Page 1: air Handling Units KompaKt

KompaKtair Handling Units

Page 2: air Handling Units KompaKt
Page 3: air Handling Units KompaKt

Description of Komfovent KompaKt units 2

KompaKt ReGo RHp 3

Reasons to choose Komfovent KompaKt units 4

Control System 6

Komfovent KompaKt ReGo 10

Rotary Heat Exchanger 11

Standard Sizes of KomfovEnt KompaKt REGo Units 11

Unit’s Selection Sample 12

KompaKt REGo 400 14

KompaKt REGo 500 16

KompaKt REGo 600 U RHp 18

KompaKt REGo 700 20

KompaKt REGo 900 U 22

KompaKt REGo 1200 U 24

KompaKt REGo 1200 p 26

KompaKt REGo 1400 U 28

KompaKt REGo 1600 U 30

KompaKt REGo 2000 U 32

KompaKt REGo 2000 p 34

KompaKt REGo 2500 U 36

KompaKt REGo 3000 U 38

KompaKt REGo 4000 U 40

KompaKt REGo 4500 U 42

KompaKt REGo 7000 44

Komfovent KompaKt ReCU 46

plate Heat Exchanger 47

Standard Sizes of KomfovEnt KompaKt RECU Units 47

KompaKt RECU 400 48

KompaKt RECU 700 50

KompaKt RECU 900 54

KompaKt RECU 1200 56

KompaKt RECU 1600 60

KompaKt RECU 1600 p 54

KompaKt RECU 2000 66

KompaKt RECU 2000 p 68

KompaKt RECU 3000 70

KompaKt RECU 4000 72

KompaKt RECU 4500 74

KompaKt RECU 7000 76

Komfovent KompaKt otK 78

KompaKt otK 700 78

KompaKt otK 1200 79

KompaKt otK 2000 80

KompaKt otK 3000 81

KompaKt otK 4000 82

accessories 83

Control System accessories 92

electric Wiring of air Handling Units 93

оrdering Key 94

Page 4: air Handling Units KompaKt

2

Komfovent KompaKt Units

86%

ther

mal efficiency and

energy saving up to

65%

ther

mal efficiency and

energy saving up to

92%

ther

mal efficiency and

energy saving up to

KomfovEnt KompaKt series off ers the standardized range of air handling units with heat recovery by rotary or plate exchanger, or just supply air units. Units’ air fl ow performance ranges from 170 m³/h to 8000 m³/h.all KompaKt units are based on the principle of pLUG & pLaY: each unit has the integrated control system and is delivered with a complete automatic control installed and pre-wired inside the unit. a modern control panel with touch-sensitive buttons is included in each KompaKt unit supplied. Due to a wide range of functions and compact size KompaKt units can be used to ensure the balanced ventilation with heat recovery or without for various application areas: dwelling, public, and industrial. Due to the availability of clever design and functions the units off er a great opportunity to keep running costs low, they are safe, reliable and durable in operation. the air is fi ltered and supplied clean and fresh to the pre mises, which is especially advisable to allergic people.

Units with high effi ciency counter cross-fl ow plate heat exchangerCapacity – 700 m3/h.Effi ciency factor – up to 92%.

KompaKt ReGoUnits with rotary heat exchangerCapacity range from 170 to 8000 m³/h.Effi ciency factor – up to 86%.

KompaKt ReCUUnits with plate heat exchanger Capacity range from 220 to 8000 m³/h. Effi ciency factor – up to 65%.

KompaKt otKfalse ceiling supply air unitsCapacity range from 100 to 4200 m³/h. Extra compact size – height is only 350 mm and 545 mm for otK 3000 and otK 4000.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 5: air Handling Units KompaKt

3

NEWNEWKompaKt ReGo RHp

VENTILATION

HEATING

COOLING

KompaKt REGo RHp series – new generation solution for residential premises. all KompaKt REGo RHp units have integrated heat pump, this technology extends air handling unit’s capabilities – the unit not only ventilates, but also heats and cools the premises. Implementation of such complex technical solution not only extends the application of the unit, but also ensures high effi ciency due to two energy recovery stages (by rotary heat exchanger and heat pump).

all KompaKt REGo RHp units have integrated intelligent C5.1 control system, which wide functionality ensures comfortable indoor climate with optimal energy consumption. the interface of modern C5.1 control panel is designed to be user friendly – easy navigation enables smart control, setting of parameters and monitoring unit operation. the units can b remotely controlled by using "Komfovent" mobile application, which matches the interfaces of C5.1 control panel. this feature is applicable for all control possibilities. So the user may control the unit in the most convenient way.

KompaKt REGo RHp units features:• HVAC systems in one unit: ventilation, heating and cooling;• Extremely high unit‘s effi ciency due to double heat recovery

process;• Universal construction of connections – ducts connection;• C5.1 control system ensures wide variety of functions;• Smart functionality in both control devices: C5.1 control panel

and smart phone.

Intelligent control

new generation solution

KK2-15-09-v1

Page 6: air Handling Units KompaKt

4

Reasons to choose Komfovent KompaKt Units

High thermal effi ciency of the unitsDepending on the exchanger type units’ heat recovery is up to 92%, because the majority of the exhaust air heat is recovered to the supplied air. Cool recovery is also possible.

effi cient heat recovery – the desired rotary wheel effi ciency is availablethe effi ciency of rotary heat exchanger may be chosen from 3 available: m, L or XL, depending on the required effi ciency level. to ensure effi cient operation and minimum operation ex-penses EC rotary motors are used with rotary heat exchangers.

Silent operation and easy mounting

KomfovEnt KompaKt units have tight, insu-lated and painted casing and high quality com-

ponents, ensuring the extremely silent operation and mounting. Covering panels of the air handling units consist of two galva-nized steel sheets, the gap between them is fi lled with fi re re-sistant thermal and sound attenuating insulation – mineral wool (λ = 0,036W/mK). the air handling units with 45 mm thick insulation may oper-ate in unheated premises. Units’ doors are manufactured with 45 mm insulation and equipped with locks. Gaps are sealed with gasket in all necessary open and removable planes. External casing surfaces are powder painted: RaL 7035 as stand-ard. It prevents the unit from corrosion.KomfovEnt KompaKt air handling units are available in two versions – vertical or horizontal. Units are compact, therefore it is easy to place them in an attic, basement or other premises. Low units’ height allows them to be mounted in the suspended ceil-ing or on the wall. the units are designed to be carried through the standard door, if the width of the unit is bigger than 900 mm – it consists of several sections.

