oldcastleprecast.com/enclosuresolutions 559-675-1813

Items Needed

• 1/4”carbidetippedmasonrydrillbit

• Cordeddrillwithhandle• Diamondtippedmasonryholesaw

• Tapemeasure• Pen/Pencil• Cordlessdrill(optional)

(optional)

Instructions

• UsingthetapemeasurefindwhereyouwantyourholetobeandmarkitwithaPen/Pencil.

• Onceyourholeismarkedtakeyourdrillwitha1/4”carbidetippedmasonrybitanddrillatthecenterofwhereyouwantyourhole.

• Usingthecordeddrillwithahandleandadiamondtippedmasonryholesawattachedmakeyourcutwiththeguideinthepilothole.

• Usethediagramonthefollowingpageforacceptableholecuttingareas.

Alwaysfollowyourcompanysafetyprocedureswhenperformingthisoperation.

Hole cut in long wall

Hole cut over rib on short wall

3

5

4

6

HOLE CUTTING INSTRUCTIONS

IM05v02©2016 Oldcastle, Inc.

1 2

oldcastleprecast.com/enclosuresolutions 559-675-1813IM05v02©2016 Oldcastle, Inc.

THE FOLLOWING MATERIAL PROPERTIES FOR POLYMER CONCRETE PRODUCTS WERE ESTABLISHED THROUGH INDEPENDENT THIRD PARTY TESTING:

COMPRESSIVE STRENGTHFLEXURAL STRENGTHMODULAS OF RUPTUREWATER ABSORPTIONIMPACT RESISTANCEFRICTION COEFFICIENTCHEMICAL RESISTANCE

ASTM C 579ASTM D 790ASTM C 99ASTM C 97ASTM D 2444ASTM C 1028ASTM D 543

> 12,500 PSI> 3,000 PSI≥ 3,000 PSI≤ 0.25%> 70 FT-LB> 0.5RESISTANT, > 75% RETENTIONPHYSICAL PROPERTIES

CONDUIT DRILLING GUIDELINES

NOTE: MINIMUM HOLE SEPARATION SHALL BE AT LEAST ONE_HALF (1/2) OF THE MINIMUM HOLE SIZE DIAMETER.

NOTES: CONDUIT PROVISIONS MAY BE DRILLED ANYWHERE WITHIN THE ACCEPTABLE PENETRATION AREA.QUANTITY OF ALLOWABLE PENETRATIONS VARIES BASED ON MIN HOLE SIZE AND MINIMUM HOLE SEPARATION.

MATERIAL PROPERTIES

ACCEPTABLE PENETRATION AREAS

LONG WALL(DEPTH VARIES - PC1730 SHOWN)

FLAT FLAT FLAT

SHORT WALL(DEPTH VARIES - 1730 SHOWN)