module 4 understanding energy effeciency provisions class 2 to 9

Post on 10-Jun-2015

451 Views

Category:

Education

5 Downloads

Preview:

Click to see full reader

DESCRIPTION

This training module is one of a series produced by the Australian Building Codes Board; the organisation responsible for the development and maintenance of the National Construction Code (NCC) For the purposes of this presentation it is assumed that participants have a general understanding of the content of ABCB training Modules One and Two

TRANSCRIPT

National Construction CodeTraining Program

MODULE FOURUnderstanding Energy

Efficiency Provisions for Class 2 to 9 Buildings

Introduction to Module Four

• This training module is one of a series produced by the Australian Building Codes Board; the organisation responsible for the development and maintenance of the National Construction Code (NCC)

• For the purposes of this presentation it is assumed that participants have a general understanding of the content of ABCB training Modules One and Two

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Building Code

Volume ThreeGuide to

Volume OneVolume OneAppendices

Volume TwoVolume One

PlumbingCode

National Construction Code Series

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Recap on Module One

• Module One was titled: An Introduction to the Building Code of Australia – Volume One and Two of the NCC Series

• The object of Module One was to provide information on-− the background to the development of the BCA − the operation of the BCA, and− the application of the BCA

Scope of the BCAIntroduction to Module 4 Methods of Compliance

The Building Code of Australia

• The BCA established minimum standards for new building work• The BCA:

− Is referenced in State /Territory law – see next slide− Is amended annually

− Requirements are intended to be cost effective

− Requirements are intended to eliminate poor practice

− Does not address best practice

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Scope of the BCAIntroduction to Module 4 Methods of Compliance

STATE & TERRITORY BUILDING ACTS

STATE & TERRITORY BUILDING REGULATIONS

TECHNICAL STANDARDS

ADMINISTRATIVE MATTERS• Approvals• Appeals• Registrations• Refurbishments• Building standard

Presentation of the BCA

• The BCA is presented in two Volumes• This is to correlate with the historic division of the building

industry

• In general, industry tends to work in either the housing sector or the commercial sector, although some large companies work in both sectors

• The BCA endeavours to follow this division

Scope of the BCAIntroduction to Module 4 Methods of Compliance

BCA Volumes One and Two

• Volume One contains requirements for the design and construction of commercial buildings; i.e. Class 2 to 9 buildings, plus some Class 10 structures

• Volume Two contains requirements for the design and construction of domestic buildings; i.e. Class 1 and 10 buildings, plus some Class 10 structures

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Recap on Module Two

• Module Two was titled: Understanding the BCA’s Performance Requirements

• The object of Module Two was to provide information on how to comply with the BCA without using Deemed-to-Satisfy Provisions – i.e. by developing an Alternative Solution which complies with the relevant Performance Requirements.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Recap on Module Two

• Volume One contains ten sections, which are identified alphabetically, i.e. Sections A to J

• The general structure and operation of the BCA is presented at Section A, which is titled ‘General Provisions’

• Section B to J contain mandatory technical requirements, which are expressed as Performance Requirements, and optional means of compliance with the Performance Requirements. These are expressed as Deemed-to-Satisfy Provisions

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Objective of Module Four

• The objective of Module Four is to provide fundamental information on BCA energy efficiency provisions relating to Class 2 to 9 buildings; i.e. multi-storey residential buildings and other commercial buildings

• The information provided in this presentation relates to the national content of the BCA and does not address State or Territory variations

Scope of the BCAIntroduction to Module 4 Methods of Compliance

BCA Energy Efficiency

BCA requirements aim to reduce the use of energy from electricity, gas, oil, or other fuels used in buildings for:

• Heating• Cooling • Ventilation • Artificial lighting • Hot water (heating and sanitary)• Other services

Scope of the BCAIntroduction to Module 4 Methods of Compliance

BCA Requirements

• The BCA only addresses energy used by a building's services to operate

• Does not include energy used in manufacturing building materials or the construction of a building (i.e. embodied energy).

• Does not include portable appliances within a building such as computers or fridges

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Background

Scope of the BCA

Methods of Compliance

Module Four

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Module Four

• Principles of Energy Efficiency• General Scope of BCA Provisions• Performance Requirements• Deemed-to-Satisfy Provisions• Alternative Solutions• Verification Methods• Administrative Matters

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Background toEnergy Efficiency Provisions

General Background

• Over the past decade international awareness of greenhouse gas (GHG) emissions and their influence on global warming has grown significantly

• GHG is a natural part of Earth’s atmosphere that captures the Sun’s warmth to keep Earth’s surface temperature at a life supporting level

Scope of the BCAIntroduction to Module 4 Methods of Compliance

• Increased concentrations of GHG will cause variations to our climate that will differ between geographic regions

• Changes may occur to temperatures, rainfall, wind speed, vegetation and animal life

• GHG emissions are increasing due to human activities such as land clearing and burning fossil fuel (e.g. coal and oil)

Scope of the BCAIntroduction to Module 4 Methods of Compliance

General Background

• 1997 – the Prime Minister issued a statement on Australia’s response to global warming that included measures to reduce energy consumption in buildings

• The building sector was not the largest contributor to national GHG emissions - although it contributed 27% of energy related GHG emissions and was the fastest growing source

• Late 1990’s - governments considered the need for new buildings to operate in an energy efficient manner

Scope of the BCAIntroduction to Module 4 Methods of Compliance

National Background

• It was apparent that market forces had not addressed the issue effectively so there was a need for regulatory reform

• Industry generally supported the need to eliminate worst practice in building design

• 2000 – Agreement by the Council of Australian Governments (COAG) to introduce energy efficiency regulations for domestic and commercial buildings

Scope of the BCAIntroduction to Module 4 Methods of Compliance

National Background

National Background

• 2001 – In response, the Australian Greenhouse Office (AGO) and the ABCB entered into an agreement to develop energy efficiency provisions and introduce these through the BCA

• 2001- 2002 - Housing energy efficiency provisions developed• January 2003 - BCA Volume Two introduced 4 star energy

efficiency provisions in climate zones 4 to 8 and 3.5 star in climate zones 1 to 3 for housing and associated buildings

• Some States/Territories had existing provisions in place and did not adopt new BCA requirements

Scope of the BCAIntroduction to Module 4 Methods of Compliance

• BCA 2005 − Introduced the same star level requirements for Class 2 and 3

buildings and Class 4 parts as for housing , i.e. SOU’s must achieve a minimum of 3 stars, but achieve a 4 star average in climate zones 4 to 8 and 3.5 star average in climate zones 1 to 3.

• BCA 2006

− Introduced requirements for Class 5 to 9 buildings

− Enhanced requirements for Class 1 and nominated Class 10a buildings from 3.5 / 4 star to 5 star

Scope of the BCAIntroduction to Module 4 Methods of Compliance

National Background

• BCA 2010

− Enhanced the requirements for Class 5 to 9 buildings

− Further enhanced the requirements for Class 1 and nominated Class 10a buildings from 5 star to 6 star

− Also enhanced requirements for Class 2 buildings and Class 4 parts of a building (average 6 star, minimum 5 star)

Scope of the BCAIntroduction to Module 4 Methods of Compliance

National Background

What is a House Star Rating?

