interlock training
Post on 14-Apr-2018
231 Views
Preview:
TRANSCRIPT
-
7/30/2019 Interlock Training
1/26
Policy and Practicefor
BypassingInterlocks
Click anywhere on the screen to continue
-
7/30/2019 Interlock Training
2/26
Why Do You Need This Information?
You were selected by your supervisor as someone who wouldmost likely have cause to install an interlock-bypass.
Read the policy on the next few slides. It is followed byadditional material that will explain why the policy wasadopted, how the process flows, and offer some interlock-
bypass examples.
-
7/30/2019 Interlock Training
3/26
page 1 page 2
-
7/30/2019 Interlock Training
4/26
Why the Policy was Developed
On October 14, 2011, two YR magnets in the Northeast Spreader regioncaught fire and sustained heavy damage. Root cause was inadequate Work Control processes and practices . Two direct causes:
LCW valves for the dipoles were shut. A jumper (interlock-bypass) in the box supply prevented the thermal switches
from tripping the power supply .
What you are about to see is damage caused by the overheating of magnetcoils in the tunnel.
Keep in mind that this might have been avoided if the overheating protection
(interlock) on the RSEP9A power supply had not been bypassed or if more peoplehad known that it was bypassed.
-
7/30/2019 Interlock Training
5/26
YR9S04
-
7/30/2019 Interlock Training
6/26
YR7S03
-
7/30/2019 Interlock Training
7/26
Damaged Coils
-
7/30/2019 Interlock Training
8/26
YR7S03 Split
-
7/30/2019 Interlock Training
9/26
Recommendation* byFire Investigation Team
Recommendation #4The use of interlock jumpers on equipment installed in theaccelerator should be avoided. In circumstances where they arerequired, they should be clearly marked to aid in identification.
All groups should have a systematic method of identifying theinstallation and removal of jumpers in addition to a method to
identify where all jumpers are installed.
* one of many
-
7/30/2019 Interlock Training
10/26
These individuals were selected to develop a policy to addressrecommendation #4 and can answer any questions you mayhave concerning the new policy or its implementation:
Interlock Bypass Team
Jonathan Creel (Cryo)
Anthony DiPette (Mechanical)
Mike Drury (SRF)
Ron Lauz (Electrical)
Randy Michaud (Operability)
Tom Oren (Documentation)
Paul Vasilauskis (MCC Ops)
-
7/30/2019 Interlock Training
11/26
Accelerator Bypassed- Interlock L ogABIL is electronic log that keeps track of bypassed interlocks in the accelerator
Follow the link ( http://opsweb.acc.jlab.org/abil/pro/ ) to familiarize yourself with ABIL. How to make or delete an entry in ABIL is straightforward and is not detailed here. You can Mouse Over
various fields to view what input information is required.
Some features of ABIL: ABIL is set up to notify individuals, via e-mail, when interlocks are bypassed, bypasses are removed, and
when their expected removal date is about to expire or has expired. ABIL notifies system owners whenexpirations dates have been exceeded.
Individuals can customize ABIL to view all bypasses or only ones they installed, group by system or showungrouped, sort on any column, move, resize, hide, unhide columns. Choices stay persistent between uses.
Individuals can sign up to receive e-mails when bypasses are installed/removed within a given system. To doso go to the Setup My Email tab and select the systems on which you want to be notified.
http://opsweb.acc.jlab.org/abil/pro/http://opsweb.acc.jlab.org/abil/pro/ -
7/30/2019 Interlock Training
12/26
Interlock Bypassed Tag
-
7/30/2019 Interlock Training
13/26
Tags located at each service building
door and near every tunnel phone
-
7/30/2019 Interlock Training
14/26
-
7/30/2019 Interlock Training
15/26
Situational Examples
The following 9 example slides are meant togive you some idea of when and how to
apply this policy. They do not cover everysingle instance you may come across. Inmost cases you will be able to determine if a
tag and/or ABIL entry is required by simplyusing your best judgment.
-
7/30/2019 Interlock Training
16/26
Example 1Crew Chief calls for support for a water flow fault on
Chopper 1 in the Injector. The fault is impeding thescheduled program. Technician determines that the flow is okay but the
electronic interlock circuit has failed. Technician and Crew Chief discuss the situation and
determine that its okay to bypass the interlock until the nextmaintenance day.
Technician makes an entry in ABIL, gets a tag number fromABIL, fills out and installs a tag at the flow meter .
Technician installs the bypass.
-
7/30/2019 Interlock Training
17/26
Example 2Crew Chief calls for support for a magnet Box Power Supply that has
faulted off and is impeding the scheduled program. In order for the Technician to troubleshoot the power supply he
must bypass one of the door interlocks. Technician fills out a tag and installs it at a location that is obvious
to anyone that the supply has an interlock bypassed. Technician bypasses the interlock. Technician replaces a faulty circuit board, determines the supply is
operational, removes the bypass, removes the tag, and tells the
Crew Chief the supply is fixed.Note: work is being performed during immediate maintenance
and therefore, by policy, did not require an ABIL entry.
