Gas Insulated Substations (GIS) Pathway for future Expansion
BY SUDIPTO BASAK Senior operations of f icer Hindustan petroleum corporation l imited
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
2
-
Overview on Conventional
Switchgears Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
3
A:Primary power lines' side B:Secondary power lines' side
1.Primary power lines 2.Ground wire 3.Overhead lines 4.Lightning arrester
5.Disconnect switch 6.Circuit breaker 7.Current transformer 8.Voltage
Transformer 9.Main transformer 10.Control building 11.Security fence
12.Secondary power lines
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
4
-
SF6 The gas that revolutionised Switchgear Technology Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
5
SF6 Properties Inert
Non Toxic
Colourless
Odourless
Non Flammable
The Edge SF6 has 2-3 times the insulating ability of air at the same pressure. SF6 is about 100 times better than air for interrupting arcs.
Minimum Clearance
Levels reduced
Sulphur
Hexaflouride
-
Minimum Clearance Level
Comparison AIS Vs GIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
6
132 KV 220 KV 400 KV 765 KV
AIS GIS (145KV)
AIS GIS (245KV)
AIS GIS (420 KV)
AIS GIS (800KV)
Mini.
Clearance
B/W Ph-Ph
1.22
0.37 2.06 0.46 4.0 0.66 7.6 0.81
Diff. in
clearance
with Next
Voltage
Level
0.84 0.09 1.94 0.20 3.6 0.15 - -
All in meters
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
7
-
Concept & Overview -GIS
A gas-insulated substation (GIS) is a substation in which the insulating medium between the phases and between the phase and earth is SF6
Gas insulated substations originated in various countries between 1968 and 1972 where there is a major need to develop technology that would allow substations to be made as compact as possible. After about 5 years of experience, the use rate increased to about 20% of new substations in these countries.
Different dielectric mediums are used in electrical equipment like Air , oil, Vacuum and SF6. In GIS, all the bus bars, breakers, isolating switches earth switches, CT, PT are immersed in SF6.
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
8
-
All Bay Functions in 1 Module Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
9
GIS MODULE Combined disconnector &
earthing switch
Current Transformers
Potential Transformers
Circuit Breakers
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
10
-
Design of Components
o Circuit Breakers
GIS uses essentially the same dead tank SF6 puffer circuit
breakers used in AIS. Instead of SF6-to-air as connections
into the substation as a whole, the nozzles on the circuit
breaker enclosure are directly connected to the adjacent GIS
module.
o Bus Bar
To connect GIS modules that are not directly connected to
each other, an SF6 bus consisting of an inner conductor and
outer enclosure is used. Support insulators, sliding electrical
contacts, and flanged enclosure joints are usually the same
as for the GIS modules.
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
11
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
12
CTs are inductive ring types installed either inside the GIS enclosure or outside the GIS enclosure.
The GIS conductor is the single turn primary for the CT. CTs inside the enclosure must be shielded from the electric field produced by the high voltage conductor or high transient voltages can appear on the secondary through capacitive coupling.
For CTs outside the enclosure, the enclosure itself must be provided with an insulating joint, and enclosure currents shunted around the CT. Both types of construction are in wide use.
Current Transformer
CURRENT TRANSFORMERS
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
13
VTs are inductive types with an iron core.
The primary winding is supported on an insulating plastic film immersed in SF6.
The VT should have an electric field shield between the primary and secondary windings to prevent capacitive coupling of transient voltages.
The VT is usually a sealed unit with a gas barrier insulator.
The VT is either easily removable so the GIS can be high voltage tested without damaging the VT, or the VT is provided with a disconnect switch or removable link
VOLTAGE TRANSFORMERS
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
14
Disconnect switches have a moving contact that opens or closes a gap
between stationary contacts when
activated by an insulating operating rod
that is itself moved by a sealed shaft
coming through the enclosure wall.
The stationary contacts have shields that provide the appropriate electric field
distribution to avoid too high a surface
stress.
The moving contact velocity is relatively low (compared to a circuit breaker
moving contact) and the disconnect
switch can interrupt only low levels of
capacitive current (for example,
disconnecting a section of GIS bus) or
small inductive currents (for example,
transformer magnetizing current).
DISCONNECT SWITCHES
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
15
Ground switches have a moving contact that opens or closes a gap between the high voltage conductor and the enclosure.
Sliding contacts with appropriate electric field shields are provided at the enclosure and the conductor.
A maintenance ground switch is operated either manually or by motor Ground switches for GIS.
A fast-acting ground switch has a high speed drive, usually a spring, and contact materials that withstand arcing so it can be closed twice onto an
energized conductor without significant damage to itself or adjacent parts.
