G3901.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E90
Rendered to:
ALUPLAST US CORP
SERIES/MODEL: IDEAL 4000
TYPE: In-Swing Tilt-Turn Casement Window
Summary of Test Results
Data File No. Glazing (Nominal Dimensions) STC OITC
G3901.01A 1-1/4" IG (1/8" annealed, 1" air space, 1/8" annealed) 32 25
G3901.01B 1-3/8" IG (1/8" annealed exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F
36 27
Reference should be made to Intertek-ATI Report No. G3901.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Acoustical Performance Test Report
ALUPLAST US CORP 180 South 1140 West
Building 16 A Bay 6 North Ogden, Utah 84404
Report No G3901.01-113-11 Test Date 10/18/16 Report Date 12/22/16 Project Scope Architectural Testing, Inc., an Intertek company ("Intertek-ATI"), was contracted to conduct a sound transmission loss test. The complete test data is included as Appendix B of this report. The client provided the test specimen. Test Methods Testing for this project was conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements ASTM E413-10, Classification for Rating Sound Insulation ASTM E1332-10a, Standard Classification for Rating Outdoor-Indoor Sound Attenuation ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods
Test Procedure All measurements were conducted in the HT test chambers at Intertek-ATI located in York, Pennsylvania. The sensitivity of the microphones was checked before measurements were conducted. The transmission loss values were obtained for a single direction of measurement. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Two sound pressure levels were made simultaneously in the receive and source rooms at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all measurements.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
G3901.01-113-11-R0 Page 2 of 6
Specimen Installation A sound transmission loss test was initially performed on a filler wall. The specimen plug was removed from the filler wall assembly. A filler wall-reducing element, consisting of two separate 2x6 wood frames filled with concrete, was used to adjust the test opening size to accommodate the test specimen. A dense neoprene gasket was placed between the two wood and concrete frames. The specimen was placed on an isolation pad in the custom test opening. Duct seal was used to seal the perimeter of the specimen to the test opening on both sides. The interior side of the specimen, when installed, was approximately 1/4" from being flush with the receive room side of the filler wall. A stethoscope was used to check for any abnormal air leaks around the test specimen prior to testing. Operable portions of the test specimen, if any, were cycled at least five times prior to testing. Test Calculations Transmission loss (TL) at each 1/3 octave frequency is the average source room sound pressure level minus the average receive room sound pressure level, plus, 10 times the log of the specimen area divided by the sound absorption of the receive room with the sample in place. STC Rating To obtain the Sound Transmission Class (STC), read the TL of the contour curve at 500 Hz. The sum of the deficiencies below the contour curve must not exceed 32. The maximum deficiency at any one frequency must not exceed 8. OITC Rating The Outdoor-Indoor Transmission Class (OITC) is calculated by subtracting the logarithmic summation of the TL values from the logarithmic summation of the A-weighted transportation noise spectrum stated in ASTM E1332.
G3901.01-113-11-R0 Page 3 of 6
Specimen Descriptions
Frame Vent
Size 47-1/4" by 59" 44" by 55-7/8"
Thickness 3-5/8" 2-3/4"
Corners Mitered Mitered
Fasteners Welds Welds
Seal Method N/A N/A
Material Vinyl Vinyl
Reinforcement Steel located in all members Steel located in all members
Thermal Break Material N/A N/A
Daylight Opening Size N/A 37-5/8" by 49-1/2"
Glazing Option A
Measured Overall Insulation Glass Unit Thickness 1.279"
Spacer Type Super spacer
Exterior Sheet Gap Interior Sheet
Measured Thickness 0.111" 1.051" 0.117"
Muntin Pattern N/A N/A N/A
Material Annealed Air* Annealed
Laminate Material N/A N/A N/A
Glazing Method Interior
Glazing Material EPDM
Glazing Bead Material Vinyl
* - Stated per Client/Manufacturer, N/A-Not Applicable
G3901.01-113-11-R0 Page 4 of 6
Specimen Descriptions (Continued)
Glazing Option B
Measured Overall Insulation Glass Unit Thickness 1.299"
Spacer Type Super spacer
Exterior Sheet Gap Interior Sheet