High effi ciency EC fansLow energy consumption – eC fans inside every unitHigh effi ciency EC (electronically commutated) motors of fans use 50% less energy than aC (alternating current) motors with voltage control. the rotary wheels are also equipped with effi -cient and silent EC motors.

pLUG & pLaY solution Smart design: all units have a fully integrated automatic control without any external electri-cal boxes.

the special automatic control system for ventilation processes, designed by our highly qualifi ed engineers, contributes to en-ergy saving. the units can be controlled from anywhere in the world using mobile devices (smartphones, computers, tablets).

temperature effi ciency

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

m – option, L – standard, XL – option

0 300 600 900 1200

92

88

84

80

76

72

XL

L

m

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 7: air Handling Units KompaKt

5

1

12

2

Hv1 H2

B CC

aa

BD D

v4 Hv5

Ba aC C

BD D

H3 v3

DD a C

a

BB

C

H5 v5

D Baa

BD

C C

H1

v2

Hv3

v1

Hv2

H4

D

D

DD

B

B

B

a

a

C

C

B

a a

a

a

B

B

C

D

D

C

C

C

closed connections opened connections

Right side inspection. Left side has the mirror view of the right.

a outdoor intakeB Supply airC Extract indoorD Exhaust air

Connection universalityof KompaKt REGo 900-4500 U

• One unit may have up to 14 connection possibilities;• Big advantage of having possibility to adapt the unit duct

connections directly on the site;• Perfect solution for keeping unit in stock;• When ordering the desired version may be chosen at once by

indicating the code of the connection.

one of the main advantages is the multipurpose application of one unit – the same unit can be of horizontal and vertical duct connections, installer can always reverse the unit into the re-quired version and choose the duct connections‘ position on site. one air handling unit – lots of connecting positions.

possible connection versions of ReGo 900-4500 U

Easy changing of connection positions: unscrew closed duct connections panels (1) and fl anges of opened connection (2), and then change their positioning to the desired connecting version. no additional changes are needed, eve rything inside the units is prepared for such change.

KK2-15-09-v1

Page 8: air Handling Units KompaKt

6

NEW

Integrated control system ensures safe operation of the air handling unit, controls preset ventilation system parameters, and optimize unit operating costs. C3 or C3.1 control system is integrated in KompaKt RECU and otK units, C5.1 control system – in KompaKt REGo air handling units.

Control systems

Komfovent С3 / C3.1 advantages:• Easy control;• Performs all functions of air handling units’ control;• The user may monitor the processes on the LCD display;• Air fl ow control and indication;• Unit PC control;• Enables to select language.

operating functions

Unit control using panel panel can be used to control unit operation: to change operation modes and parameters, to switch unit on or off anytime.

Remote switching on or off the possibility to switch unit on or off using additional device.

Supply air temperature maintenance the unit automatically supplies air according to the temperature preset by the user.

Room temperature maintenance Unit automatically supplies air of such temperature to maintain preset room temperature (15...30°C).

Set point sliding option to shift set value of the supply or room air temperature for the specifi ed period of time.

temperature maintaining mode setting

the user can select from the panel temperature to be maintained: supply air or room air temperature.

automatic temperature maintaining mode selection Depending on the outdoor temperature, maintaining mode can be selected automatically.

ventilation intensity control the user may set most economical and eff ective ventilation intensity level.

Remote unit intensity control (ovR)1, 3 the ventilation unit intensity will be controlled by contacts. the fourth level of intensity can be activated with these contacts.

Constant air volume control (Cav)1 the unit maintains set by the user supply and exhaust air volume.

variable air volume control (vav)1, 2the unit supplies and exhausts air volume correspondingly to the ventilation requirements in diff erent premises. In case of frequently changing ventilation demands this air volumes maintenance mode signally reduces the unit exploitation costs.

air quality function (aQ)1, 2 the provided ventilation intensity correction according to the increased Co2, humidity level and etc.

ventilation correction in winter time In winter time, if there is not enough heating power, temperature is maintained by decreasing ventilation intensity.

the unit weekly schedule programming

Weekly operation schedule with three daily events may be set. for each daily event, user can select ventilation intensity.

Unit operation mode selection In automatic mode unit operates according to weekly schedule. In manual mode unit constantly operates by set intensity.

Season setting for the most economic unit operation summer and winter settings are provided.

automatic season change Depending on the outside temperature, season can be changed automatically.

pump control Water pump is controlled depending on the outside temperature and according to the need.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Control panel C3 Control panel C3.1

the type of panel C3.1 or C3 should be specifi ed while ordering the unit.

20.0°C2 19.6°C

14:00Winter

C3

KK2-15-09-v1

Page 9: air Handling Units KompaKt

7

Cooling energy recovery In summer time, cooling energy is recovered to the room.

Summer night cooling3In summer night time, when cooling is required, ventilation intensity level is automatically switched to the third intensity level. air is cooled only by outdoor air, without heat or coolness recovery and additional air cooling or heating.

Exhaust air flow correction1 the user for the set time period can adjust exhaust air fan speed.

protection functionsWater heater frost protection maximum protection from water freezing.

Electric heater overheating protectionIf there is danger of overheating, heater shuts down automatically. the unit is equipped with heater cooling. When unit is shut down during the heating operation, fans will continue to operate for set time period.

plate heat exchanger frost protection When there is low outdoor temperature, heat exchanger is protected from freezing.

fan overheating protection fan motor is protected from failure.

Rotary heat exchanger rotation guard If heat exchanger has a failure, the unit operation is stopped.

Emergency shut down in case of fire If the unit is connected to the building fire alarm system, in case of fire unit operation is stopped automatically.

Emergency shut down according to the temperature value limits If supply air temperature reaches emergency level, unit operation is stopped.

Distance unit failure indication possibility to indicate unit failure in a distance from the unit.

Return water temperature maintenance

When unit is switched off in winter time, return water temperature of 25°C is maintained in hot water air heater.

other functionsfilter clogging indication In case of at least one filter clogging, warning appears on the panel display.

mode operation, temperature and time indication Supplied air filter clogging is indicated on the control panel by the red light signal.

failure indication In case of failure of a separate unit assembly or elements, the air handling unit is stopped. this is indicated by text message.

Language selection Control panel provides menu for the language selection.

air flow indication1 option to monitor unit supply and exhaust air flow (m3/h, m3/s, l/s).

Unit pC control3 option to manage and control units by computer, when connected to the pC network, or Internet.

