am ret670 settingexample2 rb

Upload: kunaljay

Post on 03-Jun-2018

244 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/12/2019 AM RET670 SettingExample2 RB

    1/21

    290

    245

    1380

    293

    292

    289

    291

    294

    Vector group 2 winding transformer

    Vector group 3 winding transformer

    1552

    1553

    1551

    REF

    REF

    1555

    Setting of Transformer protection terminal type RET670 v1.0

    Transformer: =T1 =T2 respectively

    Frequency:

    Rated data:

    50 Hz

    Rated Power 40 MVA / 40 MVA

    Voltage ratio

    Tap changer +

    Wind 1 - Ir1

    Wind 2 - Ir2

    132 kV

    8

    /

    /-

    175 A

    1155 A

    20.0 kV

    8 * 1.25 %

    ConnectionCooling

    p.u. Impedance

    CT ratio Wind 1

    CT ratio Wind 2

    VT ratio Wind 1

    at Base

    250 /

    1200132

    /

    /

    YNyn0ONAF

    0.10040 MVA

    1 A

    1 A

    0.110 kV

    VT ratio Wind 2 20 / 0.110 kV

    1. Terminal identification

    StationName: Station F

    StationNumber:

    ObjectName:Object Number:

    UnitName:

    6

    Transformer3

    RET670

    UnitNumber:

    Relay serial No

    Frequency

    Aux voltage

    1

    A1234

    50 Hz

    110.000 V

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerAppro ved Resp. d ept. Titl e Rev in d

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    1Cont

    1MRK 504 084-WEN 21

    Wereserveallrightsinthisdocumentandinthe

    informationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartiesw

    ithoutexpress

    authorityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

    BA

    Rev No

    Adjusted MDFirst issueDescri tion

    MDA d

    2006-07-052005-11-11Date

  • 8/12/2019 AM RET670 SettingExample2 RB

    2/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    2Cont

    1MRK 504 084-WEN 21

    Set analogue voltage channels.

    Name: =

    Ch U1

    IN132

    Ch U2

    IN Z0

    Ch U3

    NotUsed

    Ch U4

    UL1

    VTprimn

    VTsecn

    =

    =

    250.000

    0.110 V

    1200.000

    0.110 V

    250.000

    0.110 V

    132.000

    0.110 V

    Ch U5

    UL2

    Ch U6

    UL3

    132.000

    0.110 V

    132.000

    0.110 V

    2. Setting of analogue and digital channels.

    Configure analogue inputs for TRM1:

    Set analogue current channels

    Name:

    CTprim

    CTsec

    =

    =

    =

    Ch I1

    IL1-130

    Ch I2

    IL2-130

    250.000

    1.0 A

    250.000

    1.0 A

    Ch I3

    IL3-130

    Ch I4

    IL1-20

    250.000

    1.0 A

    1200.000

    1.0 A

    Ch I5

    IL2-20

    Ch I6

    IL3-20

    1200.000

    1.0 A

    1200.000

    1.0 A

    Set Digital IO boards

    I/O Module 1 =

    Operation

    On

    OscBlock

    40

    OscRelease

    30 Pos Slot3

    I/O Module 2I/O Module 3

    I/O Module 4

    I/O Module 5

    ==

    =

    =

    OnOn

    4040

    On

    On

    40

    40

    3030

    Pos Slot3Pos Slot3

    30

    30

    Pos Slot3

    Pos Slot3

    Note: OscBlock and OcscRel defines the filtering time at activation

    3. Setting of the analogue preprocessing function blocks SMAI (General settings/Power system)

    Set ref for DFT filter adjustment:

    Set the measured minimum value:

    DFTRefGrpn

    MeaMinValGrpn

    =

    =

    Grp7AdDFTRef

    5%

    set voltage L1 as ref

    Set the connection type

    Set negation of the function block

    Set the base voltage

    For first function block in each task time also

    ConTypeGrpn

    NegGrpn

    UBaseGrpn

    =

    =

    Ph-N

    Off

    = 130.00 kV

    SYNCH output reference DFTRefExtOut = Grp7AdDFTRef set voltage L1 as ref

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    3/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    3Cont

    1MRK 504 084-WEN 21

    4b. Differential Protect ion Setting (T2D1) under Setting group:

    Setting of minimum differential operating current

    Operation = On

    Setting of cross-over point between slope 1 and slope 2

    Setting of slope 2 stabilisation, Slope 1 has fixed stabilization

    IdMin =

    EndSection1 =

    0.25 *Ibase

    300% Ibase*C.S

    Setting of cross-over point between slope 2 and slope 3

    Setting of slope 2 stabilisation

    SlopeSection2 =

    EndSection2 =

    Setting of minimum differential operating current for unrestraint step

    Set the operation of Cross Blocking logic On-Off

    SlopeSection3 =

    Idunre =

    40% *Ibias

    300% Ibase*C.S

    80% *Ibias

    10.00 *Ibase

    Set the second and fifth harmonic stabilizing level when transformers are inside the zone

    OpCrossBlock =

    I2/I1RatioI5/I1Ratio

    ==

    Set the operation of Negative sequence differential protection!

