Medical Office Building

2

Medical Office Building

• Occupancy – 400 persons• 8 a.m. – 5 p.m. Monday - Friday

• Building Characteristics• Three stories• 40,000 square feet (200’ x 200’) per floor• Standard construction

3

Office Application

4

Office Application

5

Office Application

6

Hot Water Systems

• Primary Pumps• Secondary Pumps• Tertiary Pumps• Heat Recovery Pumps• Air Handlers• Fan Coils• Radiant Floor• Convection Units• Filter Pumps

7

Hot Water Systems

P3P3

Bo

iler

1

Bo

iler

2

Type of PumpsP1 Primary P2 Secondary P3 Tertiary P4 Domestic HWP5 Heat Recovery

P6 Filter

P5

P4

P3

P2

P1

P6

P5

Radiators In-floorFan Coils

Filter System

HWAir Handler withHeat Recovery

HWR

CW

Heat Exchanger

8

VS/VV Hot Water Systems

Return

Supply

SecondaryPumps

Boi

ler

1*

Boi

ler

2*

P1*P2*

*Sequenced

VSP1*VSP2* ΔPSensor

VS Pumpsand Controls

9

Chilled Water Applications

• Primary Pumps• Secondary Pumps• Condenser Water Pumps• Fan Coils• VAV• Air Handlers• Chilled Beams

10

Chilled Water Applications

Type of PumpsP1 Primary P2 Secondary P3 Tertiary P4 Condenser WaterP5 Air HandlersP6 Filter

P2

P6

P5

RadiantFan Coils

Filter System

Air Handlers

Ch

ille

r

ChilledBeams

CoolingTower

CondenserWater

P1

P4

Expansion TankAir Separator

Common Pipe

P3 P3P3

Ch

ille

r

P1

CHW System Differences

• Pumps are typically 3-4 times larger• Condensation concerns• Air separator location• Primary pump location• Open loop system piping

12

Parallel Pumping

• Single pumps versus multiple pumps• Advantages• Common configurations

13

Single vs. Multiple Pump Comparison Single Pump Design

• Higher HP• No redundancy• Less piping• Less maintenance• Less complicated• Higher operating cost

Multiple Pump Design• Lower HP• Redundancy• More piping• More maintenance• More complicated• Lower operating cost

14

Parallel Pumping

Common Configurations – Closed loop systems

50% Duty Pump

50% Duty Pump

(2) 50% Duty Pump

(1) 50% Standby Pump

100% Duty Pump

100% Standby Pump

15

Parallel Pumping

Parallel Pumps - What?

1000 GPM@ 100 Ft

1000 GPM@ 100 Ft

2000 GPM

2000 GPM@ 100 Ft

16

Parallel Pumping

Parallel Pumps - Why? • Parallel pumping provides additive flow at the same point of head.

17

Single Pump Curve

Flow

Head

Pump Curve

Point of Selection

18

Parallel Pump Curve

Head

Flow

Flow 1, Pump 1 Flow 1, Pump 2

Single Pump Curve

Point of Selection Duty Point

Parallel Pump Curve

19

Parallel Pumping

Parallel Pumps - Advantages• Smaller pumps• Smaller motors• Lower operating cost• Standby options• Right size pump operating more often

20

Parallel Pumping

90

80

70

60

50

40

30

20

10

0 10 1009080706050403020

100

% F

ull

Loa

d H

P

% Flow

Parallel C/S2 Pumps

Single C/S

Single ParallelC/S

• Getting more out of your pump!

21

Parallel Pumping

Pump 1 selection:500 gpm @ 100 ft

Pump 1 & 2 selection:1000 gpm @ 100 ft

Pump 1 operation:820 gpm @ 68 ft

System Curve

Operation Beyond Selection Point

22

Parallel Pumping Review

Selection Criteria•Select pumps for 50% of total flow (500 gpm, each)•Make sure each pump can cross system curve

Parallel Pump Advantage•Pump runs out to 820 gpm•Operate one pump for ≥ 80% of the time•Save operational cost!

23

Parallel Pumping Cautions

• Pumps too smallo End of curve

• Unequal sized pumpso Erratic operation

Improper parallel pump selection

24

Parallel Pumping Caution

0 200 400 600 800 1000 1200 1400Flow (gpm)

150

120

90

60

30

0

Pump 1 Pump 2 Pump 3

System Curve

Pump 1 selection:333 gpm @ 90 ft

Pump 1& 2 selection:666 gpm @ 90 ft

Pump 1, 2, &3 selection:1000 gpm @ 90 ft

Head (

ft)

End of Curve

25

Parallel Pump Caution

Unequal Size Pump Selection

26

Sequencing Parallel Pumps

Pump sequencing methods:‒ Head‒ Differential Head‒ Temperature‒ Flow‒ Current sensing

27

Sequencing Parallel Pumps

P1

P1&2

Staging point

Duty point

40

35

30

25

20

15

10

5

0

Head (

ft)

0 100 200 300 400 500 600 700 Flow (gpm)

28

Parallel Pumping

Parallel pumps - Operation• How many can you add?

• Practical limit – 6 pumps

29

Maximum Number of Parallel Pumps

P2P1

P4P3 P5 P7P6

Parallel VS Operation

30

Point E Point D

Point C

Point B

Point A

31

VS/VV Pumping

Add:• Variable frequency drive (VFD)• Programmable logic controller (PLC)• Differential pressure sensors (∆P)• Direct digital controls (DDC)

Save operating cost versus CS/CV system!

32

VS/VV Pump Energy Consumption

CS/CV

CS/VV

VS/VV

33

VS/VV Pumping

Add:• Variable frequency drive (VFD)• Programmable logic controller (PLC)• Differential pressure sensors (∆P)• Direct digital controls (DDC)

Or add…

34

Demand More

Magna3!

35

Demand More – Intelligent Control

Traditional methods• Previously discussed

Sequencing Parallel Pumps

36

Demand More - Intelligent Control

Optimized solution not only for the pumps, but for the total system conditions

• Uncontrolled (constant volume) curve• Constant pressure• Proportional pressure• Temperature control• FLOWADAPT

• AUTOADAPT

37

Demand More - Intellegent Control

Q100%25%

H

1. Uncontrolled

2. Constant pressure

3. Proportional pressure (calculated)

4. Proportional pressure (measured)

5. Temperature control

0 20 40 60 80 100

100

80

60

40

20

0

Flow in %

Eff

ect

in % 1.

2.

3.4.

5.

Get Additional Energy Savings

38

Demand More – Life Cycle Costing