Scope of the BCAIntroduction to Module 4 Methods of Compliance

• A house star rating is a quantified benchmark used to describe the energy efficiency performance of a building’s fabric based on an annual energy load

• The rating is used in the BCA and is derived using computer software packages: AccuRate, BERS and Firstrate

• It should not be confused with a Greenstar rating which is a sustainability system and includes water etc

Draft Provisions

• Originally developed through stakeholder committees, specialist working groups and specialist consultants

• Proposals were refined through industry and community consultation

• Draft provisions were subject to a formal Regulation Document process and Regulatory Impact Statement process

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Regulatory Impact Statement

• Under an IGA, the ABCB must only propose new regulation as a final option

• All proposals for change to the BCA must be subjected to a rigorous regulatory impact assessment process that includes cost benefit analysis

• The new regulation must generate the greatest net benefit for the community

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Four Stage Process

• Using a four stage process, the ABCB has now introduced energy efficiency requirements for all classes of buildings− 2003 - Class 1 & 10 (4 star / 3.5 star)− 2005 - Class 2 to 4 (4 star / 3.5 star average – 3 star

minimum)− 2006 - Class 5 to 9; plus

- Class 1 & 10 enhanced (Verification 5 star)− 2010 - Class 3 and 5 to 9 enhanced; and

- Class 2 and 4 (6 star average – 5 star minimum)- Class 1 & 10 (6 star)

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Voluntary Best Practice

• The Department of Climate Change and Energy Efficiency (DCCEE) has also developed a series of other programs - aimed at assisting designers to go beyond the minimum requirements of the BCA

• These programs promote voluntary best practice rather than BCA minimum requirements

• Information can be found at: www.climatechange.gov.au

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Principles of Energy Efficiency

Objective of BCA Provisions

• The objective of the BCA energy efficiency provisions is to reduce GHG emissions by reducing the operational energy use of buildings without reducing comfort and amenity

• BCA requirements primarily address: − heat flow - in and out of a building through the building

envelope, and− services - that use energy e.g. air-conditioning, hot water and

lighting

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Definition of Envelope

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Envelope, means the parts of a building’s fabric that separate a conditioned space or habitable room from –(a) the exterior of the building; or(b) a non-conditioned space including – (i) the floor of a rooftop plant room, lift-machine room or the like; and (ii) the floor above a carpark or warehouse; and (iii) the common wall with a carpark, warehouse or the like.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

= Walls of the building envelope General office: The external walls, roof and floor above a carpark bounding the general office are treated as part of the building envelope under the BCA definition because all rooms are conditioned.Corridor: This area is also inside the envelope because it is conditioned.

Plant Room

General Office (Conditioned)

Private Office

Access Stair

General Office (Conditioned)

Public Corridor (Conditioned)

Definition of Envelope

Definition of Service

Service, for the purposes of Part I2 and Section J, means a mechanical or electrical system that uses energy to provide air-conditioning, mechanical ventilation, hot water supply, artificial lighting, vertical transport and the like within a building, but which does not include –

(a) systems used solely for emergency purposes; and

(b) cooking facilities; and

(c) portable appliances

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Principles of Energy Efficiency

• The efficient performance of the building envelope plus the efficient operation of building services results in reduced - − demand for a service, i.e. in moderate climate zones, − size of a service, − operating time of a service, and− energy consumption of the service

• The use of fuels with the lowest practical greenhouse gas intensity

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Application of Requirements

• Not all of Australia has the same climate so the BCA elemental Deemed-to-Satisfy Provisions vary across eight (8) climate zones

• Climate zone 1 is hot and humid while climate zone 8 is cold• A map of the location of the various climate zones is provided as

Figure A1.1 – see next slide

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Climate Zone MapFigure A1.1

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Individual State and territory maps are available on the ABCB website at:

http://www.abcb.gov.au

Climate Zone Map

Application of Requirements

• The primary intent of the BCA provisions is to reduce energy required for cooling services in warmer climate zones and heating services in cooler climate zones

• The extent of specific requirements will generally vary depending on the use of the building and the climate zone in which it is located

Scope of the BCAIntroduction to Module 4 Methods of Compliance

General Scope of BCA Provisions

Sections of Volume One

• Energy efficiency provisions are primarily governed by the content of Section A and Section J of Volume One

• Section A – General Provisions – presents the general rules by which BCA is applied and is addressed in detail in Module One

• Section A also contains Part A1 – Interpretation, which presents defined terms within the BCA

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Section J – Energy Efficiency

• Section J presents both the mandatory Performance Requirements and the optional Deemed-to-Satisfy Provisions for energy efficiency in Class 2 to 9 buildings

• While compliance with the Deemed-to-Satisfy Provisions is optional, the main benefit of following this form of Building Solution is the certainty of compliance with the mandatory Performance Requirements

Scope of the BCA Methods of ComplianceIntroduction to Module 4

• Defined terms specific to the energy efficiency provisions are presented on the following slides

• BCA users should not assume the meaning of new terms and should refer to the definitions until familiar with the energy efficiency provisions

Scope of the BCA Methods of Compliance

Relevant Defined Terms

Introduction to Module 4

Relevant Defined Terms

• Air-conditioning

• Climate zone

• Conditioned space

• Envelope

• Fabric

• Fan power

• Glazing

• Illuminance

Scope of the BCA Methods of Compliance

• Illumination power density

• Lamp power density

• Latent heat gain

• Light source efficacy

• Outdoor air economy cycle

• Piping

• Pump power

• R-Value

Introduction to Module 4

Relevant Defined Terms

Scope of the BCA Methods of Compliance

• Reference building

• Reflective insulation

• Renewable energy

• Roof light

• Sensible heat gain

• Service

• Solar Heat Gain Coefficient

• Thermal calculation method

• Total R-Value

• Total U-Value

Introduction to Module 4

Energy EfficiencyPerformance Requirements

Performance Requirements

• There are three mandatory Performance Requirements for energy efficiency:− JP1 - requires a building & its services to have features that

facilitate the efficient use of energy

− JP2 - requires a building, including its services, to have features that facilitate the maintenance of systems and components appropriate to the function and use of the building

− JP3 - requires services to use energy from low greenhouse emitting sources where possible

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Performance Requirement JP1

Introduction to Module 4 Scope of the BCA Methods of Compliance

Performance Requirement JP2

Introduction to Module 4

Remember this definition?