    Setting of minimum negative sequence differential current level

    OpNegSeqDiff =

    IMinNegSeq =

    On

    15 %25 %

    Yes

    0.04 *Ibase

    Setting of the Relay operating angles.

    NegSeqROA = 60

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    4a. Setting of the Differential function data under General settings.

    Winding 1 (W1)

    Connection type Y

    Winding 2 (W2)

    Connection type D

    Rated Current W1

    TconfigForW1

    CT1ratingW1

    TraAWind1Volt

    175 A

    Yes

    250 A

    132.0 kV

    Rated Current W2

    TconfigForW2

    1155 A

    No

    CT1ratingW2

    TraBWind1Volt

    1200 A

    20.0 kV

    ZSCurrSubtrW3 On ZSCurrSubtrW2

    ClockNumTransfB

    On

    1 relative W1, hour notation

  • 8/12/2019 AM RET670 SettingExample2 RB

    4/21

    5a. Setting of Restricted Earth Fault function REF1 Included X

    Activation of the Short Circui function

    Operation = On

    Setting of the base current for the REF1 function

    Set the minimum sensitivity

    Ibase =

    Idmin =

    175 A

    10 %

    Setting of the Characteristic angles for operation.

    Set the factor for CT primary 1 rated current compared to the neutral CT.

    roa =

    CtFactorPri1 =

    Set the factor for CT primary 2 rated current compared to the neutral CT.

    Set the factor for CTsecond winding input 1 rated current compared to the neutral CT.

    CtFactorPri2 =

    CtFactorSec1 =

    60

    1.0

    1.0

    1.0

    Set the factor for CTsecond winding input 2 rated current compared to the neutral CT.

    CtFactorSec2 = 1.0

    5b. Setting of Restricted Earth Fault f unction REF2 Included X

    Activation of the Short Circui function

    Operation = On

    Setting of the base current for the REF2 function

    Set the minimum sensitivity

    Ibase =

    Idmin =

    1155 A

    10 %

    Setting of the Characteristic angles for operation.

    Set the factor for CT primary 1 rated current compared to the neutral CT.

    roa =

    CtFactorPri1 =

    Set the factor for CT primary 2 rated current compared to the neutral CT.

    Set the factor for CTsecond winding input 1 rated current compared to the neutral CT.

    CtFactorPri2 =

    CtFactorSec1 =

    60

    1.0

    1.0

    1.0

    Set the factor for CTsecond winding input 2 rated current compared to the neutral CT.

    CtFactorSec2 = 1.0

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    4Cont

    1MRK 504 084-WEN 21

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    5/21

    Setting of the tripping logic (TR01)

    Operation = On

    Set the trip pulse length

    Set the latching of the trip signal

    Program =

    tTripMin =

    3ph

    0.150 s

    Set the internal activation of Lock-out output, else only activation of Lock-out input will create Lock-out

    TripLockout =

    AutoLock =

    Off

    Off

    Setting of the tripping logic (TR02)

    Operation = On

    Set the trip pulse length

    Set the latching of the trip signal

    Program =

    tTripMin =

    3ph

    0.150 s

    Set the internal activation of Lock-out output, else only activation of Lock-out input will create Lock-out

    TripLockout =

    AutoLock =

    Off

    Off

    Setting of the tripping logic (TR03)

    Operation = On

    Set the trip pulse length

    Set the latching of the trip signal

    Program =

    tTripMin =

    3ph

    0.150 s

    Set the internal activation of Lock-out output, else only activation of Lock-out input will create Lock-out

    TripLockout =

    AutoLock =

    Off

    Off

    Setting of the tripping logic (TR04)

    Operation = On

    Set the trip pulse length

    Set the latching of the trip signal

    Program =

    tTripMin =

    3ph

    0.150 s

    Set the internal activation of Lock-out output, else only activation of Lock-out input will create Lock-out

    TripLockout =

    AutoLock =

    Off

    Off

    Setting of the tripping logic (TR05)

    Operation = On

    Set the trip pulse length

    Set the latching of the trip signal

    Program =

    tTripMin =

    3ph

    0.150 s

    Set the internal activation of Lock-out output, else only activation of Lock-out input will create Lock-out

    TripLockout =

    AutoLock =

    Off

    Off

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    5Cont

    1MRK 504 084-WEN 21

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

    Setting of the tripping matrix (TR01) used for the 132 kV CB

    Operation = On

    Set the pulse length

    Set th on delay

    PulseTime1 =

    OnDelayTime1 =

    0.150 s

    0.000 s

    PulseTime2

    OnDelayTime2

    = 0.150 s

    = 0.000 s

    PulseTime2 =

    OnDelayTime2 =

    0.150 s

    0.000 s

    Set the off delay

    OffDelayTime1 = 0.000 s OffDelayTime2 = 0.000 s OffDelayTime2 = 0.000 s

    Setting of the tripping matrix (TR02) used for the 20 kV CB

    Operation = On

    Set the pulse length

    Set th on delay

    PulseTime1 =

    OnDelayTime1 =

    0.150 s

    0.000 s

    PulseTime2

    OnDelayTime2

    = 0.150 s

    = 0.000 s

    PulseTime2 =

    OnDelayTime2 =

    0.150 s

    0.000 s

    Set the off delay

    OffDelayTime1 = 0.000 s OffDelayTime2 = 0.000 s OffDelayTime2 = 0.000 s

  • 8/12/2019 AM RET670 SettingExample2 RB

    6/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    6Cont

    1MRK 504 084-WEN 21

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Instantaneous overcurrent protection (IOC1) on HV side phases

    The function is used with a reach less than 80% of the transformer at minimum source impedance.

