SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P040AU24AA
M801P040AU24-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P040AU24AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1018847716617
1004832701599
982809678575
950779648544
910742610507
860697585463
802644512413
763585452357
660517384294
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
M801P040AU24AA 54 49 42 37 33 30
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
13-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"14-1/2"
13"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P040AU24-SUB-1AM801P040AU24-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
M801P040AU24AAUpflow / Horizontal
40,00031,00030 - 60Direct10 x 6
14
See Fan Performance Table1/5
1080115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 16x25 - 1 in.
4 Round
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
Alum. Steel-
20
2 — 452 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
2115/1/60
5.4151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
119 / 110
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P060AU24AA
M801P060AU24-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P060AU24AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1018835712611
997821702596
973800683573
941771655543
901734617505
852689571459
796636516406
731575452345
659506379277
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
M801P060AU24AA 63 56 49 44
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
13-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"14-1/2"
13"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AU24-SUB-1AM801P060AU24-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
M801P060AU24AAUpflow / Horizontal
60,00047,00030 - 60Direct
10 x 6**14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 16x25 - 1 in.
4 Round
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
Alum. Steel
20
3 — 453 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
3115/1/60
9.0151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
127 / 118
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P060AU36AA
M801P060AU36-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P060AU36AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
142612431042900
138912251039903
134511971027895
129811601005877
12361113973848
11711057931809
1099991879760
1020916817700
934831745629
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
M801P060AU36AA 56 49 44 40 37 34 32
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
13-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"14-1/2"
13"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AU36-SUB-1AM801P060AU36-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
M801P060AU36AAUpflow / Horizontal
60,00047,00030 - 60Direct
10 x 6**14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 16x25 - 1 in.
4 Round
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
Alum. Steel
20
3 — 453 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
3115/1/60
9.0151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
127 / 118
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P080BU36AA
M801P080BU36-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P080BU36AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1393 1210 1046 900
1384 1209 1052 903
136411981047895
133511771033888
129611471008869
12471107973842
11891058928808
1120999873766
1042930808717
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
M801P080BU36AA 59 54 49 46 42
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
16-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"17-1/2"
16"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BU36-SUB-1AM801P080BU36-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
M801P080BU36AAUpflow / Horizontal
80,00063,00030 - 60Direct10 x 7
14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 17x25 - 1 in.
4 Round
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
Alum. Steel
20
4 — 454 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
4115/1/60
9.0151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
142 / 132
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P080BU48AA
M801P080BU48-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P080BU48AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
183913231092788
182113251090783
179613291091780
175613191083768
171013081076758
164112751059737
157312461040719
148012011005674
13921165970630
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
M801P080BU48AA 67 62 57 53 49
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
16-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"17-1/2"
16"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BU48-SUB-1AM801P080BU48-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P080BU48AAUpflow / Horizontal
80,00064,00030 - 60Direct10 x 8
14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 17x25 - 1 in.
4 Round
Alum. Steel
20
4 — 454 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
4115/1/60
9.8151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
142 / 132
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P100BU36AA
M801P100BU36-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P100BU36AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
147612491020873
146412571046
887
144112521058
890
140812341050883
136312031028864
13071158990834
12411101936794
11631030866742
1074946780680
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
M801P100BU36AA 58 52 49 46 42 40 37 35 33
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
16-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"17-1/2"
16"
3/4"
3/4"
3-15/16"
9-5/8"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P100BU36-SUB-1AM801P100BU36-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P100BU36AAUpflow / Horizontal
100,00079,00040 - 70Direct10 x 7
14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 17x25 - 1 in.
4 Round
Alum. Steel
20
5 — 455 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
9.0151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
151 / 141
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P100CU48AA
M801P100CU48-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P100CU48AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1880166214281208
1846163514211215
1799159814021210
1740155113701193
1669149313261164
1595142412691124
1489134511991073
1381125611171009
126011571022935
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
M801P100CU48AA 67 62 57 53 49 46 44 41 39 37
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
19-3/4"
22-1/2"
28-1/4"
8-1/4"
5/8"21"
19-1/2"
3/4"
3/4"
3-15/16"
13-1/16"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CU48-SUB-1AM801P100CU48-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P100CU48AAUpflow / Horizontal
100,00079,00035 - 65Direct10 x 8
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 20x25 - 1 in.
4 Round
Alum. Steel
20
5 — 455 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
11.6151/2
H x W x D41-3/4 x 23 x 30-1/2
162 / 151
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P100CU60AA
M801P100CU60-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P100CU60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2181190816211443
2143188816091419
2104186815971395
2053183415821381
2001180015671367
1929174515331335
1856169014981302
1766 1631 1438 1256
1676157213771209
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P100CU60AA 62 57 53 49 46 44 41 39 37 35 34 32 31
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
19-3/4"
22-1/2"
28-1/4"
8-1/4"
5/8"21"
19-1/2"
3/4"
3/4"
3-15/16"
13-1/16"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CU60-SUB-1AM801P100CU60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P100CU60AAUpflow / Horizontal
100,00079,00030 - 60Direct
11 x 1014
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 20x25 - 1 in.