Scope of the BCA Methods of Compliance

Performance Requirement JP3

Introduction to Module 4 Scope of the BCA Methods of Compliance

Energy EfficiencyDeemed-to-Satisfy Provisions

Parts of Section J

Part J0 – Energy EfficiencyPart J1 – Building FabricPart J2 – Glazing Part J3 – Building SealingPart J5 – Air-Conditioning and Ventilation SystemsPart J6 – Artificial Lighting and PowerPart J7 – Hot Water Supply & Pool & Spa PlantPart J8 – Access for Maintenance & Monitoring Facilities

Introduction to Module 4 Scope of the BCA Methods of Compliance

Specifications

• Section J also has eight Specifications –Spec JV – Annual Energy Consumption CriteriaSpec J1.2 – Material PropertiesSpec J1.3 – Roof and Ceiling ConstructionSpec J1.5 – Wall ConstructionSpec J1.6 – Floor ConstructionSpec J5.2 – Ductwork Insulation and SealingSpec J5.4 – Insulation of Piping, Vessels etcSpec J6 – Lighting and Power Control Devices

Introduction to Module 4 Scope of the BCA Methods of Compliance

• Seven of the Specifications provide detailed information on components of the Deemed-to-Satisfy Provisions and must be satisfied in order to comply with the Deemed-to-Satisfy Provisions

• Alternative Solutions can be developed as another option to compliance instead of any aspect of Deemed-to-Satisfy Provisions

Introduction to Module 4

Specifications

Scope of the BCA Methods of Compliance

PART J0ENERGY EFFICENCY

Introduction to Module 4 Scope of the BCA Methods of Compliance

Part J0

Introduction to Module 4

• For apartments – House energy rating solution

− Energy rating− J0.3 for ceiling fans− Specific J1 provisions for materials & construction− J3 for sealing− J5, J6, J7 and J8 for services

• For other areas & all other buildings

− J1 to J8

Scope of the BCA Methods of Compliance

PART J1BUILDING FABRIC

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J1

• To regulate the performance of the building fabric in order to reduce heat gain and heat loss

• To reduce the need for thermal conditioning of spaces within buildings

Introduction to Module 4 Scope of the BCA Methods of Compliance

Definition of Fabric

• In essence, the fabric is a general description of the primary building elements that form the envelope

• Note that the BCA definition of fabric does not include glazing

Introduction to Module 4 Scope of the BCA Methods of Compliance

Application of Part J1

• Part J1 applies to building elements forming the envelope of a Class 2 to 9 building other than-

− a Class 7, 8 or 9b building that does not have a conditioned space, or

− an atrium or solarium that is not a conditioned space and is separated from the remainder of the building by an envelope.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Thermal Construction

• Specific parts of a building's envelope need to be insulated if they do not have thermal properties required for the climate zone in which the building is located

• Insulation must be installed to form a consistent and continuous barrier in conjunction with building members

• Gaps in the barrier allow heat in or out and reduce the efficiency of the barrier

Introduction to Module 4 Scope of the BCA Methods of Compliance

• R-Value – means the thermal resistance (m2. K/W) of a component calculated by dividing its thickness by its thermal conductivity

• In essence – the R-Value represents the ability of a material to resist heat flow

Introduction to Module 4

Other Important Terms

Scope of the BCA Methods of Compliance

• Total R-Value – means the sum of the R-Values of individual components in a composite element including any building material, insulating material, air space and associated surface resistances

Introduction to Module 4

Other Important Terms

Scope of the BCA Methods of Compliance

Thermal Insulation

Thermal insulation must –• comply with AS/NZS 4859.1; and• be installed to form a consistent and continuous barrier, other

than at studs etc, in accordance with the BCA’s and manufacturer’s requirements.

Thermal insulation may be either reflective insulation or bulk insulation

Introduction to Module 4 Scope of the BCA Methods of Compliance

Thermal Insulation

Thermal insulation needs to be installed so that –• Any required air space is provided adjacent to the reflective surface

of reflective insulation

• The thickness of bulk insulation is maintained as compression of insulation material can reduce the R-Value

• Note: Consideration needs to be given to the risk that artificial cooling or heating of internal spaces may promote condensation within adjoining elements.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Specification J1.2

Introduction to Module 4 Scope of the BCA Methods of Compliance

ROOFS

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Direction of Heat Flow

• The direction of heat flow that needs to be counteracted will depend on the climate zone

• The direction of heat flow is the dominant direction during typical hours of occupation of the building

Introduction to Module 4 Scope of the BCA Methods of Compliance

Roof & Ceiling Construction

• Must achieve the minimum Total R-Value specified in Table J1.3a for the direction of heat flow

• Some reductions apply to some buildings in selected climate zones

• Specification J1.3 presents the thermal performance of some common forms of (uninsulated) roof and ceiling construction.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Extract of Table J1.3a

Introduction to Module 4

Table J1.3a ROOFS AND CEILINGS – MINIMUM TOTAL R-VALUE FOR EACH CLIMATE ZONE

Climate Zone1, 2, 3, 4 and 5

6 7 8

Direction of heat flow Downwards Upwards

Minimum Total R-Value for a roof or ceiling with a roof upper surface absorptance value of not more than 0.4

3.2 3.2 3.7 4.8

Minimum Total R-Value for a roof or ceiling with a roof upper surface absorptance value of not more than 0.6

3.7 3.2 3.7 4.8

Minimum Total R-Value for a roof or ceiling with a roof upper surface absorptance value of more than 0.6

4.2 3.2 3.7 4.8

Scope of the BCA Methods of Compliance

Typical Absorptance Values

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Colour Value

Slate (dark grey) 0.90

Red, green 0.75

Yellow, buff 0.60

Zinc aluminium — dull 0.55

Galvanised steel — dull 0.55

Light grey 0.45

Off white 0.35

Light cream 0.30

Total R-Value

• Certain roofs with metal framing and cladding require a thermal break to be installed.

• As more downlights and fans are installed in a ceiling, the loss of insulation must be compensated for by increasing the R-Value of insulation in the remainder of the ceiling – See Table J1.3b

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Downlights Clearance

Scope of the BCAIntroduction to Module 4 Methods of Compliance

ROOF LIGHTS

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Roof Lights

• Thermal performance of roof lights is specified in Table J1.4 in terms of maximum SHGC and Total U-Value

• The application of the Table depends on the area of roof lights as a percentage of the floor area of the room or space served by the roof light

Introduction to Module 4 Scope of the BCA Methods of Compliance

Table J1.4 ROOF LIGHTS -THERMAL PERFORMANCE OF TRANSPARENT AND TRANSLUCENT ELEMENTS

Total area of roof lights serving the room or space as a percentage of the floor area of the room or space Roof light shaft

index (see Note 1) Up to 2%

More than 2% and up to 3%

More than 3% and up to 4%

More than 4% and up to 5%

Less than 0.5

SHGC of not more than 0.83 and a Total U-Value of not more

than 8.5

SHGC of not more than 0.57 and a Total U-Value of not more

than 5.7

SHGC of not more than 0.43 and a Total U-Value of not more

than 4.3

SHGC of not more than 0.34 and a Total U-Value of not more

than 3.4

0.5 to less than 1.0

SHGC of not more than 0.83 and a Total U-Value of not more

than 8.5

SHGC of not more than 0.72 and a Total U-Value of not more

than 5.7

SHGC of not more than 0.54 and a Total U-Value of not more

than 4.3

SHGC of not more than 0.43 and a Total U-Value of not more

than 3.4

1.0 to less than 2.5

SHGC of not more than 0.83 and a Total U-Value of not more

than 8.5

SHGC of not more than 0.83 and a Total U-Value of not more

than 5.7

SHGC of not more than 0.69 and a Total U-Value of not more

than 4.3

SHGC of not more than 0.55 and a Total U-Value of not more

than 3.4

2.5 and above

SHGC of not more than 0.83 and a Total U-Value of not more

than 8.5

SHGC of not more than 0.83 and a Total U-Value of not more

than 5.7

SHGC of not more than 0.83 and a Total U-Value of not more

than 4.3

SHGC of not more than 0.83 and a Total U-Value of not more

than 3.4

Introduction to Module 4 Scope of the BCA Methods of Compliance

WALLS

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Walls

• As with roofs, the construction of external walls is a major factor in the thermal efficiency of a building

• External walls are generally required to achieve a minimum Total R-Value, with or without other features

• Concessions to the minimum Total R-Value are provided for specified conditions

Introduction to Module 4 Scope of the BCA Methods of Compliance

Walls

• The general requirements for the thermal performance of external walls are specified in Table J1.5a

• The general requirements for the thermal performance of internal walls are specified in Table J1.5b

• Exceptions apply to nominated elements and openings

Introduction to Module 4 Scope of the BCA Methods of Compliance

• Requirements relate to climate zones and are expressed in Table J1.5a in terms of – − minimum Total R-Value

− minimum surface density (weight of 1 m2 of wall)− incorporation of a cavity− shading projections− specific glazing energy index options− wall orientation and solar absorptance

Introduction to Module 4

External Walls

Scope of the BCA Methods of Compliance

• Options are available in certain climate zones if more demanding glazing requirements are met

• Thermal breaks need to be provided in certain metal framed lightweight walls with a single framing member in the direction of heat flow

• Specification J1.5 presents the thermal performance of some common forms of (uninsulated) external wall construction.

