The OPzV series adopts an Immobilized Gel and Tubular Positive Plate technology. It offers high reliability and stable performance. By using die-casted positive grid and patented active material formula, it exceeds the DIN standard values and offer 20+ years design life in float service. It is very suitable for cyclic use under extreme operating conditions. This series is recommended for telecom outdoor applications, renewable energy systems and other harsh environment applications.

2V TUBULAR GEL SERIES VRLA BATTERY

OPzV350(2V350Ah)

EDIT

ION 2

016

Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.

SPECIFICATIONS General Features

Nominal Voltage (V) oNominal Capacity (20 C)

oDesigned Floating Life (20 C)

Demensions

Approx. Weight

Terminal Type

Internal Resistance

Max. Charge Current

Max. Discharge Current (5S)

Short Circuit Current

Self DischargeoFloat Charge Voltage (20~25 C)

Equalize Charge Voltage (20~25°C)

Container Material

Ambient Temperature Discharge

Ambient Temperature Charge

Ambient Temperature Storage

2

350 Ah @ C10 (to 1.80Vpc)

20+ Years

L124mm×W206mm×H506mm

28.5 kg (62.8 lbs)

Female Copper Insert M8 (torque:10~12N.m)

Approx. 0.70mΩhm (fully charged @ 20°C)

70A

1500 A

2850 A

Approx. 2% per month @ 20°Co2.25-2.29V (-3mV / C/ cell)o2.35-2.40V (-5mV / C/ cell)

ABS(UL94-V0 optional)

-40~60°Co -15~50 Co -15~40 C

Dimensions(mm) 3D Model Review

2V 350Ah Tubular 20+ yearsGel

471m

m

506m

m

124m

m

108mm

206mm

TERMINAL DIMENSION

M8mm

20mm

7m

m

Complied standards

IEC 60896-21/22DIN40742IEC61427YD/T1360EUROBAT guide, long lifeBS6290 part 4

BATTERY DISCHARGE TABLE

Constant Current Discharge Characteristics: Amps (20°C)

Constant Current Discharge Characteristics: W/cell (20°C)

