Electric Reactor
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 3Electric Reactor 2
Reactor Selection Medium Voltage Shunt Reactor
Medium Voltage Series Reactor
Medium Voltage Starting Reactor
Low-voltage Series Reactor
Inlet and Outlet Reactors for Low Voltage Inverters
1. Medium Voltage Series Reactor
The product is connected in series with shunt capacitors, and has the functions of
compensating reactive power of power grid, increasing power factor, restraining
harmonic current and limiting switching inrush current. It is suitable for high fire
protection requirements such as power system, electrified railway, metallurgy and
petrochemical industry, electromagnetic interference requirements and installation
space limited urban power substation, underground substation. Stations and
substations controlled by computers.
Series reactor is also called damper reactor. Its function is to connect capacitors in
series, limit the closing inrush current in the circuit input, and effectively suppress
harmonic current according to different reactance rates. The series reactor developed
by our company has the following characteristics:
● The iron core reactor with air gap has good magnetic flux effect. The cold rolled silicon steel sheet has high permeability and stable reactance value;
● The use of new epoxy resin material, heat-resistant insulation up to F grade, is the ideal product for users to use safely and safely;
● Adopting advanced pouring technology, the product not only has beautiful appearance and harmonious color, but also has excellent mechanical properties, durable and impact resistance.
● Rated voltageUn: 3kV, 6kV, 10kV, 20kV, 35kV ;
● LinearityL: Under 1.8In, lss inductance XL≥0.95 ;
● Reactance ratioP: 0.85%, 1%, 4.5%, 5%, 6%, 12%, 13% ( Special reactance rate can also be customized according to customer requirements ) ;
● Maximum operating currentI max: It can operate stably for a long time under 1.35 ln;
● Insulation heat resistance grade: F grade ;
● Cooling mode: natural air-cooled AN ;
● Operating Conditions: -25°C…45°C, altitude1000m, humidity 90% (Higher can also be customized according to customer requirements) ;
● Outgoing mode: coil outgoing on the same side, coil outgoing on both sides, Out of coil insulator supports out wire.
● Linearity: under1.8Incondition, L≥0.95Ln, at1.2In, I=(I3+I5+I7……) lower than 35% rated current, Maintaining this linearity and can long-term stable operation;
● In normal operation, the core temperature rise of dry core reactor is not more than 85.000, and the coil temperature rise is not more than 95.000;
● The noise of rolled grain oriented silicon sheet meets the requirements of JB/T 5346-2014 IEC 60076-6:2011 series reactor standard.
● The insulation level parameters such as power frequency withstand voltage meet the requirements of relevant national standards, and can also be manufactured according to customer requirements.
Product Usage
Features
Electrical parameters
Electrical characteristics
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 5Electric Reactor 4
● GB/T 1094.1-2011 Power transformers Part 6: reactors
● DL 462-92 Technical Specifications for Order of Series Reactors for Medium Voltage Shunt Capacitors
● GB/T 1094.1-2011 Power Transformers Part 6: Reactors
● JB/T 5346-2014 Series Reactors for Medium Voltage Shunt Capacitors
● DL 462-92 Technical Specifications for Order of Series Reactors for Medium Voltage Shunt Capacitors
Standards
1. Selection of Reactance Rate of Series Reactor
The selection principle of reactance rate is to make the corresponding total reactance
value of the harmonic component with the highest proportion in the network
close to zero, that is to say, the reactance and capacitance reactance of the second
harmonic component should be close to equal, but it should be noted that Xc and
XL can not be exactly equal, in order to prevent electromagnetic resonance and lead
to over-voltage; Sensitive resistance is slightly greater than tolerant resistance.
If the system is dominated by 5th harmonic, then XL > Xc/52 = 0.04Xc. If the system
is dominated by 3rd harmonic, then XL > Xc/32 = 0.11Xc. Usually, 4.5%, 5% and 6%
of them pay attention to suppressing 5 or more harmonics, while 12% and 13%
mainly suppress 3 or more harmonics.
2. Selection of Rated Voltage of Distribution Capacitor for Reactor with Specific
Reactance Rate
After compensating capacitor is connected in series with reactor, the voltage of
capacitor will rise somewhat, Uc=Un/(1-P) ;
Among: Un: system voltage ;
Uc: Capacitor Voltage ;
P: Reactance ratio ;
For example: 10 kV voltage system, compensating reactor series reactance is 6%
reactor, Uc=10(kV)/(1-0.06)=10.64kV
Usually, the voltage Uc of the capacitor distributed by reactor with 0.85% and 1%
reactance is 1.05 Un, 4.5%, 5% and 6% reactance is 1.1Un, and that of reactor with
12% and 13% reactance is 1.2Un; for example, the voltage Uc of reactor distributed by
reactor with 10 kV reactance is 6%, Uc=1.1Un=10 3×1.1=11 3 kV ;
3. Reactor Capacity Selection
After knowing the system voltage and reactance rate, reactor capacity SL=Sc×P
among: SL: Reactor capacity Sc: Capacitor capacity P: Reactance ratio
Please submit the following parameters and technical requirements in writing
when ordering:
1. Reactor rated capacity
2. System rated voltage and frequency
3. Capacitor rated voltage
4. Rating reactance or reactance value
5. Rated Current and Maximum Continuous Current
6. Dynamic and thermal stable current and duration
7. Other special requirements Reactor Type Selection Requirements
Requirements for Order
Model description
Connection mode
Reactance ratio (%)
Rated voltage (kV)
capacity (kVar)
Epoxy casting
S: Three-phase D: Single-phase
Series reactor
Y-shaped connection
CK
C
K1
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 7Electric Reactor 6
ModelShunt capacitor
