local exhaust ventilation plant report
Post on 13-Jan-2022
5 Views
Preview:
TRANSCRIPT
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH
E35223008923
02-MAY-2017
06-NOV-2017
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 406-NOV-2017
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman Surface GrinderHazardous substance(s) being controlled Steel, Resin and Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223008318 - dated 02/05/2017)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223008923
3/ No air flow indicators are present at appropriate points on the system to indicate the system isfunctioning correctly. Reference should be made to HSG 258 regarding the installation of air flowindicators.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223008923
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Fabric BagsCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2377 -2481 104
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2377
TP 2 Hood Face 0.08 x 0.08 -1462 11.95 0.08
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223008923
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH
E35223008318
20-OCT-2016
02-MAY-2017
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 402-MAY-2017
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223007745 - dated 20/10/2016)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223008318
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223008318
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Fabric BagsCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2073 -2283 210
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2073
TP 2 Hood Face 0.08 x 0.08 -1423 17.32 0.11
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223008318
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223007745
18-APR-2016
20-OCT-2016
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 420-OCT-2016
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
1. The hood face is starting to block with debris and should be cleared.
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223007038 - dated 18/04/2016)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223007745
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223007745
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2267 -2400 133
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2267
TP 2 Hood Face 0.08 x 0.08 -1478 13.26 0.09
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223007745
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Submission Date 2016-04-19 14:29:46
Item Surface Grinder
HS Reference https://hs.carrs-silver.co.uk/levtool.pdf
Due Date 28-04-2016
Status Completed+
Comments/Notes 19/04/16 Requested tool room operatives deal with items 1 & 3 on pages 1 & 2 of theabove report. 20/04/16 Andre dealing with this. 25/04/16 James/Andre when will thisjob be complete? From: Toolroom [mailto:toolroom@carrs-silverware.co.uk] Sent: 26April 2016 11:51 To: 'Martin Carr' Subject: RE: EDIT: Outstanding+ HS Job 28-04-2016It’s done. Andre From: Martin Carr [mailto:martin.carr@carrs-silverware.co.uk] Sent: 26April 2016 10:47 To: 'Toolroom' Subject: RE: EDIT: Outstanding+ HS Job 28-04-2016The extraction hood face is starting to block with dusts and should be cleaned. This isthe only item you need to do, if you can confirm it has been done, then I will close thejob. Martin.
Job Type HS Job
Notifier hsjobs@carrs-silver.co.uk
Carrs HS Jobs
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223007038
19-OCT-2015
18-APR-2016
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 418-APR-2016
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
1/ The extraction hood face is starting to block with dusts and should be cleaned.
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223006403 - dated 19/10/2015)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223007038
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223007038
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Fabric BagsCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2312 -2620 308
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2312
TP 2 Hood Face 0.08 x 0.08 -1514 18.98 0.12
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223007038
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH
E35223006403
20-APR-2015
19-OCT-2015
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 419-OCT-2015
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Light Test, Smoke Test, Static PressureTest, Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223005699 - dated 20/04/2015)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223006403
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223006403
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2315 -2400 85
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2315
TP 2 Hood Face 0.08 x 0.08 -1462 14.49 0.09
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223006403
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACEEM047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223005699
16-OCT-2014
20-APR-2015
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 420-APR-2015
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223005227 - dated 16/10/2014)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223005699
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223005699
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2241 -2377 136
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2241
TP 2 Hood Face 0.08 x 0.08 -1320 18.62 0.12
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223005699
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223005227
15-APR-2014
16-OCT-2014
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 416-OCT-2014
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover Tool RoomLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
1/ The capture hood is starting to block up with contaminant dusts which should be cleared.
2/ The capture hood should be lowered into the correct position, when the ginder is used for dry grinding,in order to acheive the maximum level of control.
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223004702 - dated 15/04/2014)
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223005227
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
3/ The build up of contaminant dusts on the grinder, capture hood and duct should be cleared. Theextraction should be used during all dry grinding operations.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223005227
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2143 -2306 163
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2143
TP 2 Hood Face 0.08 x 0.08 -1521 13.41 0.09
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223005227
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223004702
07-OCT-2013
15-APR-2014
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 415-APR-2014
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding Medium DustsNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
1/ The capture hood is starting to block up with contaminant dusts which should be cleared.