4 Round
Alum. Steel
20
5 — 455 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
13.4201/2
H x W x D41-3/4 x 23 x 30-1/2
162 / 151
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P120DU60AA
M801P120DU60-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P120DU60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2135190616461423
2101188116321415
2066185616171407
2036181715961391
2005177715751375
1923172415351338
1840167114941300
1750160214271246
1659153313601192
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P120DU60AA 59 56 52 49 47 44 42 40
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
23-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"24-1/2"
23"
3/4"
3/4"
3-15/16"
15-5/16"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P120DU60-SUB-1AM801P120DU60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P120DU60AAUpflow / Horizontal
120,00096,00030 - 60Direct
11 x 1014
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 24x25 - 1 in.
4 Round
Alum. Steel
20
6 — 456 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
6115/1/60
13.4201/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
186 / 174
SUBMITTAL
© 2015 Ingersoll Rand
TAG: _________________________________
Upflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P140DU60AA
M801P140DU60-SUB-1A
FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P140DU60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2462212817551450
2407211217461446
2351209617361442
2284205417191427
2216201217021411
2143194916561383
2069188716091354
1989179715641298
1908170615181241
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P140DU60AA 69 65 61 58 55 52 49 47 45
7/8" DIA. HOLESELECTRICALCONNECTION
1-1/2" DIA. HOLEGAS CONNECTION
40"
1/2"
3-3/4"
28-1/4"
5-5/16"
3/8"
2-1/8"
23-1/2"
3-13/16"
3/4"
28-3/8"19-5/8"
5/8"
4-1/16"
23-1/4"
22-1/2"
28-1/4"
8-1/4"
5/8"24-1/2"
23"
3/4"
3/4"
3-15/16"
15-5/16"
5/8"
2-1/16"
4" DIAMETERFLUE CONNECT
2-1/16"
1/2"
Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG (2)
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P140DU60-SUB-1AM801P140DU60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P140DU60AAUpflow / Horizontal
140,000111,00040 - 70Direct
11 x 1014
See Fan Performance Table3/4
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity1 - 24x25 - 1 in.
4 Round
Alum. Steel
20
7 — 457 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
7115/1/60
13.8201/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
193 / 181
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P040AD24AA
M801P040AD24-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300
M801P040AD24AA 59 49 42 37 33
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P040AD24AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1070870740633
1033850720600
1000823690577
960790663543
920753627507
860813588463
810667547420
740613483360
-490
--
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
13-1/4"14-1/2"
13"
3/4"
3/4"
9-5/8"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P040AD24-SUB-1AM801P040AD24-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P040AD24AADownflow / Horizontal
40,00031,00030 - 60
DIRECT10 x 6
14
See Fan Performance Table1/5
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 14x20 - 1in.
4 Round
Alum. Steel
20
2 — 452 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
2115/1/60
5.4151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
119 / 109
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P060AD24AA
M801P060AD24-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400
M801P060AD24AA 63 56 49 44 40
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P060AD24AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
12001025838722
1155988808689
1111951779656
1056905742618
1001859704579
924797646528
848735588478
774646502376
701558415275
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
13-1/4"14-1/2"
13"
3/4"
3/4"
9-5/8"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AD24-SUB-1AM801P060AD24-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P060AD24AADownflow / Horizontal
60,00048,00035 - 65
DIRECT10 x 7
14
See Fan Performance Table1/5
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 14x20 - 1in.
4 Round
Alum. Steel
20
3 — 453 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
3115/1/60
5.5151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
129 / 119
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P060AD36AA
M801P060AD36-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
M801P060AD36AA 56 49 44 40 37 34 32
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P060AD36AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
148013021115956
142912761100947
137512291070918
131811881035888
128211411000859
11001088965824
11121024918788
1029953859741
959882790682
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
13-1/4"14-1/2"
13"
3/4"
3/4"
9-5/8"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AD36-SUB-1AM801P060AD36-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P060AD36AADownflow / Horizontal
60,00048,00030 - 60
DIRECT11 x 7
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 14x20 - 1in.
4 Round
Alum. Steel
20
3 — 453 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
3115/1/60
11.6151/2
H x W x D41-3/4 x 16-1/2 x 30-1/2
129 / 119
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P080BD45AA
M801P080BD45-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
M801P080BD45AA 64 57 52 48 44 41
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P080BD45AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1798138412101005
175013671150970
169213331108808
164213001075775
157512751042767
150012331008733
14251192967700
13251142925675
12251083867617
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
16-1/4"17-1/2"
16"
3/4"
3/4"
9-5/8"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BD45-SUB-1AM801P080BD45-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P080BD45AADownflow / Horizontal
80,00064,00035 - 65
DIRECT10 x 8
14
See Fan Performance Table1/3
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 14x20 - 1 in.
