Asset Register – Mechanical Services Outdoor Swimming Pool - Letchworth
Z:\3188\SBR\Asset Register Report\N.H.D.C
Asset Register and Conditions Schedule
for the
Mechanical Engineering Services
at
North Herts Leisure Centre,Outdoor Swimming Pool, Letchworth
Rev Reason for Issue Date
A Preliminary Issue 13/05/2013
Building Services Consultant Engineers
David Bedwell & PartnersManor House Yard,
Royston,Herts.
SG8 7BZ
(Tel: 01763 241556)(Fax: 01763 246487)
Email – mail@bedwell.uk.com
Asset Register – Mechanical Services Outdoor Swimming Pool - Letchworth
Z:\3188\SBR\Asset Register Report\N.H.D.C
Mechanical Services Specification
Table of Contents
Section Description
1.0 Introduction, Purpose and Format
2.0 Contractor’s Examinations, Checks and Tests
3.0 Exclusions / Clarification
Appendix A Asset Register : Conditions Schedule
Appendix B Summary Asset Register
Appendix C Excerpt from CIBSE Guide Volume M (2008) – Indicative LifeExpectancy for Building Services Plant, Equipment andSystems.
Appendix D Excerpts from B & S E (HVCA) SFG 20 (2012) – the StandardMaintenance Specification for Mechanical and ElectricalServices to Buildings
Asset Register – Mechanical Services Outdoor Swimming Pool - Letchworth
Z:\3188\SBR\Asset Register Report\N.H.D.C
1.0 Introduction, Purpose and Format
1.1.0 Introduction
1.1.1 The maintenance philosophy adopted in this document relate to theexisting / installed mechanical equipment and plant and suchmaintenance regimes that shall be adopted in terms of PLANNEDPREVENTATIVE MAINTENANCE (PPM)
1.1.2 As its name implies PPM is a method of maintenance whichnecessitates well-defined maintenance routines for plant andequipment at regular pre-determined intervals. In contrast toRESPONSE MAINTENANCE which is effectively breakdownmaintenance; the philosophy underlying PPM is that plant andequipment is kept operating at or near its peak efficiency.
If PPM is organised and undertaken properly it will produce significantbenefits, the most important of these being the reduction of high repaircosts and energy costs and the elimination of lost revenue resultingfrom forced closure of facilities.
1.1.3 Initially the implementation of PPM is costly but in the long term will besubstantially less expensive than a response maintenance policy.
1.2.0 Purpose
1.2.1 The purpose of this document is identify all items of mechanicalservices equipment and plant currently installed at the Outdoor Pool,Letchworth, and subsequently the required PPM regime which shall bethe responsibility of the successful Contractor to perform.
1.2.0 Format
a) The PPM details included in this document are based upon performancerequirements as distinct from detailed schedules of the numerousspecific examinations, tests and checks that will be required of thesuccessful Contractor to achieve the standard of maintenance required.
b) In order to comply with the maintenance standards set out in theschedule the successful Contractor will therefore be required, not only tocomplete the stipulated tests, checks and examinations in accordancewith SFG20 (2012), but also to respond to any works necessary toachieve the standard of maintenance identified in the schedules.
c) The Contractor will be expected to complete all maintenancerequirements in accordance with the frequency intervals as specified inSFG20 (2012) and shall pay all costs relating to such works.
Asset Register – Mechanical Services Outdoor Swimming Pool - Letchworth
Z:\3188\SBR\Asset Register Report\N.H.D.C
d) It should also be clearly understood, with regard to the period withinwhich corrective maintenance or repair is to be achieved, that where, inthe opinion of the Contract Administrator, failure to complete such worksmay give rise to potential injury to staff or users, the minimum statedresponse times will be applied. In certain circumstances it may on theother hand be the case that stated response times may be extended bythe Contract Administrator, when for example the subject building is notin use.
e) Much of the information appertaining to manufacturers, equipment / planttechnical data, current condition, etc as identified in Appendix’s A and Bis self-evident but for the avoidance of misunderstanding the followingadditional explanatory notes are provided:-
Condition Panel:
The intention of this panel is to indicate the condition of the item ofequipment at the date of tender invitation and is based on a scale of 1 to5. The classifications attributed to each point on the scale are asfollows:-
1 = In need of Repalacement2 = Poor Condition for Age, but still serviceable3 = Average Condition for Age4 = Good Condition for Age5 = As New (Excellent Condition)
Reference Appendix A the Asset Register : Conditions Schedule theassessed condition is identified by enlarged figures highlighted in boldtext.