capacity(kvar)
CapacitorVoltage
(kV)
Ratedreactance
(%)
Ratedreactance
(Ω)
Ratedcurrent
(A)
Ratedcapacity
(kvar)
Rated loss
Size (mm)Icon Notes Weight(kg)L W H a b D
CKSC-5/10-5
100
11 3 5 61.07 5.2 5 124 730 450 645 400 350 12 95
CKSC-6/10-6 11 3 6 73.28 5.2 6 163 730 450 695 400 350 12 105
CKSC-12/10-12 12 3 12 173.2 4.8 12 273 790 450 795 430 350 14 160
CKSC-10/10-5
200
11 3 5 30.24 10.5 10 239 790 450 635 430 350 12 125
CKSC-12/10-6 11 3 6 36.29 10.5 12 275 790 450 700 430 350 12 140
CKSC-24/10-6 12 3 12 86.60 9.6 24 479 835 500 795 460 400 12 215
CKSC-15/10-5
300
11 3 5 20.23 15.7 15 305 805 450 680 440 350 12 145
CKSC-18/10-6 11 3 6 24.27 15.7 18 373 820 450 700 50 350 12 165
CKSC-36/10-12 12 3 12 57.74 14.4 36 647 865 500 860 480 400 12 270
CKSC-20/10-5
400
11 3 5 15.12 21 20 417 820 450 760 450 350 12 185
CKSC-24/10-6 11 3 6 18.15 21 24 478 835 500 750 460 400 12 200
CKSC-48/10-12 12 3 12 43.30 19.2 48 793 910 500 885 500 400 14 330
CKSC-25/10-5
500
11 3 5 12.12 26.2 25 483 835 500 805 460 400 12 215
CKSC-30/10-6 11 3 6 14.54 26.2 30 557 850 500 790 470 400 12 230
CKSC-60/10-12 12 3 12 34.50 24.1 60 947 955 500 925 530 400 14 390
CKSC-30/10-5
600
11 3 5 10.08 31.5 30 552 850 500 800 470 400 12 230
CKSC-36/10-6 11 3 6 12.10 31.5 36 647 880 500 785 480 400 12 255
CKSC-72/10-12 12 3 12 28.77 28.9 72 1080 970 500 945 530 400 14 430
CKSC-35/10-5
700
11 3 5 8.65 36.7 35 623 850 500 850 470 400 12 250
CKSC-42/10-6 11 3 6 10.38 36.7 42 723 910 500 820 500 400 14 300
CKSC-84/10-12 12 3 12 24.67 33.7 84 1215 985 500 995 540 400 14 485
CKSC-40/10-5
800
11 3 5 7.56 42 40 693 895 500 830 490 400 12 280
CKSC-48/10-6 11 3 6 9.07 42 48 798 910 500 865 500 400 14 320
CKSC-96/10-12 12 3 12 21.59 38.5 96 1345 1000 500 1020 550 400 14 525
CKSC-45/10-5
900
11 3 5 6.73 47.2 45 752 910 500 830 500 400 14 305
CKSC-54/10-6 11 3 6 8.07 47.2 54 879 955 500 855 530 400 14 355
CKSC-108/10-12 12 3 12 19.2 43.3 108 1467 1000 500 1060 550 400 14 545
CKSC-50/10-5
1000
11 3 5 6.05 52.5 50 823 910 500 875 500 400 14 325
CKSC-60/10-6 11 3 6 7.26 52.5 60 947 955 500 900 530 400 14 380
CKSC-120/10-12 12 3 12 17.28 48.1 120 1583 1015 500 1075 560 400 14 600
CKSC-60/10-5
1200
11 3 5 5.04 63 60 737 950 500 960 520 400 14 350
CKSC-72/10-6 11 3 6 6.05 63 72 868 1080 500 960 560 400 14 380
CKSC-144/10-12 12 3 12 14.37 57.8 144 1435 1110 500 1165 600 400 16 630
CKSC-75/10-5
1500
11 3 5 4.03 78.7 75 889 1080 500 985 560 400 14 420
CKSC-90/10-6 11 3 6 4.84 78.8 90 1075 1080 500 1090 560 400 14 480
CKSC-180/10-12 12 3 12 11.51 72.2 180 1587 1140 500 1190 620 400 16 830
CKSC-90/10-5
1800
11 3 5 3.36 94.5 90 1012 1080 500 1095 560 400 16 470
CKSC-108/10-6 11 3 6 4.03 94.5 108 1189 1080 500 1100 580 400 16 570
CKSC-216/10-12 12 3 12 9.6 86.6 216 2026 1200 550 1230 660 450 16 1105
ModelShunt capacitor
capacity(kvar)
CapacitorVoltage
(kV)
Ratedreactance
(%)
Ratedreactance
(Ω)
Ratedcurrent
(A)
Ratedcapacity
(kvar)
Rated loss
Size (mm)Icon Notes Weight(kg)L W H a b D
CKSC-120/10-5
2400
11 3 5 2.52 126 120 1305 1110 500 1055 600 400 16 640
CKSC-144/10-6 11 3 6 3.02 126 144 1435 1110 500 1120 600 400 16 695
CKSC-288/10-12 12 3 12 7.2 115.5 288 2487 1230 600 1275 700 500 16 1350
CKSC-135/10-5
2700
11 3 5 2.24 141.7 135 1394 1110 600 1170 600 500 16 680
CKSC-162/10-6 11 3 6 2.69 141.7 162 1580 1110 500 1180 620 400 16 795
CKSC-324/10-12 12 3 12 6.39 130.0 324 2570 1260 600 1385 700 500 16 1435
CKSC-150/10-5
3000
11 3 5 2.02 157.5 150 1478 1120 500 1215 600 400 16 725
CKSC-180/10-6 11 3 6 2.42 157.5 180 1614 1140 500 1160 620 400 16 820
CKSC-360/10-12 12 3 12 5.75 144.4 360 2745 1260 600 1380 700 500 16 1510
CKSC-165/10-5
3300
11 3 5 1.83 173.2 165 1585 1140 500 1175 620 400 16 800
CKSC-198/10-6 11 3 6 2.2 173.2 198 1880 1140 500 1205 620 400 16 915
CKSC-396/10-12 12 3 12 5.23 158.8 396 3194 1300 650 1340 750 550 16 1750
CKSC-180/10-5
3600
11 3 5 1.68 189 180 1745 1140 500 1170 620 400 16 880
CKSC-216/10-6 11 3 6 2.02 189 216 2004 1200 500 1250 660 400 16 1050
CKSC-432/10-12 12 3 12 4.8 173.3 432 3575 1330 650 1375 750 550 18 1870
CKSC-200/10-5
4000
11 3 5 1.51 210 200 1885 1140 500 1190 620 400 16 875
CKSC-240/10-6 11 3 6 1.81 210 240 2175 1200 550 1260 660 450 16 1090
CKSC-480/10-12 12 3 12 4.32 192.5 480 3690 1330 650 1495 750 550 18 2050
CKSC-210/10-5
4200
11 3 5 1.45 219.7 210 1995 1200 550 1235 660 450 16 1030
CKSC-252/10-6 11 3 6 1.74 220.5 252 2105 1200 550 1235 660 450 16 1220
CKSC-504/10-12 12 3 12 4.11 202.2 504 3915 1350 650 1420 780 550 18 2215
CKSC-225/10-5
4500
11 3 5 1.35 236.2 225 2105 1200 500 1240 660 400 16 1075
CKSC-270/10-6 11 3 6 1.61 236.2 270 2325 1260 600 1290 700 500 16 1370
CKSC-540/10-12 12 3 12 3.84 216.2 540 3934 1380 600 1510 780 500 18 2215
CKSC-240/10-5
4800
11 3 5 1.26 252 240 2145 1200 500 1305 660 400 16 1125
CKSC-288/10-6 11 3 6 1.51 252 288 2390 1260 600 1280 700 500 16 1405
CKSC-576/10-12 12 3 12 3.6 231 576 4218 1380 600 1570 780 500 18 2400
CKSC-250/10-5
5000
11 3 5 1.21 262 250 2090 1200 500 1310 660 400 16 1150
CKSC-300/10-6 11 3 6 1.45 262 300 2420 1260 600 1380 700 500 16 1445
CKSC-600/10-12 12 3 12 3.45 240.7 600 4415 1460 650 1520 830 550 18 2755
CKSC-270/10-5
5400
11 3 5 1.12 283.5 270 2382 1200 500 1330 700 400 16 1795
CKSC-324/10-6 11 3 6 1.34 283.5 324 2690 1260 600 1360 700 500 16 1485
CKSC-648/10-12 12 3 12 3.2 259.9 648 4715 1490 650 1560 830 550 18 2875
CKSC-300/10-5
6000
11 3 5 1.01 315 300 2434 1260 600 1320 700 500 16 1455
CKSC-360/10-6 11 3 6 1.21 315 360 2725 1260 600 1460 700 500 16 1590
CKSC-720/10-12 12 3 12 2.88 288.8 720 5055 1490 650 1570 830 550 18 3070
CKSC-330/10-5
6600
11 3 5 0.92 346.5 330 2625 1260 600 1350 700 500 16 1495
CKSC-396/10-6 11 3 6 1.1 346.5 396 3025 1330 650 1380 750 550 16 1865
CKSC-792/10-12 12 3 12 2.62 317.7 792 5615 1520 700 1690 880 600 18 3665
Technical parameters and dimensions
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.