1 – function is provided for units with EC fans.2 – accessories ordered additionally.3 – additionally ordered function only for C3 control panel.

KK2-15-09-v1

Page 10: air Handling Units KompaKt

8

Detailed information for the user• Air flow indication in (m3/h, m3/s, l/s).• Thermal efficiency of the heat exchanger (%).• Heat exchanger recovered energy (kW).• Thermal energy saving indicator (%).• Operation time counters of fans (h).• Heater energy consumption counter (kWh).• Heat exchanger recovered energy counter (kWh).

various operating modes• 5 different operation modes: Comfort1, Comfort2, Eco nomy1,

Economy2, and Special. User may set supply and extract air vo-lumes as well as air temperature for each of mode separately.

• Temperature control modes: Supply air / Extract air / Room. possibility to select which temperature to be maintained.

• Flow control modes: Constant Air Volume (CAV), Variable Air volume (vav), Direct controlled volume (DCv).

• Universal operating schedule with up to 20 events, for which of them user can assign weekday(s) and one of five operation modes.

• Holliday scheduling allows the user to change operation mode or switch off the air handing unit at some dates of the year. Up to 10 events are possible.

extended control possibilities• Controlling up to 30 units connected into a network from one

panel. • Ability to connect the controller to the Internet network and

manage it via a standard internet browser without any acces-sories.

• Possibility to control air handling unit by Smartphone via android oS.

• Ability to control the unit not only by a control panel or a computer, but also by different external devices (switch, timer, etc.) and systems (e.g. the smart house system).

Connectivity & protocols • Modbus RTU over RS-485• Modbus TCP over Ethernet• BACnet/IP over Ethernet

Control system Komfovent C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 11: air Handling Units KompaKt

9

extended control functions C5.1

air quality controltwo different air quality values may be set for two different unit operating modes (e.g. Comfort and Economy). these values will be maintained by automatically increasing or reducing the intensity of ventilation.

outdoor compensated ventilation

this function adjusts the air vo lume depending on the outdoor temperature. It is possible to enter four temperature points where two of them define winter conditions and the other two define summer conditions. Upon entering the compensation curve according to the outdoor temperature, the current intensity of ventilation is decreased or increased accordingly.

Summer night cooling this function is intended for energy saving in summer: utilising the outside chill of night hours to cool down the heated rooms. the user may enable or disable function at any time as well as set the room temperature at which the function is automatically activated.

Override functionoverride control of the unit can be performed by an external device (timer, switch, thermostat, etc.). the signal received from the outside activates the function which switches the unit to the pre-programmed mode ignoring the current operating mode.

minimum temperature control this function forces the reduction of the supply and extract air volumes set by the user when the heater capacity available in the unit is insufficient and/or heat recovery does not ensure the supply of the minimum temperature to the room.

Humidity control

an air handling unit can be ordered with an air humidity control function. If this function is avai lable the user is able to choose the humidity control location: supply air, extract air or room. the user is also able to choose the method of control: humidification, dehumidification or both at a time.

Circulation pumps control on demand

Both heating and cooling pumps are controlled according to the current need for heating or cooling instead of a season control.

air flow density compensation air density depends on the temperature. C5.1 offers a function which adjusts the air flows automatically to avoid any misba lance in rooms while being ventilated.

operation on demand the air handling unit start-up function is designed to start the unit operating in off mode when one of the selected para meters (Co2, air quality, humidity, or temperature) has exceeded the critical limit.

Change-over function Control of combined water heater- cooler and DX cooler reversing to the heating mode.

new safety featuresRotary or plate heat exchanger failure protection

this function observes the thermal efficiency of the heat exchanger. If it does not reach the required level a fault is recorded and indicated.

Rotary or plate heat exchanger anti-frost

Under the low outdoor temperature conditions, this function is constantly observing decreasing tendency of the heat exchan ger thermal efficiency, determines the moment when the heat exchanger starts freezing, and activates the defrosting function automatically.

Service time a warning message appears when the continuous operation of the aHU has reached 12 months.

Rotor cleaning functionthis function ensures that the rotary heat exchanger does not pollute when turned-off. When the air handling unit operates without heat recovery, i.e. when the rotor does not rotate for some time, it is forcibly activated for a little so that moving air flows could blow possible dust.

Rotor warm-up functionthis function forcibly activates the rotary heat exchanger if the air handling unit is turned off for some time and the temperature inside the unit or ventilation system is low enough for the rotor to freeze.

Circulation pumps start-up in off mode

this function starts water circulation pumps for a short period of time when they are off longer than the set period.

Warning for too low air flow If the air handling unit does not reach the air volume set within the time set, the user is warned by an informative message.

External stop Shut-down function from external device. may be used with or without an automatic unit restart.

Emergency shut-down in case of fire

the external fire alarm is provided when the unit is connec ted to the building fire alarm system. there is also an internal fire alarm to detect an increased temperature inside the air handling unit or the ventilation system.

Intelligent self-diagnostic Self-check function of controller and elements of the air hand ling unit. If a fault is detected, C5.1 terminates the operation of the unit and warns about such a fault using the respective informative messages.

KK2-15-09-v1

Page 12: air Handling Units KompaKt

10

+20°C-14°C

(+11°C*) +20°C-23°C**

DC

aB

Komfovent KompaKt ReGoair handling units with rotary heat exchanger.Capacity range from 170 to 8000 m3/h

Heat energy Saving In the process of ventilation the heat of the exhaust air is recovered to the supplied air – the unit allows up to 86% heat recovery.

effi cient Heat Under the normal operational conditions, the rotary heat exchanger does not freeze: exchanger at outdoor temperatures below -20°C, no additional warming up required of the supply air which results in heat energy even at hard frosts. the application of the rotary heat exchanger allows reducing the energy consumption for warming up the supply air by approximately 4 times.

air humidity balanceUnder the normal operating conditions the condensate does not form in the process of heat exchange in the rotary heat exchanger, because 93% of the humidity is returned to the premises. the excess moisture is removed outside. the air in the premises is less drained and the air humidity balance is maintained. as the condensate does not form, the drainage is not necessary – this simplifi es the mounting of the unit.