Maintenance Schedule:
The Asset Register : Conditions Schedule includes reference toAppendix D, SFG20 (2012), the Standard Maintenance Specification forMechanical and Electrical Services to Buildings. Each Equipment / Plantdata sheet makes reference to the applicable maintenance clause thusidentifying the extent and frequency at which the required PPM shall beundertaken.
i.e. – Clause 05-23 of SFG20 (2012) refers to “05” Boilers/HeatGenerators and “23” LTHW Boilers.
Note: it is assumed that as competent M&E Maintenance Contractorsthat those tendering for this particular project will have access to theirown in house version of SFG20 (2012) and subsequently a copy of thisparticular document is not attached.
Asset Register – Mechanical Services Outdoor Swimming Pool - Letchworth
Z:\3188\SBR\Asset Register Report\N.H.D.C
Economic Life:
As Appendix C, this the economic life expectancy obtained from CIBSEGuide Volume M (2008) – Indicative Life Expectancy for BuildingServices Plant, Equipment and Systems; and/or that which one wouldnormally expect to be achieved.
Predicted Future Life:
The predicted life is deemed to be the economic life less the number ofyears the item has been in operation or, where this is not known, thefuture anticipated life based upon its present condition, maintenancehistory and general state of repair.
It is acknowledged that although it is possible to keep many items ofmechanical plant operational for periods substantially in excess of theiranticipated life, the repair and maintenance costs of so doing may, aftera certain time, dictate that replacement is a more viable and costeffective option.
2.0 Contractors Examinations, Checks and Tests
It will be the responsibility of the successful Contractor to formulatedetailed inspection schedules and rotas to comply with the generalintention of the examinations, tests and checks stipulated within thisdocument and SFG 20 (2012).
3.0 Exclusions / Clarification
The Contractor’s attention is drawn to the fact that repair, maintenanceand inspection of the following items are expressly excluded from thiscontract:-
Shower thermostatic controls Chlorine alarms Trend heating and lighting control systems PA Systems Intruder Alarms Fire alarms
The testing of water systems in terms of the Control / Prevention ofLegionellae – NHDC will commission these specific works under aseparate contract.
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX A
- Asset Register: Conditions Schedule
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 01
Equipment / Plant Ref: Gas Fired Boiler - No1
Model Type: Potterton ISIS HE
No Off: 1 of 2
Location: Plant Room
Manufacturer: Potterton CommercialWood Lane,Erdington,Birmingham.B24 9QP
Tel: 0845 070 1055
Load/Duty: 440kW Gas input: 48m3/hr
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: A0882 Date of Manufacture: 2001
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 05-23
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 02
Equipment / Plant Ref: Pressure Jet Burner - No1
Model Type: Riello RS50 two stage gas burner
No Off: 1 of 2
Location: Plant Room
Manufacturer: Riello LtdThe Ermine Centre,Ermine Business Park,Huntingdon,Cambridgeshire.PE29 6WX
Tel: 01480 432144
Load/Duty: 290kW to 580kW Gas input: 0.78kg/Nm3
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: .75kW
R P M: N A
Running Current: 3A max
Starting Current: 13.8A max
Serial Number: 3784620 / 02052000050CE – 0085AP0735
Date of Manufacture: 2005
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 4 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 06-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 03
Equipment / Plant Ref: Gas Fired Boiler – No2
Model Type: Ideal Viceroy GT 400
No Off: 2 of 2
Location: Plant Room
Manufacturer: Ideal Standard LtdPO Box 103National Avenue,Kingston Upon Hull,East Yorkshire.HU5 4JN
Tel: 01482 492251
Load/Duty: 390 to 450kW Gas input: 48m3/hr
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: CE 0049/49 (AQ/0952) Date of Manufacture: 2010
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 17 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 05-23
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 04
Equipment / Plant Ref: Pressure Jet Burner – No 2
Model Type: Riello RS50 two stage gas burner
No Off: 2 of 2
Location: Plant Room
Manufacturer: Riello LtdThe Ermine Centre,Ermine Business Park,Huntingdon,Cambridgeshire.PE29 6WX
Tel: 01480 432144
Load/Duty: 290kW to 580kW Gas input: 0.78kg/Nm3
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: .75kW
R P M: N A
Running Current: 3A max