Electric Reactor 9
Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 8
ModelShunt capacitor
capacity(kvar)
CapacitorVoltage
(kV)
Ratedreactance
(%)
Ratedreactance
(Ω)
Ratedcurrent
(A)
Ratedcapacity
(kvar)
Rated loss
Size (mm)Icon Notes Weight(kg)L W H a b D
CKSC-350/10-5
7000
11 3 5 0.86 367.5 350 2675 1260 600 1430 700 500 16 1535
CKSC-420/10-6 11 3 6 1.04 367.5 420 3335 1330 650 1480 750 550 18 1975
CKSC-840/10-12 12 3 12 2.47 336.9 840 5805 1540 700 1620 880 600 18 3750
CKSC-360/10-5
7200
11 3 5 0.84 378 360 2680 1250 600 1470 700 500 16 1600
CKSC-432/10-6 11 3 6 1.01 378 432 3395 1330 650 1530 750 550 18 2035
CKSC-864/10-12 12 3 12 2.4 346.6 864 5995 1540 700 1620 880 600 18 3950
CKSC-390/10-5
7800
11 3 5 0.78 409.4 390 3395 1260 600 1470 700 500 16 1673
CKSC-468/10-6 11 3 6 0.93 409.4 468 3515 1330 650 1490 750 550 18 2080
CKSC-936/10-12 12 3 12 2.22 375.5 936 6175 1600 700 1750 910 600 18 4105
CKSC-400/10-5
8000
11 3 5 0.76 416 400 3395 1330 650 1490 750 550 18 2010
CKSC-480/10-6 11 3 6 0.91 416 480 3585 1360 650 1540 750 550 18 2150
CKSC-960/10-12 12 3 12 2.16 385.1 960 6370 1600 700 1770 910 600 18 4430
Note: 1. Dimensions in the table are for reference. Manufacturing is based on the size confirmed by the outline drawing. Reactors with special specifications and sizes can also be manufactured as required by customers.
2. For single-phase products, please consult our company.
● Shape size of dry series reactor above 100 kvar ● Shape size of dry series reactor below 100kvar
2. Medium Voltage Starting Reactor
Start-up reactor is a kind of current-limiting reactor specially used for step-down
starting of large-scale asynchronous motor, which is connected in series with
three-phase windings of three-phase asynchronous motor, i.e., each phase winding
of reactor and motor winding are connected in series to form Y or D connection.
When the motor starts, the reactor is switched on and off to limit the starting
current of the motor to the appropriate value. When the impedance is small and
the current is large, the starting current is about 5 times the rated current, and the
voltage mainly falls on the reactor. After the start-up, the reactor is removed and
the power supply voltage of the motor restores to the normal rated voltage.
The design of starting reactor suitable for 3kV, 6kV and 10kV can be operated
continuously for 2 minutes and restarted after 6 hours interval. If the starting
requirement exceeds this condition, it should be explained when ordering.
The iron core starter reactor designed and manufactured by our company has the
following characteristics:
● Flame retardant, fire-proof, explosion-proof, high safety in use;
● The coil is poured by epoxy vacuum, and the winding forms a rigid whole of sealing and moisture-proof. The air is self-cooled. It can be started directly at the initial installation and operates for a long time without maintenance.
● Long service life, can meet the 30 years of thermal aging life cycle.
● The product has good thermal stability and strong overload capacity.
● Compared with the traditional oil-immersed reactor and air-core reactor, the dry-core starter reactor has the advantages of light weight, small space occupation, simple structure and convenient installation.
● The insulation temperature level reaches F grade (155 °C). Under normal operation, the core temperature rise of the dry core startup reactor is not more than 85K, and the coil temperature rise is not more than 95K.
● The loss of dry core starter reactor is lower than that of oil-immersed reactor.
● Altitude not exceeding1000m (Over 1000m altitude, must be mentioned when ordering );
● Operating ambient temperature: 25°C~+45°C;
● Installation in the house, without any violent vibration, harmful gas or dust. Cannot installation of nearby inflammable and explosive articles;
● When the start-up time is 2 minutes (once or several times accumulated), it should be cooled for 6 hours before starting again.
● IEC 60076-6: 2007
● GB 1094.6-2011 Power transformers Part 6: reactors
Product Usage
Feature
Conditions of Use
Standards
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 11Electric Reactor 10
Rated voltage(kV)
Starting capacity(kvar)
Epoxy casting
S: Three-phase D: Single-phase
Start-up reactor
1. Determination of Start-up VoltageStart-up reactor phase voltage is determined by the formula below:
among:UxN: Rated line voltage of three-phase AC motor (V);
Kxj: When starting, the minimum required torque of the motor is a multiple of the rated torque, When the motor power is 0.6-100 kW, Kxj=0.8, Other general chooseKxj=0.6;
Kqj: Initial starting torque of AC motor is multiple of rated torque under rated voltage, Kqj=0.9~2.5, Details of the determined values are shown in the selected motor sample parameters.
2. Determination of Start CurrentStart-up reactor current is determined by the formula below:
Amount: IN:Rated current of AC motor(A);KqL: Under rated voltage, the starting current of AC motor is multiple of rated current.
3. Start-up reactor reactance per phase(XL'): XL=UL/IL(Ω)
4. Determination of Start-up Capacity: SL=3×UL×IL (kVA)
5. Start-up reactor has a tap besides rated reactance value (XL). The reactance value (XLi) at the tap is generally 0.85 times that of rated reactance value (XL), that is, XLi=0.85×XL. The tap reactance value can also be manufactured according to customer's requirements.