    Setting of operation

    Set the Base current for the function on which the current levels are based

    Operation =

    Ibase =

    On

    175 A

    Setting of operation mode

    Operating level of the instantaneous O/C protection

    OpMode =

    IP>> =

    Set a multiplier at inrush used when the binary input is activated

    StValMult =

    1 out of 3

    1500% *Ibase

    1.00

    Instantaneous Earth fault protection (IEF1) on 132 kV side phases

    The function is used with a reach less than 80% of the transformer at minimum source impedance.

    Setting of operation

    Set the Base current for the function on which the current levels are based

    Operation =

    Ibase =

    On

    175 A

    Operating level of the instantaneous O/C protection

    Set a multiplier at inrush used when the binary input is activatedIN>> =

    StValMult =

    1500% *Ibase

    1.00

    Instantaneous overcurrent protection (IOC2) on 20 side phases

    The function is used with a reach less than 80% of the transformer at minimum source impedance.

    Setting of operation

    Set the Base current for the function on which the current levels are based

    Operation =

    Ibase =

    On

    1155 A

    Setting of operation mode

    Operating level of the instantaneous O/C protection

    OpMode =

    IP>> =

    Set a multiplier at inrush used when the binary input is activated

    StValMult =

    1 out of 3

    1000% *Ibase

    1.00

    Instantaneous Earth fault protection (IEF2) on 20 side phases

    The function is used with a reach less than 80% of the transformer at minimum source impedance.

    Setting of operation

    Set the Base current for the function on which the current levels are based

    Operation =

    Ibase =

    On

    1155 A

    Operating level of the instantaneous O/C protection

    Set a multiplier at inrush used when the binary input is activated

    IN>> =

    StValMult =

    1000% *Ibase

    1.00

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    7/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    7Cont

    1MRK 504 084-WEN 21

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Setting of Fuse Failure supervision function based on U0-I0, U2-I2 and dU-dI (FSD)

    Setting of the operation for the Fuse failure supervision

    Setting of the operating mode for the Fuse failure supervision

    Operation =

    OpMode =

    On

    UZsIZs

    Setting of the Base voltage level on which the directional polarizing voltage is based

    Set the Base current for the function on which the current levels are based

    UBase =

    Ibase =

    Setting of the 3U0 (UZs) voltage required to give operation

    Setting of the 3I0 (IZs) current which will block the fuse failure function

    3U0> =

    3I0< =

    20.0 kV

    1155 A

    20% *UBase

    10% *Ibase

    Setting of the U2 (UNs) voltage required to give operation

    Setting of the I2 (INs) current which will block the fuse failure function

    3U2> =

    3I2< =

    Setting of the operation for the DU> and DI< measuring function

    Setting of the DU> voltage required to give operation

    Operation DUDI =

    DU> =

    20% *UBase

    10% *Ibase

    Off

    20% *UBaseSetting of the DI< current which will block the fuse failure function

    Setting of the operate voltage for phase voltages

    IPH> =

    UPH> =

    Setting of the operate value for phase currents

    Setting of the seal-in function On-Off giving seal-in of alarm until voltages are symmetrical and high

    DI< =

    SEALIN =

    10% *Ibase

    70% *UBase

    10% *Ibase

    On

    Set the voltage level for the seal-in of the function

    Note! At operation symmetrical voltages (reset of DLD) is required to reset the FUSE function.

    Setting of the U< voltage

    USealIn< =

    Setting of under current

    UDLD< =

    IDLD< =

    60% *UBase

    60% *UBase

    20% *Ibase

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    8/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    8Cont

    1MRK 504 084-WEN 21

    Setting of four step Earth fault overcurrent function (TEF1) on 20 kV side neutral

    Activation of the earth fault function

    Set the Base current for the function on which the current levels are based

    Setting of the Base voltage level on which the directional polarizing voltage is based