Introduction to Module 4

External Walls

Scope of the BCA Methods of Compliance

Table J1.5a OPTIONS FOR EACH PART OF AN EXTERNAL WALL

Climate zone Options

(a) (i) Achieve a minimum Total R-Value of 3.3.

(ii) The minimum Total R-Value in (i) is reduced-

(A) for a wall with a surface density of not less than 220 kg/m2, by 0.5; and

(B) for a wall that is-

(aa) facing the south orientation as described in Figure J2.3, by 0.5; or

(bb) shaded with a projection shade angle in accordance with Figure J1.5 of-

(AA) 15 degrees to not more than 45 degrees, by 0.5; or

(BB) more than 45 degrees, by 1.0; and

(C) if the outer surface solar absorptance value is not more than 0.6, by 0.5.

1, 2 and 3

(b) Where the only space for insulation is provided by a furring channel, top hat section, batten or the like—

(i) achieve a minimum Total R-Value of 1.4; and

(ii) satisfy glazing energy index Option B of Table J2.4a; and

Introduction to Module 4

External Walls

Scope of the BCA Methods of Compliance

• Requirements relate to climate zones and are expressed in Table J1.5b in terms of-− minimum Total R-Value− whether enclosed− amount of any mechanical ventilation− amount of glazing

Introduction to Module 4

Internal Walls

Scope of the BCA Methods of Compliance

FLOORS

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Floors

• A floor that forms part of a building's envelope must achieve the appropriate minimum Total R-Value in Table J1.6.

• A floor with an in-slab heating or cooling system must be insulated around the vertical edge of its perimeter with insulation having an R-Value of not less than 1.0. This requirement also applies if the floor is located in climate zone 8.

• In climate zones 1 to 6 – the Total R-Value for a floor can be reduced if the Total R-Value for roof and ceiling construction is increased.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Introduction to Module 4

Location

Climate zone

1 2 3 4 5 6 7 8

(a) A slab on ground-(i) without an in-slab heating or cooling system(ii) with an in-slab heating or cooling system

Nil Nil Nil Nil Nil Nil 1.0 2.0

1.25 1.25 1.25 1.25 1.25 1.25 1.25 2.25

(b) A suspended floor without an in-slab heating or cooling system and with the non-conditioned space -

(i) enclosed; and(ii) if mechanically ventilated, by not more than

1.5 air changes per hour of outside air.

1.0 1.0 Nil Nil 1.0 1.0 1.5 2.5

(c) For a suspended floor with an in-slab heating or cooling system and the non-conditioned space -

(i) enclosed; and(ii) if mechanically ventilated, by not more than

1.5 air changes per hour of outside air.

1.25 1.25 1.25 1.25 1.25 1.25 1.75 2.75

(d) For other than (a), (b) or (c) 2.0 2.0 2.0 2.0 2.0 2.0 2.0 3.5

Table J1.6 FLOOR MINIMUM TOTAL R-VALUE

Scope of the BCA Methods of Compliance

PART J2EXTERNAL GLAZING

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J2

• Good glazing design contributes to energy efficiency in buildings by – − utilising natural light − enhancing solar heat gains in southern winters− restricting heat losses in southern winters and− restricting unwanted heat gains in summer or in hotter

climates

Introduction to Module 4 Scope of the BCA Methods of Compliance

Factors Affecting Heat Transfer

• Location of the building• Total area of glazing• Type of glass and frame used• Degree of exposure to the sun – influenced by orientation to the

sun and shading• Use of air-conditioning to condition the space

Introduction to Module 4 Scope of the BCA Methods of Compliance

Two Basic Considerations

• For glazing, the BCA provisions consider two main thermodynamic effects-

− heat conduction through the glazing due to temperature differences on either side of the glazing, and

− solar radiation directly through the glazing into the building

Introduction to Module 4 Scope of the BCA Methods of Compliance

Solar Radiation Through Glass

Introduction to Module 4

Short wave radiation passes through glazing.

Heat is absorbed by interior surfaces and re-radiated.

Re-radiated long wave radiation is trapped inside the building

Scope of the BCA Methods of Compliance

Performance of Basic Glazing

• The insulated external wall has a Total R-Value of 2.8

• The wall contains 6 mm single layer clear glazing in aluminum frames

• The thermal resistance of the glazing would equate to a total R-Value of around 0.17

• Therefore the required wall insulates against heat transfer around 16 times better than basic glazing

Introduction to Module 4 Scope of the BCA Methods of Compliance

High-Rise Buildings

• The building envelope of a high-rise building will often have large glazed areas. Therefore, glazing can become the greatest source of heat transfer and air infiltration for a conditioned space.

• Also, the higher a conditioned space is located above ground level, the greater the wind pressure and the potential for air infiltration.

Introduction to Module 4 Scope of the BCA Methods of Compliance

A Definition of Glazing

• Glazing – for the purposes of Section J, means a transparent or translucent element and its supporting frame located in the envelope, and includes a window other than a roof light.

Introduction to Module 4 Scope of the BCA Methods of Compliance

• Total U-Value means the thermal transmittance (W/m2.K) of the composite element allowing for the effect of any air spaces and surface resistances.

• Solar Heat Gain Coefficient (SHGC) – means the fraction of incident irradiance on the transparent or translucent element of a glazing system that adds heat to a building’s space.

• In essence – a measure of how well the glazing system limits the heat energy of the sun – the lower the number the less energy it transmits.

Introduction to Module 4

Other Relevant Terms

Scope of the BCA Methods of Compliance

• Conductance – relates to the transfer of heat.

The rate of conductance depends on the ambient temperature either side of the glazing and Total U-Value of the glazing.

• Solar heat gain – is heat gain caused by solar radiation passing through glazing.