Please submit the following parameters and technical requirements in writing
when ordering:
1, Power of Starting Motor
2, System rated voltage and frequency
3, Rated Current of Motor and Start Percentage of Reduced Voltage of Motor
4, Dynamic and thermal stable current and duration
5, Other special requirements
Reactor Type Selection Requirements
Requirements for Order
Model description
Asynchronous motor
K2
K1
CK
ModelRated
voltagekV
Type capacity
kvar
Startup current
A
Rated reactance
Ω
Motor power
kW
Installation dimensions Reference weight
kgL W H a b D
QKSC-355/6.6 6.6 355 88.3 15.11 272 750 400 720 400 300 18 180
QKSC-385/6.6 6.6 385 95.2 14.01 292 750 400 710 400 300 18 185
QKSC-420/6.6 6.6 420 104.4 12.78 353 780 450 700 400 350 18 220
QKSC-505/6.6 6.6 505 125.5 10.63 390 780 450 720 400 350 18 230
QKSC-550/6.6 6.6 550 136.4 9.78 419 780 450 790 400 350 18 240
QKSC-650/6.6 6.6 650 161.8 8.24 507 795 450 810 400 350 18 280
QKSC-670/6.6 6.6 670 166.8 8.0 546 795 450 815 400 350 18 285
QKSC-745/6.6 6.6 745 185.2 7.2 575 795 450 820 400 350 18 290
QKSC-800/6.6 6.6 800 200 6.67 617 795 450 880 400 350 18 300
QKSC-840/6.6 6.6 840 209.6 6.36 658 795 450 885 400 350 18 310
QKSC-905/6.6 6.6 905 225.4 5.92 704 825 450 820 450 350 18 320
QKSC-945/6.6 6.6 945 236 5.65 750 825 450 880 450 350 18 350
QKSC-1065/6.6 6.6 1065 265.5 5.02 850 825 450 890 450 350 18 355
QKSC-1140/6.6 6.6 1140 284.5 4.69 900 825 450 940 450 350 18 370
QKSC-1210/6.6 6.6 1210 301.9 4.42 1000 870 450 860 450 350 18 410
QKSC-1480/6.6 6.6 1480 369.7 3.61 1200 870 450 920 450 350 18 430
QKSC-1550/6.6 6.6 1550 387 3.45 1300 870 450 950 450 350 18 450
QKSC-1845/6.6 6.6 1845 460.2 2.9 1500 915 450 1010 500 350 18 550
QKSC-1980/6.6 6.6 1980 494.7 2.7 1650 915 450 1015 500 350 18 560
QKSC-2170/6.6 6.6 2170 542.3 2.46 1750 945 500 990 500 400 18 600
QKSC-2600/6.6 6.6 2600 648.9 2.06 2000 945 500 1040 500 400 18 620
QKSC-2965/6.6 6.6 2965 740 1.8 2250 990 500 1080 550 400 18 730
QKSC-3300/6.6 6.6 3300 824.1 1.62 2500 990 500 1150 550 400 18 770
Connection mode
Technical parameters and dimensions
Specification, Model and Size of 6.6kV Voltage Start Reactor
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.
Electric Reactor 13
Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 12
ModelRated
voltagekV
Type capacity
kvar
Startup current
A
Rated reactance
Ω
Motor power
kW
Installation dimensions Reference weight
kgL W H a b D
QKSC-690/10 10 690 113.5 17.85 507 885 450 960 450 350 18 270
QKSC-755/10 10 755 124.5 16.23 546 885 450 960 450 350 18 360
QKSC-835/10 10 835 126.7 15.95 575 885 450 970 450 350 18 370
QKSC-900/10 10 900 148.1 13.65 658 885 450 970 450 350 18 375
QKSC-945/10 10 945 155.8 12.97 704 885 450 975 450 350 18 375
QKSC-1025/10 10 1025 169 11.96 750 915 450 950 500 350 18 390
QKSC-1105/10 10 1105 181.9 11.11 800 915 450 980 500 350 18 410
QKSC-1160/10 10 1160 190.9 10.59 850 915 450 980 500 350 18 415
QKSC-1165/10 10 1165 191.5 10.55 900 915 450 980 500 350 18 415
QKSC-1360/10 10 1360 224 9.02 1000 945 450 950 500 350 18 450
QKSC-1520/10 10 1520 250.3 8.07 1100 945 450 1020 500 350 18 490
QKSC-1640/10 10 1640 269.9 7.49 1200 990 450 960 550 350 18 540
QKSC-1775/10 10 1775 292.4 6.91 1300 990 450 970 550 350 18 545
QKSC-1915/10 10 1915 315.7 6.4 1400 990 450 990 550 350 18 550
QKSC-2070/10 10 2070 340.8 5.93 1500 990 450 995 550 350 18 555
QKSC-2290/10 10 2290 377 5.36 1650 1020 500 1000 550 400 18 620
QKSC-2465/10 10 2465 405.9 4.98 1750 1020 500 1060 550 400 18 660
QKSC-2760/10 10 2760 454.6 4.45 2000 1020 500 1120 550 400 18 690
QKSC-3055/10 10 3055 503.7 4.01 2250 1050 500 1130 600 400 18 770
QKSC-3390/10 10 3390 558.7 3.62 2500 1050 500 1160 600 400 18 790
Note:
1. The specifications in the table correspond to 65% step-down starting of the motor, reserve 80% step-down starting tap. The dimensions in the table are for reference. The size of the fabrication is confirmed by the outline drawing. The reactor with special specifications can also be manufactured according to customer's requirements.
2. For single-phase products, please consult our company.
● Shape size of dry start reactor
3. Medium Voltage Shunt Reactor
Parallel reactor refers to the reactor connected in parallel with line load, which is used
in power system. Its main function is to restrain the line terminal voltage rise caused
by line capacitive reactive power when transmission line is under light load. At the
same time, the input of parallel reactor can reduce the secondary current when system
grounding fault occurs, which is beneficial to eliminating generators. Self-excitation
and other functions.
The shunt reactor can operate safely for a long time at the highest voltage of the
system. For the iron core shunt reactor, the accuracy of reactance value is required
to be high, and the inductance reduction of the shunt reactor at the rated voltage of
150% system is not more than 5%.
Our company designed and manufactured parallel reactor iron core column whole
vacuum pouring, high reactance value accuracy, low loss, low noise, strong structure.
Our company designed and manufactured iron core start reactor insulation heat
resistance grade F, and has the following characteristics:
● Flame retardant, fire-proof, explosion-proof, high safety in use;
● The coil is poured by epoxy vacuum, and the winding forms a rigid whole of sealing and moisture-proof. The air is self-cooled. It can be started directly at the initial installation and operates for a long time without maintenance.
● Long service life, can meet the 30 years of thermal aging life cycle;
● The product has good thermal stability and strong overload capacity.