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223004249 - dated 07/10/2013)
2/ Test results recorded indicate no marked system performance deterioration since the last ThoroughExamination and Test.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223004702
3/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during workactivities.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223004702
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2163 -2387 224
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2136
TP 2 Hood Face 0.08 x 0.08 -2036 14.54 0.09
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223004702
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223004249
10-APR-2013
07-OCT-2013
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 407-OCT-2013
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Safety Data Sheets Not Presented. Substances
Witnessed - Steel, Resin & Grinding MediumDusts
Number of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223003797 - dated 10/04/2013)
2/ Test results recorded indicate no marked system performance deterioration since the last Thorough
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223004249
Examination and Test.
3/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during workactivities.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
The following supporting documents, held by Martin Carr, have been witnessed and are readily availableon the companies' intranet site;
Risk Assessment / COSHH Assessment
Material Safety Data Sheet(s)
Previous Thorough Examination and Test Report(s)
The following supporting documents have not been witnessed;
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223004249
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2117 -2396 279
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2117
TP 2 Hood Face 0.08 x 0.08 -1352 18.92 0.12
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223004249
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223003797
11-OCT-2012
15-APR-2013
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 410-APR-2013
Type of Inspection Thorough Examination and Test
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Safety Data Sheets Not Presented. Substances
Witnessed - Steel, Resin & Grinding MediumDusts
Number of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
1/ Cross-reference with the last Thorough Examination and Test report
(E35223003335 - dated 11/10/2012)
2/ Test results recorded indicate no marked system performance deterioration since the last Thorough
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 4 E35223003797
Examination and Test.
3/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during workactivities.
4/ Please provide test holes for the measurement of PSI and PSO.
5/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
6/ COSHH Management System Documentation
In accordance with the requirements of HS(G)258 - Controlling Airborne Contaminants at Work, thefollowing supporting documents have not been witnessed and should be made readily available;
Risk Assessment / COSHH Assessment
Safety Data Sheet(s)
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
7/ Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
8/ Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 4 E35223003797
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2006 -2305 299
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 2006
TP 2 Hood Face 0.08 x 0.08 -1362 18.37 0.12
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 4 E35223003797
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223003335
04-APR-2012
11-OCT-2012
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 311-OCT-2012
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Safety Data Sheets Not Presented. Substances
Witnessed - Steel, Resin & Grinding MediumDusts
Number of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
Cross-reference with the last Thorough Examination and Test report
(E35223002913 - dated 04/04/2012)
Test results recorded indicate no marked system performance deterioration since the last Thorough
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 3 E35223003335
Examination and Test.
1/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during workactivities.
2/ Please provide test holes for the measurement of PSI and PSO.
3/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
COSHH Management System Documentation
In accordance with the requirements of HS(G)258 - Controlling Airborne Contaminants at Work, thefollowing supporting documents have not been witnessed and should be made readily available;
Risk Assessment / COSHH Assessment
Safety Data Sheet(s)
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 3 E35223003335
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2072 -2445 373
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2072
TP 2 Hood Face 0.08 x 0.08 -1109 18.61 0.12
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223002913
28-SEP-2011
04-APR-2012
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 304-APR-2012
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Safety Data Sheets Not Presented. Substances
Witnessed - Steel, Resin & Grinding MediumDusts
Number of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
Cross-reference with the last Thorough Examination and Test report
(E35223002488 - dated 28/09/2011)
Test results recorded indicate no marked system performance deterioration since the last Thorough
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 3 E35223002913
Examination and Test.
1/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during workactivities.
2/ Please provide test holes for the measurement of PSI and PSO.