Measured Thickness 0.117" 0.925" 0.114", 0.029", 0.114"
Muntin Pattern N/A N/A N/A
Material Annealed Air* Laminated
Laminate Material N/A N/A PVB
Glazing Method Interior
Glazing Material EPDM
Glazing Bead Material Vinyl
Components
Type Quantity Location
Weatherstrip
Hollow bulb gasket 1 Row Perimeter of frame
Hollow gasket with 1/4" leaf gasket 1 Row Perimeter of vent
Hardware
Tilt-turn hinge 2 Hinge jamb
Multi-point lock system 1 Perimeter of vent
Keeper 8 Perimeter of frame
Drainage
1" by 3/16" Weep slot 2 Sill face
1" by 1/8" Weep slot 2 Bottom rail of vent
* - Stated per Client/Manufacturer, N/A-Not Applicable
G3901.01-113-11-R0 Page 5 of 6
Specimen Descriptions (Continued)
Test Option Total Weight (lbs) Average Weight (lbs/ft2)
A 102 5.27
B 125 6.46
Comments A drawing of the test specimen is included in Appendix D. Intertek-ATI will store samples of test specimens for four years. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Zachary P. Golden Kurt A. Golden Technician - Acoustical Testing Project Lead – Acoustical Testing ZPG:jmcs
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix A: Equipment description (1) Appendix B: Complete test results (4) Appendix C: Photographs (1) Appendix D: Drawing (1)
G3901.01-113-11-R0 Page 6 of 6
Revision Log
Rev. # Date Page(s) Revision(s)
R0 12/22/16 N/A Original Report Issue
This report produced from controlled document template ATI 00271, revised 08/31/15.
TL Test Opening4.27 m (14 ft) wide by
Vibration break between source and receive rooms3.05 m (10 ft) high
Receive Room 234 m3 (8291.3 ft3)
1251 Pistonphone Calibrator
Source Room
Rotating vane and stationary diffusers Temperature and humidity controlledIsolation pads under the floor
65105 05/16Microphone Calibrator Norsonic
N/A-Not Applicable
206.6 m3 (7296.3 ft3)Stationary diffusers only
Temperature and humidity controlled
Maximum Size Description
Microphone and Preamplifier
*- Note: The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Test Chamber:
Volume Description
03/16
Source Room
Environmental IndicatorComet T7510 Source Room 64914 03/16
Comet T7510
Receive Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64910
Receive Room
MicrophonePCB Piezotronics
Receive Room
Environmental Indicator64915
12/15
Receive Room
378B20 Microphone and Preamplifier 64908 12/15
378B20 Microphone and Preamplifier 64911 12/15
Microphone and Preamplifier 12/15
Receive Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64909 12/15
Receive Room
MicrophonePCB Piezotronics
12/15
Receive Room
MicrophonePBC Piezotronics 378B20 Microphone and Preamplifier 64907 12/15
Microphone and Preamplifier 65103
Source Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64906
64905Source Room
MicrophonePCB Piezotronics
Source Room
MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64902 07/16
64903 12/15
378B20
12/15
Source Room
MicrophonePCB Piezotronics 378B20
Source Room
MicrophonePCB Electronics 378B20
Data Acquisition Unit National Instruments PXI-1033
Description ATI NumberDate of
Calibration
Data Acquisition card 65126 05/16 *
G3901.01 -113-11
Appendix A
Instrumentation:
Instrument Manufacturer Model
G3901.01-113-11-R0
Appendix B
Complete Test Results
STC Rating (Sound Transmission Class)
Deficiencies (Sum of Deficiencies)
OITC Rating (Outdoor-Indoor Transmission Class)
00.19
0.21 0
5000
6.9 12.5
Notes: 1) Receive Room levels less than 5 dB above the Background levels are red.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
41.1 0.21 -
4000
Page 1 of 2ATI 00760 Revised 05/23/16
25
93
36.6
32
7.8 15.8
40.6
42
94
45 42.4
27
3150 6.2 10.0
8.4
49
95
2500 6.0 93 46
1250 10.9 6.6 44.4
7.32000 6.6 95 44 44.7
0
0.35 0
1600 8.3 7.0
0.23 097 47
0.19 0
103 52 45.0 0.19
1000 13.7 6.0 97 50
0800 16.9 5.8 100 55 39.4 0.42
0.24 0
630 18.9 5.6 100 60 35.3
41.6
00.46
500 21.0 5.7 96 60 30.8 0.25 1
400 24.9 5.9 96 65 25.8 0.38 5
0.80 8
315 28.2 5.5 99 73 20.8 0.36 7
1.03 0
250 34.6 5.6 106 84 16.7
0.87 2
200 40.1 4.8 106 84 17.6 0.65 4
4.7 104 83 16.9
80 39.2 4.6 105 84 17.9
76 23.9
100 37.4 5.0 106 76 26.8 1.50 -
SPL SPL
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
Test Date 10/18/16
Data File No. G3901.01A
Client Aluplast US Corp
Description
(Hz) (dB) (m²) (dB) (dB)
1.84 -
160 41.4
Limit Deficiencies
125 37.5 4.8 104
Number
(dB)
Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-1/4" IG (1/8" annealed,
1" air space, 1/8" annealed)
22.8 °C
Confidence of
50%
Specimen Area 1.80 m² Receive Temp. 22.9 °C Source Temp.