    Operation =

    Ibase =

    On

    1000 A

    Setting of parameters for f irst stage

    Setting of the operating direction for the stage

    UBase= =

    DirMode1 =

    Setting of the operating characteristic

    Setting of the operating current level in primary values

    Characteristic1 =

    IN1>' =

    20.0 kV

    NonDir

    IEC NI

    100 A

    Set the current multiplier for IN1 valid at activation of input ENMULT

    Set the definite time delay, when definite time characteristic has been selected

    IN1> =

    IN1Mult =

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    t1 =

    k1 =

    10% *Ibase

    2.00

    0.30 s

    0.20

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t1Min =

    ResetTypeCrv1 =

    Set the release of Harmonic restraint blocking for the stage

    Setting of parameters for second stage

    tReset1 =

    HarmRestrain1 =

    0.30 s

    Instantaneous

    0.02 s

    On

    Setting of the operating direction for the stage

    Setting of the operating characteristicDirMode2 =

    Characteristic2 =

    Setting of the operating current level in primary values

    Set the current multiplier for IN2 valid at activation of input ENMULT

    IN2>' =

    IN2> =

    Off

    IEC NI

    600 A

    60% *Ibase

    Set the definite time delay, when definite time characteristic has been selected

    Set the back-up trip time delay multiplier for inverse characteristic

    IN2Mult =

    t2 =

    Set the Minimum operating time for inverse characteristic

    Select the reset curve type for the inverse delay

    k2 =

    t2Min =

    2.00

    0.30 s

    0.20

    0.30 s

    Set the Reset time delay for definite time delayed function

    Set the release of Harmonic restraint blocking for the stage

    ResetTypeCrv2 =

    tReset2 =

    HarmRestrain2 =

    Instantaneous

    0.02 s

    On

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    9/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    9Cont

    1MRK 504 084-WEN 21

    Setting of parameters for third stage

    Setting of the operating direction for the stage

    DirMode3 = Off

    Setting of the operating characteristic

    Setting of the operating current level in primary values

    Characteristic3 =

    IN3> =

    IEC NI

    1200 A

    Set the current multiplier for IN3 valid at activation of input ENMULT

    Set the definite time delay, when definite time characteristic has been selected

    IN3> =

    IN3Mult =

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    t3 =

    k3 =

    120% *Ibase

    2.00

    0.30 s

    0.20

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t3Min =

    ResetTypeCrv3 =

    Set the release of Harmonic restraint blocking for the stage

    Setting of parameters for fourth s tage

    tReset3 =

    HarmRestrain3 =

    0.30 s

    Instantaneous

    0.02 s

    On

    Setting of the operating direction for the stage

    Setting of the operating characteristic

    DirMode4 =

    Characteristic4 =

    Setting of the operating current level in primary values

    Set the current multiplier for IN4 valid at activation of input ENMULT

    IN4> =

    IN4> =

    Off

    IEC NI

    2000 A

    200% *Ibase

    Set the definite time delay, when definite time characteristic has been selected

    Set the back-up trip time delay multiplier for inverse characteristic

    IN4Mult =

    t4 =

    Set the Minimum operating time for inverse characteristic

    Select the reset curve type for the inverse delay

    k4 =

    t4Min =

    2.00

    0.30 s

    0.20

    0.30 s

    Set the Reset time delay for definite time delayed function

    Set the release of Harmonic restraint blocking for the stage

    ResetTypeCrv4 =

    tReset4 =

    Set of Direction, Harmonic blocking and SOTF functionality

    Setting of the minimum neutral point polarizing voltage level for the directional funtion

    HarmRestrain4 =

    3U0>Dir =

    Instantaneous

    0.02 s

    On

    1.00 %*Ubase

    Set the relay characteristic angle, i.e. the angle between the neutral point voltage and current

    Setting of the operating current level for the directional release. Note! Sensitivity at RCA

    AngleRCA =

    IN>DirCmp =

    Set the definite time delay for the directional comparison function

    tDirCmp =

    -65 deg Normal zero sequence source angle at direct earthing

    3% *Ibase

    0.05 s

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    10/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    10Cont

    1MRK 504 084-WEN 21

    Enable the harmonic restraint measuring function

    Setting of the harmonic content in IN current blocking level

    HarmRestrain = On

    Set the harmonic seal-in blocking at parallel transformers on if problems are expected due to sympatetic inrush.

    Set the current level to be blocked to seal-in the Harmonic blocking on this level if sympatetic inrush is expected.

    2ndHarmStab =

    BlockParTransf =

    25% of I

    On

    Set the SOTF function operating mode

    Select the input signal which shall activate the SOTF function

    UseStartVal =

    SOTF =

    Select the input signal which shall activate the undertime function

    Select the step to be uset in SOTF mode

    ActivationSOTF =

    ActUndertime =

    IN1>

    Off

    CloseCommand

    CloseCommand

    Set the time after closing or position change during which the SOTF function is active

    Set the time delay for the SOTF trip

    UseStartVal =

    t4U =

    Set the time delay for the undertime trip i.e acclerated trip from the selected stage at closing

    Enable Harmonic restraint function in SOTF

    tSOTF =

    tUndertime =

    IN2>

    1.00 s

    0.30 s

    0.30 s

    HarmResSOTF = Off

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    11/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    11Cont

    1MRK 504 084-WEN 21

    Setting of four stage Phase overcurrent funct ion (TOC1) on W1 (130) side phases

    Activation of the phase overcurrent function

    Operation =

    Set the Base current for the function on which the current levels are based

    Setting of the Base voltage level on which the directional polarizing voltage is based

    Ibase =

    UBase= =

    On

    175 A

    132.0 kV

    Set the Characteristic angle for the directional characteristic

    Set the operating angle for the characteristic (around the RCA)

    RCA =

    Arg2Qad =

    Setting of the operating current level for phase selection in primary values

    Set the number of phases required to get the Phase selection (phase start) outputs

    IPh> =

    gives IMinOpPhSel =

    60 deg

    60 deg

    140 A

    12% *Ibase

    Enable the harmonic restraint measuring function

    Setting of the harmonic content in IN current blocking level

    StartPhSel =

    HarmRestrain =

    Setting of parameters for f irst stage

    Setting of the operating direction for the stage

    2ndHarmStab =

    DirMode1 =

    1 out of 3

    Off

    20% of I

    NonDir

    Setting of the operating characteristic

    Setting of the operating current level in primary values

    Characteristic1 =

    I1> =

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing.

