Made in
Germ
any
M
aulb
urg
T>70°C :
A
t >85°C
T>70°C :
A
t >85°C
LCD
(liquid crystal display)
Symbols
3 keys
Snap-fit
Sybmol Meaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a
warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked,i.e. if no input is possible.
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA or
FOUNDATION Fieldbus is in progress.
SIMULATION_SWITCH_ENABLE
This communication symbol appears when simulation in FOUNDATION Fieldbus is enabled via the DIP
switch.
Micropilot M FMR250
Endress+Hauser 29
Operating elements The operating elements are located inside the housing and are accessible for operation by opening the lid of the
housing.
Function of the keys
Key(s) Meaning
O or V Navigate upwards in the selection list
Edit numeric value within a function
S or W Navigate downwards in the selection list
Edit numeric value within a function
X or Z Navigate to the left within a function group
F Navigate to the right within a function group, confirmation.
O and For
S and FContrast settings of the LCD
O and S and F
Hardware lock / unlock
After a hardware lock, an operation of the instrument via display or
communication is not possible!
The hardware can only be unlocked via the display. An unlock parameter must
be entered to do so.
Micropilot M FMR250
30 Endress+Hauser
Local operation Operation with VU331
The LC-Display VU331 allows configuration via 3 keys directly at the instrument. All device functions can be
set through a menu system. The menu consists of function groups and functions. Within a function, application
parameters can be read or adjusted. The user is guided through a complete configuration procedure.
L00-FMRxxxxx-07-00-00-en-002
Operation with handheld unit Field Communicator DXR375
All device functions can be adjusted via a menu operation with the handheld unit DXR375.
L00-FMR2xxxx-07-00-00-yy-007
Note!
Further information on the handheld unit is given in the respective operating manual included in the transport
bag of the DXR375.
XX
X
XS
S
OO FF
F
F
HOME
FG00 F000 F001 F002 F003 F004 ...
FG01
FG02
FG03
FG04
FG05
FG06
FG07
...
ENDRESS + HAUSER
E+–
Headline Position indicator
Main value UnitSymbol
Selection list
Function groups -> Functions
Help text
Envelopecurve
Bargraph
1# % &
Copy
G H I
P Q R S
, ( ) ‘
A B C
Paste
PageOn
PageUp
DeleteBksp
Insert
J K L
T U V
_ < >
D E F
Hot Key
+ Hot Key
M N O
W X Y Z
+ * /
4
7
.
2
5
8
0
375FIELD COMMUNICATOR
3
6
9
-
FMR231: LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
dsdmdmdf das.asdas faasas la.
PageOn
PageUp
Bksp
Delete
Delete
FMR231: LIC0001
ONLINE
1 GROUP SELECTION
2 PV 8.7 m
HELP SAVE
dsdmdmdf das.asdas faasas la.
FMR231: LIC0001
GROUP SELECTION
HOMESAVE
dsdmdmdf das.asdas faasas la.H
FMR231: LIC0001
HOMESAVE
dsdmdmdf das.asdas faasas la.H
Bksp
1 BASIC SETUP
2 SAFETY SETTINGS
BASIC SETUP
1 MEASURED VALUE
4 PROCESS COND.
5 EMPTY CALIBR.
3 MEDIUM PROPERTY
4 EXTENDED CALIB.
5 OUTPUT
3 LINEARISATION
2 TANK SHAPE
Micropilot M FMR250
Endress+Hauser 31
Remote operation The Micropilot M can be remotely operated via HART, PROFIBUS PA and FOUNDATION Fieldbus. Local
adjustments are also possible.
ToF Tool – Fieldtool Package
The ToF Tool is a graphic and menu-guided operating program for measuring devices from
Endress+Hauser. It is used for the commissioning, data storage, signal analysis and documentation of the
devices. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP. You can set
all parameters via the ToF Tool.