Source Receive
Receive Humidity 49% Source HumidityTechnician
FreqBackground
AbsorptionSpecimen
TL
95%
Zachary Golden
SPL
Receive Temp. 22.8 °C
Data File No.
ATI 00760 Revised 05/23/16
Description Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-1/4" IG (1/8" annealed,
1" air space, 1/8" annealed)
Specimen Area
Client
Receive Humidity 49% 50%Technician Zachary Golden
G3901.01A
Source Humidity
10/18/16Test Date
22.9 °C Source Temp.
Aluplast US Corp
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
1.80 m²
Page 2 of 2
0
10
20
30
40
50
60
70
80
90
100
31.5 63 125 250 500 1000 2000 4000 8000
Sou
nd
Tra
nsm
issi
on
Lo
ss (
dB
)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL Contour Curve
STC Rating (Sound Transmission Class)
Deficiencies (Sum of Deficiencies)
OITC Rating (Outdoor-Indoor Transmission Class)
4000
00.23
0.26 0
ATI 00760 Revised 05/23/16
5000
6.8 13.3
Notes:
Page 1 of 2
1) Receive Room levels less than 5 dB above the Background levels are red.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
47.2 0.29 -
28
27
93
44.0
36
7.7 17.5
95 45 43.7
46 40.4
36
94
443150 6.3 10.6
8.7
41
95
2500 6.2
42.8
93
1250 10.6 6.6 45.4
7.52000 6.8
0
0.34 0
1600 8.7 7.0
0.26 097 46
0.19 0
102 52 44.8 0.12
1000 13.4 6.0 97 48
0800 17.5 5.8 100 52 42.5 0.39
0.25 0
630 20.3 5.5 100 56 39.4
44.1
00.46
500 22.6 5.6 96 55 36.6 0.29 0
400 26.5 5.7 96 60 31.4 0.35 4
0.69 6
315 30.5 5.5 99 67 26.7 0.42 5
1.11 0
250 36.7 5.3 106 78 23.1
1.01 8
200 40.8 4.8 106 81 20.7 0.64 5
4.6 104 84 15.2
80 39.0 4.5 106 82 20.4
76 23.9
100 36.4 5.0 105 74 28.0 1.54 -
SPL SPL
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
Test Date 10/18/16
Data File No. G3901.01B
Client Aluplast US Corp
Description
(Hz) (dB) (m²) (dB) (dB)
1.72 -
160 41.4
Limit Deficiencies
125 39.4 5.1 104
Number
(dB)
Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-3/8" IG (1/8" annealed
exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F
20.8 °C
Confidence of
45%
Specimen Area 1.80 m² Receive Temp. 21.5 °C Source Temp.
Source Receive
Receive Humidity 44% Source HumidityTechnician
FreqBackground
AbsorptionSpecimen
TL
95%
Zachary Golden
SPL
1.80 m² Receive Temp. 20.8 °C
Data File No.
ATI 00760 Revised 05/23/16
Description Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-3/8" IG (1/8" annealed
exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F
Specimen Area
Client
Receive Humidity 44% 45%Technician Zachary Golden
G3901.01B
Source Humidity
10/18/16Test Date
21.5 °C Source Temp.
Aluplast US Corp
AIRBORNE SOUND TRANSMISSION LOSSASTM E 90
Page 2 of 2
0
10
20
30
40
50
60
70
80
90
100
31.5 63 125 250 500 1000 2000 4000 8000
Sou
nd
Tra
nsm
issi
on
Lo
ss (
dB
)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL Contour Curve
G3901.01-113-11-R0
Appendix C
Photographs
Receive Room View of Installed Test Specimen
Source Room View of Installed Test Specimen
G3901.01-113-11-R0
Appendix D
Drawing