    Set the definite time delay, when definite time characteristic has been selected

    gives I1> =

    I1Mult =

    IEC NI

    230 A

    131% *Ibase

    1.00

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    t1 =

    k1 =

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t1Min =

    ResetTypeCrv =

    0.30 s

    0.20

    0.30 s

    Instantaneous

    Set the release of Harmonic restraint blocking for the stage

    Setting of parameters for second stage

    tReset1 =

    HarmRestraint1 =

    Setting of the operating direction for the stage

    Setting of the operating characteristic

    DirMode2 =

    Characteristic2 =

    0.02 s

    Off

    Off

    IEC NI

    Setting of the operating current level in primary values

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing

    I2> =

    I2> =

    Set the definite time delay, when definite time characteristic has been selected

    I2Mult =

    t2 =

    920 A

    526% *Ibase

    1.00

    0.30 s

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    12/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    12Cont

    1MRK 504 084-WEN 21

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    k2 = 0.20

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t2Min =

    ResetTypeCrv2 =

    0.30 s

    Instantaneous

    Set the release of Harmonic restraint blocking for the stage

    Setting of parameters for third s tage

    tReset2 =

    HarmRestraint2 =

    Setting of the operating direction for the stage

    Setting of the operating characteristic

    DirMode3 =

    Characteristic3 =

    0.02 s

    Off

    Off

    IEC NI

    Setting of the operating current level in primary values

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing

    I3'> =

    I3> =

    Set the definite time delay, when definite time characteristic has been selected

    Set the back-up trip time delay multiplier for inverse characteristic

    I3Mult =

    t3 =

    3149 A

    1800% *Ibase

    1.00

    0.30 s

    Set the Minimum operating time for inverse characteristic

    Select the reset curve type for the inverse delay

    k3 =

    t3Min =

    Set the Reset time delay for definite time delayed function

    Set the release of Harmonic restraint blocking for the stage

    ResetTypeCrv3 =

    tReset3 =

    0.20

    0.30 s

    Instantaneous

    0.02 s

    Setting of parameters for fourth s tageSetting of the operating direction for the stage

    HarmRestraint3 =

    DirMode4 =

    Setting of the operating characteristic

    Setting of the operating current level in primary values

    Characteristic4 =

    I4>' =

    Off

    Off

    IEC NI

    2100 A

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing

    Set the definite time delay, when definite time characteristic has been selected

    I4> =

    I4Mult =

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    t4 =

    k4 =

    1200% *Ibase

    1.00

    0.30 s

    0.20

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t4Min =

    ResetTypeCrv4 =

    Set the release of Harmonic restraint blocking for the stage

    tReset4 =

    HarmRestraint4 =

    0.30 s

    Instantaneous

    0.02 s

    Off

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    13/21

  • 8/12/2019 AM RET670 SettingExample2 RB

    14/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    14Cont

    1MRK 504 084-WEN 21

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    k2 = 0.05

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t2Min =

    ResetTypeCrv2 =

    0.30 s

    Instantaneous

    Set the release of Harmonic restraint blocking for the stage

    Setting of parameters for third s tage

    tReset2 =

    HarmRestraint2 =

    Setting of the operating direction for the stage

    Setting of the operating characteristic

    DirMode3 =

    Characteristic3 =

    0.02 s

    Off

    Reverse

    Note! Used as blockable bus protection. Blocked from

    Def

    feeder OC

    Setting of the operating current level in primary values

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing

    I3'> =

    I3> =

    Set the definite time delay, when definite time characteristic has been selected

    Set the back-up trip time delay multiplier for inverse characteristic

    I3Mult =

    t3 =

    1732 A

    150% *Ibase

    1.00

    0.12 s

    Set the Minimum operating time for inverse characteristic

    Select the reset curve type for the inverse delay

    k3 =

    t3Min =

    Set the Reset time delay for definite time delayed function

    Set the release of Harmonic restraint blocking for the stage

    ResetTypeCrv3 =

    tReset3 =

    0.20

    0.30 s

    Instantaneous

    0.02 s

    Setting of parameters for fourth s tageSetting of the operating direction for the stage

    HarmRestraint3 =

    DirMode4 =

    Setting of the operating characteristic

    Setting of the operating current level in primary values

    Characteristic4 =

    I4>' =

    Off

    Off

    IEC NI

    13857 A

    Set the multiplier for start value which is activated when the multiplier input is activated, normally at CB closing