-
7/30/2019 Interlock Training
18/26
Example 3Its a maintenance day and your ATLis to work on a
water flow meter that malfunctioned and requiredbypassing the interlock has been approved. Technician removes the bypass. Technician replaces the flow meter and verifies
operation. Technician removes the tag.
Technician deletes the ABIL entry.
-
7/30/2019 Interlock Training
19/26
Example 4Crew Chief calls for support for an RF cavity that has faulted off and
is impeding the scheduled program. Technician determines that there is a water flow fault that will not
clear. Technician and Crew Chief discuss the situation and determine
that bypassing the RF Zone is the best course of action. However,
the technicians want to continue making repairs in a non-intrusiveway to operations.
Zone is bypassed. Technician makes an entry in ABIL, gets a tag number from ABIL,
fills out and installs a tag at a visible location.
Technician bypasses the water flow interlock and continuesworking on the zone.
Note : This started as immediate maintenance but changed when the zone wasbypassed. In that case an ABIL entry was not required for the water flow faultUNTIL the decision was made to bypass the zone with the interlock bypass inplace.
-
7/30/2019 Interlock Training
20/26
Example 5While running beam to Hall C it became necessary to ask
permission to mask the Compton Ion Chamber FSDnode.
Operator/Crew Chief discuss this with the Hall C RunCoordinator and get permission to mask it. Operator makes an entry in ABIL. NO TAG
REQUIRED.
Operator masks the node.Note: An ABIL entry was required but a tag was notbecause the interlock-bypass was made via asoftware variable.
-
7/30/2019 Interlock Training
21/26
Example 6Crew Chief calls for support for valves that will not open
because of a vacuum fault that will not clear; this isimpeding the scheduled program. Technician determines that there is not a leak and adjusting the set
point to a level below the allowable threshold will clear the problem.
Technician and Crew Chief discuss the situation, call for approval(if necessary), and if approved, make the adjustment.
No ABIL entry or tag are required.
Note: An ABIL entry would be required if the set point requiredadjustment above the allowable threshold.
-
7/30/2019 Interlock Training
22/26
Example 7
Crew Chief calls for support for a valve that indicatesbeing closed and will not respond. Technician determines that the valve is actually open but the limit
switch on the valve is faulty giving a false indication. Technician and Crew Chief discuss the situation and determine its
okay to bypass the limit switch. Technician makes an entry in ABIL, gets a tag number from ABIL,
fills out and installs a tag at a visible location. Technician installs a jumper on the switch readback connector so
that the valve now indicates open.
-
7/30/2019 Interlock Training
23/26
Example 8While running beam Crew Chief receives an accelerator
ODH alarm. Crew Chief contacts the Safety System Group (SSG).
SSG technician determines that the ODH head needs to be bypassed and gets permission from the Crew Chief to do so.
Technician makes an ABIL entry.
Technician disables the alarm in the PLC. No tag is required. Note: An ABIL entry was required but a tag was not
because the interlock-bypass was made via a PLC
set point.
-
7/30/2019 Interlock Training
24/26
Example 9Technician is working on a piece of equipment in her shop. The job
requires that she bypass an interlock in order to calibrate it. Technician installs a tag at a visible location. No ABIL entry is
required.
Technician installs the bypass. Tag remains in place as long as the interlock is bypassed. Lets say
for this example that the bypass needs to remain in place becausethe bad part causing the problem is on order.
A few days later the equipment is needed to repair the accelerator to
restore the scheduled program. If the interlock bypass is still required AND it was determined that
the equipment could be run with the bypass in place, an ABILentry is required and the ABIL number placed on the existing tag.
-
7/30/2019 Interlock Training
25/26
Summary
You took this training because you were identified as someonewho will likely be bypassing an interlock.
This policy is important. We cannot afford another fire caused
by an interlock being bypassed due to limited knowledge. You can direct any questions you may have to your supervisor
or one of the team members that developed this policy. Typically both a tag and ABIL entry are required, but in some
cases only one is. Tags are available both in the service buildings and in the
tunnel.
-
7/30/2019 Interlock Training
26/26
If you have read and understand the policy, the reasonfor it, and the ten examples provided, click the box
below to update your record.
Confirmation
CONFIRM
https://misportal.jlab.org/mis/training/online_courses/completeClass.cfm?classId=77169https://misportal.jlab.org/mis/training/online_courses/completeClass.cfm?classId=77169https://misportal.jlab.org/mis/training/online_courses/completeClass.cfm?classId=77169https://misportal.jlab.org/mis/training/online_courses/completeClass.cfm?classId=77169