Type des. Part no.
Prep. Anoop A Parapurath 2013-08-16 Doc. kind Declaration of Conformity No. of p.
Appr. Michael Stanek 2013-08-16 Title Switchsync PWC600 version 1.0 - IEC 61850 MICS
25Resp. dept IDC/PT Approved
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 1
FILE: 1MRK511297-WEN_PWC600_version_1.0.0_IEC_61850_MICS; SAVEDATE: 2013-08-16 11:42; TEMPLATE: Techn_Doc_Stand_P.dot C; SKELETON: 1MRK3-475 en
ABB Switchsync PWC600 version 1.0 – IEC 61850 MICS
(Model Implementation Conformance Statement)
Template version 0.1
Date: April 24, 2008
UCA International Users Group
Testing Sub Committee
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 2
ABB PWC600 version 1.0 – IEC 61850 MICS ...................................................... 1
1 Introduction................................................................................................... 3
1.1 Scope................................................................................................ 31.2 Denominations .................................................................................. 31.3 Related documents............................................................................ 3
2 Logical Nodes List ........................................................................................ 4
3 Logical Node Extensions.............................................................................. 6
3.1 New Logical Nodes............................................................................ 63.1.1 IB16FCVB ................................................................................ 63.1.2 B16IFCVI.................................................................................. 73.1.3 ACBMSCBR............................................................................. 73.1.4 RCHLCCH Revision 1 .............................................................. 9
3.2 Extended Logical Nodes.................................................................... 93.2.1 LLN0 ...................................................................................... 103.2.2 SECLLN0 Revision 1.............................................................. 113.2.3 SSLLN0.................................................................................. 113.2.4 LPHD Revision 5 .................................................................... 123.2.5 SSCPOW ............................................................................... 123.2.6 CNTGGIO Revision 1 ............................................................. 133.2.7 DPGGIO Revision 1 ............................................................... 133.2.8 MVGGIO Revision 1............................................................... 143.2.9 SPGGIO Revision 1 ............................................................... 143.2.10 SP16GGIO Revision 2............................................................ 153.2.11 VSGGIO Revision 1 ............................................................... 163.2.12 AGSAL Revision 1.................................................................. 163.2.13 CVMMXN ............................................................................... 173.2.14 CMMXU Revision 1 ................................................................ 183.2.15 VMMXU Revision 1 ................................................................ 183.2.16 VNMMXU Revision 1.............................................................. 193.2.17 CMSQI Revision 2.................................................................. 193.2.18 VMSQI Revision 2 .................................................................. 203.2.19 DRPRDRE ............................................................................. 203.2.20 SSXCBR ................................................................................ 21
4 Common Data Class Extensions ............................................................... 22
5 Enum types Extensions.............................................................................. 23
6 Control Block Extensions........................................................................... 24
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 3
1 Introduction
ABB IED Switchsync PWC600 version 1.0 is based on ABB IED 650 series version 1.3. This model implementation conformance statement is applicable for ABB IED Switchsync PWC600 version 1.0.
This MICS document specifies the modelling extensions compared to IEC 61850 edition 1Clause 2 contains the list of implemented logical nodes. Clause 3 describes the new and extended logical nodes. Clause 4 describes the new and extended common data classes (if any).Clause 5 describes the new and extended enum types. Clause 6 describes any other extensions.
1.1 Scope
The purpose of this document is to serve as the MICS, Modelling Implementation Conformance Statement according to IEC 61850-10. It covers the content of the product ABB IED Switchsync PWC600 version 1.0. The document contains the description and layout of the Logical Node types, the vendor specific Logical Nodes and the vendor specific additions to the standard Logical Nodes. The details of the respective DATA types are described in the ICD file. There is no vendor specific Common Data Classes defined in these products. Each Logical Node type represents a function or a part of a function.
1.2 Denominations
Although not required nor defined in IEC 61850, the ABB IED 650 Series family supports version handling of the Logical Node types. The reason is that it shall be easy to distinguish between the LN types used in different version of the products based upon the same platform and the version of the platform. The revisions of LN type higher than 0 have Revision<No> concatenated with the LN type name.DATA types are not version handled.