GB 1094.6-2011 Power transformers Part 6: reactors
JB/T 10775 Parameters and Requirements of 6KV-35KV Dry Parallel Reactor
● Rated voltage: 6kV, 10kV, 35kV
● LinearityL: Under1.5In, lss inductance XL≥0.95
● Maximum operating currentImax: Long-term stable operation under 1.2In
● Insulation heat resistance grade: F grade
● Cooling mode: natural air-cooled AN
● Operating Conditions: -25°C~+45°C, Altitude1000m, humidity90% (Higher can also be customized according to customer requirements)
● Outgoing mode: coil side outgoing mode, Out of coil insulator supports out wire
● Connection Group Number: Y Connection, D Connection
Product Usage
Feature
Standards
Electrical parameters
Specification, model size of 10kV start-up reactor
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 15Electric Reactor 14
Model description
Connection mode
Rated voltage(kV)
capacity(kvar)
Epoxy casting
S: Three-phase D: Single-phase
Start-up reactor
Please submit the following parameters and technical requirements in writing
when ordering:
1, Single-phase shunt reactor/three-phase shunt reactor
2, Rated voltage and maximum operating voltage
3, Rated capacity
4, Rated current
5, Rated reactance
6, Cooling mode(AN)
7, Conditions of Use (in-house)
8, Other special requirements
Requirements for Order
Model
Reactorcapacity
(kvar)
Ratedvoltage
(kV)
OperatingVoltage
(kV)
Maxoperating
voltage(kV)
Ratedreactance
(Ω)
Ratedcurrent
(A)
ConnectionGroups
Ratedloss(W)
Size (mm) Icon NotesWeight
(kg)L W H a b D
BKSC-25/10 25 10 10.5 12 4408.9 1.375 Y 710 820 560 785 450 400 12 240
BKSC-50/10 50 10 10.5 12 2205.2 2.749 Y 1000 850 560 910 470 400 14 360
BKSC-100/10 100 10 10.5 12 1102.4 5.449 Y 1390 955 560 970 530 400 14 575
BKSC-150/10 150 10 10.5 12 734.99 8.248 Y 1890 1000 560 1150 550 400 14 825
BKSC-200/10 200 10 10.5 12 551.26 10.997 Y 2340 1030 560 1210 570 400 14 980
BKSC-250/10 250 10 10.5 12 441.02 13.746 Y 2770 1075 560 1260 590 400 16 1160
BKSC-300/10 300 10 10.5 12 367.5 16.496 Y 3170 1105 600 1265 610 420 16 1250
BKSC-350/10 350 10 10.5 12 315.0 19.245 Y 3560 1150 600 1290 630 420 16 1460
BKSC-400/10 400 10 10.5 12 275.63 21.994 Y 3940 1165 600 1305 640 420 16 1550
BKSC-450/10 450 10 10.5 12 245.01 24.743 Y 4300 1210 600 1375 670 420 16 1675
BKSC-500/10 500 10 10.5 12 220.5 27.493 Y 4650 1270 650 1380 700 460 16 1965
BKSC-600/10 600 10 10.5 12 183.75 32.991 Y 5330 1315 650 1395 720 460 18 2310
BKSC-700/10 700 10 10.5 12 157.5 38.49 Y 5990 1330 650 1440 730 460 18 2535
BKSC-800/10 800 10 10.5 12 137.81 43.988 Y 6620 1360 680 1470 750 520 18 2770
BKSC-900/10 900 10 10.5 12 122.5 49.487 Y 7230 1420 680 1510 780 520 18 3110
BKSC-1000/10 1000 10 10.5 12 110.25 54.986 Y 7820 1435 680 1590 790 520 18 3395
Note:
1. Dimensions in the table are for reference. Manufacturing is based on the size confirmed by the outline drawing. Reactors with special specifications and sizes can also be manufactured as required by customers.
2. For single-phase products, please consult our company
Technical parameters and dimensions
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.
Electric Reactor 17
Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 16
● Shape diagram of dry shunt reactor (△Connection)
● Shape diagram of dry shunt reactor (Y-Connection)
CK □ G - □ / □ - □
4. Low-voltage Series Reactor
With the development of modern power industry, power electronic equipments
are widely used. Power electronic equipments are non-linear loads. The harmonic
currents generated by power electronic equipments are harmful to the power grid.
They will cause serious interference to measuring, driving and calculating equipments.
The harmonic and voltage distortion will also cause power supply accidents. The
resonant frequency of low voltage series reactor with shunt capacitor is capacitive at
power frequency to change the power factor of power frequency, while the resonant
frequency is inductive, so as to prevent parallel resonance and suppress harmonics.
● Low loss
● Low noise
● Closing inrush current of high suppression circuit
● Strong Harmonic Suppression Ability
● Natural cooling
● Normal Closed Temperature Protection (Optional)
● Standards: IEC 289, GB 1094.6, GB 9644 and etc.
● Insulation heat resistance grade: H (180 degrees)
● Phase Number: Single Phase and Three Phase
● Rated Frequency: 50/60HZ
● system voltage: 230V, 400V, 690V
● Rated voltage of matching capacitor: 250V, 440V, 450V, 480V, 525V, 720V, 780V
● Rated reactance rate: 1%, 5.67%, 6%, 7%, 12%, 13%, 14%
● Operating environment: -25/45°C, Average temperature does not exceed 40 °C
● Continuous operation of 135% rated current, temperature rise not exceeding 95K (resistance test)
● Permissible error of reactance value: 0~+10%;
● Maximum operating current: below 35% of third, fifth and seventh harmonics and below 120% of effective current
Product Usage
Feature
Standards
Product range
Reactance ratio (%)
Rated voltage (kV)
Rated capacity (kvar)
Dry
S: Three-phase D: Single-phase
Series reactor
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 19Electric Reactor 18
orderProduct Model
(TYPE)Capacitor
rated capacity(kvar)
Capacitorrated voltage
( V )
inductance(mH)
overall dimension(mm)
L×W×H
Installationdimensions (mm)
E×F
1 CKSG-0.6/0.4-6 10 450 3.882 180×140×186 160×100
2 CKSG-0.9/0.4-6 15 450 2.588 180×140×187 160×100
3 CKSG-1.2/0.4-6 20 450 1.941 180×165×197 160×115
4 CKSG-1.5/0.4-6 25 450 1.584 180×165×198 160×115
5 CKSG-1.8/0.4-6 30 450 1.290 180×170×198 160×115
6 CKSG-2.1/0.4-6 35 450 1.106 210×155×241 190×105
