NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 1

NFPA 101®Life Safety Code®

Changes 2000 to 2012Ron Coté, P.E.

Principal EngineerNFPA – Quincy, MA

Special thanks to Jim Lathrop, Koffel Associates

for content for this presentation

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 2

• Numerous changes from 2000 to 2012

• Most changes help to facilitate compliance with the Code

• Focus on key changes

19.3.4.3.2 Emergency Forces Notification. Fire department notification shall be accomplished in accordance with 9.6.4

Exception: Smoke detection devices or smoke detection systems equipped with reconfirmation features shall not be required to automatically notify the fire department unless the alarm condition is reconfirmed after a period not exceeding 120 seconds.

2012 Edition19.3.4.3.2 Emergency Forces Notification.

19.3.4.3.2.1 Fire department notification shall be accomplished in accordance with 9.6.4.

19.3.4.3.2.2 Smoke detection devices or smoke detection systems equipped with reconfirmation features shall not be required to automatically notify the fire department, unless the alarm condition is reconfirmed after a period not exceeding 120 seconds.

2000 Edition

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 3

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 4

• New Chapter 43• Categories

— Repair— Renovation— Modification— Reconstruction— Change of use or

change of occupancy

— Addition

• Non-sprinklered must comply with 18.4.3 unless major

• Major renovations— Defined— Sprinkler the smoke compartment involved— Sprinkler options permitted per smoke

compartment

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 5

• 2.1(1)* Referenced documents applicable only to the extent called for within the Code

• 2.1(2) Where requirements of referenced document differ from the Code, the Codegoverns

• 2.1(3) Existing installations permitted to be continued in use provided lack of conformity with referenced documents does not present a serious hazard to occupants

Requirements for Existing

Requirements for New

Minimum

Per Chapter 43

Permitted with

CAUTION and

Research

STOP!NOT

Permitted!

10

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 6

• 3.3.21.6* Normally Unoccupied Building Service Equipment Support Area. A building service equipment support area in which people are not expected to be present on a regular basis.

• A.3.3.2.1.6 [detailed annex]• 7.13 Normally Unoccupied

Building Service Equipment Support Areas.

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 7

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 8

• ≥ 2 occupancies in a building• 2 options for compliance

— Separated occupancies— Mixed occupancies

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 9

• 6.1.14.3.2* The building shall comply with the most restrictive requirements of the occupancies involved

.• A.6.1.14.3.2 For example, a common path of

travel that occurs wholly in a business tenant space, in a multiple occupancy building containing assembly and business occupancies, should not have to meet the assembly occupancy common path of travel limitation.

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 10

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 11

NA

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 12

• …to prevent or dissuade occupants from traveling past the level of discharge.

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 13

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 14

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 15

• Without undercuts, louvers, or grilles • Maximum 3/4 in. clearance under the bottom of

a NEW door

8.5.6 Penetrations

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 16

• 10 (not 4) hours in a 24-hour period

• Per NFPA 25

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 17

• Must be protected by automatic sprinklers within 12 years of adoption of the Code

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 18

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 19

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 20

• Wheeled equipment and carts in use

• Wheeled medical emergency equipment

• Patient lift and transport equipment

• Fixed furniture• Must maintain ≥5 ft

clear width

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 21

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 22

• General— Permission— Separation— Hazardous Contents Areas— Suite Subdivision

• Sleeping Suites• Patient-Care Non-Sleeping Suites• Non-Patient-Care Suites

Patient Sleeping Room Suites

76

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 23

Patient Sleeping Room Suites

• Sleeping Suites— Arrangement— Number of Means of Egress— Maximum Size— Travel Distance

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 24

• Maximum 7500 ft2, unless• >7500 ft2 but ≤10,000 ft2 permitted where:

— Direct visual supervision, and— Full automatic smoke detection , and— (QR Sprinklers are mandated anyway)

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 25

Sleeping Suite7,500 sq. ft.

• ≤5000 ft2, unless• ≤7500 ft2 where smoke compartment has:

— sprinkler system and complete smoke detection OR— sprinkler system with QRS

• >7500 ft2 but ≤10,000 ft2 where: — Direct visual supervision , and— Total coverage (complete) automatic smoke

detection, and— Sprinkler system protection with QRS

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 26

• Arrangement— Number of intervening rooms eliminated

• Number of Means of Egress— Egress though adjoining suite permitted (2nd

route)• Maximum Size

— No increases – (addressed for 2015)• Travel Distance

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 27

• In accordance with primary use and occupancy of the space

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 28

Key Plan:Alcohol Based Hand Rub Dispenser

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 29

No Longer Required

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 30

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 31

61

NFPA 101®, Life Safety Code®Changes 2000 to 2012

30th Annual AHCA SeminarOrlando, FLSeptember 23, 2014 32

• NFPA Customer Advisory Group

• 800-344-3555, Option 3

• www.nfpa.org/101