The ToF Tool supports the following functions:
• Configuration of transmitters in online operation
• Singal analysis via envelope curve
• Tank linearisation
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA191 and the RS 232 C serial interface of a computer
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
• FOUNDATION Fieldbus, PROFIBUS PA and HART via the FXA193/FXA291 service interface
Note!
You can use the ToF Tool to configure the Endress+Hauser parameters for devices with "FOUNDATION
Fieldbus signal". You need an FF configuration program to be able to configure all the FF-specific parameters
and to integrate the device into an FF network.
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can
configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT
standard. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
FieldCare supports the following functions:
• Configuration of transmitters in online operation
• Signal analysis via envelope curve
• Tank linearization
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA191 and the RS 232 C serial interface of a computer
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
Micropilot M FMR250
32 Endress+Hauser
Menu-guided commissioning
MicropilotM-en-415
Signal analysis via envelope curve
MicropilotM-en-416
Micropilot M FMR250
Endress+Hauser 33
Tank linearization
MicropilotM-en-417
Micropilot M FMR250
34 Endress+Hauser
Operation with NI-FBUS configurator (only FOUNDATION Fieldbus)
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedule
based on the fieldbus concepts.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
• Set block and device tags
• Set device addresses
• Create and edit function block control strategies (function block applications)
• Configure vendor-defined function and transducer blocks
• Create and edit schedules
• Read and write to function block control strategies (function block applications)
• Invoke Device Description (DD) methods
• Display DD menus
• Download a configuration
• Verify a configuration and compare it to a saved configuration
• Monitor a downloaded configuration
• Replace devices
• Log project download changes
• Save and print a configuration
L00-fmxxxxxx-20-00-00-en-001
Micropilot M FMR250
Endress+Hauser 35
Certificates and approvals
CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the
instrument passing the required tests by attaching the CE-mark.
Ex approval See "Ordering information" on Page 36-38.
External standards and
guidelines
EN 60529
Protection class of housing (IP-code)
EN 61010
Safety regulations for electrical devices for measurement, control, regulation and laboratory use.
EN 61326-X
EMC product family standard for electrical equipment for measurement, control and laboratory use.
NAMUR
User association for automation technology in process industries.
RF approvals R&TTE, FCC
Micropilot M FMR250
36 Endress+Hauser
Ordering information
Micropilot M FMR250 Instrument selection
L00-FMR250xx-16-00-00-en-001
T12 T12 T12F12 F12F23 F23
Non-hazardousarea
IS
E FKM Viton GLT
Certificate