    Set the definite time delay, when definite time characteristic has been selected

    I4> =

    I4Mult =

    Set the back-up trip time delay multiplier for inverse characteristic

    Set the Minimum operating time for inverse characteristic

    t4 =

    k4 =

    1200% *Ibase

    1.00

    0.30 s

    0.20

    Select the reset curve type for the inverse delay

    Set the Reset time delay for definite time delayed function

    t4Min =

    ResetTypeCrv4 =

    Set the release of Harmonic restraint blocking for the stage

    tReset4 =

    HarmRestraint4 =

    0.30 s

    Instantaneous

    0.02 s

    Off

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    15/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    15Cont

    1MRK 504 084-WEN 21

    Setting of two s tep Overvoltage protection function (TOV)

    Activation of the Overvoltage function

    Setting of the Base voltage level on which the voltage settings are based

    Operation = On

    Setting of the parameters for stage 1

    Setting of the U> voltage

    UBase= =

    Setting of the Overvoltage function measuring mode for involved voltages

    U1>'=

    U1> =

    OpMode1 =

    20.0 kV

    13.9 kV

    120% *UBase

    1 out of 3

    Setting of the characteristic for the time delay, inverse or definite time

    Setting of the definite time delay, when selected

    Characterist1 =

    t1 =

    Setting of the definite time reset time

    Set the time delay multiplier for inverse characteristic, when selected

    t1Reset =

    k1 =

    Definite

    5.000 s

    0.025 s

    0.05

    Setting of the definite minimum operating time for the inverse characteristic

    Set the reset time curve for inverse characteristict1Min =

    ResetTypeCrv1 =

    Set the reset ratio (hystereses) for the function

    Setting of the parameters for stage 2

    Setting of the U>> voltage

    HystAbs1 =

    1.000 s

    Instantaneous

    0.995

    Note! Not used

    Setting of the Overvoltage function measuring mode for involved voltages

    U2>>'=

    U2> =

    OpMode2 =

    Setting of the characteristic for the time delay, inverse or definite time

    Setting of the definite time delay, when selected

    Characterist2 =

    t2 =

    16.0 kV

    80% *UBase

    1 out of 3

    Definite

    5.000 s

    Setting of the definite time reset time

    Set the time delay multiplier for inverse characteristic, when selected

    t2Reset =

    k2 =

    Setting of the definite minimum operating time for the inverse characteristic

    Set the reset time curve for inverse characteristic

    t2Min =

    ResetTypeCrv2 =

    0.025 s

    0.05

    1.000 s

    Instantaneous

    Set the reset ratio (hystereses) for the function

    HystAbs2 = 0.995

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    16/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    16Cont

    1MRK 504 084-WEN 21

    Setting of two step Undervoltage protection function (TUV)

    Activation of the Overvoltage function

    Setting of the Base voltage level on which the voltage settings are based

    Operation = On

    Setting of the parameters for stage 1

    Setting of the U< voltage

    UBase= =

    Setting of the Overvoltage function measuring mode for involved voltages

    U

  • 8/12/2019 AM RET670 SettingExample2 RB

    17/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    17Cont

    1MRK 504 084-WEN 21

    Setting of Breaker failure function (BFP1) for 132 kV

    Activation of the Breaker failure function

    Operation =

    Setting of the operating mode for retrip of own breaker

    Set the used principle for current check

    RetripMode =

    BUTripMode =

    On

    Retrip Off

    1 out of 3

    Set the used principle forback-up tripping, with or without contact resp current checks

    Set the Base current for the function on which the current levels are based

    FunctionMode =

    Ibase =

    Setting of the operating current level

    Setting of the operating current level for Neutral current

    IP> =

    IN> =

    Current

    175 A

    10% *Ibase

    10% *Ibase

    Set the retrip time delay

    Set the back-up trip time delay

    t1 =

    t2 =

    Set the back-up trip time delay for Multi-phase start

    Set an additional time delay for a second back-up trip step if used. Will be added to t2 B-u trip time without checks.

    t2MPh =

    t3 =

    0.050 s

    0.120 s

    0.120 s

    0.030 s

    Set the length of the trip pulse

    Set the current level above which the contact base operation (if selected) is blocked

    tPulse =

    I>BlkCont =

    Set the time to alarm for CB faults if input is used

    tCBAlarm =

    0.200 s

    20% *Ibase

    5.000 s

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    18/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    18Cont

    1MRK 504 084-WEN 21

    Setting of Breaker failure function (BFP2) for 20 kV Circuit breaker

    Activation of the Breaker failure function

    Operation =

    Setting of the operating mode for retrip of own breaker

    Set the used principle for current check

    RetripMode =

    BUTripMode =

    On

    Retrip Off

    1 out of 3

    Set the used principle forback-up tripping, with or without contact resp current checks

    Set the Base current for the function on which the current levels are based

    FunctionMode =

    Ibase =

    Setting of the operating current level

    Setting of the operating current level for Neutral current

    IP> =

    IN> =

    Current

    175 A

    10% *Ibase

    10% *Ibase

    Set the retrip time delay

    Set the back-up trip time delay

    t1 =

    t2 =

    Set the back-up trip time delay for Multi-phase start

    Set an additional time delay for a second back-up trip step if used. Will be added to t2 B-u trip time without checks.