Low noise levelKomfovEnt KompaKt air handling units are equipped with silently operating fans and sound insulation, which ensures low noise level.

advantages of Komfovent KompaKt ReGo Units

* temperature after the heat exchanger** minimal outdoor temperature -40°С

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

86%

ther

mal efficiency and

energy saving up to

KK2-15-09-v1

Page 13: air Handling Units KompaKt

11

7000

4000

3000

2500

2000

1600

1200

1400

900

700

500

400

0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4600 5000 5400 8000 m3/h

0 0.11 0.22 0.33 0.44 0.55 0.67 0.78 0.89 1 1.11 1.22 1.28 1.38 1.5 2,2 m3/s

4500

20 % 120 % 20 % 120 %

600

Rotary Heat exchanger

the effi ciency on the demand up to 86%: three levels of rotor effi ciency are available. optimum effi ciency is achieved with m type rotor, higher values may be reached with standard L type or optional XL type rotor.

air handling units are equipped with two types of rotary heat exchangers:• Heat exchanger is made from aluminum foil. It recovers heat

(during the heating season) or cold (in summer, if the air is conditioned). It recovers moisture.

• Heat exchanger is made from hygroscopic aluminum foil. It recovers heat (during the heating season) or cold (in summer, if the air is conditioned). Heat exchangers of this type regene-rate moisture more efficiently.

energy effi cient eC motorall rotary heat exchangers are equipped with EC motors, which save the energy and ensure the smooth rotor operation and control.

advantages of Rotary Heat exchanger• High efficiency coefficient – up to 86%.• Not freezing.• 4 times lower energy consumption for warming up the air. • Humidity is transferred to supply air – there is no need for

additional humidifier in the premises.• No drainage is necessary – easy unit installation.• Very compact in size.• Cooled air may be recovered that results in the reduced

energy consumption for air cooling.

as an additional protection for very low outdoor temperatures such as -30oC and lower, it is recommended to use duct mounted preheater.

Design:1. aluminum rotor is made from corrugated

and flat plates of aluminum foil. Rotor has a multitude of metal channels for laminar air flow.

2. Galvanized steel frame3. Shaft with bearings 4. Sealing band between airflows5. EC motor6. Rotor belt

Standard sizes of Komfovent KompaKt ReGo units

performance range

Uni

ts s

izes

Effi ciency of aHU

KK2-15-09-v1

Page 14: air Handling Units KompaKt

12

KompaKt ReGo 400

ReGo 400H312 312

152

155

155

585

210

210

152640790510 510

160 (4x)

D

a

С

B

8

3

7 451 26

D

D

a

a

C

C

B

B

D

B

C

a

a

C

B

D

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

accessories

panel thickness 45 mmUnit weight 48 kgnominal air fl ow 400 m3/hSupply voltage 1~ 230 vmaximal operating current 6,2 apaint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. automatic control devices8. Connection of main cable

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

a outdoor intake C Extract indoorB Supply air D Exhaust air

thickness 45 mmUnit weight 48 kg

KompaKt ReGo 400

ReGo 400H312 312

152

155

155

585

210

210

152640790510 510

160 (4x)

D

a

С

B

8

3

7 451 26

D

a

C

C

B

B

D

a

D

B

C

a

a

C

B

D

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

accessories

panel thickness 45 mmUnit weight 48 kgnominal air fl ow 400 m3/hSupply voltage 1~ 230 vmaximal operating current 6,2 apaint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. automatic control devices8. Connection of main cable

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

a outdoor intake C Extract indoorB Supply air D Exhaust air

thickness 45 mmthickness 45 mmthickness 45 mmUnit weight 48 kg

/h

UnIt’SSeLeCtIon

SampLe

for some units right and left sides are mirrored, but in some units they are rotated. Choose the right side of unit installation.

Shown as left

Shown as right

KK2-15-09-v1

Page 15: air Handling Units KompaKt

13

Sfp 1,25Sfp 1

Sfp 0,75

Sfp 0,5

150 200 250 300 350 400 450

90

86

82

78

74

70

XLL

m

temperature effi ciencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 9,1 12,2 13,7 14,6 15,5 16,4 21,8

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: fi lter M5, rotary heat exchanger L and electric air heater.

150 200 250 300 350 400 450

XL

L

m

0

40

- 40

- 80

80

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air fl ow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air fl ow rate (m3/h)

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 410x200x46 mm

eC fansInput power at point 100 pa / 400 m3/h 94 WRotation speed 3280 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e)Capacity 1 kWair temperature, Δt 7,5°C* option

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air fl ow rate (m3/h)

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 280 m3/h (78 l/s), 100 pa.

octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 400 HeSupply Inlet 29 39 51 55 54 54 49 42 60,2Supply outlet 34 46 57 62 62 60 56 50 67,2Exhaust Inlet 29 39 51 55 54 54 49 42 60,2Exhaust outlet 34 46 57 62 62 61 57 52 67,5Casing 31 41 49 46 45 43 35 28 52,8

Surroundings 23 33 36 34 36 32 25 18 41,4

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

Sfp 1,25Sfp 1,25Sfp 1,25Sfp 1

Sfp 0,75Sfp 0,75Sfp 0,75

Sfp 0,5Sfp 0,5Sfp 0,5

150 200 250 300 350 400 450

90

86

82

78

74

70

XLL

m

temperature effi ciencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 9,1 12,2 13,7 14,6 15,5 16,4 21,8

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: fi lter M5, rotary heat exchanger L and electric air heater.

150 200 250 300 350 400 450

XL

L

m

0

40

- 40

- 80

80

air fl ow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air fl ow rate (m3/h)

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

tem

p. e

ffi ci

ency

(%)

t

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 410x200x46 mm

eC fansInput power at point 100 pa / 400 m3/h 94 WRotation speed 3280 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e)Capacity 1 kWair temperature, Δt 7,5°C* option

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air fl ow rate (m3/h)

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 280 m3/h (78 l/s), 100 pa.

octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 400 HeSupply Inlet 29 39 51 55 54 54 49 42 60,2Supply outlet 34 46 57 62 62 60 56 50 67,2Exhaust Inlet 29 39 51 55 54 54 49 42 60,2Exhaust outlet 34 46 57 62 62 61 57 52 67,5Casing 31 41 49 46 45 43 35 28 52,8