3/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
COSHH Management System Documentation
In accordance with the requirements of HS(G)258 - Controlling Airborne Contaminants at Work, thefollowing supporting documents have not been witnessed and should be made readily available;
Risk Assessment / COSHH Assessment
Safety Data Sheet(s)
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. Process stood down
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 3 E35223002913
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2124 -2403 279
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2124
TP 2 Hood Face 0.08 x 0.08 -1320 14.60 0.09
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK, SHEFFIELD, S20 3FH
E35223002488
28-MAR-2011
30-SEP-2011
Andrew Allen
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 328-SEP-2011
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Safety Data Sheets Not Presented. Substances
Witnessed - Steel, Resin & Grinding MediumDusts
Number of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None
Other Observations
Cross-reference with the last Thorough Examination and Test report
(E35223002138 - dated 28/03/2011)
1/ Capture effective up to 0.15m from the hood face, which should be positioned accordingly during work
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 3 E35223002488
activities.
2/ Please provide test holes for the measurement of PSI and PSO.
3/ We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted toa safe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
COSHH Management System Documentation
In accordance with the requirements of HS(G)258 - Controlling Airborne Contaminants at Work, thefollowing supporting documents have not been witnessed and should be made readily available;
Risk Assessment / COSHH Assessment
Safety Data Sheet(s)
Air Monitoring/Sampling Report(s),
Commissioning Report
LEV User Manual/ Logbook
Refer to Report No E35223002138, dated 28/03/2011, for system diagram.
Please provide the fan and motor technical data and filter efficiency data.
Condition at Time of Test Normal. (Process stood down)
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 3 E35223002488
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2254 -2315 61
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2254
TP 2 Hood Face 0.08 x 0.08 -1425 16.08 0.10
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223002138
28-SEP-2010
28-MAR-2011
Allen, Andrew
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 528-MAR-2011
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding MediumNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None.
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None.
Other Observations
Please provide test holes for the measurement of PSI and PSO.
We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted to asafe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
Please provide the fan and motor technical data.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 5 E35223002138
Please provide the filter efficiency data.
Capture effective up to 0.15m from the hood, which should be positioned accordingly during workactivities.
The following supporting documents, as indicated in HS(G)258 - Controlling Airborne Contaminants atWork, have not been witnessed and should be made readily available; Risk Assessment, CoSHHAssessment, Safety Data Sheet(s), Air Monitoring/Sampling Report(s), Commissioning Report, UserManual and Logbook.
Condition at Time of Test Normal. (Process stood down)
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2306 -2325 19
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2306
TP 2 Hood Face 0.08 x 0.08 -1517 16.89 0.11
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 5 E35223002138
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )See additional cover forsystem diagram
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 5 E35223002138
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 5 of 5 E35223002138
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223001800
30-MAR-2010
30-SEP-2010
Allen, Andrew
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 528-SEP-2010
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding MediumNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None.
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None.
Other Observations
We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted to asafe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
Please provide the fan and motor technical data.
Please provide the filter efficiency data.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 5 E35223001800
Capture effective up to 0.15m from the hood, which should be positioned accordingly during workactivities.
The following supporting documents, as indicated in HS(G)258 - Controlling Airborne Contaminants atWork, have not been witnessed and should be made readily available; Risk Assessment, CoSHHAssessment, Safety Data Sheet(s), Air Monitoring/Sampling Report(s), Commissioning Report, UserManual and Logbook.
Condition at Time of Test Normal. (Process stood down)
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2260 -2306 46
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2260
TP 2 Hood Face 0.08 x 0.08 -1446 16.58 0.11
See additional cover forsystem diagram
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 5 E35223001800
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 5 E35223001800
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 5 of 5 E35223001800
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223001448
21-SEP-2009
01-APR-2010
Allen, Andrew
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 530-MAR-2010
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding MediumNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None.
Defects NOT affecting the level of control and particulars of any repairs or modifications required
None.
Other Observations
We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted to asafe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
Please provide the fan and motor technical data.
Please provide the filter efficiency data.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 5 E35223001448
Capture effective up to 0.15m from the hood, which should be positioned accordingly during workactivities.
The following supporting documents, as indicated in HS(G)258 - Controlling Airborne Contaminants atWork, have not been witnessed and should be made readily available; Risk Assessment, CoSHHAssessment, Safety Data Sheet(s), Air Monitoring/Sampling Report(s), Commissioning Report, UserManual and Logbook.