1.3 Related documents
Document Id Title
IEC 61850-5 (2003) Communication Networks and Systems in Substations – Part 5: Communication requirements for functions and device models
IEC 61850-6 (2003) Communication Networks and Systems in Substations Part 6: Configuration description language for communication in electrical substations related to IEDs
IEC 61850-7-1 (2003) Communication Networks and Systems in Substations Part 7-1: Basic communication structure for substation and feeder equipment – Principles and models
IEC 61850-7-2 (2003) Communication Networks and Systems in Substations Part 7-2: Basic communication structure for substations and feeder equipment – Abstract communication service interface (ACSI)
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 4
Document Id Title
IEC 61850-7-3 (2003) Communication Networks and Systems in Substations Part 7-3: Basic communication structure for substation and feeder equipment – Common data classes
IEC 61850-7-4 (2003) Communication Networks and Systems in Substations Part 7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes and data classes
IEC 61850-8-1 (2003) Communication Networks and Systems in Substations Part 8-1: Specific communication service mapping (SCSM) –Mapping to MMS(ISO/IEC 9506 Part 1 and Part 2)
IEC 61850-10 (2005) Communication Networks and Systems in Substations Part 10: Conformance testing
ABB 1MRG010658 IED 650 series ver 1.3 - IEC 61850 PIXIT Protocol Extra Information
ABB 1MRG010660 IED 650 series ver 1.3 - IEC 61850 PICS Protocol Information Conformance Statement
ABB 1MRG010659 IED 650 series ver 1.3 - IEC 61850 TICS Tissue Information Conformance Statement
Since Switchsync PWC600 version 1.0 is based on ABB IED 650 series version 1.3, PIXIT, PICS and TICS of ABB IED 650 version 1.3 are applicable to Switchsync PWC600 version 1.0 also.
2 Logical Nodes List
The following table contains the list of logical nodes implemented in the device:
C: Logical Nodes for control
CPOW (Point-on-wave switching)
F: Logical Nodes for conversion functions
FCVB (Integer to Boolean converter)
FCVI (Boolean to integer converter)
G: Logical Nodes for generic references
GGIO (Generic process I/O)
GSAL (Generic security application)
L: System Logical Nodes
LCCH (Physical communication channel supervision)
LPHD (Physical device information)
LLN0 (Logical node zero)
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 5
R: Logical nodes for protection related functions
RDRE (Disturbance recorder)
M: Logical Nodes for metering and measurement
MMXN (Non phased related measurement)
MMXU (Measurement)
MSQI (Sequence and imbalance)
S: Logical Nodes for sensors and monitoring
SCBR (Circuit breaker monitoring)
X: Logical Nodes for switchgear
XCBR (Circuit breaker)
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 6
3 Logical Node Extensions
The following table use
M : Data is mandatory in IEC-61850-7-4.
O: Data is optional in IEC-61850-7-4 and is used in the device.
E: Data is an extension to IEC-61850-7-4.
C: Data is conditional in IEC-61850-7-4.
3.1 New Logical Nodes
New logical nodes have the lnNs attribute in the Name plate. The value of lnNs is $, which in this case is a reference to the MICS document.
The ABB IED650 Series platform contains the following new functions:
LN Class Prefix LN Type Description
FCVB IB16 IB16FCVB Integer to Boolean converter
FCVI B16I B16IFCVI Boolean to integer converter
SCBR ACBM SCBR Advanced CB operation and monitoring
LCCH RCH RCHLCCHPhysical communication channel supervision, redundant channels
3.1.1 IB16FCVB
FCVB class
Attribute
Name
DATA
TypeExplanation
M/O/E/
CRemarks
FCVB Integer to bool converter
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
ISCSO ABB_b_dINC Integer status controllable status output
M Controllable
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 7
3.1.2 B16IFCVI
FCVI class
Attribute
Name
DATA
TypeExplanation
M/O/E/
CRemarks
FCVI Bool16 to integer converter
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
OutInt ABB_b_dINS Integer output M
3.1.3 ACBMSCBR
SCBR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
SCBRAdvanced CB operation and
monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC ModeM
Beh ABB_a_dINS BehaviourM
Health ABB_c_dINS HealthM
NamPlt ABB_a_dLPL Name plateM lnNs=$ refers to the MICS
MechHealth ABB_v1_dINS Mechanical behaviour alarmE
OpTmAlm ABB_v1_dSPS Switch operating time
exceeded
E
OpCntAlm ABB_v1_dSPS Number of operations
(modelled in XCBR) has
exceeded the alarm
E
OpCntWrn ABB_v1_dSPS Number of operations
(modelled in XCBR) exceeds
the warning limit
E
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 8
MaxRkRiAlm ABB_v1_dSPS Maximum number of re-
ignitions or re-strikes detected
E
UnstOpChr ABB_v1_dSPS Unstable CB operating
characteristics, as determined
from detected switching
instants of recent operation
E
CntrPos ABB_v1_dSPS Contradicting mechanical and
electrical CB position
indications
E
SwA ABB_v1_dMV Current that was interrupted
during last open operation
E
AuxSwTmOp
n
ABB_v1_dMV Auxiliary switches timing openE