Starting Current: 13.8A max
Serial Number: 3784702 / 0246000338C E – 0085AP0735
Date of Manufacture: 2010
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 9 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 06-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 05
Equipment / Plant Ref: HWS Plate Heat Exchanger
Model Type: UKE6B – 21 section plate LPHW heat exchanger
No Off: 1 of 1
Location: Plant Room
Manufacturer: U K Exchangers LtdUnit 55Stilebrook RoadOlneyBuckinghamshireMK46 5EA
Tel: 01234 244320
Load/Duty: 880 kW
Primary LPHW @ 80oC F and 60
oC R / Secondary LPHW @ 50
oC F and 30
oC R
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: .N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: C14935 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 19 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 29-07
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 06
Equipment / Plant Ref: Primary LPHW Heating Pump/s
Model Type: UPSD 100 – 60 (operating on pump speed No. 3)
No Off: 1 of 1
Location: Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury Road,Leighton Buzzard,Beds.LU7 4TL
Tel: 01525 850000
Load/Duty: Q = 21m3/hr @ 65kPA
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 1370W
R P M: N A
Running Current: 2.9A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 2 to 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Pump head No 1 will require replacment in the next 12 to 24 months
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 07
Equipment / Plant Ref: Secondary LPHW Heating Pump
Model Type: FHE4 65-125/05/A
No Off: 1 of 1
Location: Plant Room
Manufacturer: Lowara UK LtdMillwey Rise Industrial Estate,Axminster,Devon.EX13 5HU
Tel: 01297 630230
Load/Duty: Q = 24 to 54m3/hr @ 4.4 to 2.2m head
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.75 HP / 0.55kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 107440790 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 08
Equipment / Plant Ref: Main Pool Circulation Pump/s
Model Type: Flow Serve 125-100CPXM250
No Off: 1 of 1
Location: Plant Room
Manufacturer: Flowserve GB LtdLowfield Works,P O Box 17,Newark,Notts.NG24 3EN
Tel: 01636 249600
Load/Duty: Q = 500gpm @ 20ft head
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.75 HP / 0.55kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 527936-002-01 / 02 Date of Manufacture: 2005
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 09
Equipment / Plant Ref: LPHW Heating Feed and Expansion Tank
Model Type: N A
No Off: 1 of 1
Location: Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Unknown
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 56-01 and 56-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 10
Equipment / Plant Ref: Incoming Gas Supply
Model Type: Gas Meter and 3No. Parallel Gas Governors
No Off: 1 of 1
Location: Plant Room
Manufacturer: Dresser Measurement Division10201 Westheimer Road,Houston,Texas.USA
Load/Duty: “5M”
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 74986507 Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: Undefined
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 11
Equipment / Plant Ref: Chlorine Scavenging Device
Model Type: Gasmaster 1
No Off: 1 of 1
Location: Plant Room
Manufacturer: Crowcon Detection (UK) LtdUnit 2,2-6 Blacklands Way,Abingdon.OX14 1DY
Tel: 01235 401528
Load/Duty: N A
Voltage: 240V
Phase: 1
Hz / (CPS): 50
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years – due to caustic environment Predicted Future Life: 1-2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 12
Equipment / Plant Ref: Sodium Hypo-Chlorinate Dosing Set
Model Type: N A
No Off: 1 of 1
Location: Plant Room
Manufacturer: LMI Milton RoyUSA
Load/Duty: 17ltrs/hr
Voltage: 240V
Phase: 1
Hz / (CPS): 50
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: CFB135-360N1 / 010451911 Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: Undefined
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65 -
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 13
Equipment / Plant Ref: Sodium Hypo-Chlorinate Dosing Set
Model Type: N A
No Off: 1 of 1
Location: Plant Room
Manufacturer: LMI Milton RoyUSA
Load/Duty: 17ltrs/hr
Voltage: 240V
Phase: 1
Hz / (CPS): 50
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: CFB135-360N1 / 00750424 Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 Predicted Future Life: Undefined
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65 -
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 14
Equipment / Plant Ref: Main Pool Backwash Plant
Model Type: ?