Fast-acting ground switches are frequently used at the connection point of the
GIS to the rest of the electric power network, not only in case the connected
line is energized, but also because the fast-acting ground switch is better able
to handle discharge of trapped charge and breaking of capacitive or inductive
coupled currents on the connected line.
GROUND SWITCHES
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
16
SF6-to-air bushings are made by attaching a hollow insulating cylinder to a flange on the
end of a GIS enclosure. The insulating
cylinder contains pressurized SF6 on the
inside and is suitable for exposure to
atmospheric air on the outside.
The conductor continues up through the center of the insulating cylinder to a metal
end plate. The outside of the end plate has
provisions for bolting to an air insulated
conductor.
The insulating cylinder has a smooth interior. Sheds on the outside improve the
performance in air under wet and/or
contaminated conditions. Electric field
distribution is controlled by internal metal
shields. Higher voltage SF6-to-air bushings
also use external shields. The SF6 gas inside
the bushing is usually the same pressure as
the rest of the GIS.
AIR CONNECTION
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
17
To connect a GIS directly to a transformer, a special SF6-to-oil bushing
that mounts on the transformer is used.
The bushing is connected under oil on one end to the transformers high voltage
leads.
The other end is SF6 and has a removable link or sliding contact for connection to
the GIS conductor.
The bushing may be an oil-paper condenser type or more commonly today,
a solid insulation type. Because leakage
of SF6 into the transformer oil must be
prevented, most SF6-to-oil bushings have
a centre. section that allows any SF6
leakage to go to the atmosphere rather
than into the transformer
DIRECT TRANSFORMER CONNECTIONS
-
Design of Components Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
18
LCC local control cabinet The control and power wires of all operating mechanisms, auxillary switches,
alarms, heaters, CTs and VTs are brought from the GIS equipment modules to the LCC using shielded multiconductor control cables.
LCC has a mimic diagram of the part of the GIS being controlled. Associated with the mimic diagram are control switches and position indicators for the circuit breaker and switches.
Annunciations and Electrical interlockings are also incorporated in the LCC
Gas Monitoring System The pressure of the SF6 gas varies with temperature, so a mechanical
temperature-compensated pressure switch is used to monitor the equivalent of gas density.
GIS is filled with SF6 to a density far enough above the minimum density for full dielectric and interrupting capability so that from 10 to 20% of the SF6 can be lost before the performance of the GIS detieorates. The density alarm provide a warning of gas being lost, and can be used to operate the circuit breakers and switches to put a GIS that is losing gas into a condition selected by the user
Microprocessor based measurement systems are available that provide pressure, transmitter, density and even percentage of proper SF6 content.
LCC & GAS MONITORING SYSTEM
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
19
-
Advantages over AIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
20
LOW SPACE REQUIREMENT
-
Advantages over AIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
21
LOW SPACE REQUIREMENT
Usage of SF6 Gas brings down the minimum clearance level and makes GIS more compact
The weight and size of the GIS equipment do not change appreciably with the voltage class as bulk of the current carrying components and enclosures have identical dimensions for similar thermal and short time current
The additional insulation required for the next voltage class is achieved by increased gas density
Owing to these flexibilities, a few manufacturers offer the same equipment for two voltage classes.
Even when the GIS equipment is designed for an individual voltage class, the dimensions and weights of the equipment differ marginally.
Rated Voltage 145 KV 170 KV 245 KV
Bay Width, m 1.5 2.0 2.0
Bay Depth, m 3.3 3.35 3.4
Bay Height, m 3.2 3.4 3.4
Floor Area, Sq. m 4.95 6.7 6.8
Volume, m3 15.84 22.78 23.12
Weight, Kg 3800 5000 5700
Floor Landing, Kg/Sq. m 765 750 840
-
Advantages over AIS
Experience has shown that the internal parts of GIS are so well protected inside the metal enclosure that they do not
age and as a result of proper material selection and
lubricants, there is negligible wear of the switch contacts.
GIS will not need to be opened for maintenance.
The external operating mechanisms and gas monitor systems should be visually inspected, with the frequency
of inspection determined by experience.
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
22
LOW MAINTENANCE
-
Advantages over AIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
24
LOW TRANSPORT & INSTALLATION COST
A large number of versions are small enough to be
transported in containers or on trucks with phases open
spread open for quick installation, thus saving on transport
cost and installation times.
-
Advantages over AIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
25
Operation at Low temperatures
GIS performs perfectly in harsh climates, even under snow and ice loads, or at temperatures down to -60C with pure SF6. This is due to the well covered movable parts that are mechanically protected against the influence of heavy snow and ice-loads. Additionally these can be provided with a thermostat driven heating mechanism.