Surroundings 23 33 36 34 36 32 25 18 41,4

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

these charts are needed for unit performance evaluation for diff erent effi ciencies of rotary heat exchanger. Unit performance chart data presented for L type rotary heat exchanger and m5 class fi lter. as all KompaKt REGo units must correspond to high energy effi ciency requirements, L type rotary heat exchanger of higher effi ciency is used as a standard. optional XL type rotary heat exchanger gives possibility to reach maximum effi ciency of recovery. pressure drop graph is used to check if unit performance is still in the right unit working zone, for example:Unit is selected for 300 m3/h and 160 pa static pressures marked by point 1 in the performance chart. to check standard unit with XL or m type rotary working zone it is needed to calculate additional pressure drop. XL type rotary must be evaluated in the performance graph: i.e. pressure drop of 50 pa (data from the pressure graph, point 2) must be added to static pressure in point 1 to get performance point of unit (300 m3/h). Unit with XL performance has parameters in point 2 (static pressure 210 pa for 300 m3/h, thermal effi ciency 85.5%). Checking for point 2 is it remains in its working zone. In case if working point is out of performance zone – bigger size unit must be selected for higher effi ciency rotary heat exchanger. the same actions must be done selecting unit with optional m rotary heat exchanger. Find value in pressure drop graph (it will always be minus); subtract this value in the performance graph to get point 1. the unit data in point 3 will be (300 m3/h, 120 pa, effi ciency of 78%).

to calculate the p for EC motor use formula: p = Sfp*v; where Sfp – kW/(m3/s) and v – m3/s. to calculate Sfp for aC motor use formula: Sfp = p/v; where p – kW and v – m3/s.

1 (L)2 (XL)

3 (m)

3 (m)

1 (L)

2 (XL)

2 (XL)

1 (L)

3 (m)

temperature effi ciency

additional pressure drop

performance ReGo 400

KK2-15-09-v1

Page 16: air Handling Units KompaKt

14

KompaKt ReGo 400

ReGo 400H312 312

152

155

155

585

210

210

152640790510 510

160 (4x)

D

a

С

B

8

3

7 451 26

D

D

a

a

C

C

B

B

D

B

C

a

a

C

B

D

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

accessories

panel thickness 45 mmUnit weight 48 kgnominal air fl ow 400 m3/hSupply voltage 1~ 230 vmaximal operating current 6,2 apaint color RaL 7035Control panel KomfovEnt C5.1

Shown as left

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. automatic control devices8. Connection of main cable

Shown as right

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

KK2-15-09-v1

Page 17: air Handling Units KompaKt

15

150 200 250 300 350 400 450

XL

L

m

0

40

- 40

- 80

80

Sfp 1,25Sfp 1

Sfp 0,75

Sfp 0,5

150 200 250 300 350 400 450

90

86

82

78

74

70

XLL

m

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 410x200x46 mm

eC fansInput power at point 100 pa / 400 m3/h 94 WRotation speed 3280 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e)Capacity 1 kWair temperature, Δt 7,5°C* option

additional pressure drop

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

performance ReGo 400

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 280 m3/h (78 l/s), 100 pa.

octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 400 HeSupply Inlet 29 39 51 55 54 54 49 42 60,2Supply outlet 34 46 57 62 62 60 56 50 67,2Exhaust Inlet 29 39 51 55 54 54 49 42 60,2Exhaust outlet 34 46 57 62 62 61 57 52 67,5Casing 31 41 49 46 45 43 35 28 52,8

Surroundings 23 33 36 34 36 32 25 18 41,4

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 9,1 12,2 13,7 14,6 15,5 16,4 21,8

KK2-15-09-v1

Page 18: air Handling Units KompaKt

16

ReGo 500H

ReGo 500v

1015

940

186

225

635

250 (4x)

200 (4x)

228

245

245

390

390

635 635

1060185

198

198

198

700

198

185228

D

D

a

a

С

С

B

B

7

7

2

4

1

5

3

6

9301080

3

16 452

D

a

C

BB a

C D B D a C

D

a

C

B

D C

a B

a C B D

KompaKt ReGo 500

panel thickness 45 mmUnit weight v/H 140/90 kgnominal air fl ow 500 m3/hSupply voltage 1~ 230 vmaximal operating current 6,9 apaint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable

Shown as left

Shown as right

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 19: air Handling Units KompaKt

17

9088868482807876

300 350 400 450 500 550 600

XL

L

m

XL

L

m0

40

- 40

- 80

80

300 350 400 450 500 550 600

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 540x260x46 mm

eC fansInput power at point 100 pa / 500 m3/h 86 WRotation speed 2250 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e) Capacity 1 kWair temperature, Δt 6°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)acoustic Data

a-weighted sound power levels Lwa, dB(a). operation point: 350 m3/h (97 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 500 H(v)eSupply Inlet 30 35 47 53 51 48 43 35 56,7Supply outlet 35 42 54 59 58 54 50 43 63,2Exhaust Inlet 30 35 47 53 51 48 43 35 56,7Exhaust outlet 35 42 54 59 58 54 50 44 63,2Casing 32 37 46 44 43 39 31 25 50,0

Surroundings 24 29 33 32 34 28 21 15 38,7

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 500

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 10,8 13,4 14,6 15,4 16,2 16,9 21,6

KK2-15-09-v1

Page 20: air Handling Units KompaKt

18

KompaKt ReGo 600 U RHp

ReGo 600 UH RHp

540 190

440

543 1250

1393

649

200 (4x)

203

285

607

615

803

892

Сa

B D

1250

803

892

966

1066194

200 (4x)

185

456

649

aB

DC

ReGo 600 Uv RHp

D

a

C

BB a

C D

D

a

C

B

D C

a B

a

C

B

D

B

D

a

C

1 7 231086 549

NEW

panel thickness 50 mmUnit weight 110 kgnominal air fl ow 600 m3/hSupply voltage 1~ 230 vmaximal operating current 600 U RHp-1,8 9,5 amaximal operating current 600 U RHp-2,8 11,5 apaint color RaL 7035Control panel KomfovEnt C5.1

Shown as right

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. Compressor9. Supply air coil10. Exhaust air coil

a outdoor intake C Extract indoorB Supply air D Exhaust air

Shown as left

p. 83 p. 86p. 88

new page

KK2-15-09-v1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Page 21: air Handling Units KompaKt

19

300 400 500 600 700 800

90

86

82

78

74

70

6

5,5

5

4,5

4

3,5

3

10

8

6

4

2

0

600 U RHp-1,8

600 U RHp-2,8

600 U RHp-2,8

5

4

3

2

1

0

kW

0 100 200 300 400 500 600 700 800

500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

600 U RHp-1,8

-20 -15 -10 -5 0 5 10 15

25 30 35

%

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 500x280x46 mm

eC fans Input power at point 100 pa / 600 m3/h 153 WRotation speed 2500 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 1 kWair temperature, Δt at 600 m3/h 5°C* option