No Off: 1 of 1
Location: Plant Room
Manufacturer: Undefined
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: Undefined Predicted Future Life: Undefined
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 57-01 and 57-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 15
Equipment / Plant Ref: Electric Water Heater
Model Type: Heatrae Sadia
No Off: 1 of 1
Location: Plant Room
Manufacturer: Heatrae Sadia LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420220
Load/Duty: 10ltr storage capacity
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 0 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 16
Equipment / Plant Ref: Electric Water Heater
Model Type: Redring Vortex Instant 3
No Off: 1 of 1
Location: First Aid Room
Manufacturer: Redring Xpelair Group LtdNewcombe House,Newcombe Way,Orton Southgate,Peterborough.PE2 6SE
Tel: 0844 3727761
Load/Duty: 3kW
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
The existing electric water is not suitable for application (installed in First Aid Room), the heater should bethermostatically controlled with fail safe diversion to cold water thus preventing scalding.
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 17
Equipment / Plant Ref: Electric Water Heater
Model Type: Heatrae Sadia – Megaflo DD 300 HE
No Off: 1 of 1
Location: Female Changing Rooms
Manufacturer: Heatrae Sadia LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420220
Load/Duty: 300ltr storage capacity
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 2 x 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 95 : 050 : 373 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-15
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 18
Equipment / Plant Ref: Thermostatic Mixing Valve – common to 3No. showers
Model Type: Meynell RADA 20
No Off: 1 of 1
Location: Female Changing Rooms
Manufacturer: Kohler Mira LtdCromwell RoadCheltenhamGloucestershireGL52 5EPMira Ltd Registered
Tel: 0844 571 1777
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 61-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 19
Equipment / Plant Ref: 3 No. Pre-Plumbed Shower Panels
Model Type: Mira PA 2
No Off: 3
Location: Female Changing Rooms
Manufacturer: Kohler Mira LtdCromwell RoadCheltenhamGloucestershireGL52 5EPMira Ltd Registered
Tel: 0844 571 1777
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years Predicted Future Life: 2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 20
Equipment / Plant Ref: Thermostatic Mixing Valve – to 2No. basins
Model Type: Saracen 15 TMV
No Off: 1
Location: Female Changing Rooms
Manufacturer: Saracen Ltd
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 61-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 21
Equipment / Plant Ref: Electric Water Heater
Model Type: Heatrae Sadia – Megaflo DD 300 HE
No Off: 1 of 1
Location: Male Changing Rooms
Manufacturer: Heatrae Sadia LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420220
Load/Duty: 300ltr storage capacity
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 2 x 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 95 : 050 : 373 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-15
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 22
Equipment / Plant Ref: Thermostatic Mixing Valve – common to 3No. showers
Model Type: Meynell RADA 20
No Off: 1 of 1
Location: Male Changing Rooms
Manufacturer: Kohler Mira LtdCromwell RoadCheltenhamGloucestershireGL52 5EPMira Ltd Registered
Tel: 0844 571 1777
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 61-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 23