Long time discharge capacity for Solar & Wind applications

PARAMETERS FOR SOLAR & WIND APPLICATIONS

F. V / T i m e

1 . 9 0 V

1 . 8 7 V

1 . 8 5 V

1 . 8 3 V

1 . 8 0 V

1 . 7 5 V

1 . 7 0 V

1 . 6 5 V

1 . 6 0 V

1 0 m i n

1 2 8

1 7 5

2 0 1

2 3 4

2 6 2

2 7 8

3 0 3

3 5 3

3 8 5

1 5 m i n

1 2 5

1 6 3

1 8 4

2 0 5

2 3 8

2 6 1

2 8 7

3 2 3

3 5 5

3 0 m i n

11 7

1 4 5

1 5 9

1 7 2

1 9 2

2 2 5

2 4 7

2 7 0

2 8 6

1 h

9 8 . 0

11 4

1 2 5

1 3 8

1 5 2

1 6 5

1 7 4

1 8 6

1 9 1

2 h

8 3 . 4

9 3 . 3

1 0 3

11 0

11 6

1 2 1

1 2 6

1 2 9

1 3 2

3 h

7 0 . 0

7 7 . 1

8 3 . 0

8 7 . 6

9 2 . 0

9 4 . 5

9 6 . 3

9 8 . 0

1 0 0

5 h

5 1 . 8

5 6 . 2

5 9 . 9

6 1 . 3

6 2 . 5

6 3 . 7

6 4 . 8

6 6 . 2

6 9 . 6

8 h

3 7 . 1

3 9 . 4

4 1 . 2

4 2 . 5

4 3 . 1

4 3 . 8

4 4 . 5

4 5 . 2

4 6 . 0

1 0 h

3 0 . 6

3 2 . 4

3 3 . 7

3 4 . 3

3 5 . 0

3 6 . 1

3 6 . 8

3 7 . 5

3 8 . 2

F. V / T i m e

1 . 9 0 V

1 . 8 7 V

1 . 8 5 V

1 . 8 3 V

1 . 8 0 V

1 . 7 5 V

1 . 7 0 V

1 . 6 5 V

1 . 6 0 V

1 0 m i n

2 4 8

3 3 1

3 7 6

4 3 3

4 7 8

4 9 8

5 3 5

6 1 3

6 5 4

1 5 m i n

2 4 2

3 11

3 4 6

3 8 1

4 3 5

4 7 0

5 1 0

5 6 5

6 0 7

3 0 m i n

2 2 7

2 7 7

3 0 0

3 2 0

3 5 4

4 1 0

4 4 4

4 7 6

4 9 5

1 h

1 9 2

2 2 1

2 3 8

2 6 0

2 8 3

3 0 4

3 1 7

3 3 2

3 3 7

2 h

1 6 5

1 8 2

1 9 9

2 1 0

2 1 9

2 2 5

2 3 1

2 3 5

2 3 6

3 h

1 3 9

1 5 2

1 6 2

1 6 9

1 7 5

1 7 7

1 7 9

1 8 0

1 8 1

5 h

1 0 4

11 2

11 8

11 9

1 2 0

1 2 1

1 2 2

1 2 3

1 2 4

8 h

7 4 . 6

7 8 . 7

8 1 . 7

8 3 . 4

8 3 . 6

8 4 . 0

8 4 . 5

8 4 . 9

8 5 . 6

1 0 h

6 1 . 9

6 4 . 9

6 6 . 9

6 7 . 5

6 8 . 2

6 9 . 4

7 0 . 2

7 0 . 8

7 1 . 4

Capacity OPzV350 Final Voltage

C20(Ah)

C24(Ah)

C48(Ah)

C72(Ah)

C100(Ah)

C120(Ah)

C240(Ah)

378

385

403

420

438

445

455

1.80V

1.85V

Over voltage disconnect: 2.45±0.01V/cell

Regulation/equalize voltage:

Array reconnection voltage:

Float voltage setting:

Low voltage alarm voltage:

Low voltage disconnect:

Load reconnect voltage:

Temp. compensate coefficient:

2.40±0.01V/cell

2.25±0.005V/cell

2.27±0.005V/cell

1.90±0.005V/cell

1.95±0.005V/cell

2.09±0.01V/cell

-5mV/cell/°C

Voltage value@ 20~25°C

Solar & Wind applications parameters settings

FINAL VOLTAGE SETTINGS RECOMMENDED ACCORDING TO THE DISCHARGE CURRENT

Discharge Currentl(A)

Final of Voltage

I<0.05C 0.05C ≤ I<0.08C 0.08C ≤ I<0.2C 0.2C ≤ I <0.6C 0.6C ≤ I<1.0C 1C≤I ≤ 2C

≥1.90 Vpc ≥1.85 Vpc ≥1.80 Vpc ≥1.75 Vpc ≥1.7 Vpc ≥1.6 Vpc

Parameters settings

EDIT

ION 2016

ADD:No.18,Keji Road,Science&Technology Industry Zone,Ninghai,Zhejiang,China,315600

Tel:+86-574-88111982 Fax:+86-574-56655050

E-mail:

Http://www.sbb-battery.com

sale@sbb-battery.com

ADD:No.18,Keji Road,Science&Technology Industry Zone,Ninghai,Zhejiang,China,315600

Tel:+86-574-88111982 Fax:+86-574-56655050

E-mail:

Http://www.sbb-battery.com

sale@sbb-battery.com

Temperature vs Float Life

Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.Sunbright Power Co.,LTD.

Charge Characteristic

0

20 0.02

60

40

0 3

95

110

80

(CA) (V/Cell)

126 15 18

80%Discharge

Charge Current

Time (hour)

0

2.40

2.20

2.00

1.80

Charg

eC

apacit

y

Charg

eC

urr

ent

Charg

eVolt

age

50%Discharge

(%) oConstant Charge At 0.15CA-2.40V (20 C)

0.05

0.10

0.15

9

Charge Capacity

ChargeVoltage

Discharge Characteristic(20℃)

Dis

charg

e V

oltage (

V/C

ell)

Min Hour

1CA

0.25CA0.55CA0.1CA 0.05CA

2.17

2.00

1.83

1.67

1.60

1.33

0 2 6 12 30 60 3 10 20

2.25V/Cell

25

20

10

5

0

Life

(years

)

Temperature ( )oC

10 20 30 40 50

Self Discharge Characteristucs

Storage time : months

201812 1610 148642

Capaci

ty (

%)

0

20

40

60

80

100

120

o40 C o30 C

o20 C

o10 C

Cyde Life vs Depth of Discharge

10 20 30 40 9050 60 70 80 100

1000

2000

3000

4000

5000

6000

0

Depth of discharge(%)

Cycl

e life

Capacity vs Temperature

Temperature (°C)

Capacit

y (%

)

0

20

40

60

80

100

120

-20 -10 0 10 20 30 40 50

Charge Voltage Capacity vs Temperature

-10-20

2.20

2.10

2.30

2.40

2.50

100

Float Voltage

20

2.60

4030

Temperature(°C)

50

Charg

e V

olt

age(V

) Equalize Voltage

Charge Capacity vs Time

100

90

80

70

60

50

40

30

20

10

0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Charge time(hours)

Available

capacit

y(%

) 25% DoD 50% DoD 75% DoD 100%DoD

Charge Condition:1.Charge voltage: 2.35Vpc2.Charge current: I10

3.Ambient temperature: 25°C

2V TUBULAR GEL SERIES VRLA BATTERY

OPzV350(2V350Ah)

top related