E FKM Viton GLT E FKM Viton GLT
XPdust Ex
Type of antenna/Seal
Communication
Housing
HART HART HARTPA PA PAFF FF FF
Micropilot M FMR250
Endress+Hauser 37
Ordering structure Micropilot M FMR250
10 Approval:
A Non-hazardous area
1 ATEX II 1/2G EEx ia IIC T6
4 ATEX II 1/2G EEx d [ia] IIC T6
G ATEX II 3G EEx nA II T6
B ATEX II 1/2GD EEx ia IIC T6, Alu blind cover
C ATEX II 1/2G EEx ia IIC T6, ATEX II 1/3D
D ATEX II 1/2D, Alu blind cover
E ATEX II 1/3D
I NEPSI Ex ia IIC T6
J NEPSI Ex d(ia)ia IIC T6
Q NEPSI DIP
L TISS EEx d (ia) IIC T3
S FM IS-Cl.I/II/III Div.1 Gr.A-G
T FM XP-Cl.I/II/III Div.1 Gr.A-G
N CSA General Purpose
U CSA IS-Cl.I/II/III Div.1 Gr.A-G
V CSA XP-Cl.I/II/III Div.1 Gr.A-G
Y Special version
20 Antenna:
4 Horn 80mm/3"
5 Horn 100mm/4"
6 Parabolic 200mm/8"
9 Special version
30 Antenna seal; Temperature:
E FKM Viton GLT; -40 to 200°C/-40 to 392 °F
Y Special version
40 Antenna extension:
1 Not selected
2 250mm/10"
3 450mm/18"
9 Special version
50 Process connection:
GGJ Thread EN10226 R1-1/2, 316L
GNJ Thread ANSI NPT 1-1/2", 316L
X3J UNI flange DN200/8"/200A, 316L
max PN1/14.5lbs/1K, compatible DN200 PN10/16, 8" 150lbs, 10K 200A
XCJ Top target pos., UNI DN100/4"/100A, 316L
max PN1/14.5lbs/1K, compatible DN100 PN10/16, 4" 150lbs, 10K 100A
XEJ Top target pos., UNI DN200/8"/200A, 316L
max PN1/14.5lbs/1K, compatible DN200 PN10/16, 8" 150lbs, 10K 200A
CMJ DN80 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C)
CQJ DN100 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C)
ALJ 3" 150lbs RF, 316/316L flange ANSI B16.5
APJ 4" 150lbs RF, 316/316L flange ANSI B16.5
KLJ 10K 80A RF, 316L flange JIS B2220
KPJ 10K 100A RF, 316L flange JIS B2220
YY9 Special version
FMR250- Product designation (part 1)
Micropilot M FMR250
38 Endress+Hauser
Ordering structure Micropilot M FMR250 (continued)
60 Output; Operation:
A 4-20mA HART; 4-line display VU331, envelope curve display on site
B 4-20mA HART; w/o display, via communication
K 4-20mA HART; prepared for FHX40, remote display (Accessory)
C PROFIBUS PA; 4-line display VU331, envelope curve display on site
D PROFIBUS PA; w/o display, via communication
L PROFIBUS PA; prepared for FHX40, remote display (Accessory)
E FOUNDATION Fieldbus; 4-line display VU331, envelope curve display on site
F FOUNDATION Fieldbus; w/o display, via communication
M FOUNDATION Fieldbus; prepared for FHX40, remote display (Accessory)
Y Special version
70 Housing:
A F12 Alu, coated IP65 NEMA4X
B F23 316L IP65 NEMA4X
C T12 Alu, coated IP65 NEMA4X, separate connection compartment
D T12 Alu, coated IP65 NEMA4X + OVP, separate connection compartment,
OVP = overvoltage protection
Y Special version
80 Cable entry:
2 Gland M20x1.5 (EEx d > thread M20)
3 Thread G1/2
4 Thread NPT 1/2"
9 Special version
90 Additional option:
K Air purge connection G1/4
M Air purge connection NPT 1/4"
Y Special version
FMR250- Complete product designation
Micropilot M FMR250
Endress+Hauser 39
Accessories
Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code:
543199-0001). The shipment includes the protective cover and tension clamp.