Compressor and aHU data

Refrigerant R134a

Compressor heating capacity600 U RHp-1,8 1800 W

600 U RHp-2,8 2800 W

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 500 m3/h (139 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReGo 600 U RHpSupply Inlet 37 45 51 56 55 53 49 44 60,9Supply outlet 36 49 61 67 65 62 57 49 70,7Exhaust Inlet 28 38 49 55 53 50 44 34 58,4Exhaust outlet 36 49 61 67 65 62 57 49 70,7Casing 34 45 53 49 47 44 35 27 55,9

Surroundings 26 37 39 37 38 32 25 17 44,4

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5.

performance ReGo 600 U RHp

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

air flow rate (m3/s)

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

tota

l (kW

)

tota

l hea

ting

capa

city

, kW

outside temperature, °C

Heating mode

tota

l coo

ling

capa

city

, kW

outside temperature, °C

Cooling mode

application: 20°C, RH 45% indoor

application: 24°C, RH 55% indoor

total (heating and cooling) – rotary heat recovery + heat pump.

new page

KK2-15-09-v1

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

Page 22: air Handling Units KompaKt

20

KompaKt ReGo 700

ReGo 700H

ReGo 700v

1015

940

186

225

635

250 (4x)

250 (4x)

228

245

245

390

390

635 635

1060185

198

198

198

198

185228

D

D

a

a

С

С

B

B

7

7

2

4

1

5

3

6

700

9301080

3

16 452

D

a

C

BB a

C D B D a C

D

a

C

B

D C

a B

a C B D

panel thickness 45 mmUnit weight v/H 140/90 kgnominal air fl ow 700 m3/hSupply voltage 1~ 230 vmaximal operating current 11,5 apaint color RaL 7035Control panel KomfovEnt C5.1

Shown as right

Design1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable

Shown as left

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 23: air Handling Units KompaKt

21

300 400 500 600 700 800

90

86

82

78

74

70

XL

L

m

300 400 500 600 700 800

XL

L

m

0

40

- 40

- 80

80

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

0 100 200 300 400 500 600 700 800 900

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 540x260x46 mm

eC fans Input power at point 100 pa / 700 m3/h 115 WRotation speed 2200 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 2 kWair temperature, Δt 8,6°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

performance ReGo 700

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 490 m3/h (136 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 700 H(v)eSupply Inlet 27 38 50 56 54 52 46 37 59,8Supply outlet 32 45 57 63 61 58 53 45 66,7Exhaust Inlet 27 38 50 56 54 52 46 37 59,8Exhaust outlet 32 45 57 63 61 59 54 46 66,9Casing 29 40 49 46 45 42 33 25 52,5

Surroundings 21 32 36 34 36 31 23 15 41,1

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

m – option, L – standard, XL – option

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 11,7 12,2 13,6 14,5 15,4 16,4 21,8

KK2-15-09-v1

Page 24: air Handling Units KompaKt

22

KompaKt ReGo 900 U

ReGo 900 UH

ReGo 900 Uv

248248 400400

895895 13451505

895

237

237

420

420

4

9

8

56 3 1 2

С

B D

a315 (4x)

1345

750

248

895

75

100

248

400

895

63

2

1

5

9 8

4

D

a

С

B

315 (4x)

B

a C

D

a C B

C

a

D D B

D

C a

B

C a a

D

B

C B D

7

7

7

panel thickness 50 mmUnit weight 195 kgnominal air fl ow 900 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 7,7 amaximal operating current (W) 3,3 a paint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=15 mm) only for W

Shown as left

Shown as right

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 25: air Handling Units KompaKt

23

500 600 700 800 900 1000 1100

XL

m

L

90

85

80

75

70

500 600 700 800 900 1000 1100

XLL

m

0

40

- 40

- 80

80

0 200 400 600 800 1000 1200

0 0,05 0,1 0,15 0,2 0,25 0,3500

400

300

200

100

0

Sfp 1,25Sfp 1

Sfp 0,75

Sfp 0,5

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 3,5 3,5 3,5 3,5 5,3 4,5flow rate, dm3/h 156 156 156 306 900 792pressure drop, kpa 1 1 1 1,6 13 10Connection, ” 1/2temperature in/RH–out/RH, °C/% 10,3-22 30/50-

18/8926/70-18/95

air filters. Supply / exhaust filter class En779:2011 m5/f7*type Compact Dimensions bxhxl 800x400x46 mm

eC fans Input power at point 100 pa / 900 m3/h 165 WRotation speed 2500 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 3 kWair temperature, Δt 10°C* option

performance ReGo 900 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 630 m3/h (175 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 900 UH(v)eSupply Inlet 23 34 45 51 51 50 45 35 56,2Supply outlet 28 40 51 57 58 57 52 44 62,9Exhaust Inlet 23 34 45 51 51 50 45 36 56,3Exhaust outlet 28 40 51 57 58 57 52 44 62,9Casing 25 36 44 42 43 40 33 25 48,9

Surroundings 17 28 31 30 34 29 23 15 37,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 10,3 14,0 15,1 15,8 16,5 17,2 21,6

KK2-15-09-v1

Page 26: air Handling Units KompaKt

24

KompaKt ReGo 1200 U

ReGo 1200 UH

ReGo 1200 Uv

248248 400400

895895 13451505

895

237

237

420

420

4

9

8

56 3 1 2

С

B D

a315 (4x)

1345

750

248

895

75

100

248

400

895

63

2

1

5

9 8

4

D

a

С

B

315 (4x)

7

7

7

B

a C

D

a C B

C

a

D D B

D

C a

B

C a a

D

B

C B D

panel thickness 50 mmUnit weight v/H 195 kgnominal air fl ow 1200 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 12,5 amaximal operating current (W) 6,5 a paint color RaL 7035Control panel KomfovEnt C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=15 mm) only for W

Shown as left

Shown as right

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 88 p. 89

KK2-15-09-v1

Page 27: air Handling Units KompaKt

25

500 600 700 800 900 1000 1100 1200 1300 1400

XLL

m

0

40

- 40

- 80

80

90

85

80

75

70

65500 600 700 800 900 1000 1100 1200 1300 1400

XL

m

L

500

400

300

200

100

00 200 400 600 800 1000 1200 1400

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35

Sfp 1,25

Sfp 1

Sfp 0,75

Sfp 0,5

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Compact Dimensions bxhxl 800x400x46 mm

eC fans Input power at point 100 pa / 1200 m3/h 180 WRotation speed 1820 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 4,5 kWair temperature, Δt 11,1°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)Changeover water heating/cooling exchanger (CHW)

