ashrae standard 206-2013 - aceeeaceee.org/files/pdf/conferences/hwf/2013/8a-reedy.pdf · ashrae...

Post on 01-Feb-2018

227 Views

Category:

Documents

1 Downloads

Preview:

Click to see full reader

TRANSCRIPT

ASHRAE Standard

206-2013

Method of Testing for Rating of Multi-Purpose Heat Pumps for Residential Space Conditioning and Water Heating

Wayne Reedy Oak Ridge National Laboratory

2 Presentation name

BACKGROUND

• Development of standard was supported by ORNL as part of the U.S. Department of Energy’s effort to facilitate market penetration of multifunction heat pumps.

• In order to achieve an instantly recognizable, authoritative document, a test standard was requested of ASHRAE, which in turn established a Standard Project Committee to develop Standard 206

3 Presentation name

206 applies to electrically powered unitary

heat pump equipment that provides both

space conditioning and water heating

functions, and may include other

functions, such as dehumidification and/or

ventilation.

SCOPE

4 Presentation name

• 206 addresses air-source, water-source, ground water-source, ground-source closed loop, and direct geoexchange equipment.

• It applies to air-source equipment rated below 65,000 Btu/h [19,000 W], and water-source, ground water-source, ground-source closed loop, and direct geoexchange equipment rated below 135,000 Btu/h [40,000 W].

SCOPE

5 Presentation name

• 206 addresses single-capacity, dual-

capacity, and variable-capacity equipment

• Provides for up to 7 modes of equipment

operation

o Space conditioning only

o Dedicated water heating

o Dehumidification+space conditioning

o Dehumidification

o Space conditioning+water heating

o Dehumidification+space

conditioning+water heating

o Dehumidification+water heating

SCOPE

6 Presentation name

• Space conditioning may be heating or

cooling

• Dehumidification may be during

summer or winter

• Dedicated water heating may be during

summer or winter, with the heat source

being either indoor or outdoor

SCOPE

7 Presentation name

• Test procedure covers packaged, split, mini-

split, and triple split equipment configurations

• Refrigerant-to-water HX may be internal or

external to a heat pump section or water

storage tank

• Specifies refrigerant and water line

lengths/configuration for all options

SCOPE

8 Presentation name

• ANSI/ASHRAE Standard 37Methods of Testing for Rating Electrically Driven Unitary Air-

Conditioning and Heat Pump Equipment (Steady-State Performance)

• ANSI/ASHRAE Standard 116Methods of Testing for Rating Seasonal Efficiency of Unitary Air

Conditioners and Heat Pumps

STANDARD 206 IS AN EXTENSION

OF AND CONSISTENT WITH:

9 Presentation name

• AHRI Standard 210/240 Standard for Unitary Air-Conditioning and Air-Source Heat Pump

Equipment

• ANSI/AHRI/ASHRAE ISO Standard 13256-1Water-source heat pumps - testing and rating for performance -

Part 1: Water-to-air and brine-to-air heat pumps

• AHRI Standard 870Standard for Performance Rating of Direct GeoExchange Heat Pumps

• ANSI/ASHRAE Standard 118.2Method of Testing for Rating Residential Water Heaters

STANDARD 206 IS ALSO CONSISTENT

WITH:

10 Presentation name

ANSI/ASHRAE Standard 137Methods of Testing for Efficiency of Space-Conditioning/Water-

Heating Appliances that Include a Desuperheater Water Heater

and

various waivers from DOE’s Central Air

Conditioner and Central Air Conditioning Heat

Pump Test Procedure

STANDARD 206 SHOULD

REPLACE:

11 Presentation name

• Committee was made up of 15 voting

members, representing manufactures,

testing laboratories, electric utilities, and a

university; AHRI was a non-voting member.

SPC 206 INCLUDED

REPRESENTATION FROM ALL

INDUSTRY SEGMENTS

12 Presentation name

• Water heating load

• Space latent load

• Space sensible load

CALCULATION PROCEDURE IS

A BIN PROCESS BASED ON:

13 Presentation name

206 space cooling design load follows

Standard 116 in setting the total space

cooling load for 10% oversizing relative to

actual unit total capacity at 95°F test point

206 then applies a 0.76 sensible heat factor

to determine the space design sensible

cooling load

SPACE SENSIBLE LOAD

14 Presentation name

The latent cooling load for the combined

appliance in Standard 206 is made up of an

internal latent gain and a ventilation latent gain.

SPACE LATENT LOAD

15 Presentation name

• The water heating load is assumed evenly

distributed over the hours of the year.

• The hot water usage is taken as 243.4

liters/day (64.3 gallons/day) from ASHRAE

118.2-20064, which is the test standard for

standalone residential water heaters.

• Using inlet and outlet water temperatures

from ASHRAE 118.2-20064 of 14.2°C (58°F)

and 57.2°C (135°F) respectively and a water

heater energy factor of 0.90 yields an hourly

water heating load of 496.9 W (1696 Btu/h).

WATER HEATING LOAD

16 Presentation name

• Three performance descriptors are used to

completely describe the performance of the

combined appliance:

o Combined appliance space conditioning

performance for the cooling season;

o Combined appliance space conditioning

performance for the heating season;

o Combined appliance water heating

performance on an annual basis.

• In all cases, the descriptor ends in a subscript

“ca” to designate “combined appliance”.

PERFORMANCE DESCRIPTORS

17 Presentation name

• Air-source equipment

o SEERca

o HSPFca

o EFwca

• Water-source equipment

o EERca

o COPca

o EFwca

PERFORMANCE DESCRIPTORS

18 Presentation name

• Approved as an ASHRAE standard

6/26/2013

• Available from ASHRAE in paper or

electronic form

• Includes an excel spreadsheet to

perform calculations

STATUS:

19 Presentation name

QUESTIONS

COMMENTS

top related