Depends on: − the SHGC of the glazing unit, and− its exposure to solar radiation, e.g. location, shading and

orientation

Introduction to Module 4

Other Relevant Terms

Scope of the BCA Methods of Compliance

Part J2 Deemed-to-Satisfy Provisions

Introduction to Module 4 Scope of the BCA Methods of Compliance

Application of Part J2

• Part J2 applies to building elements forming the envelope of a building other than:

− a sole-occupancy unit of a Class 2 building or Class 4 part of a building; or

− a Class 7, 8 or 9b building that does not have a conditioned space; or

− an atrium or solarium that is not a conditioned space and is separated from the remainder of the building.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Part J2.4 Glazing Calculation

Introduction to Module 4 Scope of the BCA Methods of Compliance

Glazing

• The calculation requires the assessment of glazing in each storey for each orientation

• The method requires calculation of-− allowable air-conditioning energy value; and− aggregated air-conditioning energy value

• Aggregated values must not exceed allowable values for each storey in each orientation

Introduction to Module 4 Scope of the BCA Methods of Compliance

• The calculation also requires consideration of –– the orientation – Figure J2.3– the shading projection to height dimensions (P/H) – Figure J2.4– the projection to glazing head dimensions (G) – Figure J2.4– shading details – Part J2.5

Introduction to Module 4

Glazing

Scope of the BCA Methods of Compliance

Orientation

• North orientation reduces summer sun and maximises winter sun

• A building facade, including the glazing it contains, is considered to face North if it faces any direction in the North orientation sector of Figure J2.3 – see the next slide

• The orientations of other facades, including the glazing they contain, are determined in a similar way

Introduction to Module 4 Scope of the BCA Methods of Compliance

Orientation Sectors – Figure J2.3

Introduction to Module 4 Scope of the BCA Methods of Compliance

Calculation of P/H

• Shading for a projection is expressed as P/H• Refer to Part J2.5 for shading details (projection and shading

device)• P is a horizontal measurement from the external face of the

glazing to the edge of the shading projection

• H is the vertical measurement from the glazing sill to the underside of the shading projection

Introduction to Module 4 Scope of the BCA Methods of Compliance

First floor P = 600mmH = 2300mmP/H = 0.26

Ground floor P = 1200mmH = 1400mmP/H = 0.86

FIGURE J2.4P

H

P

H

• First calculation – measure the facade area of each storey for each orientation

• Multiply each facade area by the energy index obtained from Table J2.4a

• “Option A” values apply unless “Option B” values are used to comply with J1.5

• The resulting values are the allowances for the actual design

Introduction to Module 4

Glazing

Scope of the BCA Methods of Compliance

Table J2.4a

Introduction to Module 4

TABLE J2.4a ENERGY INDEX

Climate zone Application

Energy index option 1 2 3 4 5 6 7 8

A 0.067 0.132 0.091 0.086 0.092 0.090 0.059 0.027 Class 3 and 9c building

B 0.060 0.124 0.078 0.063 0.071 0.061 0.037 Not applicable

A 0.180 0.217 0.221 0.227 0.257 0.220 0.170 0.046 Display glazing in a shop or showroom B 0.173 0.209 0.208 0.204 0.236 0.191 0.148 Not applicable

A 0.130 0.181 0.172 0.142 0.175 0.116 0.083 0.023 Glazing in other than a Class 3 or 9c building or display glazing in a shop or showroom

B 0.123 0.173 0.159 0.113 0.145 0.082 0.058 Not applicable

Note: Option A applies to all glazing other than where compliance with Option B is required by Table J1.5a.

Scope of the BCA Methods of Compliance

• Second calculation – measure the aggregated air-conditioning energy value

• Apply the required formula to each individual glazing element of a storey at each orientation – see next slide

• Add individual glazing values to achieve the aggregate air-conditioning energy value for the storey and orientation

Introduction to Module 4

Glazing

Scope of the BCA Methods of Compliance

A1 [ SHGC1 ( CA x SH1 + CB x SC1 ) + CC x U1] where;

A1 = the area of glazing element 1

SHGC1 = the SHGC of glazing element 1

CA CB CC = the energy constants A, B and C for the specific orientation from Table J2.4b

SH1 = the heating shading multiplier for glazing element 1 obtained from Table J2.4c

SC1 = the cooling shading multiplier for glazing element 1 obtained from Table J2.4d

U1 = the Total U-Value of glazing element 1

Introduction to Module 4 Scope of the BCA Methods of Compliance

• A Class 5 building in climate zone 5 has a 15m x 15m footprint and a storey height of 2.7m

• The area of each facade for each storey is 15 x 2.7 = 40.5 m2 • Energy Index from Table J2.4a for Option B in climate zone 5 is

0.145

• The allowed aggregate air-conditioning energy value for each facade of each storey is 5.87

Introduction to Module 4

Example

Scope of the BCA Methods of Compliance

• Firstly we need to calculate the aggregate air-conditioning energy value for each glazing element in each facade of a typical storey

• Each facade has three windows 2m wide x 1m high with a U-Value of 7.9 and a SHGC of 0.83 (clear in aluminium)

• Shading projection of 450 mm, 300 mm above the glazing head, i.e. P/H = 0.35

Introduction to Module 4

Example

Scope of the BCA Methods of Compliance

North Facade Calculation

A1(SHGC1 [CA x SH1+ CB x SC1] + CC x U1)

= 2 (0.83 x [-0.06 x 0.975 + 1.46 x 0.81] + -0.02 x 7.9)

= 2 (0.83 x [-0.0585 + 1.1826] + -0.158)

= 2 (0.83 x [1.124] + -0.158)

= 2 (0.933 + -0.158)

= 1.55

There are three equal windows on typical storey of North facade – so total North is 4.65

Introduction to Module 4 Scope of the BCA Methods of Compliance

East Facade Calculation

A1(SHGC1 [CA x SH1+ CB x SC1] + CC x U1)

= 2 (0.83 x [-0.18 x 0.935 + 1.32 x 0.885] + 0 x 7.9)

= 2 (0.83 x [- 0.1683 + 1.1682] + 0)

= 2 (0.83 x [0.9999] + 0)

= 2 (0.8299)

= 1.66

There are three equal windows on typical storey of East facade – so total East is 4.98

Introduction to Module 4 Scope of the BCA Methods of Compliance

South Facade Calculation

A1(SHGC1 [CA x SH1+ CB x SC1] + CC x U1)

= 2 (0.83 x [-0.47 x 0.943 + 0.41 x 0.908] + 0.07 x 7.9)

= 2 (0.83 x [-0.443 + 0.372] + 0.553)

= 2 (0.83 x [-0.071] + 0.553)

= 2 (-0.059 + 0.553)

= 0.99

There are three equal windows on typical storey of South facade – so total South is 2.97

Introduction to Module 4 Scope of the BCA Methods of Compliance

West Facade Calculation

A1(SHGC1 [CA x SH1+ CB x SC1] + CC x U1)

= 2 (0.83 x [-0.28 x 0.935 + 1.13 x 0.875] + 0.02 x 7.9)

= 2 (0.83 x [-0.262 + 0.989] +0.158)

= 2 (0.83 x [0.727] + 0.158)

= 2 (0.603 + 0.158)

= 1.52

There are three equal windows on typical storey of West facade – so total West is 4.56

Introduction to Module 4 Scope of the BCA Methods of Compliance

Summary

North Facade = 4.65

East Facade = 4.98

South Facade = 2.97

West Facade = 4.56

The allowance for each facade of each storey is 5.87 so the proposed design complies with Part J2.4 as the value for each facade is less than the allowance.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Glazing Calculators

• The ABCB has developed spreadsheet calculators to assist in designing and checking the glazing for both residential and commercial buildings

• Calculators require the input data related to the specific building • Calculators are available from the ABCB website

Introduction to Module 4 Scope of the BCA Methods of Compliance

Introduction to Module 4 Scope of the BCA Methods of Compliance

PART J3BUILDING SEALING

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J3

• Energy required for heating or cooling will be reduced if buildings are adequately sealed to minimise – − loss of conditioned air in a building− entry of unconditioned air into a conditioned space

Introduction to Module 4 Scope of the BCA Methods of Compliance

Application of Part J3

• Part J3 applies to building elements forming the envelope of a Class 2 to 9 building other than-− a building in climate zones 1, 2, 3 and 5 where the only means

of air-conditioning is by using an evaporative cooler; or− a permanent ventilation opening, in a space where a gas

appliance is located, that is necessary for the safe operation of a gas appliance; or

− a Class 6, 7, 8 and 9b building that does not have a conditioned space; or

Introduction to Module 4 Scope of the BCA Methods of Compliance

− a building or space where the mechanical ventilation required by Part F4 provides sufficient pressurisation to prevent infiltration; or

− an atrium or solarium that is not a conditioned space and is separated from the remainder of the building by an envelope.