Operation in Hazardous areas
GIS performs perfectly in environments filled with corrosive and harmful chemicals as the movable parts are enclosed under sealed containers. It is ideal for use in the presence of highly inflammable gases because of the perfect sealing of sparks and arcs. This makes it ideal of petrochemical installations
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
26
-
Major Suppliers
SrNo. Name of the
company
Product Range Product
Name
1 GE 72.5 800 KV XD
2 SIEMENS 72.5 800 KV 8D RANGE
3 HYOSUNG 25.8 800 KV HICO
4 ABB 72.5 1200 KV ENK-ELK
5 ALSTOM 72.5 800 KV F35-T155
6 CG 72.5 145 KV GT01
7 SEL ELECTRIC 7.2 40.5 KV TPR6
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
27
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
28
-
Life Cycle cost analysis of
GIS & AIS
Life Cycle cost of HV Substation
Cost of Acquisition
Cost of Operation
Renewal Cost
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
29
-
Composition of Cost Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
30
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
AIS GIS
Composition of Cost 145 KV H-Arrangement
System Cost Ground Acquisition Costs Scheduled Maint Cost
Unscheduled Maint Cost Replacement of Equipment
Cost of
Acquisition
Cost of
Operation
Renewal
Cost
Cost of
Acquisition
Cost of Operation
Renewal Cost
-
Life Cycle cost analysis of
GIS & AIS Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
31
LIFE CYCLE COST AIS GIS
Planning and Engineering 100% 80%
Real Estate 100% 40%
Primary Equipment 100% 120%
Secondary Equipment 100% 100%
Earthwork, civil work, Structures 100% 60%
Electrical Assembly and Erection 100% 70%
Maintenance 100% 50%
Outage 100% 50%
Life Cycle costs after 10 Years 100% 71%
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
32
-
Further Advancement in
GIS Technology
Gas Insulated Transformers
SMART GIS Integrated Electronic CTs and PTs
Combined earthing switch and disconnector
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
33
FOR FURTHER SPACE REDUCTION
-
Flow of the Presentation
Conclusion
Advancement in GIS Technology
Life Cycle cost analysis of GIS & AIS
Major Suppliers in India for GIS
Advantages over conventional Substations
Design of Gas Insulated Substations
Concept and overview of Gas Insulated Substations
SF6 The gas that revolutionized the switchgear technology
Overview on Conventional substation
Gas insulated Switchgears - Pathway for future expansions, By Sudipto Basak
34
-
Conclusion
Even though the equipment cost of GIS is higher than that of AIS due to the grounded metal enclosure, the low space requirement, the high degree of factory assembly, the lower erection, commissioning and maintenance cost makes it more cost effective in the long run.
Also with increase in system voltage AIS take very large areas because of the long insulating distances in atmospheric air. Cost comparisons of GIS projected that, on a total installed cost basis, GIS costs would equal AIS costs at 345 kV. For higher voltages, GIS was expected to cost less than AIS.
Due to its superior operational advantages like error free control by
LCC, insulation from corrosive and inflammable environment and higher seismic qualification due to lower centre of gravity and high compactness it becomes a better product over AIS in sensitive and hazardous location like those of petrochemical and oil & gas industries.
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
35
-
Bibliography
IEEE Guide for Gas-Insulated Substations, IEEE Std. C37.122.1-1993. IEEE Standard for Gas-Insulated Substations, IEEE Std. C37.122-1993. IEC 517: 1990, Gas-insulated metal-enclosed switchgear for rated voltages of 72.5 kV and
above (3rd ed.).
IEEE Guide for Moisture Measurement and Control in SF6 Gas-Insulated Equipment, IEEE Std. 1125-1993
IEC 1634: 1995, IEC technical report: High-voltage switchgear and controlgear use and handling of sulphur hexafluoride (SF6) in high-voltage switchgear and controlgear.
User guide for the application of gas-insulated switchgear (GIS) for rated voltages of 72.5 kV and above, CIGRE Report 125, Paris, April 1998.
Operating experience of gas-insulated switchgear (GIS) and its influence on the future substation design, Paper 23-04 of CIGRE General Meeting, Paris, 1982.
Paper on Modern Subterranean Substations in GIS Technology by Bert Strassburger (Siemens)
Paper on Gas Insulated Substations by R.Rajmohan (East Coast Energy Ltd) Article on Substations that embellish not blemish the streetscape from November 2009
issue of Living Energy Journal
High Voltage GIS by M/s ABB Substation life cycle cost management supported by Stochastic optimization algorithm, by
Martin Hinow - ETH-Zurich (Switzerland), Mark Waldron National Grid (UK), Dr. Lorenz Muller-ABB(Switzerland), Heinz Aeschbach, Karsten Pohlink, Areva T&D AG (Switzerland)
Gas insulated Switchgears - Pathway for future expansions, By Sudipto
Basak
36
-
THANK YOU QUESTIONS PLEASE..