Winter SummerWater temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 4,7 4,7 4,7 4,7 7,0 6,0flow rate, dm3/h 206 206 206 206 1188 1044pressure drop, kpa 1 1 1 1 21 16Connection, ” 1/2temperature in/RH–out/RH, °C/% 10,4-22 30/50-

18/8926/70-18/95

performance ReGo 1200 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 840 m3/h (233 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 1200 UH(v)eSupply Inlet 34 40 47 50 49 47 44 34 55,0Supply outlet 39 47 53 56 56 54 52 44 61,7Exhaust Inlet 34 40 47 50 49 48 45 35 55,3Exhaust outlet 39 47 53 56 56 54 52 44 61,7Casing 35 42 46 42 42 38 32 24 49,9

Surroundings 27 34 33 30 33 27 22 14 39,2

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 10,4 13,2 14,4 15,2 16,0 16,8 21,6

KK2-15-09-v1

Page 28: air Handling Units KompaKt

26

ReGo 1200 pe

KompaKt ReGo 1200 p

220 1360 751510480

110

445

445

1050

940

245

245

315 (4x)

8 12 5 6

4 1 3

a

DB

C

220480

7

a

a

D

D

B

B

C

C

C

C

D

D

a

a

B

B

panel thickness 50 mmUnit weight 135 kgnominal air fl ow 1200 m3/hSupply voltage 3~ 400 vmaximal operating current 10,3 apaint color RaL 7035Control panel KomfovEnt C5.1

REGo 1200pE – with removable doors. REGo 1200pES – with sliding doors.

Shown as left

Shown as rightDesign1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. automatic control devices

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

KK2-15-09-v1

Page 29: air Handling Units KompaKt

27

9590858075706560

200 400 600 800 1000 1200 1400

XL

Lm

200 400 600 800 1000 1200 1400

0

40

- 40

- 80

80

XL

Lm

Sfp 1,25

Sfp 0,5

Sfp 1

Sfp 0,75

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 410x420x46 mm

eC fans Input power at point 100 pa / 1200 m3/h 340 WRotation speed 2340 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 3 kWair temperature, Δt 10°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 840 m3/h (233 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 1200 peSupply Inlet 37 44 53 55 52 51 48 38 59,5Supply outlet 42 51 59 61 60 57 55 46 66,1Exhaust Inlet 37 44 53 55 52 51 48 38 59,5Exhaust outlet 42 51 59 61 60 57 55 47 66,1Casing 38 46 51 45 44 40 34 26 53,8

Surroundings 30 38 38 33 35 29 24 16 42,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 1200 pe

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 6,3 10,1 11,9 13,1 14,2 15,4 22,3

KK2-15-09-v1

Page 30: air Handling Units KompaKt

28

KompaKt ReGo 1400 U

ReGo 1400 UH

ReGo 1400 Uv

248248 400400

895895 13451505

895

237

237

420

420

4

9

8

56 3 1 2

С

B D

a315 (4x)

1345

750

248

895

75

100

248

400

895

63

2

1

5

9 8

4

D

a

С

B

315 (4x)

7

7

7

B

a C

D

a C B

C

a

D D B

D

C a

B

C a a

D

B

C B D

panel thickness 50 mmUnit weight v/H 195 kgnominal air fl ow 1400 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 12,7 amaximal operating current (W) 6,7 a paint color RaL 7035Control panel KomfovEnt C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=15 mm) only for W

Shown as left

Shown as right

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 31: air Handling Units KompaKt

29

500 600 700 800 900 1000 1100 1200 1300 1400

XLL

m

0

40

- 40

- 80

80

90

85

80

75

70

65500 600 700 800 900 1000 1100 1200 1300 1400

XL

m

L

500

400

300

200

100

00 200 400 600 800 1000 1200 1400 1600

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4

Sfp 1,25

Sfp 1

Sfp 0,75

Sfp 0,5

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

air filters. Supply / exhaust filter class En779:2011 m5/f7*type Compact Dimensions bxhxl 800x400x46 mm

eC fans Input power at point 100 pa / 1400 m3/h 240 WRotation speed 2050 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 4,5 kWair temperature, Δt 9,6°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)Changeover water heating/cooling exchanger (CHW)

Winter SummerWater temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 5,8 5,8 5,8 5,8 8,2 7,1flow rate, dm3/h 255 255 255 501 1404 1224pressure drop, kpa 1 1 1 3,8 28 21Connection, ” 1/2temperature in/RH–out/RH, °C/% 9,7-22 30/50-

18/8926/70-18/95

performance ReGo 1400 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 980 m3/h (272 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 1400 UH(v)eSupply Inlet 36 42 48 52 51 49 46 36 56,9Supply outlet 41 49 55 58 58 56 54 46 63,7Exhaust Inlet 36 42 48 52 51 50 47 37 57,2Exhaust outlet 41 49 55 58 58 56 54 46 63,7Casing 37 43 47 43 43 40 33 26 51,1

Surroundings 29 35 34 31 34 29 23 16 40,3

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 9,7 12,6 14,0 14,8 15,7 16,6 21,7

KK2-15-09-v1

Page 32: air Handling Units KompaKt

30

KompaKt ReGo 1600 U

ReGo 1600 UH

ReGo 1600 Uv

245245

300x400 (4x)300x400 (4x)

400x300 (4x)

404404

900900 1505

1505

750

280

1565

990

990

30

100

225

404

900

263

263

464

464

63

4

9

8

56 3 1 2

2

1

5

9 8

4

D

D

a

a

С

С

B

B

D

C

C

a

a

C

B

D

D

B

C

D

B

a

a

B

D

B

C

a

a

C

B

D

7

7

7

panel thickness 45 mmUnit weight 270 kgnominal air fl ow 1600 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 12,7 amaximal operating current (W) 6,7 a paint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=28 mm) only for W

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as right

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 33: air Handling Units KompaKt

31

XLL

m

90

85

80

75

70

651000 1100 1200 1300 1400 1500 1600 1700 1800 1900

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900

XL

L

m

0

40

- 40

- 80

80

0 0,1 0,2 0,3 0,4 0,5

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

air flow rate (m3/h)

m – option, L – standard, XL – option

additional pressure drop

pres

sure

dro

p (p

a)

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 800x450x46 mm

eC fans Input power at point 100 pa / 1600 m3/h 340 WRotation speed 2290 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 4,5 kWair temperature, Δt 8,6°C* option