L00-FMR2xxxx-00-00-06-en-001
Remote display FHX40
L00-FMxxxxxx-00-00-06-en-003
Technical data (cable and housing) and product structure:
ENDRESS+HAUSER
MICROPILOT II
ENDRESS+HAUSER
MICROPILOT II
IP 65
Order Code:Ser.-No.:
Order Code:Ser.-No.:
MessbereichMeasuring range
MessbereichMeasuring rangeU 16...36 V DC
4...20 mA
U 16...36 V DC4...20 mA
max. 20 m
max. 20 m
Ma
de
in G
erm
any
Ma
ulb
urg
Made in
Germ
any
Maulb
urg
T>70°C :
A
t >85°C
T>70°C :
A
t >85°C
F12 / F23 / T12 housing
ENDRESS+HAUSER
ENDRESS+HAUSER
IP 65IP 65
Order Code:Ser.-No.:
Order Code:Ser.-No.:
MessbereichMeasuring range
MessbereichMeasuring rangeU 16...36 V DC
4...20 mA
U 16...36 V DC4...20 mA
max. 20 m
max. 20 m
Mad
e in
Ger
man
y
M
aulb
urg
Mad
e in
Ger
man
y
M
aulb
urg
T>70°C :
A
t >85°C
T>70°C :
A
t >85°C
3.23”(82)
0.25”(6.3)
4.17”(106)
4.80”(122)
4.72”(120)
3.15”(80)
max. 3.15”(80)
min. 1.18”(30)
3.78”(96)
3.46”(88)
6.30”(160)
4.65”(118)
7.09”(180)
0.33”(8.5)
Micropilot MLevelflex MProsonic M
Separate housingFHX 40, NEMA 4(IP 65)
Cable
4.80”(122)
5.91”(150)
Wall-mounting(without mounting bracket)
Pipe-mounting(mounting bracket and plate
supplied optionally,see product structure)
pipe
Max. cable length 20 m (65 ft)
Temperature range -30 to +70 °C (-22 to 158 °F)
Degree of protection IP65 acc. to EN 60529 (NEMA 4)
Materials Housing: AlSi12; cable glands: nickle plated brass
Dimensions [mm] / [inch] 122 x 150 x 80 (HxWxD) / 4.8 x 5.9 x 3.2
Micropilot M FMR250
40 Endress+Hauser
For connection of the remote display FHX40 use the cable which fits the communication version of the
respective instrument.
Commubox FXA191 HART For intrinsically safe communication with ToF Tool/FieldCare via the RS232C interface. For details refer to
TI237F/00/en.
Commubox FXA195 HART For intrinsically safe communication with ToF Tool/FieldCare via the USB interface. For details refer to
TI404F/00/en.
Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to
TI405C/07/en.
Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70
• Gammapilot M FMG60
• Levelflex M FMP4x
• Micropilot FMR130/FMR131
• Micropilot M FMR2xx
• Micropilot S FMR53x, FMR540
• Prosonic FMU860/861/862
• Prosonic M FMU4x
• Tank Side Monitor NRF590 (with additional adapter cable)
ToF Adapter FXA291 The ToF Adapter FXA291 connects the Commubox FXA291 via the USB interface of a personal computer or
a notebook to the following Endress+Hauser instruments:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70
• Gammapilot M FMG60
• Levelflex M FMP4x
• Micropilot FMR130/FMR131
• Micropilot M FMR2xx
• Micropilot S FMR53x, FMR540
• Prosonic FMU860/861/862
• Prosonic M FMU4x
• Tank Side Monitor NRF590 (with additional adapter cable)
For details refer to KA271F/00/a2.
Approval:
A Nn-hazardous area
1 ATEX II 2 G EEx ia IIC T6, ATEX II 3D
S FM IS Cl.I Div.1 Gr.A-D
U CSA IS Cl.I Div.1 Gr.A-D
N CSA General Purpose
K TIIS ia IIC T6 (in preparation)
Cable:
1 20m/65ft; for HART
5 20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus
Additional option:
A Basic version
B Mounting bracket, pipe 1"/ 2"
FHX40 - Complete product designation
Micropilot M FMR250
Endress+Hauser 41
Documentation
Technical Information Fieldgate FXA320, FXA520
Technical Information for Fieldgate FXA320/520, TI369F/00/en.
