Challenges and Solutions in Microgrid Controls and Protection

Scott Manson

SEL ES Technology Director

Complexity

TimeInvention

Features

added

Reset

Recent microgrid advancements

Conventional solution

Advanced relay solution

Self-configuring communications

No tuning controls

Meter

Relay 25

Meter

Relay 25

Utility

Genset

Battery

PLC

LS

AVRGOV

ControllerPCPLC

Microgrid

controller

PCInverter

Meter

Relay

HMI

Microgrid controller

Recent microgrid advancements

Conventional solution

Advanced relay solution

Self-configuring communications

No tuning controls

Utility

Genset Inverter

Battery

Advanced

relay

Advanced

relay

Advanced

relay

Recent microgrid advancements

Conventional solution

Advanced relay solution

Self-configuring communications

No tuning controls

Hi! I’m a generator.

Great! Send me data.

Generation

relay

PCC relay

Tactical Microgrid Standard

Recent microgrid advancements

Conventional solution

Advanced relay solution

Self-configuring communications

No tuning controls

Tactical Microgrid Standard

Recent microgrid advancements

Conventional solution

Advanced relay solution

Self-configuring communications

No tuning controls

Frequency

(Hz)

Power

(kW)

60

58

56

30

0

15

Antiquated controlsState-space energy

packet controls

0 50 100 150 200250 30047

49

51

53

55

Isochronous mode

Generator tripAutomatic synchronization start

Circuit breaker open

Underfrequency Level 1

shed 0.93 MW

Oscillation start governor

Time (seconds)

Fre

qu

ency (

Hz)

Power (MW)

10 14 18

Microgrid instability caused by load efficiency improvement project

1 /

R (

MW

/ H

z)

0

Gain

0.02

0.04

0.06

0.08

1 10 100 1,000

Grid size (MW)

10,000

STG-A, -B, and -C

(50-fold)

STG-D

1

10

100

1,000

1 10 100 1,000

Grid size (MW)

10,000

Small grid

Large grid

Utility gridObserved

Predicted

Curve fit

Microgrid instability caused by load efficiency improvement project

PI

Variable load compositions negatively impact microgrid resiliency

Topology R –R DOL

1 60% 0% 40%

2 50% 50% 0%

P = V • IR =

I

V

Inverters create “twitchy” power systems

Power

Frequency

LoadPower,

frequency

Time

Rotating generation frequency

Rotating generation power

Inverter-based power

Inverter-based frequency

Mea

sure

d fre

quen

cy (

Hz)

60.04

60.02

60.00

59.98

59.96

59.94

Power (kW)

– 0 20 40– 60

Power (kW)

– 0 20 40

Synthetic inertia makes inverters difficult to dispatch

Correct behavior Actual behavior

Inverters produce less fault current than generators

Silicon limit time Stop commutation time

Inverter fault currents produce inconsistent Clark, Parks, and Sequence components

Inverter fault currents are restricted by inverter and battery health

Battery SoC

dynamic limits

Battery SoC

dynamic limits

Power systems are safer when inverters are controlled by programmable relays

Recording shows “day in the life of a relay”

Loads

Loads

PCC

SEL-751

655 15 25 35 45 55Time (cycles)

5,000

0Voltage (V)

500

0Current (A)

Recording shows “day in the life of a relay”

Recording shows “day in the life of a relay”

0.8 10.60.40.20Time (seconds)

59

60

Frequency

(Hz)

VAB

voltage

(kV rms)

0

20

0

700

IA

current

(A rms)

Relay trips

Fault starts

Breaker

opens

Microgrid controller

sheds load

Load current

is interrupted

Frequency recovers!

5 6 7 8 9 10

50.5

49.5

49

50

51

Time

Frequency

(Hz)

Nonresilient power systemcHIL simulation

Island 1

Island 2

Island 3Island 6

Island 5

Island 4

Same power system with SEL relay controlcHIL simulation

34 35 36 37 38 39

50.5

49.5

49

50

51

Time

Frequency

(Hz)

cHIL testing improves microgrid ROI

0 10 20 30 40 50 60–20K

–15K

–10K

–5K

0

5K

USD

Iteration

SDN simplifies security for critical infrastructure

Whitelisting

Minimal software

U.S. manufacturing

Mature processes

Vertical integration

Policy, plan, and procedure

SEL-2742S SDN Switch Additional SEL devices

Connect with us