Introduction to Module 4

Application of Part J3

Scope of the BCA Methods of Compliance

Chimneys & Flues

• The chimney or flue of an open solid-fuel burning appliance must be provided with a damper or flap that can be closed to seal the chimney or flue

Introduction to Module 4 Scope of the BCA Methods of Compliance

Roof Lights

• Roof lights must be sealed or capable of being sealed, when serving a conditioned space or specific habitable rooms and must be constructed with – − an imperforate ceiling diffuser; or− a weatherproof seal; or− an occupant operated shutter system.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Windows & Doors

Introduction to Module 4

• Doors and openable windows must be fitted with edge seals if in –– the envelope of a conditioned space; or– the external fabric of a habitable room or public area in climate

zones 4, 5, 6, 7 and 8.• Edge seals may be compressible or fibrous strips• External swing doors must have a draft protection device fitted to the

bottom edge.• Compliance with AS 2047 is acceptable

Scope of the BCA Methods of Compliance

• When a main entrance door to a building opens into a conditioned space an air lock, self-closing, revolving door or similar must be installed

• Exemptions apply for specific small conditioned spaces and open fronted cafes/restaurants that incorporate other provisions

Introduction to Module 4

Windows & Doors

Scope of the BCA Methods of Compliance

Exhaust Fans

Introduction to Module 4

• Must be fitted with a sealing device if in –– a conditioned space; or– a habitable room in climate zones 4, 5, 6, 7 and 8.

• A sealing device includes –– a self-closing damper; or– a filter – such as in a kitchen rangehood.

Scope of the BCA Methods of Compliance

Roofs, Walls & Floors

• Roofs, walls, floors and door and window openings that are part of the envelope or the external fabric of specific habitable rooms or public areas, must be sealed to minimise air leakage

• Exemptions apply to openings required for smoke hazard management

Introduction to Module 4 Scope of the BCA Methods of Compliance

Evaporative Coolers

• Evaporative coolers serving a heated space or a habitable room or public area in climate zones 4, 5, 6, 7 and 8 must be fitted with a sealing device, such as a self-closing damper.

Introduction to Module 4 Scope of the BCA Methods of Compliance

PART J5AIR-CONDITIONING AND VENTILATION SYSTEMS

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J5

• Efficient design of air-conditioning and ventilation systems is an essential part of building environment management

• Increasing demands for internal thermal comfort drive the need for energy efficient systems

• The NCC has a range of measures that remove poor practice from new installations and encourage efficient system design.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Air-Conditioning Systems

• Must be capable of being shut-down –− when the building is not occupied

− when an external door of a Class 3 SOU is left open.

• If fitted with motorised outside air and return dampers; those dampers must close when system is shutdown.

• Must have ductwork insulated and sealed.

Introduction to Module 4 Scope of the BCA Methods of Compliance

• Serving parts of a building with different needs must– − control the temperature of each part (zone or area)− not mix actively heated or cooled air

− limit reheating of air.• If they provide the required mechanical ventilation, must have an outdoor

air economy cycle when unit capacity is over –− 35kWr in climate zones 4 to 8; and− 50kWr in climate zones 2 & 3 (Exemptions apply).

Introduction to Module 4

Air-Conditioning Systems

Scope of the BCA Methods of Compliance

• Serving a Class 3 SOU, must be capable of controlling different temperatures for both sleeping periods and "other" periods.

• Fans must have variable speed control when the supply quantity is varied.

• Fan power must not exceed the limits in Table J5.2 where air flow rate is over 1000L/s (Exemptions apply).

Introduction to Module 4

Air-Conditioning Systems

Scope of the BCA Methods of Compliance

Introduction to Module 4

Air-Conditioning Systems

Scope of the BCA Methods of Compliance

• Energy efficiency requirements for air-conditioning systems must not inhibit –

− the smoke hazard management operation of the system; and− essential ventilation for specific enclosures.

Introduction to Module 4

Air-Conditioning Systems

Scope of the BCA Methods of Compliance

Mechanical Ventilation Systems

• Must be capable of being shut-down when the building is not occupied.

• Serving a conditioned space; must not exceed the requirements of Part F4 by more than 20% (Exemptions apply).

Introduction to Module 4 Scope of the BCA Methods of Compliance

• With an air flow rate greater than 1000 L/s;

− have fan power to air flow rate ratio – 0.5W/(L/s) without filters 0.75W/(L/s) with filters

− if serving a conditioned space in other than climate zone 2, where the occupant density is less than 1person/m2, must have special characteristics.

Introduction to Module 4

Mechanical Ventilation Systems

Scope of the BCA Methods of Compliance

• With an air flow rate greater than 1000 L/s;− Serving a carpark for more than 40 vehicles, must be controlled

by an atmospheric contaminant monitoring system in accordance with AS 1668.2 (1991 edition)

Introduction to Module 4

Mechanical Ventilation Systems

Scope of the BCA Methods of Compliance

• Energy efficiency requirements for mechanical ventilation systems must not inhibit–

− the smoke hazard management operation of the system− essential ventilation for specific enclosures.

Introduction to Module 4

Mechanical Ventilation Systems

Scope of the BCA Methods of Compliance

Time Switches

• A time switch complying with Specification J6 must be fitted to the following – − air-conditioning systems greater than 10kWr− ventilation systems with an air flow rate greater than 1000L/s− heating systems greater than 10Kwheating

Introduction to Module 4 Scope of the BCA Methods of Compliance

Heating & Cooling Systems

• Providing heating or cooling for air-conditioning must have piping, tanks, vessels, heat exchangers and other components containing heated or chilled fluid, insulated as per Specification J5.4.

Introduction to Module 4 Scope of the BCA Methods of Compliance

• If water is circulated at greater than 2 L/s –− Must be designed so that total pump power does not exceed

the allowance in Table J5.4a; and− Must have the pump capable of varying its speed when the

pump power is greater than 3kW.• If the system has more than one water heater, chiller or coil, it

must be capable of stopping the flow of water to those components not operating.