Equipment / Plant Ref: 3 No. Pre-Plumbed Shower Panels
Model Type: Mira PA 2
No Off: 3
Location: Male Changing Rooms
Manufacturer: Kohler Mira LtdCromwell RoadCheltenhamGloucestershireGL52 5EPMira Ltd Registered
Tel: 0844 571 1777
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years Predicted Future Life: 2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 24
Equipment / Plant Ref: Thermostatic Mixing Valve – to 2No. basins
Model Type: Saracen 15 TMV
No Off: 1
Location: Male Changing Rooms
Manufacturer: Saracen Ltd
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 61-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 25
Equipment / Plant Ref: Electric Water Heater
Model Type: Heatrae Sadia “Handy” 3
No Off: 1 of 1
Location: Ladies W C
Manufacturer: Heatrae Sadia LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420100
Load/Duty: 3kW
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 2007
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 26
Equipment / Plant Ref: Electric Water Heater
Model Type: Ariston EP 15 UR
No Off: 1 of 1
Location: Kitchen
Manufacturer: Ariston UK LtdAriston Building,Hughenden Avenue,High Wycombe,Buckinghamshire.HP13 5FT
Tel: 0333 240 6666
Load/Duty: 15ltr storage capacity
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 2kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 877071 05 09 320 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 27
Equipment / Plant Ref: Incoming Mains Cold Water Supply
Model Type: 4” Gate Valve + 2 x NRVs
No Off: 1 of 1
Location: Kitchen
Manufacturer: N A
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged Bold figure denotes assessed condition:
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 28
Equipment / Plant Ref: Extract Fan
Model Type: 9” Extract Fan – “EMMA” (wall mounted)
No Off: 1 of 1
Location: Kitchen
Manufacturer: N A – “budget” DIY extract fanavailable from Builders Merchants.
Load/Duty: N A
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: Undefined
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 0 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 29
Equipment / Plant Ref: Electric Water Heater
Model Type: Heatrae Sadia “BT”
No Off: 1 of 1
Location: Office / Staff Room
Manufacturer: Heatrae Sadia LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420220
Load/Duty: 25ltr storage capacity
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 1-2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 30
Equipment / Plant Ref: Electric Water Heater
Model Type: IMI Santon “Sanspray”
No Off: 1 of 1
Location: Male W C
Manufacturer: Santon UK LtdHurricane Way,Norwich,Norfolk.NR6 6EA
Tel: 01603 420220
Load/Duty: 3kW
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 3kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: Approx. 2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-14
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: Letchworth Outdoor Swimming Pool
Date: April 2013
Ref: A R 31
Equipment / Plant Ref: Mechanical Services Control Panel
Model Type: Boiler / LPHW HTG Controls
No Off: 1 of 1
Location: Plant Room
Manufacturer: D Benson (Controls) LtdBeckbridge RoadNormanton Industrial EstateNormantonWest YorkshireWF6 1QS
Tel: 01924 894162
Load/Duty: N A
Voltage: 240V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 30 years Predicted Future Life: Approx. 1 - 2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-01 to 14-16 inclusive
Comments and Other Relevant Details: Reported that the internal control units no longer operate;automatic mode overridden with the equipment / plant now running in manual mode.