7 CKSG-2.4/0.4-6 40 450 0.968 220×175×255 190×120
8 CKSG-2.7/0.4-6 45 450 0.861 225×185×255 200×120
9 CKSG-3.0/0.4-6 50 450 0.775 225×180×256 200×120
10 CKSG-3.3/0.4-6 55 450 0.705 225×200×266 200×135
11 CKSG-3.6/0.4-6 60 450 0.646 225×200×266 200×135
12 CKSG-3.9/0.4-6 65 450 0.596 225×205×267 200×135
13 CKSG-4.2/0.4-6 70 450 0.554 300×235×265 280×150
14 CKSG-4.5/0.4-6 75 450 0.517 300×235×265 280×150
15 CKSG-4.8/0.4-6 80 450 0.484 300×240×265 280×150
16 CKSG-5.1/0.4-6 85 450 0.456 300×240×265 280×150
17 CKSG-5.4/0.4-6 90 450 0.431 300×240×265 280×150
Y-connection
K1
CK
C
Wiring method
Technical parameters and dimensions(The way of wire going out can be changed according to customer's requirements)
Three-phase rated voltage 450V rated reactance rate 6%
orderProduct Model
(TYPE)Capacitor
rated capacity(kvar)
Capacitorrated voltage
( V )
inductance(mH)
overall dimension(mm)
L×W×H
Installationdimensions (mm)
E×F
1 CKSG-0.7/0.4-7 10 480 5.149 180×140×186 160×100
2 CKSG-1.05/0.4-7 15 480 3.432 180×160×197 160×115
3 CKSG-1.4/0.4-7 20 480 2.564 180×165×197 160×115
4 CKSG-1.75/0.4-7 25 480 2.053 180×165×198 160×115
5 CKSG-2.1/0.4-7 30 480 1.711 210×155×241 190×105
6 CKSG-2.45/0.4-7 35 480 1.468 220×175×255 190×120
7 CKSG-2.8/0.4-7 40 480 1.284 220×175×255 190×120
8 CKSG-3.15/0.4-7 45 480 1.142 225×185×256 200×120
9 CKSG-3.5/0.4-7 50 480 1.028 225×200×266 200×135
10 CKSG-3.85/0.4-7 55 480 0.933 225×200×267 200×135
11 CKSG-4.2/0.4-7 60 480 0.856 225×200×291 200×135
12 CKSG-4.55/0.4-7 65 480 0.790 225×210×291 200×145
13 CKSG-4.9/0.4-7 70 480 0.734 225×210×291 200×145
14 CKSG-5.25/0.4-7 75 480 0.685 300×235×265 280×150
15 CKSG-5.6/0.4-7 80 480 0.642 300×235×266 280×150
16 CKSG-5.95/0.4-7 85 480 0.604 300×240×266 280×150
17 CKSG-6.3/0.4-7 90 480 0.571 300×240×266 280×150
orderProduct Model
(TYPE)Capacitor
rated capacity(kvar)
Capacitorrated voltage
( V )
inductance(mH)
overall dimension(mm)
L×W×H
Installationdimensions (mm)
E×F
1 CKSG-1.2/0.4-12 10 525 10.539 180×160×197 160×115
2 CKSG-1.8/0.4-12 15 525 7.026 195×150×241 170×105
3 CKSG-2.4/0.4-12 20 525 5.269 210×165×255 190×120
4 CKSG-3.0/0.4-12 25 525 4.215 210×170×255 190×120
5 CKSG-3.6/0.4-12 30 525 3.513 210×195×266 190×135
6 CKSG-4.2/0.4-12 35 525 3.011 210×200×291 190×145
7 CKSG-4.8/0.4-12 40 525 2.635 210×200×291 190×145
8 CKSG-5.4/0.4-12 45 525 2.342 300×225×265 280×150
9 CKSG-6.0/0.4-12 50 525 2.111 300×235×325 280×150
10 CKSG-6.6/0.4-12 55 525 1.919 300×240×326 280×170
11 CKSG-7.2/0.4-12 60 525 1.759 300×240×326 280×170
12 CKSG-7.8/0.4-12 65 525 1.624 300×240×326 280×170
13 CKSG-8.4/0.4-12 70 525 1.507 300×245×326 280×170
14 CKSG-9.0/0.4-12 75 525 1.407 300×245×237 280×170
Three-phase rated voltage 480V rated reactance rate 7%
Three-phase rated voltage 525V rated reactance rate 12%
Note: 1. Shape size is for reference. The size is determined by technical agreement contract.2. For single-phase products, please consult our company
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.
Electric Reactor 21
Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 20
● Diagram of low-voltage series reactor
Rated inductance (mH)
Rated current (A)
Rated voltage (kV)
"I" Input reactor; "O"Output reactor
Reactor
CKSG □ - □ - □ / □
5. Inlet and Outlet Reactors for Low Voltage Inverters
With the rapid development of power electronics technology, AC variable frequency speed regulation has become the mainstream of electric drive since 1990s, and its application scope is increasingly widespread. But because the frequency converter is used in various electrical environments, if appropriate protection measures are not taken, the stability and reliability of the frequency converter will be affected. Practice has proved that proper selection of distribution reactor and frequency converter can effectively prevent the impact of overvoltage and surge current caused by the operation of AC incoming switch, reduce the harmonic pollution of power grid caused by frequency converter, and improve the power factor of frequency converter.
● High linearity characteristic;● Low loss;● Low noise;● Simple installation;● Long service life.
● Standards: IEC 289, GB 1094.6, JB/T 9644 and etc.● Insulation heat-resistant grade: H (180 degrees);● Phase number: three-phase;● System voltage: 380V, 400V, 660V system;● Operating environment: -25/45°C, Average temperature not exceeding40°C.
● Input reactor: also known as power supply coordination reactor, its main function is to suppress the sudden change of grid voltage and the current impact caused by overvoltage operation, effectively protect the frequency converter and improve its power factor;
● Output reactor: Connected between the output end of the converter and the load (motor), it can suppress the noise of the converter and filter the high-frequency harmonics into the motor, reduce the leakage current caused by the input high-order harmonics, smooth filter, reduce the transient voltage dv/dt, prolong the service life of the motor, reduce the noise of the motor and reduce the eddy current loss. Protect the power switching elements inside the frequency converter.
Product Usage
Feature
Standards
Product parameters
Product Classification
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 23Electric Reactor 22
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGI-0.38-5/2.8 A 1.5 5 2.8 2% 3 135 120 110 110 80 12
CKSGI-0.38-7/2 A 2.2 7 2 2% 2 135 120 110 110 80 12
CKSGI-0.38-10/1.4 A 3.7 10 1.4 2% 2 135 120 110 110 80 12