Operating Instructions Micropilot M
Correlation of operating instructions to the instrument:
Instrument Output Communication Operating
Instructions
Description of
Instrument
Functions
Brief Operating
Instructions
(in the
Instrument)
FMR250 A, B, K HART BA284F/00/en BA291F/00/en KA235F/00/a2
C, D, L PROFIBUS PA BA331F/00/de BA291F/00/de KA235F/00/a2
E, F, M FOUNDATION Fieldbus BA336F/00/de BA291F/00/de KA235F/00/a2
Micropilot M FMR250
42 Endress+Hauser
Certificates Correlation of safety instructions (XA) and certificates (ZE) to the instrument:
Instrument Certificate Explosion protection Output Communication Housing PTB 04 ATEX XA
FMR250 A Non-hazardous area A, B, C,
D, K, L
E, F, M
HART,
PROFIBUS PA
FOUNDATION Fieldbus
— — —
1 ATEX II 1/2G EEx ia IIC T6 A, B, K HART A, B, D 2108 XA313F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, B, D 2108 XA343F
4 ATEX II 1/2G EEx d [ia] IIC T6 A, B, K HART C 2108 XA314F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
C 2108 XA344F
G ATEX II 3G EEx nA II T6 A, B, C,
D, K, L
E, F, M
HART,
PROFIBUS PA
FOUNDATION Fieldbus
— 2108 XA233F
B ATEX II 1/2GD EEx ia IIC T6, Alu blind cover A, B, K HART A, B 2108 XA312F
A, B HART D 2108 XA312F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, B 2108 XA342F
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
D 2108 XA342F
C ATEX II 1/2G EEx ia IIC T6
ATEX II 1/3D
A, B, K HART A, B 2108 XA312F
A, B HART D 2108 XA312F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, B 2108 XA342F
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
D 2108 XA342F
D ATEX II 1/2D, Alu blind cover A, B, K HART C 2108 XA315F
A, B HART A, B, D 2108 XA315F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
C 2108 XA345F
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
A, B, D 2108 XA345F
E ATEX II 1/3D A, B, K HART A, D, C 2108 XA315F
A, B HART B 2108 XA315F
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, D, C 2108 XA345F
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
B 2108 XA345F
Micropilot M FMR250
Endress+Hauser 43
Correlation of Control Drawings (ZD) to the instrument:
Instrument Certificate Explosion
protection
Output Communication Housing ZD
FMR250 S FM IS A, B, K HART A, B ZD168F/00/en
A, B HART D ZD168F/00/en
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, B ZD208F/00/en
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
D ZD208F/00/en
T FM XP A, B, K
C, D, L
E, F, M
HART
PROFIBUS PA
FOUNDATION Fieldbus
C ZD169F/00/en
U CSA IS A, B, K HART A, B ZD170F/00/en
A, B HART D ZD170F/00/en
C, D, L
E, F, M
PROFIBUS PA
FOUNDATION Fieldbus
A, B ZD209F/00/en
C, D
E, F
PROFIBUS PA
FOUNDATION Fieldbus
D ZD209F/00/en
V CSA XP A, B, K
C, D, L
E, F, M
HART
PROFIBUS PA
FOUNDATION Fieldbus
C ZD171F/00/en
This product may be protected by at least one of the following patents.
Further patents are pending.
• US 5,387,918 i EP 0 535 196
• US 5,689,265 i EP 0 626 063
• US 5,659,321
• US 5,614,911 i EP 0 670 048
• US 5,594,449 i EP 0 676 037
• US 6,047,598
• US 5,880,698
• US 5,926,152
• US 5,969,666
• US 5,948,979
• US 6,054,946
• US 6,087,978
• US 6,014,100
United States
Endress+Hauser, Inc.
2350 Endress Place
Greenwood, IN 46143
Tel. 317-535-7138
Sales 888-ENDRESS
Service 800-642-8737
fax 317-535-8498
inquiry@us.endress.com
www.us.endress.com
TI390F/24/ae/09.07
© 2007 Endress+Hauser, Inc.
Canada
Endress+Hauser Canada
1075 Sutton Drive
Burlington, ON L7L 5Z8
Tel. 905-681-9292
800-668-3199
Fax 905-681-9444
info@ca.endress.com
www.ca.endress.com
Mexico
Endress+Hauser, México, S.A. de C.V.
Fernando Montes de Oca 21 Edificio A Piso 3
Fracc. Industrial San Nicolás
54030. Tlalnepantla de Baz
Estado de México
México
Tel: +52 55 5321 2080
Fax +52 55 5321 2099
eh.mexico@mx.endress.com
www.mx.endress.com
top related