Introduction to Module 4

Heating & Cooling Systems

Scope of the BCA Methods of Compliance

Introduction to Module 4

Heating & Cooling Systems

Table J5.4a MAXIMUM PUMP POWER

Maximum pump power (W/m2 of the floor area of the conditioned space)

Cooling or heating load (W/m2 of the floor area of the conditioned

space) Chilled water Condenser water Heating water

Up to 100 1.3 0.9 1.0

101 to 150 1.9 1.2 1.3

151 to 200 2.2 2.2 1.7

201 to 300 4.3 3.0 2.5

301 to 400 5.0 3.6 3.2

More than 400 5.6 5.6 3.6

Scope of the BCA Methods of Compliance

• A heater for heating a space via water must achieve a thermal efficiency complying with Table J5.4b when tested to BS 7190.

• Heaters for heating a space other than via water must use one of the fuels specified.

• Outdoor heaters must satisfy specific requirements.• Package air-conditioning equipment with a capacity of not less

than 65kWr must achieve an energy efficiency ratio (Table J5.4d).• A refrigerant chiller up to 350 kWr must achieve a minimum

energy efficiency ratio when determined in accordance with AHRI 550/590 (Table J5.4e).

Introduction to Module 4

Heating & Cooling Systems

Scope of the BCA Methods of Compliance

• A maximum fan power is specified for – − certain air-cooled condenser fan motors− cooling tower fans− closed circuit cooler fans− evaporative condenser fans, and− spray water pump of a closed circuit cooler or evaporative

condenser

Introduction to Module 4

Heating & Cooling Systems

Scope of the BCA Methods of Compliance

Miscellaneous Exhaust Systems

• Miscellaneous exhaust systems with an air flow rate more than 1,000L/s and linked to equipment with variable demand, must be designed to minimise exhausting conditioned air and provide means for -− lowering energy use (e.g. fan speed controls); and− stopping the motor when the system is not needed.

• Exemptions apply

Introduction to Module 4 Scope of the BCA Methods of Compliance

PART J6ARTIFICIAL LIGHTING

AND POWER

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J6

• Measures for artificial lighting and power are designed to curb unreasonable energy use

• Artificial lighting also places additional load on air-conditioning systems due to the heat generated

• Minimum limitations on artificial lighting contribute to a reduction in energy use

Introduction to Module 4 Scope of the BCA Methods of Compliance

Some Defined Terms

• Lamp power density means the total of the maximum power rating of the lamps in a space, other than those plugged into socket outlets, divided by the area of the space.

• Illumination power density means the total of the power that will be consumed by the lights in a space, including any lamps, ballasts, current regulators and control devices other than those plugged into socket outlets, divided by the area of the space.

Introduction to Module 4 Scope of the BCA Methods of Compliance

• Light source efficacy means the luminous flux of a lamp or the total radiant flux in the visible spectrum weighted by the spectral response of the eye, divided by the electric power that will be consumed by the lamp but excluding ballast and control gear power losses.

Introduction to Module 4

Some Defined Terms

Scope of the BCA Methods of Compliance

Application of Part J6

• Part J6 applies to all buildings except Class 8 electricity network substations.

• Provisions relate to the specific Class of building and the use of the room.

• Specific provisions relate to either interior artificial lighting or artificial lighting around the perimeter of a building.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Interior Artificial Lighting

• In a Class 2 or 4 sole-occupancy unit –

− the lighting power density must not exceed 5W/m2 (4W/m2 on balconies); OR

− the illumination power density must not exceed 5W/m2 (4W/m2 on balconies) other than when adjusted for one of the control devices in Table J6.2b.

Introduction to Module 4 Scope of the BCA Methods of Compliance

• In a Class 2 or 4 sole-occupancy unit –

− the calculation must reflect the proposed installation and not just the maximum electrical load of a batten holder

− halogen lamps must be separately switched from fluorescent lamps

Interior Artificial Lighting

Introduction to Module 4 Scope of the BCA Methods of Compliance

Introduction to Module 4

Interior Artificial Lighting

• In a Class 3 or 5 to 9 building –

− the aggregate design illumination power load must not exceed the sum of the allowances obtained by multiplying – the area of each space; and the maximum illumination power density in Table J6.2a.

• Exceptions apply, including emergency lighting in accordance with Part E4.

Scope of the BCA Methods of Compliance

Introduction to Module 4

Extract from Table J6.2a Table J6.2a MAXIMUM ILLUMINATION POWER DENSITY

SpaceMaximum illumination power density (W/m2)

Auditorium, church and public hall 10

Board room and conference room 10

Carpark – general 6

Carpark – entry zone (first 20 m of travel) 25

Common rooms, spaces and corridors in a Class 2 building 8

Control room, switch room, and the like 9

Courtroom 12

Dormitory of a Class 3 building used only for sleeping 6

Dormitory of a Class 3 building used for sleeping and study 9

Entry lobby from outside the building 15

Scope of the BCA Methods of Compliance

Introduction to Module 4

Extract from Table J6.2b Table J6.2b ILLUMINATION POWER DENSITY ADJUSTMENT FACTOR

ItemDescription Illumination

power density adjustment factor

Lighting timer in accordance with Specification J6

For corridor lighting 0.7

Motion detector in accordance with Specification J6

(a) Where— (i) at least 75% of the area of a space is controlled by one or more motion detectors; or(ii) an area of less than 200 m2 is switched as a block by one or more detectors.

0.9

(b) Where up to 6 lights are switched as a block by one or more detectors.

0.7

(c) Where up to 2 lights are switched as a block by one or more detectors.

0.55

Scope of the BCA Methods of Compliance

Controls for Artificial Lighting

• Artificial lighting of a room or space must be individually operated by a switch or other control device.

• In a Class 3 SOU, other than accommodation for the aged, a device must be provided to cut power to lights and air-conditioners etc when the SOU is not occupied

• Particular characteristics and the operation of artificial lighting switches are specified

• Exemptions to control requirements are specified

Introduction to Module 4 Scope of the BCA Methods of Compliance

Decorative & Display Lighting

• Decorative and display lighting - − must be controlled separately from other lighting;− have manual switches for each area; and− have a time switch if the lighting load exceeds 1 kW.

• Window display lighting must be controlled separately from other display lighting.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Perimeter Artificial Lighting

• External perimeter lighting must be controlled by a time switch or daylight sensor

• If the total lighting load exceeds 100 W, the lighting is to –− have an average light source efficacy no less than 60

Lumens/W; or

− be controlled by a motion detector.

• Have a separate time switch if used for decoration

Introduction to Module 4 Scope of the BCA Methods of Compliance

Water Storage Units

• Power supply to boiling or chilled water storage units must have a time switch.

Introduction to Module 4 Scope of the BCA Methods of Compliance

PART J7HOT WATER SUPPLY, POOLS

AND SPAS

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part J7

• The measures addressing hot water supply cover hot water for food preparation, sanitary purposes and pool or spa heating.

• The intent of the provisions is to –– reduce heat loss from hot water systems/storage water

heaters; and – limit energy supply, the amount of energy used and heat

loss from pools and spas.• Reduced heat loss will produce energy savings.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Hot Water Supply

• Systems for food preparation and sanitary purposes, must comply with Section 8 of AS/NZS 3500.4.

• Main requirements are insulation and a heat trap.• Solar systems in climate zones 1, 2 and 3 are exempt.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Pools & Spas

• Heating must be by using one of the approved energy sources

• Where some or all of the heating is by gas or heat pump, a swimming pool or spa which shares a pool reticulation system must have –– a cover; and– a time switch to control the operation of the heater.