CKSGI-0.38-15/0.93 A 5.5 15 0.93 2% 3 150 120 110 130 80 12
CKSGI-0.38-20/0.7 A 7.5 20 0.7 2% 4 165 130 130 140 90 12
CKSGI-0.38-30/0.47 A 11 30 0.47 2% 5 165 130 135 140 90 12
CKSGI-0.38-40/0.35 A 15 40 0.35 2% 5 180 130 135 160 90 12
CKSGI-0.38-50/0.28 A 18.5 50 0.28 2% 8 180 140 160 160 100 12
CKSGI-0.38-60/0.24 A 22 60 0.24 2% 8 180 140 185 160 100 12
CKSGI-0.38-90/0.16 A 37 90 0.16 2% 13 315 170 200 295 130 12
CKSGI-0.38-120/0.12 B 45 120 0.12 2% 19 360 190 235 340 150 12
CKSGI-0.38-150/0.095 B 55 150 0.095 2% 22 360 200 280 340 160 12
CKSGI-0.38-200/0.07 B 75 200 0.07 2% 37 465 235 300 445 195 12
CKSGI-0.38-250/0.056 B 110 250 0.056 2% 44 465 245 365 445 205 12
CKSGI-0.38-290/0.048 B 132 290 0.048 2% 50 465 245 415 445 205 12
CKSGI-0.38-330/0.042 B 160 330 0.042 2% 58 465 245 480 445 205 12
CKSGI-0.38-390/0.036 B 185 390 0.036 2% 85 570 285 495 555 245 12
CKSGI-0.38-490/0.028 B 220 490 0.028 2% 108 570 295 505 555 255 12
CKSGI-0.38-530/0.026 B 240 530 0.026 2% 112 570 305 505 550 265 12
CKSGI-0.38-600/0.023 B 280 600 0.023 2% 130 570 305 550 550 265 12
CKSGI-0.38-660/0.021 B 300 660 0.021 2% 135 575 310 550 560 270 12
CKSGI-0.38-800/0.017 B 380 800 0.017 2% 140 575 310 550 560 270 12
CKSGI-0.38-1000/0.014 B 450 1000 0.014 2% 150 580 330 570 560 290 12
CKSGI-0.38-1250/0.011 B 550 1250 0.011 2% 170 580 330 570 560 290 12
CKSGI-0.38-1600/0.0087 B 630 1600 0.0087 2% 200 600 350 590 580 310 12
Note: Selection Table of 380V Input AC Reactor (4% Voltage Drop) (Refer to Selection Table of 690V Input AC Reactor (2% Voltage Drop)
Technical parameters and dimensions
1, Input reactor
● Selection Table of 380V Input AC Reactor (2% Voltage Drop)
Note: Selection Table of 690V Input AC Reactor (3% Voltage Drop) (Refer to Selection Table of 1140V Input AC Reactor (2% Voltage Drop)
● Selection Table of 690V Input AC Reactor (2% Voltage Drop)
● Selection Table of 1140V Input AC Reactor (2% Voltage Drop)
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltaz vvge drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGI-0.69-15/1.7 A 15 15 1.7 2% 5 180 130 135 160 90 12
CKSGI-0.69-25/1.05 A 22 25 1.05 2% 5 180 130 135 160 90 12
CKSGI-0.69-35/0.73 A 37 35 0.73 2% 9 225 140 155 200 100 12
CKSGI-0.69-55/0.465 A 45 55 0.465 2% 11 235 150 155 210 110 12
CKSGI-0.69-70/0.365 A 55 70 0.365 2% 14 240 150 180 220 110 12
CKSGI-0.69-90/0.285 A 75 90 0.285 2% 18 270 160 185 250 120 12
CKSGI-0.69-125/0.2 B 90 125 0.2 2% 25 310 165 200 280 120 12
CKSGI-0.69-160/0.16 B 110/132 160 0.16 2% 27 330 200 285 310 160 12
CKSGI-0.69-200/0.125 B 160 200 0.125 2% 32 330 200 300 310 160 12
CKSGI-0.69-250/0.105 B 220 250 0.105 2% 38 330 200 305 280 160 12
CKSGI-0.69-300/0.085 B 250 300 0.085 2% 44 330 200 310 290 160 12
CKSGI-0.69-400/0.065 B 315/355 400 0.065 2% 56 330 210 315 290 170 12
CKSGI-0.69-500/0.05 B 450 500 0.05 2% 60 330 220 320 300 180 12
CKSGI-0.69-650/0.04 B 500/560 650 0.04 2% 65 330 220 325 300 180 12
CKSGI-0.69-800/0.032 B 630/750 800 0.032 2% 75 350 230 340 310 190 12
CKSGI-0.69-950/0.027 B 800 950 0.027 2% 85 350 230 340 310 190 12
CKSGI-0.69-1200/0.021 B 900/1000 1200 0.021 2% 105 400 250 380 350 210 12
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGI-1.14-25/1.7 A 37 25 1.7 2% 9 210 140 160 190 100 12
CKSGI-1.14-35/1.25 A 55 35 1.25 2% 12 240 145 165 220 105 12
CKSGI-1.14-55/0.78 A 75 55 0.78 2% 18 265 160 185 240 120 12
CKSGI-1.14-65/0.65 A 90 65 0.65 2% 18 265 160 185 240 120 12
CKSGI-1.14-80/0.54 A 110 80 0.54 2% 23 270 165 210 250 125 12
CKSGI-1.14-90/0.48 A 132 90 0.48 2% 25 325 165 225 300 125 12
CKSGI-1.14-120/0.36 B 160 120 0.36 2% 32 340 170 330 320 130 12
CKSGI-1.14-150/0.29 B 200 150 0.29 2% 37 340 180 335 320 140 12
CKSGI-1.14-200/0.22 B 250 200 0.22 2% 48 400 200 390 380 160 12
CKSGI-1.14-230/0.19 B 315 230 0.19 2% 52 400 200 390 380 160 12
CKSGI-1.14-260/0.17 B 400 260 0.17 2% 60 400 205 390 280 165 12
CKSGI-1.14-300/0.14 B 450 300 0.14 2% 67 400 205 395 380 165 12
CKSGI-1.14-350/0.12 B 500 350 0.12 2% 75 465 230 445 445 190 12
CKSGI-1.14-420/0.10 B 630 420 0.1 2% 85 465 240 460 445 200 12
CKSGI-1.14-500/0.087 B 710 500 0.087 2% 95 480 260 470 460 220 12
CKSGI-1.14-570/0.075 B 800 570 0.075 2% 1.1 480 260 475 460 220 12
CKSGI-1.14-660/0.065 B 1000 660 0.065 2% 1.3 500 280 490 480 240 12
CKSGI-1.14-800/0.054 B 1200 800 0.054 2% 1.5 540 300 530 520 260 12
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 25Electric Reactor 24
Note:
1. Selection Table of 380V Output AC Reactor (2% Voltage Drop) (Refer to Selection Table of 690V Output AC Reactor (1% Voltage Drop)
2. Selection Table of 380V Output AC Reactor (3% Voltage Drop) (Refer to Selection Table of 1140V Output AC Reactor (1% Voltage Drop)
3. Selection Table of 380V Output AC Reactor (4% Voltage Drop) (Refer to Selection Table of 690V Output AC Reactor (2% Voltage Drop)
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGO-0.38-5/1.4 A 1.5 5 1.4 1% 1 130 115 95 100 75 12
CKSGO-0.38-7/1.0 A 2.2 7 1 1% 1 130 115 95 100 75 12
CKSGO-0.38-10/0.7 A 3.7 10 0.7 1% 1 130 115 95 100 75 12
CKSGO-0.38-15/0.47 A 5.5 15 0.47 1% 2 130 115 95 100 75 12
CKSGO-0.38-20/0.35 A 7.5 20 0.35 1% 2 155 125 110 130 85 12
CKSGO-0.38-30/0.23 A 11 30 0.23 1% 5 180 130 135 140 90 12
CKSGO-0.38-40/0.18 A 15 40 0.18 1% 5 180 130 135 140 90 12
CKSGO-0.38-50/0.14 A 18.5 50 0.14 1% 5 180 130 135 140 90 12
CKSGO-0.38-60/0.12 A 22 60 0.12 1% 5 180 130 135 140 90 12
CKSGO-0.38-80/0.087 A 30 80 0.087 1% 8 210 140 160 170 100 12
CKSGO-0.38-90/0.78 A 37 90 0.78 1% 8 210 140 160 170 100 12