AuxSwTmCls ABB_v1_dMV Auxiliary switches timing
close
E
RctTmOpn ABB_v1_dMV Reaction time measurement
open
E
RctTmCls ABB_v1_dMV Reaction time measurement
close
E
OpSpdOpn ABB_v1_dMV Operation speed openE
OpSpdCls ABB_v1_dMV Operation speed closeE
OpTmOpn ABB_v1_dMV Operation time openE
OpTmCls ABB_v1_dMV Operation time closeE
Tmp ABB_v1_dMV Temperature e.g. inside drive
mechanism
E
RsUnst ABB_v1_dSPC Reset input to exit from CB
unstable state
E Controllable
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 9
3.1.4 RCHLCCH Revision 1
LCCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LCCH
Physical communication
channel supervision,
redundant channels
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
ChLiv ABB_a_dSPS Physical channel status; true, if channel receives telegrams within a specified time interval
M
RedChLiv ABB_a_dSPS Physical channel status of redundant channelYe
C
FerCh ABB_b_dINS Frame error rate on this channel
O
RedFerCh ABB_b_dINS Frame error rate on redundant channel
O
3.2 Extended Logical Nodes
The following logical nodes are included in the product. All extra data that has been added, is marked as
“E” (Extended), these data contains the “dataNs” attribute with a reference the MICS.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 10
LN Class Prefix
(default)
LN Type Description
LLN0
LLN0 General LN0 for LD0
SEC SECLLN0 Logical node 0 for logical device SECAUD
SS SSLLN0 Logical node for logical device SS
LPHD LPHD Physical device information
CPOW SS SSCPOW Point-on-wave switching
GGIO
CNT CNTGGIO Generic counters
DP DPGGIO Generic double point status
MV MVGGIO Generic measured value
SP SPGGIO Generic single point status
SP16 SP16GGIO Generic single point status, 16 outputs
SPC8 SPC8GGIO Single point command, 8 SPC’s
VS VSGGIO Versatile Switch
GSAL A AGSAL Security
MMXN CV CVMMXN Service value reading of power
MMXU
C CMMXU Current monitoring
V VMMXU Voltage monitoring
VN VNMMXU Voltage monitoring Ph-Gnd
MSQIC CMSQI Current monitoring, sequence values
V VMSQI Voltage monitoring, sequence values
RDRE DRP DRPRDRE Disturbance recorder
XCBR S SXCBR Circuit breaker
3.2.1 LLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 11
3.2.2 SECLLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 for logical
device SECAUD
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
3.2.3 SSLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 for logical
device SS
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_b_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 12
3.2.4 LPHD Revision 5
LPHD class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LPHD Physical device information
Data
Common Logical Node Information
PhyNam ABB_b_dDPL Physical device name plate M
PhyHealth ABB_c_dINS Physical device health M
Status Information
Proxy ABB_b_dSPS Indicates if this LN is a proxy
M
3.2.5 SSCPOW
CPOW class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CPOW Point-on-wave switching Logical device is SS
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
TmExc ABB_a_dSPS Maximum allowed time exceeded
O
StrPOW ABB_a_dSPS CPOW started O
OpOpn ABB_a_dACT Open switch O
OpCls ABB_a_dACT Close switch O
UnCtlSw ABB_v1_dSPS Uncontrolled switching operation
E
LosRefSig ABB_v1_dSPS Loss of reference signal E
LosCSig ABB_v1_dSPS Loss of compensation signal or sensor fault
E
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 13
3.2.6 CNTGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Event counters
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Cnt1 ABB_v1_dBCR Output of counter 1 E Data type for counter value is INT32 (INT128 is not supported)
Cnt2 ABB_v1_dBCR Output of counter 2 E Data type for counter value is INT32 (INT128 is not supported)
Cnt3 ABB_v1_dBCR Output of counter 3 E Data type for counter value is INT32 (INT128 is not supported)
Cnt4 ABB_v1_dBCR Output of counter 4 E Data type for counter value is INT32 (INT128 is not supported)
Cnt5 ABB_v1_dBCR Output of counter 5 E Data type for counter value is INT32 (INT128 is not supported)
Cnt6 ABB_v1_dBCR Output of counter 6 E Data type for counter value is INT32 (INT128 is not supported)
RsCnt ABB_v1_dSPC Reset counters E Controllable
3.2.7 DPGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Generic double point status
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
DPCSO ABB_b_dDPC General position indication O Controllable
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 14
3.2.8 MVGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Generic measured value
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
AnIn ABB_a_dMV Measured value O
3.2.9 SPGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Single point control
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Ind ABB_c_dSPS Output status O
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 15
3.2.10 SP16GGIO Revision 2
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIOGeneric single point
status, 16 outputs
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Ind ABB_c_dSPS General indication (binary