    t2MPh =

    t3 =

    0.050 s

    0.120 s

    0.120 s

    0.030 s

    Set the length of the trip pulse

    Set the current level above which the contact base operation (if selected) is blocked

    tPulse =

    I>BlkCont =

    Set the time to alarm for CB faults if input is used

    tCBAlarm =

    0.200 s

    20% *Ibase

    5.000 s

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    19/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    19Cont

    1MRK 504 084-WEN 21

    Configuration of HMI display

    Setting of LED's functionality

    Operation

    Restart

    Set the sequence type for the 15 LED's. Following alternative behaviour is available.

    tMax

    On

    0.0 s

    0.0 s

    Follow-S

    Follow-F

    LatchedAck-F-S

    LatchedAck-S-FLatchedColl-F

    LatchedReset-S

    Set the behaviour for each of the LED's

    Follow the fault with Steady light

    Follow the fault with Flickering light

    Latched with flickering until ack, then steady if fault is on

    Latched with steady until ack, then flickering if fault is on

    Latched steady until reset, then steady if fault is on.

    SeqTypeLED1

    SeqTypeLED2

    SeqTypeLED3

    SeqTypeLED4

    SeqTypeLED5

    SeqTypeLED6

    SeqTypeLED7

    SeqTypeLED8

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    =

    =

    LatchedAck-S-F

    LatchedAck-S-FSeqTypeLED9

    SeqTypeLED10

    SeqTypeLED11

    SeqTypeLED12

    SeqTypeLED13

    SeqTypeLED14

    SeqTypeLED15

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    =

    =

    LatchedAck-S-F

    LatchedAck-S-F

    = LatchedAck-S-F

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    20/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    ABB PTSX

    TPADate

    Setting of Transformer protection relay RET670

    2005-11-11 40 MVA 132/20 kV TransformerDocument No.

    BSheet

    20Cont

    1MRK 504 084-WEN 21

    Set the Operation of the Fault Locator and Fault Recorder functions

    Operation=

    Recording times

    On

    PreFault Rec T=

    PostFault Rec T=

    0.10 s

    0.80 s

    TimeLimit=

    PostRetrig=

    2.00 s

    Off

    ZeroAngleRef=

    OpModeTest=

    7

    On

    Fault locator data

    DistUnit= km

    Configuration of DREP Binary singals to be presented on HMI and DR printouts.

    Binary signals

    Channel No

    Ch

    1

    2

    Signal name

    DIF-TRIP

    DIF-TRIPRES

    3

    4

    5

    6

    DIF-TRIPUNRES

    DIF-TRNS

    DIF-TRNSSENS

    DIF-STL1

    Signal description LED

    Differential function trip

    Differential function trip restraint

    On

    On

    Operation Trig level

    On

    On

    Trig on 1

    Trig on 1

    Differential function trip unrestraint

    Differential function trip NS unrestr

    On

    On

    Differential function trip NS sens

    Diff function start L1

    On

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    7

    8

    9

    10

    DIF-STL2

    DIF-STL3

    Not Used

    Not Used

    11

    12

    13

    14

    Diff function start L2

    Diff function start L3

    Off

    Off

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    Off

    Off

    Trig on 1

    Trig on 1

    Differential function Blk 2nd harm L1

    Differential function Blk 2nd harm L2

    Off

    Off

    Differential function Blk 2nd harm L3

    Differential function Blk 5th harm L1

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    Off

    Trig on 1

    Trig on 1

    Mask

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    15

    1617

    18

    19

    20

    21

    22

    BUSCB-BFPTRIP

    BUSCB-BFPRETRIP

    BUSCB-PDTRIP

    Differential function Blk 5th harm L2

    Differential function Blk 5th harm L3

    Off

    OffDifferential function Wav Blk L1

    Differential function Wav Blk L2

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1On

    On

    Trig on 0

    Trig on 0

    Differential function Wav Blk L3

    Bus CB Breaker failure trip

    Off

    On

    Bus CB Breaker failure retrip

    Bus CB Pole Discordance trip

    Off

    On

    On

    On

    Trig on 0

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    23

    24

    25

    26

    TIECB-BFPTRIP

    TIECB-BFPRETRIP

    27

    28

    29

    30

    TIECB-PDTRIP

    W1-IOC-TRIP

    W1-TOC-TRIP

    Tie CB Breaker failure trip

    Tie CB Breaker failure retrip

    On

    Off

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Tie CB Pole Discordance trip

    Off

    On

    W1 Instantanous OC Trip

    W1 Delayed OC Trip

    On

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Show

    ShowShow

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    31

    32

    33

    34

    W1-TOC-STL1

    W1-TOC-STL2

    W1-TOC-STL3

    W1-IEF-TRIP

    39

    40

    W1-REF-TRIP

    W1-REF-START

    W1 Delayed OCStart L1

    W1 Delayed OCStart L2

    Off

    Off

    W1 Delayed OCStart L3

    W1 Instantanous EF Trip

    Off

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    W1 REF Trip

    W1 REF Start

    Off

    Off

    Off

    Off

    Trig on 1

    Trig on 1

    Show

    Show

    Show

    Show

    Show

    Show

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06

  • 8/12/2019 AM RET670 SettingExample2 RB

    21/21

    Project

    StationF 130/20 kV S/S for ABB RET 670 CustomerApproved Resp. dept. Title Rev ind

