  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    1/6

    Air Insulated Indoor Switchgear

    Cubicle VHA 36 with HPA circuit breaker for 36 kV and 24 kV

  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    2/6

    2

    2 ABB

    Advantage ABB

    120 years of technology and innovation

    Unparalleled domain competence

    A vast global experience

    Total solution provider

    Large installed base

    Environment-friendly technologies

    ABB is a global leader in Power and Automation technologies

    that enable utility and industry customers to improve

    performance while lowering environmental impact. The ABB

    Group of companies operate in around 100 countries.

    In India, ABB serves customers with the complete range ofpower and automation technologies. The company has a vast

    installed base, extensive manufacturing facilities and a

    countrywide marketing and service presence.

    The Power Technologies division offers electric, gas and water

    utilities as well as industrial and commercial customers a wide

    range of products, systems and services for power generation,

    transmission and distribution. ABBs turnkey solution

    capabilities in the sector range from Electrical Balance of Plant

    (EBOP) for power plants, bulk power transmission, substations

    and complete electrification to utility automation and

    distribution systems.

    The product offering covers a wide spectrum of technologies

    across the entire voltage range including indoor and outdoor

    circuit breakers, air and gas insulated switchgear,

    disconnectors, capacitor banks, reactive power

    compensators, power transformers, distribution transformers,

    instrument transformers, Compact Substations (CSS) and

    Ring Main Units (RMU).

    ABB a global technology leader Air insulated indoor switchgearCubicle type - VHA 36

    Designed and type tested to meet

    IEC 60298 & 60694 / IS: 13227

    Fully compartmentalised construction with IP4X degree of

    protection externally and IP2X between compartments

    Independent exhaust vent for all compartments

    Integral earthing switch (optional)

    Breaker compartment

    Cassette mounted breaker placed on elevated level with test

    position of breaker behind closed door

    Interlocks :- Racking in/out of breaker from test to service position and

    vice-versa with cubicle door closed only

    - To prevent racking in/out of breaker, when

    breaker is in closed position

    - To prevent door from opening when breaker is in

    service position

    Multiple guides for safe and enduring

    alignment of fixed & moving power contacts

    Live parts covered by automatic shutters when breaker is

    racked out

    Provision for padlocking of CB compartment door

  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    3/6

    ABB 3

    Metering compartment

    Adequate space for protection and metering

    equipment, control switches, lamps, etc.

    Apparatus customised as per requirement

    Cable & Current Transformer (CT)compartment

    Potential Transformer (PT) compartment

    Withdrawable line PT provided in the breaker panel

    Removable fuses mounted on the PT

    Safety shutters between PT and cable compartment close

    automatically on PT withdrawal

    Busbar compartment

    Tubular conductors fixed on through bushings

    Spacious busbar compartment for adequate

    air clearance

    Option for busbar insulation

    Option for shrouds on joints

    Slip-on CTs

    Spacious compartment to accommodate

    1 set of CTs and 2 runs of cables option of rear extension

    for extra CTs/cables

    Adequate height for cable termination

    Access to cable terminals provided from rear of the panel

  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    4/6

    4 ABB

    Commitment to quality and sustainability

    Description Unit Rating

    Rated voltage kV 24 36

    Rated frequency Hz 50

    Rated busbar current A 630, 1250, 1600, 2000, 2500

    Short time withstand current kA (3 secs) 26.3

    kAp 100

    Insulation levels kVrms/kVp 50/125 70/170

    Width x Depth x Height mm 1216 x 2300 x 2500

    Weight with circuit breaker (approx.) Kg 1500

    Degree of protection

    Enclosure IP4X IP4X

    Within the switchgear IP2X IP2X

    General arrangement drawing VHA 36

    Dimensions in mm

    ABB Indias manufacturing facilities conform to the highest quality standards and environment norms.

    These products are manufactured at ABBs works in Nashik which has the following certifications.

    ISO 9001 for quality standards

    ISO 14001 for environment standards

    ISO 18001 for occupational health and safety standards

    Technical details

  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    5/6

    ABB 5

    Technical details

    Description Unit Rating

    Rated voltage kV 24 36

    Insulation levels kVrms/kVp 50/125 70/170

    Normal current (400C amb.) A 1250, 1600, 2000

    Breaking capacity kA 26.3

    Making capacity kAp 66

    Short time withstand current kA 26.3 for 3 sec.

    Gas pressure bar (abs) 3 - 3.5

    Opening time ms 36 - 45

    Arcing time ms 15

    Total break time ms 60

    Making time ms 75

    Operating sequence - 0 - 3 min - CO - 3 min - CO

    0 - 0.3 sec - CO - 3 min - CO

    Weight (approx.) Kg 300

    Salient features

    Sulphur Hexafluoride (SF6) used as insulation and arc

    interruption medium

    Arc control and extinction achieved by puffer principle

    Operationally safe and reliable across a wide range of

    ambient temperatures (50 to 400C)

    Capable of interrupting small magnetising and capacitive

    currents

    Features of operating mechanism:

    O-C-O operation without recharging

    Closing spring charged by motor in less than 15

    seconds

    Electrical anti-pumping

    Provision for manual recharging

    Synchronisation and fast auto-reclosure duty

    Indoor switchgear, circuit breaker type HPA

  • 8/8/2019 Air+Insulated+Indoor+Switchgear

    6/6

    1VDS22001-YN/Re

    v.A,2

    005-07

    ABB LimitedMedium Voltage Equipment

    Street No. 17MIDC, SatpurNashik 422 007Tel: +91 253-2351095 98Fax: +91 253-2351260

    Exports Marketing Office:ManejaVadodara 390 013Tel: +91 265-2638930Fax: +91 265-2638908

    NBCC Tower4th FloorNo. 15, Bhikaji Cama PlaceNew Delhi 110 066Tel: +91 11 26186000Fax: +91 11 26197592/84035

    4th FloorNo. 9Elgin RoadKolkata 700 020Tel: +91 33 22832906/8Fax: +91 33 22832990

    ABB HouseDr. S B PathBallard EstateMumbai 400 038Tel: +91 22 56318231 39Fax: +91 22 56318276/77

    Embassy Star, 1st FloorNo. 8, Palace RoadVasanth NagarBangalore 560 052Tel: +91 80 22949779Fax: +91 80 22949808

    Century PlazaNo. 3C, 3D & 3F, 3rd Floor561 / 562, Anna SalaiTeynampet (Mount Road)Chennai 600 018Tel: +91 44 24340201Fax: +91 44 24340282

    Vandana House1st FloorG E Road, RamkundRaipur 492 001Tel: +91 771 5060816-8Fax: +91 771 5053391www.abb.co.in

    North

    East

    West South

    Central