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX B
- Summary Asset Register
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX C
- Excerpt from CIBSE Guide Volume M (2008)
Indicative Life Expectancy for Building Services Plant, Equipment and Systems
Ref: CIBSE Guide Volume M (2008)
Indicative Life Expectancy for Building Services Plant, Equipment and Systems – excerpt from CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Boiler Plant
Shell and tube boilers (steam and HTHW)
20 Water treatment is very important
Water tube boilers (steam and HTHW) 25 Water treatment is very important
Electrode/electric boilers (steam and HTHW)
25 Water treatment is very important
Shell and tube boilers (MTHW/LTHW) 20
Water tube boilers (MTHW/LTHW) 25
Electrode/electric boilers (MTHW/LTHW)
25
Cast iron sectional boilers (MTHW/LTHW)
25
Steel boilers (MTHW/LTHW) 15
Condensing boilers (MTHW/LTHW) 15
Refrigeration Plant - medium to large capacity
Centrifugal chiller 15 See note 1
Reciprocating chiller 20 See note 1
Screw chiller 20 See note 1
Absorption chiller 20
Refrigeration Plant - open type cooling towers
Plastic coated metal cooling tower of plastic coating
25 Consider thickness, bonding and quality
Galvanised metal cooling tower 12 Consider thickness and quality of galvanising
Timber constructed cooling tower which can extend life
10 Consider quality of timber preservation
Ceramic cooling tower 35
Plastic constructed cooling tower 20 Consider thickness and quality of plastic
Epoxy treated metal cooling tower 15
Stainless steel cooling tower 30 Consider quality and thickness of stainless steel
Refrigeration Plant - external heat rejection
Air cooled condensers 20
Evaporative condensers 20
Air blast dry air coolers - plastic coated metal of plastic coating
25 Consider thickness, bonding and quality
Air blast dry air coolers - galvanised metal 20 Consider thickness and quality of galvanising
Air blast dry air coolers — epoxy treated metal
20
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Boiler Plant Auxiliaries
Oil storage tanks — external protection 20 Depends on thickness of metal and corrosion protection
Oil storage tanks — underground 15 Depends on thickness of metal and corrosion protection
Combustion controls 12
Boiler electrodes 8
Feed pumps 15
Water treatment 15
Atmospheric gas burners 15
Forced air gas burners 12
Oil burners 12
Solid fuel handling plant 15 Conveyor system up to 20 years
High temperature fans 15
Instrumentation 10
Oil distribution system for boiler plant 15
Gas distribution system for boiler plant 20
Mild steel flue 15 Depends on thickness of metal and corrosion protection
Stainless steel flue 20 Check quality of stainless steel
Brick or concrete chimney — external 40
Brick or concrete chimney — internal 50
Steel chimney — external 30 Depends on thickness of metal and corrosion protection
Water Tanks
Cast iron water cisterns 35
Mild steel (treated) water cisterns 15 Not for domestic or drinking water purposes
Plastic water cisterns 35 High quality structural support is necessary
Galvanised metal water cisterns 12
Ductwork - systems and components
Ductwork (galvanised) 30
Ductwork (plastic) need to be considered 20 Mechanical damage and expansion
Ductwork (flexible circular) 20 Mechanical damage needs to be considered also cleaning difficulties
Fans (heavy duty centrifugal) 25
Fans (centrifugal) 20
Fans (axial) 20
Fans (propeller) 15
Fans (roof mounted units) 15
Fire dampers: curtain type 12
Coils (copper fins) heating 25
Coils (copper fins) cooling 25 Consider operational duty — wet surfaces
Coils (aluminium fins) heating 15 Consider quality and thickness of aluminium fins and exposure to adverse external conditions
Coils (aluminium fins) cooling 15 Consider quality and thickness of aluminium fins and exposure to adverse and wet external conditions
Coils (galvanised) heating 12
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Ductwork - systems and components (contd…)
Spray cooler coils (copper electro-tinned) and washers
15
Eliminators (galvanised) 10
Eliminators (plastic) 15
Eliminators (stainless steel) 20
Coils (electric) 10
Thermal wheels 15
Filters (automatic) — excluding media 15
Filters (panel) — excluding media 20
Filters (electrostatic) 15
Filters (activated carbon) — excluding media
15
Grilles and diffusers (anodised aluminium) 25
Grilles and diffusers (painted metal) 30
Plate recuperator 20
Dampers manual 20
Dampers automatic 15