input)
O
GrInd ABB_v1_dSPS OR of all indications 1-16 E
Ind2 ABB_c_dSPS General indication no 2 E
Ind3 ABB_c_dSPS General indication no 3 E
Ind4 ABB_c_dSPS General indication no 4 E
Ind5 ABB_c_dSPS General indication no 5 E
Ind6 ABB_c_dSPS General indication no 6 E
Ind7 ABB_c_dSPS General indication no 7 E
Ind8 ABB_c_dSPS General indication no 8 E
Ind9 ABB_c_dSPS General indication no 9 E
Ind10 ABB_c_dSPS General indication no 10 E
Ind11 ABB_c_dSPS General indication no 11 E
Ind12 ABB_c_dSPS General indication no 12 E
Ind13 ABB_c_dSPS General indication no 13 E
Ind14 ABB_c_dSPS General indication no 14 E
Ind15 ABB_c_dSPS General indication no 15 E
Ind16 ABB_c_dSPS General indication no 16 E
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 16
3.2.11 VSGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Versatile switch
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
DPCSO ABB_d_dDPC Double point controllable status output
O Controllable
3.2.12 AGSAL Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GSAL SecurityLogical device is
SECAUD
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
OpCntRs ABB_f_dINC Resetable Security Violations counter
M Controllable
NumCntRs ABB_m_dINS Number of counter resets O According to Edition 2
AuthFail ABB_a_dSEC Authorisation failures M Controllable
AcsCtlFail ABB_a_dSEC Access control failures detected
M Controllable
SvcViol ABB_a_dSEC Service privilege violations M Controllable
Ina ABB_a_dSEC Inactive associations M Controllable
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 17
3.2.13 CVMMXN
MMXN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXNService value reading of
power
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
Amp ABB_a_dMV Current I (rms) not allocated to a phase
O
Hz ABB_a_dMV Frequency O
PwrFact ABB_a_dMV Power Factor not allocated to a phase
O
Vol ABB_a_dMV Voltage V (rms) not allocated to a phase
O
VolAmp ABB_a_dMV Apparent Power (S) not allocated to a phase
O
VolAmpr ABB_a_dMV Reactive Power (Q) not allocated to a phase
O
Watt ABB_a_dMV Power (P) not allocated to a phase
O
ALd ABB_v1_dSPS Current is leading voltage E
ALg ABB_v1_dSPS Current is lagging voltage E
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 18
3.2.14 CMMXU Revision 1
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Current monitoring
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
A ABB_a_dWYE Phase currents (IL1, IL2, IL3) O
3.2.15 VMMXU Revision 1
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Voltage monitoring
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
PPV ABB_a_dDEL Phase to phase voltages (VL1VL2, …)
O
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 19
3.2.16 VNMMXU Revision 1
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Voltage monitoring Ph-Gnd
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
PhV ABB_a_dWYE Phase to ground voltages (VL1ER, …)
O
3.2.17 CMSQI Revision 2
MSQI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MSQICurrent monitoring,
sequence values
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
SeqA ABB_a_dSEQ Positive, Negative and Zero Sequence Current
C
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 20
3.2.18 VMSQI Revision 2
MSQI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MSQIVoltage monitoring,
sequence values
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
SeqV ABB_a_dSEQ Positive, Negative and Zero Sequence Voltage
C
3.2.19 DRPRDRE
RDRE class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RDRE Disturbance recorder
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
RcdMade ABB_a_dSPS Recording made M
FltNum ABB_b_dINS Fault Number M
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 21
3.2.20 SSXCBR
XCBR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
XCBR Circuit breaker Logical device is SS
Data
Common Logical Node InformationMod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Loc ABB_a_dSPS Local operation (local means without substation automation communication, hardwired direct control)
M
OpCnt ABB_b_dINS Operation counterM
Pos ABB_b_dDPC Switch positionM Status only
BlkOpn ABB_f_dSPC Block openingM Status only
BlkCls ABB_f_dSPC Block closingM Status only
CBOpCap ABB_b_dINS Circuit breaker operating capability
M
POWCap ABB_v1_dINS Point on wave switching capability
E
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 22
4 Common Data Class Extensions
No common data class extensions have been made.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 23
5 Enum types Extensions
No Enum types extensions have been made.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 24
6 Control Block Extensions
No Control block extensions have been made.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRK511297-WEN en d1 25
REVISION
Rev. ind. Page (P) Chapt. (C)
Description Date Dept./Init.
d0 All Initial version 18June2013/IDC/INANPAR1
d1 All Updated after receiving comments from Reijo. Used the 650 Ver 1.3 as basis
11/July/2013/IDC/INANPAR1