4 Round
Alum. Steel - Type I
20
4 — 454 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
4115/1/60
9.1151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
146 / 135
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P100CD48AA
M801P100CD48-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P100CD48AA 62 57 53 49 46 44 41 39 37
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P100CD48AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
1965164514071202
1915162713981208
1865160513871205
1805157513751195
1740153513471166
1670148213181140
1587142112751105
1500133011901045
137012201095970
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
19-1/4"21"
19-1/2"
3/4"
3/4"
13-1/16"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CD48-SUB-1AM801P100CD48-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P100CD48AADownflow / Horizontal
100,00080,00035 - 65
DIRECT10 x 8
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 16x20 - 1in.
4 Round
Alum. Steel
20
5 — 455 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
11.6151/2
H x W x D41-3/4 x 23 x 30-1/2
166 / 154
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P100CD60AA
M801P100CD60-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P100CD60AA 62 57 53 49 46 44 41 39 37 35 34 32 31
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P100CD60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2165196217051492
2113192716881467
2060189116711442
1995183916361414
1929178616001385
1842172415471346
1755166214921307
1674158114351243
1593150013771179
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
19-1/4"21"
19-1/2"
3/4"
3/4"
13-1/16"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CD60-SUB-1AM801P100CD60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P100CD60AADownflow / Horizontal
100,00080,00030 - 60
DIRECT11 x 10
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 16x20 - 1 in.
4 Round
Alum. Steel - Type I
20
5 — 455 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
12.8151/2
H x W x D41-3/4 x 23 x 30-1/2
167 / 155
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P120DD60AA
M801P120DD60-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P120DD60AA 59 56 52 49 47 44 42 40
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P120DD60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2241198117211476
2202196217051466
2163194216881456
2106190416711440
2049186616531423
1979180516111392
1908174315691361
1804168015151302
1700161714611243
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
23-1/4"24-1/2"
23"
3/4"
3/4"
15-5/16"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P120DD60-SUB-1AM801P120DD60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P120DD60AADownflow / Horizontal
120,00096,00035 - 65
DIRECT11 x 10
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 16x20 - 1 in.
4 Round
Alum. Steel - Type I
20
6 — 456 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
6115/1/60
12.8151/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
189 / 176
SUBMITTAL
© 2012 Ingersoll Rand
TAG: _________________________________
Downflow/ Horizontal Induced Draft Single Stage Gas Furnace
Ameristar
M801P140DD60AA
M801P140DD60-SUB-1A
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400
M801P140DD60AA 69 65 61 58 55 52 49 47 45
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)
MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90
M801P140DD60AA
4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red
2377211518061527
2321208117931507
2265204617791486
2199199217381473
2133193816961459
2050187216551422
1967180516141384
1877172715561329
1786164914971273
7/8" HOLE WITH PLUG
1-1/2" DIA. GASCONNECTION(ALTERNATE)
7/8" DIA. HOLESELECTRICALCONNECTION
1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)
40"
20-1/4"
10"
5-5/16"1/2"
3-3/4”
19"
8-1/4"
3/4"
28"
19-5/8"
5/8"
4-1/8"
23-1/4"24-1/2"
23"
3/4"
3/4"
15-5/16"
2-1/8"
2-1/8"
12-3/8"
10"
5/8"
FLUE OPENING
24-1/2"
29-1/2"
5"
7"
SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET
1/2"
4" O
3-15/16"
3-3/8
3-1/2
31
5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET
7-3/8"
1-5/8” HOLEWITH PLUG
1-5/8” HOLEWITH PLUG
1-5/8” HOLE WITH PLUG
1-5/8” HOLE WITH PLUG
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.
Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032
Technical Literature - Printed in U.S.A.
LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes
Mechanical Specifications
AmeristarFurnacesFurnaceM801Submittal-05/15M801P140DD60-SUB-1AM801P140DD60-SUB-1
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.
QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.
BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.
AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).
STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.
FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter
b. Vent proving pressure switch.
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
M801P140DD60AADownflow / Horizontal
140,000113,00045 - 75
DIRECT11 x 10
14
See Fan Performance Table3/4
1075115/1/60
CentrifugalDirect - 1
1/50 - 3180115/1/60
1.09No
High Velocity2 - 16x20 - 1in.
4 Round
Alum. Steel
20
7 — 457 — 56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
7115/1/60
13.8201/2
H x W x D41-3/4 x 26-1/2 x 30-1/2
196 / 183