Alu-Coustic 25 M0 / M1acoustic semi-rigid duct
➤ advantages• Phonic attenuation.
• Reducing of the condensation and the heat losses.
➤ range• Diameters : 100 to 500 mm.
➤ application• Installations of ventilation, air conditioning and CMV.
➤ construction / composition• Microperforated semi-rigid aluminium interior duct.
• Glasswool mattress (thickness : 25 mm, density : 16 kg/m3).
• Steam barrier aluminium/Polyester.
➤ packaging• Length of 3 m compressed to 1,5 m up to Ø 315 mm.
• Ø superior to 315 mm not compressed.
• In individual cartons.
➤ specifications• The valves will be connected to the main network by a circular
semi-rigid duct in microperforated aluminium, phonically isolated by a glasswool mattress with exterior multi-layer aluminium coating.
• The semi-rigid duct will have fire grading M0/M1.
• Type Alu-Coustic, France Air brand.
Alu-Phonic 25 M0 / M0acoustic semi-rigid duct
➤ advantages• Phonic attenuation.
• Reducing of the condensation and the heat losses.
• Possibility of building around the duct.
➤ range• Diameters : 100 to 400 mm.
➤ application• Installation of hot water, ventilation, air conditioning and CMV.
➤ construction / composition• Microperforated semi-rigid aluminium interior duct.
• Glasswool mattress (thickness : 25 mm, density : 16 kg/m3).
• Steam barrier.
➤ packaging• Length of 3 m not compressed.
➤ specifications• The valves will be connected to the main network by a circular
semi-rigid duct in microperforated aluminium, phonically isolated by 25 mm of glasswool with exterior semi-rigid aluminium coating.
• The semi-rigid duct will have fire grading M0/M0.
• Type Alu-Phonic, France Air brand.
• The ducts must be cut with a metal saw or with a sharp blade.• Use a male-male connection (RM) for assembly of 2 lengths.• Ensure airtightness between the interior duct and the connection with a Alu Butyl, Fib-Air® or sheeted FA 52 strip.• Push the glasswool a few centimeters back.• Tighten the exterior duct and ensure the airtightness with an aluminium strip Fib-Air®, then complete with flat collar Multidiam or Monofil.
technical description➤ Fire grading
• M0/M1 : product M1 with interior duct is classified M0.
➤ Limits of use• Temperature : - 30 °C to + 250 °C.• Maximum temperature : 300 °C.• Maximum pressure : 2 000 Pa - Ø > 400 : 1000 Pa.
➤ Features• Acoustic attenuations (according to norm NF ISO 7235
August 1995) : tolerance of ± 0,5 dB for 1 linear metre of Alu-Coustic duct.
Diameter(mm)
Frequency (Hz)63 125 250 500 1000 2000 4000 8000
80 10 8 13 13 32 45 35 30
100 7 7 11 12 30 45 28 23
125 5 5 9 11 28 45 24 17
160 4 4 6 11 25 36 19 14
200 3 3 5 10 22 31 15 13
250 2 2 4 9 21 22 13 9
315 1 2 3 9 19 17 10 7
400 1 2 3 8 18 13 9 5
500 1 1 2 8 16 10 7 4
technical description➤ Fire grading
• M0/M0 : interior duct, glasswool and exterior duct classified MO.
➤ Limits of use• Temperature : - 30 °C to + 250 °C.• Maximum temperature : 300 °C.• Maximum pressure : 3 000 Pa.
➤ Features• Acoustic attenuations (according to norm NF ISO 7235
August 1995) : tolerance of ± 0,5 dB for 1 linear metre of Alu-Phonic duct.
Diameter(mm)
Frequency (Hz)63 125 250 500 1000 2000 4000 8000
80 10 8 13 13 32 45 35 30
100 7 7 11 12 30 45 28 23
125 5 5 9 11 28 45 24 17
160 4 4 6 11 25 36 19 14
200 3 3 5 10 22 31 15 13
250 2 2 4 9 21 22 13 9
315 1 2 3 9 19 17 10 7
400 1 2 3 8 18 13 9 5
500 1 1 2 8 16 10 7 4