• Swimming pools, and spas with a capacity of more than 680 L, must be provided with a time switch to control the operation of a circulation pump.

Introduction to Module 4 Scope of the BCA Methods of Compliance

PARTS I2 & J8MAINTENANCE & MONITORING

Introduction to Module 4 Scope of the BCA Methods of Compliance

Maintenance

• Maintenance measures for energy efficiency installations are contained within two Parts – − Part J8 – Access for maintenance & facilities for

monitoring

− Part I2 – Energy efficiency installations

Introduction to Module 4 Scope of the BCA Methods of Compliance

PART J8ACCESS FOR MAINTENANCE & FACILITIES FOR MAINTENANCE

Introduction to Module 4 Scope of the BCA Methods of Compliance

Access for Maintenance

• Part J8 applies to all Class 2 to 9 buildings, except within a sole-occupancy unit of a Class 2 or a Class 4 part of a building.

• Access must be provided to all plant, equipment and components that require maintenance in accordance with Part I2.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Facilities for Monitoring

• A building or sole-occupancy unit with a floor area more than 500m2 must have –

– facility to record the consumption of gas and electricity.• A building with a floor area of more than 2500m² must have facility

to individually record the energy consumption of –− Air-conditioning plant− Artificial lighting− Appliance power

Introduction to Module 4

− Central hot water supply− Lifts, escalators etc− Ancillary plant

Scope of the BCA Methods of Compliance

PART I2ENERGY EFFICIENCY

INSTALLATIONS

Introduction to Module 4 Scope of the BCA Methods of Compliance

Principles of Part I2

• Maintenance of energy efficiency installations is essential to ensure ongoing compliance with design standards.

• Part I2 seeks to ensure that equipment and installations required under Section J continue to operate in an effective manner.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Application of Part I2

• Part I2 does not apply to services that serve only one SOU of a Class 2 building, or serve only a Class 4 part of a building

Introduction to Module 4 Scope of the BCA Methods of Compliance

Components of Services

• Components must be maintained to ensure they perform to a standard not less than they were originally required to achieve.

• A list of typical components to be maintained is provided in Part I2.

Introduction to Module 4 Scope of the BCA Methods of Compliance

Alternative Solutions

Option to Develop an Alternative Solution

• To comply with BCA Performance Requirements some practitioners will follow Deemed-to-Satisfy Provisions.

• However – it’s often preferable to design something different to Deemed-to-Satisfy and to develop an Alternative Solution.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Remember theBCA Structure?

Complying with the Performance RequirementsCompliance with the Performance Requirements can only be achieved by –

a) complying with the Deemed-to-Satisfy Provisions, or

b) formulating an Alternative Solution which-

(i) complies with the Performance Requirements, or

(ii) is shown to be at least equivalent to the Deemed-to-Satisfy Provisions; or

c) a combination of a) and b)

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Design Flexibility

• The BCA provides two pathways to formulate an Alternative Solution:

− formulating an Alternative Solution to meet the Performance Requirements; or

− formulating an Alternative Solution to at least equate to Deemed-to-Satisfy Provisions.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Flexibility in Compliance

• Either of these options can be explored to establish the most appropriate pathway for a particular Alternative Solution

• A decision regarding the most appropriate pathway may be influenced by the views of the Certifying Authority

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Consultation

• It is beneficial to discuss an Alternative Solution with the Certifying Authority before lodging an application for approval

• Also discuss the scope of supporting documentation needed to be provided

• The Certifying Authority can advise on likely Assessment Methods but should not become involved in development of the design

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Developing Alternative Solutions

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Alternative Solutions

• The development of Alternative Solutions was covered in detail in Module Two

• Relevant BCA provisions can be found in Section A of Volume One

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Assessment Methods

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Assessment Methods

• Assessment methods were discussed in detail in Module Two

• Methods for assessing Building Solutions are listed in Part A0.9

• The Certifying Authority will assess compliance of Alternative Solutions

• The applicant is required to demonstrate compliance with the relevant Performance Requirements

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Assessment Methods

Four Assessment Methods are listed in Part A0.9:

− Evidence of Suitability described in Part A2.2− Verification Methods

− Comparison with Deemed-to-Satisfy Provisions

− Expert Judgement

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Evidence of Suitability

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Evidence of Suitability

• Forms of Evidence of Suitability is listed in Part A2.2 of Volume One

• The listed processes are generally third party mechanisms that may be used to assist either the formulation or assessment of Building Solutions

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Evidence of Suitability

• Registered Testing Authority report• Certificate of Conformity / current Certificate of Accreditation

• Certification from appropriately qualified persons

• Certification from a body accredited by the Joint Accreditation System of Australia and New Zealand (JAS-ANZ)

• Any other form of documentary evidence

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Verification Methods

What is a Verification Method?

• Verification Method is defined as –– a test, inspection, calculation or other method that determines

whether a Building Solution complies with the relevant Performance Requirements

• This definition allows a broad range of processes to be used to verify compliance

• One Verification Method is offered for energy efficiency requirements

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Verification Method JV3

• Requires the use of a thermal calculation method complying with ABCB Protocol for Building Energy Analysis Software

• Applies to all Class 3, 5, 6, 7, 8 and 9 buildings.

• Applies the thermal calculation method to verify that the annual energy consumption of the proposed building does not exceed the annual energy consumption of a reference building.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Verification Method JV3

• Reference building means a hypothetical building that is used to calculate the maximum allowable annual energy load, or maximum allowable annual energy consumption for the proposed building.

• Criteria to be used within the calculations of annual energy consumption are specified, including compliance with Specification JV in some cases.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Verification Method JV3

• Requires three computer modelling runs:

Run 1 - reference building with DTS fabric and services

Run 2 - proposed building with proposed services

Run 3 - proposed building with proposed envelope and Deemed-to-Satisfy services

• Runs 2 and 3 are then compared with Run 1

• The annual energy consumption from Run 2 and 3 must be no larger than the allowance for Run 1.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Specification JV

• Need only be used if the building operates for more than 2,500 hours per year

• Has rules for calculating annual energy consumption:− Tables 2a to 2g specify daily occupancy and operation

profiles for buildings− Table 2h specifies internal heat gains from appliances and

equipment− Table 2i specifies hot water supply rates

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Extract of Table 2b

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Summary

Scope of the BCAIntroduction to Module 4 Methods of Compliance

• JV3 applies to all Class 3, 5, 6, 7, 8 and 9 buildings

• Models building fabric and services; and• Compares the annual energy consumption of the proposed

building with that of a reference building

Administrative Matters

Assessment of Designs

• Application of these energy efficiency provisions may need to be undertaken by specialist designers

• Similarly – assessment of design proposals may need input from specialists

• Certifying Authorities may need specialist training or require certification of compliance by specialists

Scope of the BCAIntroduction to Module 4 Methods of Compliance

Administrative Matters

• All State/Territory jurisdictions have administrative provisions for the design and construction of buildings.

• Energy efficiency is an issue for which specific administrative processes may exist, e.g. energy efficiency assessors may be required to be accredited.

• Practitioners need to be aware of relevant processes and ensure they comply.

• How the NCC applies to alterations, additions and renovations can vary between State and Territories.

Scope of the BCAIntroduction to Module 4 Methods of Compliance

That's it!

Are there any questions?

Scope of the BCAIntroduction to Module 4 Methods of Compliance

top related