Condition at Time of Test Normal. (Process stood down)
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal TrayEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-2304 -2341 37
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )TP 1 Duct 0.08 -2304
TP 2 Hood Face 0.08 x 0.08 -1277 16.60 0.11
See additional cover forsystem diagram
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 5 E35223001448
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 4 of 5 E35223001448
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 5 of 5 E35223001448
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Date of previous examination and tests
Location
Contract No.Policy No. Report No.
Name of User
005
Date of commencement of examination and tests
Date of Report
Engineer Surveyor
Competent PersonAllianz Engineering
+44 (0) 1428 722407UK Tel:ROI Tel: +00353 (0) 1 613 4081
V810b
Local Exhaust Ventilation Plant Report
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE
NV09796703
TROY HOUSE, 2 HOLBROOK AVENUE, HOLBROOK,SHEFFIELD, S20 3FH
E35223001087
17-MAR-2009
25-SEP-2009
Allen, Andrew
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom.Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator.
www.allianzengineering.co.uk
Health & Safety at Work etc. Act 1974
Side 1 of 321-SEP-2009
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032Manufacturer Dust Extraction LtdSerial Number 59190Location of Air Mover IntegralLocation of Process Tool RoomProcess(es) being controlled Jones Shipman GrinderHazardous substance(s) being controlled Steel, Resin & Grinding MediumNumber of Extraction Points 1Maximum number that can be used at one time 1Exhaust air returned to WorkplacePrimary filter fitted YesSecondary filter fitted No
Visual Assessment of the level of control SatisfactoryAir Sampling Results We recommend the return air be monitored to
ensure that it is not above the set limits for thecontaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test,Velocity Measurements
Defects AFFECTING the level of control and particulars of any repairs or modifications required
None.
Defects NOT affecting the level of control and particulars of any repairs or modifications required
Contaminant dust is present on the clean side of the filter housing. Investigation as to the cause should becarried out and the dusts cleaned away in order to prevent them being exhausted back to the workplace.
Other Observations
We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted to asafe place in the open air. Where this is not possible then consideration should be given to the fitting ofexplosion deflector plates or the re-siting of the collector unit. In no case should it be discharged intooccupied workrooms or areas containing combustible materials.
Please provide the fan and motor technical data.
Please provide the filter efficiency data.
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 2 of 3 E35223001087
Capture effective up to 0.15m from the hood, which should be positioned accordingly during workactivities.
Condition at Time of Test Normal. (Process stood down)
Fan Details
Manufacturer Dust Extraction LtdSerial NumberType CentrifugalRotation (viewed from drive end) Anti-clockwise
mØSize 0.4Volume Flow m s3 -1
Speed rpm
Motor Details
Manufacturer Not MarkedSerial no.Speed rpmPower kW
Primary Filter
Medium Cloth FabricCollector Type Metal BinEfficiency %
Secondary Filter
MediumCollector TypeEfficiency %
Details of Test Results
Primary filter inlet Pressure(Pa)
Primary filter outlet Pressure(Pa)
Pressure Difference(Pa)
-1284 -2234 950
-13
Test Point and Type Size Results of Inspection
Duct / Face / PointHood / Duct
Size(m)
StaticPressure
(Pa)
Face / DuctVelocity(ms )
Point No.-1
VolumeFlow
(m s )PS1 Duct 0.08 -1284
PS2 Hood Face 0.08 x 0.08 -681 11.91 0.08
Report No.
V810b
Local Exhaust Ventilation Plant Report
Health & Safety at Work etc. Act 1974
Side 3 of 3 E35223001087
Calibrated Test Equipment Details
Thermal Anemometer 120622Electronic Manometer ACE EM 047Rotating Vane Anemometer Not UsedOther N/A
Examination carried out on behalf of:Client NameAddress
This report shall not be reproduced without the approval of Allianz Engineering and the client for whom it was produced.
CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARETROY HOUSE2 HOLBROOK AVENUEHOLBROOKSHEFFIELDS20 3FH
Local Exhaust Ventilation Plant Report Health & Safety at Work etc. Act 1974
Allianz
Name of User: CARRS OF SHEFFIELD LTD T/AS CARRS SILVERWARE Policy Number: NV09796703
Contract Number:Location: TROY HOUSE, 2 HOLBROOK
AVENUE, HOLBROOK, SHEFFIELD, S20 3FH
Report Number: E35223000716
Type of Inspection Thorough Periodic
Regulations Applicable Regulation 9 of COSHH
Identification of LEV Plant and Process
Plant Number LEV032
Manufacturer Dust Extraction Ltd
Serial Number 59190
Location of Air Mover Integral
Location of Process Tool Room
Process(es) Being Controlled Jones Shipman Grinder
Hazardous Substance(s) Being Controlled Steel, Resin & Grinding Medium
Number of Extraction Points 1
Maximum Number that can be used at one time 1
Exhaust air Returned to Workplace
Primary Filter Fitted Yes
Secondary Filter Fitted NoVisual Assessment of the level of control
Satisfactory
Air Sampling Results We recommend the return air be monitored to ensure that it is not above the set limits for the contaminants.
Tests Undertaken Visual, Smoke Test, Static Pressure Test, Velocity Measurements
Defects AFFECTING the level of control
None.Defects NOT affecting the level of control
Contaminant dust is present on the clean side of the filter housing. Investigation as to the cause should be carried out and the dusts cleaned away in order to prevent them being exhausted back to the workplace. Other Observations We note that the dust collector unit is fitted with explosion relief facility. This facility should be ducted to a safe place in the open air. Where this is not possible then consideration should be given to the fitting of explosion deflector plates or the re-siting of the collector unit. In no case should it be discharged into occupied workrooms or areas containing combustible materials. Please provide the fan and motor technical data. Please provide the filter efficiency data. Capture effective up to 0.15m from the hood, which should be positioned accordingly during work activities.Condition at Time of Test Normal. (Process stood down) Fan Details
Manufacturer Dust Extraction Ltd
Serial Number
Type Centrifugal
Rotation (Viewed from Drive End) Anti-clockwise
Size Ø 0.4 m
Page 1 of 2Local Exhaust Ventilation Plant Report
16/04/2009https://www.eservices-allianzengineering.co.uk/eServices/interface/Reports/...
Details of Results
Calibrated Test Equipment
Allianz Engineering, Head Office, Haslemere Road, Liphook, Hampshire, GU30 7UN, United Kingdom. Allianz Engineering Inspection Services Ltd. Registered in England Number: 5441840. Registered Office: 57 Ladymead, Guildford, Surrey, GU1 1DB, United Kingdom.
Allianz plc, Allianz House, Elmpark, Merrion Road, Dublin 4, Republic of Ireland. Allianz plc trading as Allianz is regulated by the Irish Financial Regulator. Registered in Ireland number 143108.
www.allianzengineering.co.uk
Volume flow m3s-1
Speed rpm
Motor Details
Manufacturer Not Marked
Serial Number
Speed rpm
Power kW
Primary Filter
Medium Cloth Fabric
Collector Type Metal Bin
Efficiency %
Secondary Filter
Medium
Collector Type
Efficiency %
Primary filter inlet Pressure (Pa)
Primary filter outlet Pressure (Pa)
Pressure Difference (Pa)
-781 -2208 1427
Test Point Type and Size Results of Inspection
Point Number
Duct/Face/Point Hood/Duct Size (m)
Static Pressure
(Pa)
Face/Duct Velocity (ms-1)
Volume Flow
(m3s-1)PS1 Duct 0.08 -781 PS2 Hood Face 0.08 x 0.08 10.12 0.06
Thermal Anemometer Rotating Vane Anemometer 120622 Not UsedElectric Manometer Other ACE EM 047 N/A
Client's Report Notes [These notes DO NOT form part of the Allianz Inspection Report]
Date of previous examination 12/09/2008Competent Person
Date of completion of examination and tests 17-Mar-2009 Allianz Engineering
Date of Report 17-Mar-2009 UK Tel: +44 (0) 1428 722407 ROI Tel: +00353 (0) 1 613 4081
Engineer Surveyor A. Allen
This is an electronically produced copy of an original report held on the AllianzEngineering computer database called FACE
Page 2 of 2Local Exhaust Ventilation Plant Report