Steam humidifier (direct) 10 Maintenance is very important
Steam humidifier (electric generated) 8 Maintenance is very important
Water spray humidifier 12 Early signs of corrosion must be dealt with
Pan type humidifier 10 Early signs of corrosion must be dealt with
Chemical dehumidifiers (excluding medium)
15
External louvres (anodised aluminium) 25 Regular cleaning is important to avoid possible breakdown of surface coating
External louvres (steel painted) 20 Early signs of corrosion must be dealt with
Attenuators 25 Consider type of lining, adhesive and fixing of acoustic material
Packaged air handling/conditioning units (internal)
20
Packaged air handling/conditioning units (external)
15 Consider type of corrosion protection
Air Conditioning Terminal Units
Fan coil units (heating and cooling) 15
Induction units 20
Terminal reheat units 20
VAV terminal units (bellows type) 15
VAV terminal units (box type) 15
Double duct terminal units 15
Chilled ceiling panels 25 Flexible water pipework connections - depending on type -10 years
Chilled beams 20 Flexible water pipework connections - depending on type -10 years
Ventilated ceilings 25
VRV units 10
VVT fan powered terminal units 15
Split systems 10
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Heating Terminal Units
Radiators (cast iron) 25
Radiators (steel) 15 Water condition is important
Radiators (2mm thick steel) 20 Water condition is important
Radiators aluminium 20 Water condition is important and materials in system
Radiator painting 5 Use correct type of paint
Unit heaters (steam and hot water) 15
Unit heaters (gas and electric) 10
Radiant heaters (steam and hot water) 20
Radiant heaters (electric) 10
Fan coil units (heating only) 15
Natural convectors water 20
Natural convectors electric 10
Underfloor heating with concrete encased steel pipes
25 Suggest a long-term bonded warranty is obtained — corrosion prevention of steel pipes
Underfloor heating with concrete encased plastic pipes
30 Suggest a long-term bonded warranty is obtained — consider quality of plastic pipes
Underfloor electric heating 20
Ceiling heating (hot water) 25
Ceiling heating (electric) 15
Electric storage heaters 10
Pipework Systems and Components
Open pipework systems (steel) 25
Closed pipework systems (steel) 30
Open pipework systems (copper) 35 Consider tube thickness and quality of copper
Closed pipework systems (copper) 40 Consider tube thickness and quality of copper
Open pipework systems (steel galvanised) 25
Closed pipework systems (steel galvanized)
35
Refrigerant pipework systems 20 See note 1
Steam pipework system 25
Condensate pipework system 12 Consider type of material, wall thickness and water treatment
Condensate collecting vessel 12 Consider type of material, wall thickness and water treatment
Open expansion vessel 10
Closed expansion vessel with membrane 15
Water treatment plant 15
Water treatment control and measurement equipment
10
Pumps (base mounted) 20
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Pipework Systems and Components (contd…)
Pumps (pipework mounted) 15
Pumps (glandless) 10
Pumps (sump and well) 12
Pumps (condensate) 10
Bellows flexible (steel) 10
Bellows flexible (rubber) 8
Bellows expansion (steel) 10
Valves (glandless) 20
Valves (glands) 15
Calorifiers 20
Heat exchangers (shell and tube) 25
Ductwork and vessel thermal insulation (blanket type)
30 Consider type of fixing and mechanical damage
Pipework and vessel thermal insulation (moulded type)
30 Consider fire and smoke rating
Drainage and Public Health
Internal waste, foul and rainwater drainage (cast iron)
35
Internal waste, foul and rainwater drainage (copper)
40
Internal waste, foul and rainwater drainage (plastic)
20 Consider mechanical damage & any expansion requirement
Below ground salt glazed drainage 40 Consider possibility of damage and structural movement
Below ground cast iron drainage 45 Consider possibility of ground and structural movement
Below ground plastic drainage 40 Consider mechanical damage
Above ground rainwater – plastic 25
Sanitary ware 25
Fire Fighting and Protection Systems
Alternate wet and dry sprinklers 20 Consider corrosion; see CIBSE Guide E(28)section 8.1.7.3
Wet sprinklers 25 Consider corrosion
Wet risers 20
Dry risers 25
Foam systems 15
Portable fire appliances 8
Fire hose reels 15
Fire hydrants 30
Fire alarms (electrical) 20
Battery support for fire alarm 10
Fire dampers (curtain type) 15