CKSGO-0.38-120/0.58 B 45 120 0.58 1% 14 260 150 180 220 110 12
CKSGO-0.38-150/0.047 B 55 150 0.047 1% 11 280 160 235 240 120 12
CKSGO-0.38-200/0.035 B 75 200 0.035 1% 12 280 160 275 240 120 12
CKSGO-0.38-250/0.028 B 110 250 0.028 1% 17 280 170 280 240 130 12
CKSGO-0.38-290/0.024 B 132 290 0.024 1% 19 280 170 280 240 130 12
CKSGO-0.38-330/0.021 B 160 330 0.021 1% 22 280 175 280 240 135 12
CKSGO-0.38-390/0.018 B 185 390 0.018 1% 24 295 185 290 255 145 12
CKSGO-0.38-490/0.014 B 220 490 0.014 1% 29 295 195 290 255 155 12
CKSGO-0.38-530/0.013 B 250 530 0.013 1% 36 355 225 360 310 185 12
CKSGO-0.38-600/0.012 B 280 600 0.012 1% 41 355 225 360 310 185 12
CKSGO-0.38-660/0.011 B 300 660 0.011 1% 45 355 225 380 310 185 12
CKSGO-0.38-800/0.0087 B 380 800 0.0087 1% 55 365 235 380 320 195 12
CKSGO-0.38-1000/0.007 B 450 1000 0.007 1% 65 375 245 400 330 205 12
CKSGO-0.38-1250/0.0058 B 550 1200 0.0058 1% 75 385 260 415 340 220 12
CKSGO-0.38-1600/0.0043 B 630 1600 0.0043 1% 95 400 280 420 360 240 12
2, Output reactor
● Selection Table of 380V Output AC Reactor (1% Voltage Drop) ● Selection Table of 690V Output AC Reactor (1% Voltage Drop)
● Selection Table of 690V Output AC Reactor (2% Voltage Drop)
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGO-0.69-15/0.85 A 15 15 0.85 1% 3 170 125 110 130 85 12
CKSGO-0.69-25/0.51 A 22 25 0.51 1% 3 170 125 125 130 85 12
CKSGO-0.69-35/0.36 A 37 35 0.36 1% 4 195 130 130 155 90 12
CKSGO-0.69-55/0.23 A 45 55 0.23 1% 6 195 130 135 155 90 12
CKSGO-0.69-70/0.182 A 55 70 0.182 1% 9 235 140 155 195 100 12
CKSGO-0.69-90/0.142 A 75 90 0.142 1% 11 235 150 155 195 110 12
CKSGO-0.69-125/0.1 B 90 125 0.1 1% 15 280 155 275 240 115 12
CKSGO-0.69-160/0.08 B 110/132 160 0.08 1% 18 280 160 280 240 120 12
CKSGO-0.69-200/0.064 B 160 200 0.064 1% 24 310 170 305 270 130 12
CKSGO-0.69-250/0.05 B 220 250 0.05 1% 30 310 180 305 270 140 12
CKSGO-0.69-300/0.042 B 250 300 0.042 1% 46 415 215 405 375 195 12
CKSGO-0.69-400/0.032 B 315/355 400 0.032 1% 57 440 240 430 400 200 12
CKSGO-0.69-500/0.025 B 450 500 0.025 1% 85 540 285 550 500 245 12
CKSGO-0.69-650/0.02 B 500/560 650 0.02 1% 105 580 305 600 540 265 12
CKSGO-0.69-800/0.016 B 630/750 800 0.016 1% 120 620 330 650 580 290 12
CKSGO-0.69-950/0.013 B 800 950 0.013 1% 135 660 360 750 620 320 12
CKSGO-0.69-1200/0.01 B 900/1000 1200 0.01 1% 150 720 420 950 680 380 12
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGO-0.69-15/1.7 A 15 15 1.7 2% 4 205 130 130 165 90 12
CKSGO-0.69-25/1.05 A 22 25 1.05 2% 6 195 130 135 155 90 12
CKSGO-0.69-35/0.73 A 37 35 0.73 2% 11 255 145 165 215 105 12
CKSGO-0.69-55/0.465 A 45 55 0.465 2% 14 255 150 180 215 110 12
CKSGO-0.69-70/0.365 A 55 70 0.365 2% 14 255 150 180 215 110 12
CKSGO-0.69-90/0.285 A 75 90 0.285 2% 17 270 150 200 230 115 12
CKSGO-0.69-125/0.2 B 90 125 0.2 2% 29 335 190 405 295 150 12
CKSGO-0.69-160/0.16 B 110/132 160 0.16 2% 29 345 190 280 305 150 12
CKSGO-0.69-200/0.125 B 160 200 0.125 2% 34 350 190 310 310 150 12
CKSGO-0.69-250/0.105 B 220 250 0.105 2% 44 350 190 360 310 150 12
CKSGO-0.69-300/0.085 B 250 300 0.085 2% 45 350 195 370 310 155 12
CKSGO-0.69-400/0.065 B 315/355 400 0.065 2% 56 365 210 385 325 170 12
CKSGO-0.69-500/0.06 B 450 500 0.06 2% 69 385 235 415 345 195 12
CKSGO-0.69-650/0.04 B 500/560 650 0.04 2% 89 445 255 485 405 215 12
CKSGO-0.69-800/0.032 B 630/750 800 0.032 2% 105 465 275 500 425 235 12
CKSGO-0.69-950/0.027 B 800 950 0.027 2% 130 490 300 520 450 260 12
CKSGO-0.69-1200/0.021 B 900/1000 1200 0.021 2% 170 520 330 580 480 290 12
www.australindo.co.idProduct specification and Information in this publication can change at any time without prior notice.Product specification and Information in this publication can change at any time without prior notice.PT. Australindo Graha Nusa
Electric Reactor 27Electric Reactor 26
● Selection Table of 1140V Output AC Reactor (1% Voltage Drop)
Reactor Model figure number
power(kW)
Rated current(A)
Inductance(mH)
voltage drop
weight(kg)
overall dimension (mm)
L W H a b φ
CKSGO-1.14-25/0.85 A 37 25 0.85 1% 5 195 130 135 155 90 12
CKSGO-1.14-30/0.7 A 45 30 0.7 1% 6 195 130 135 155 90 12
CKSGO-1.14-40/0.55 A 55 40 0.55 1% 11 235 150 155 195 110 12
CKSGO-1.14-55/0.38 A 75 55 0.38 1% 11 235 150 155 195 110 12
CKSGO-1.14-65/0.32 A 90 65 0.32 1% 13 240 150 180 200 110 12
CKSGO-1.14-80/0.26 A 110 80 0.26 1% 15 270 150 200 230 110 12
CKSGO-1.14-90/0.23 A 132 90 0.23 1% 17 270 160 185 230 120 12
CKSGO-1.14-120/0.18 B 160 120 0.18 1% 19 290 160 300 250 120 12
CKSGO-1.14-130/0.16 B 185 130 0.16 1% 19 290 160 310 250 120 12
CKSGO-1.14-150/0.14 B 200 150 0.14 1% 22 290 160 320 250 120 12
CKSGO-1.14-200/0.11 B 250 200 0.11 1% 28 325 175 330 285 135 12
CKSGO-1.14-230/0.09 B 315 230 0.09 1% 32 340 185 360 300 145 12
CKSGO-1.14-300/0.07 B 400 300 0.07 1% 39 340 195 380 300 155 12
CKSGO-1.14-350/0.06 B 500 350 0.06 1% 41 345 195 380 305 155 12
CKSGO-1.14-420/0.05 B 630 420 0.05 1% 48 345 195 385 305 155 12
CKSGO-1.14-500/0.042 B 710 500 0.042 1% 58 355 225 415 315 185 12
CKSGO-1.14-570/0.036 B 800 570 0.036 1% 64 355 225 420 315 185 12
CKSGO-1.14-600/0.032 B 1000 600 0.032 1% 68 415 240 450 375 200 12
CKSGO-1.14-800/0.026 B 1200 800 0.026 1% 85 455 270 480 415 230 12
● Contour Diagram of Low Voltage Inlet and Outlet Line Reactor(Rated current: 5~90A)
● Contour Diagram of Low Voltage Inlet and Outlet Line Reactor(Rated current: △90A)
PT. AUSTRALINDO GRAHA NUSA
LELCO BuildingJl. Tomang Raya No. 14Jakarta 11430 - Indonesia
Tel. +62(21) 560 5678Fax. +62(21) 567 3402marketing@australindo.co.id
www.australindo.co.id