    Max DegerfaltPrepared

    Engineer

    TPADate

    Setting of Transformer protection relay RET670

    2005 11 11 40 MVA 132/20 kV Transformer

    BSheet

    21

    41

    42

    W1-REF-DIROK

    W1-REF-BLK2H

    W1 REF Dir OK

    W1 REF Block 2nd harmonic

    On

    On

    On

    On

    Trig on 1

    Trig on 1

    43

    44

    45

    46

    W1-TEF-TRIP

    W1-TEF-START

    W1-TEF-2NDHARM

    47

    48

    49

    50

    W2-BFPTRIP

    W2-BFPRETRIP

    W1 Delayed EF Trip

    W1 Delayed EF Start

    On

    Off

    W1 Delayed EF 2nd Harm blk Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    Off

    Trig on 1

    Trig on 1

    Off

    Off

    W2 Breaker failure trip

    W2 Breaker failure retrip

    On

    Off

    Off

    Off

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show51

    52

    53

    54

    W2-TOC-TRIP

    W2-TOC-STL1

    W2-TOC-STL2

    W2-TOC-STL3

    55

    56

    57

    58

    W2-REF-TRIP

    W2-REF-ST

    W2-REF-DIROK

    W2-REF-BLK2H

    W2 Delayed OC Trip

    W2 Delayed OCStart L1

    On

    Off

    W2 Delayed OCStart L2

    W2 Delayed OCStart L3

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    W2 REF Trip

    W2 REF Start

    On

    Off

    W2 REF Dir OK

    W2 REF Block 2nd harmonic

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    59

    60

    61

    62

    W2-TEF-TRIP

    W2-TEF-START

    W2-TEF-2NDHARM

    W2-TOV-TRIP

    63

    64

    65

    66

    W2-TOV-TR2

    W2-TOV-START

    W2-TUV-TRIP

    W2-TUV-TR2

    W2 Delayed EF Trip

    W2 Delayed EF Start

    On

    Off

    W2 Delayed EF 2nd Harm blk

    W2-Time Overvoltage Trip

    Off

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    W2-Time Overvoltage TR2

    W2-Time OvervoltageStart

    On

    Off

    W2-Time Undervoltage Trip

    W2-TimeUndervoltage TR2

    On

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    67

    68

    69

    70

    W2-TUV-START

    W3-TRV-TRIP

    W3-TRV-TR2

    W3-TRV-START

    71

    72

    7374

    W2-BFPTRIP

    W2-BFPRETRIP

    W2-TOC-TRIPW2-TOC-STL1

    W2-Time UndervoltageStart

    W2-Time netral point voltage Trip

    Off

    On

    W2-Time Neutral point voltage TR2

    W2-Time Neutral point voltageStart

    On

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    W3 Breaker failure trip

    W3 Breaker failure retrip

    On

    Off

    W3 Delayed OC TripW3 Delayed OCStart L1

    OnOff

    On

    On

    Trig on 1

    Trig on 1

    OnOn

    Trig on 1Trig on 1

    75

    76

    77

    78

    W2-TOC-STL2

    W2-TOC-STL3

    W2-TEF-TRIP

    W2-TEF-START

    79

    80

    81

    82

    W2-TEF-2NDHARM

    W2-FSD-STGEN

    W2-TTR-TRIP

    W3-TTR-TRIP

    W3 Delayed OCStart L2

    W3 Delayed OCStart L3

    Off

    Off

    W3 Delayed EF Trip

    W3 Delayed EF Start

    On

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    W3 Delayed EF 2nd Harm blk

    VT Fuse failure

    Off

    Off

    W2 Trip

    W3 Trip

    On

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Show

    Show

    Show

    Show

    Show

    Show

    ShowShow

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    83

    84

    85

    86

    BUCH TRIP

    PRESS TRIP

    WIN-TEMP-TRIP

    OIL-TEMP-TRIP

    87

    88

    89

    90

    WIND TEMP ALARM

    OIL TEMP ALARM

    ACT GR1

    ACT-GR2

    Buchholz Trip

    Pressure Trip

    On

    On

    Winding temperature trip

    Oil temperature trip

    On

    On

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    Winding temperature Alarm

    Oil temperature Alarm

    Off

    Off

    ActiveGroup 1

    Active Group 2

    Off

    Off

    On

    On

    Trig on 1

    Trig on 1

    On

    On

    Trig on 1

    Trig on 1

    91

    92

    93

    TEST-ACTIVE Test Active Off

    Off

    Off

    On

    Off

    Trig on 1

    Trig on 1

    Off Trig on 1

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Show

    Wereserveallrightsinthisdocumentandinthe

    infor

    mationcontainedtherein.

    Reproduction,use

    ordisclosuretothirdpartieswithoutexpress

    auth

    orityisstrictlyforbidden.

    ABBPTSX

    Printout2006-07-06