Computer room fire extinguishing system 15 Consider environmental impact and possible phasing out of fire extinguishing agent
Smoke and heat detectors 10
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Electrical Distribution Network
Main supply switchgear and distribution equipment
30
Transformers (dry type) 30
Transformers (oil type) 30
Mains cables (permanent installations) 30
Electrical Installations in Buildings
Final circuits and outlets 20
Lighting installations (internal) 20 Low voltage decorative may be limited to 10 years
Lighting installations (external) 15
Emergency lighting 20
Electrical motors (general) 15 Smaller motors may have a shorter life — check with supplier
Motor speed control devices 10
Motor control centres 20
Electrical Generating Plant
Alternators 25
Continuously rated gas/oil engines (frequent use)
15
Continuously rated gas/oil engines (standby)
25
Continuously rated steam engines (frequent use)
25
Continuously rated steam turbines (frequent use)
25
Oil storage 30
Controls & instrumentation 20
Mains failure sensors 15
Battery support 10 Building Management and Controls - electrics and electronics
Personal computer 10 Alternative name — supervisor. Reference note 2.0
PC operating system 8 See note 2
BMS operating system 8
Autodial modem 8
Printer 5 With frequent use operating costs are important
Screened network (hardwiring) 25 Should be future proofed with additional cable wireways. See note 2
Network communication devices 10 Proprietary devices or gateways — may require support. See note 2
Damper actuators 10
Intelligent outstations 10 See note 2
Sensors 8 Periodic loop tuning and calibration should be considered
Control valves 15
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Building Management and Controls- electrics and electronics (contd…)
Control dampers 15
Electronic/pneumatic interfaces 10
Utility metering 20
Pagers 5
Remote display panels 10 See note 2
Hardwiring between devices 25 Screened cables may be necessary
Controls General
Pneumatic controls 20
Electric controls 20
Electronic controls 15
Hydraulic valve actuators 10
Pneumatic valve actuators 15
Self-contained valve actuators 8
Miscellaneous Electrical Equipment and Plant
Lead acid batteries (sealed) 5
Nickel alkaline batteries (vented) 20
Battery chargers 20
Clock systems 15
Communication systems 20 Voice and data. See note 2
Public address systems 20
Intruder alarms and intercommunications 10
Uninterrupted power supply systems 20
Closed circuit television and video 10
Television and satellite systems 15 See note 2
Lightning protection 25
Lighting control and management system 15
Continuous flow electrical heaters 12
Electrical water heaters 12
Electrical storage heaters with ventilation 20
Electrical floor heating 25
Electrical heater (on peak) 8
Window unit air conditioner 8
Residential single or split package air conditioner
10
Commercial through the wall air conditioner 10
Water cooled air conditioner 15
Residential air to air heat pump 10
Commercial air to air heat pump 15
Commercial water to air heat pump 15
Miscellaneous Mechanical Equipment and Plant
Kitchen (cooking and support systems) 15
Laundries (equipment and support systems) 20
Water features 15 Water treatment is very important
Computer room air conditioning 15
Tea rooms (equipment and support systems) 15
Hand dryers 5
Drinking fountains 10
Vending machines 8
Sanitary towel disposal 10
Food/container waste disposal 5
Waste paper shredders/disposal 10
Stair/lobby ventilation 20
Fire protection (pipes and ducts) 20 Damage to fire protection should be examined at frequent intervals
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Miscellaneous Mechanical Equipment and Plant (contd…)
Incinerators 15
Gas or oil fired furnaces 15 Selection of heat exchanger material is important
Domestic gas fired warm air heaters 15
Domestic gas fired boilers 10
Domestic gas fired combination boilers 10
Gas fired hot water (storage and continuous) 12
Gas fires 8
Vertical Transportation
Lifts 15
Escalators 15
Security
Access systems (door releases, card readers, key pads)
10
CCTV cameras 10
CCTV control systems & multiplexers 15
Infra red lighting 10
Intruder detection 15
Note 1 - The phasing out of CFCs and HCFCs may require replacement of equipment earlier than originally planned
Note 2 - Technology changes can influence early replacement
Note 3 - Ensure that all heat exchangers especially refrigerant cooling and heat pumps
systems are suitable for UK operating conditions