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 7 7 7 7 9,3 8,1flow rate, dm3/h 310 310 310 610 1584 1368pressure drop, kpa 1 1 1 1 3,0 2,3Connection, ” 1

temperature in/RH–out/RH, °C/% 8,9-22 30/50–

18/8926/70-18/95

temperature efficiency

air flow rate (m3/h)

performance ReGo 1600 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1120 m3/h (272 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 1600 UH(v)eSupply Inlet 36 41 47 51 52 50 47 38 57,1Supply outlet 41 48 54 57 59 57 55 48 64,0Exhaust Inlet 36 41 47 51 52 51 48 39 57,4Exhaust outlet 41 48 54 57 59 57 55 48 64,0Casing 37 43 46 43 43 40 34 26 50,7

Surroundings 29 35 33 31 34 29 24 16 40,1

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

tem

p. e

ffici

ency

(%)

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 8,9 12,0 13,5 14,4 15,4 16,3 21,9

KK2-15-09-v1

Page 34: air Handling Units KompaKt

32

KompaKt ReGo 2000 U

ReGo 2000 UH

ReGo 2000 Uv

245245

300x400 (4x)300x400 (4x)

400x300 (4x)

404404

900900 1505

1505

750

280

1565

990

990

30

100

225

404

900

263

263

464

464

63

4

9

8

56 3 1 2

2

1

5

9 8

4

D

D

a

a

С

С

B

B

7

7

7

D

C

C

a

a

C

B

D

D

B

C

D

B

a

a

B

D

B

C

a

a

C

B

D

panel thickness 50 mmUnit weight 285 kgnominal air fl ow 2000 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 14,9 amaximal operating current (W) 5,0 apaint color RaL 7035Control panel KomfovEnt C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as right

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=28 mm) only for W

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 35: air Handling Units KompaKt

33

90

85

80

75

70

651000 1200 1400 1600 1800 2000 2200 2400

XLL

m

1000 1200 1400 1600 1800 2000 2200 2400

XL

L

m

0

40

- 40

- 80

80

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 800x450x46 mm

eC fans Input power at point 100 pa / 2000 m3/h 320 WRotation speed 2000 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 7,5 kWair temperature, Δt 11°C* option

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 10 10 10 10 11,7 10,1flow rate, dm3/h 435 435 435 855 2016 1728pressure drop, kpa 1 1 1 1 4,6 3,5Connection, ” 1temperature in/RH–out/RH, °C/% 7,3-22 30/50-

18/8926/70-18/88

performance ReGo 2000 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1400 m3/h (389 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 2000 UH(v)eSupply Inlet 30 43 52 54 52 51 46 38 58,8Supply outlet 35 50 59 60 60 58 54 48 65,8Exhaust Inlet 30 43 52 54 52 52 46 39 59,0Exhaust outlet 35 50 59 60 60 58 54 48 65,8Casing 32 45 50 44 44 41 33 26 53,0

Surroundings 24 37 37 32 35 30 23 16 41,9

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency

tem

p. e

ffici

ency

(%)

air flow rate (m3/h)

m – option, L – standard, XL – option

additional pressure drop

pres

sure

dro

p (p

a)

air flow rate (m3/h)

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 7,3 10,9 12,6 13,7 14,7 15,8 22,1

KK2-15-09-v1

Page 36: air Handling Units KompaKt

34

KompaKt ReGo 2000 p

107

600

1317

1210

305

305

355 (4x)

C

B a

D

1 28 5

6 4

264526

20602205

72 264

ReGo 2000pe

D

D

a

a

B

B

C

C

B

B

D

D

a

a

C

C

600

3

7

panel thickness 50 mmUnit weight 280 kgnominal air fl ow 2000 m3/hSupply voltage 3~ 400 vmaximal operating current 12,8 apaint color RaL 7035Control panel KomfovEnt C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as rightDesign1. Rotary heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. automatic control devices

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

KK2-15-09-v1

Page 37: air Handling Units KompaKt

35

Sfp 1,25

Sfp 0,5

Sfp 1

Sfp 0,75

400

300

200

100

00 400 800 1200 1600 2000 2400

0 0,1 0,2 0,3 0,4 0,5 0,6

86

85

84

83

82

811000 1200 1400 1600 1800 2000 2200 2400

XL

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 560x420x96 mm

eC fansInput power at point 100 pa / 2000 m3/h 550 WRotation speed 2900 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 7,5 kWair temperature, Δt 10,5°C* option

air flow rate (m3/h)

temperature efficiency

tem

p. e

ffici

ency

(%)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter F7, rotary heat exchanger – XL.

performance ReGo 2000pe

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 10,8 12,2 13,7 14,6 15,5 16,4 21,6

KK2-15-09-v1

Page 38: air Handling Units KompaKt

36

KompaKt ReGo 2500 U

ReGo 2500 UH

ReGo 2500 Uv

245245

300x400 (4x)300x400 (4x)

400x300 (4x)

404404

900900 1505

1505

750

280

1565

990

990

30

100

225

404

900

263

263

464

464

63

4

9

8

56 3 1 2

2

1

5

9 8

4

D

D

a

a

С

С

B

B

7

7

7

D

C

C

a

a

C

B

D

D

B

C

D

B

a

a

B

D

B

C

a

a

C

B

D

panel thickness 50 mmUnit weight 285 kgnominal air fl ow 2500 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 16,7 amaximal operating current (W) 6,3 apaint color RaL 7035Control panel KomfovEnt C5.1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as right

Design1. Rotary heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tubes only for W9. Condensate drain (in summertime the water

trap must be installed D=28 mm) only for W

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 39: air Handling Units KompaKt

37

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

XLL

m

900 1300 1700 2100 2500 2900

90

85

80

75

70

65

60

XL

L

m

0

40

- 40

- 80

80

900 1300 1700 2100 2500 2900

m – option, L – standard, XL – option

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 800x450x46 mm

eC fans Input power at point 100 pa / 2500 m3/h 710 WRotation speed 2600 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 7,5 kWair temperature, Δt 8,4°C* option

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 14 14 14 14 14,6 12,6flow rate, dm3/h 614 614 614 1208 2484 2160pressure drop, kpa 1 1 1 1 6,9 5,3Connection, ” 1temperature in/RH–out/RH, °C/% 5,4-22 30/50-

18,5/8826/70-18/95

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1750 m3/h (486 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 2500 UH(v)eSupply Inlet 37 45 54 60 59 57 55 50 64,8Supply outlet 42 53 61 67 67 65 64 62 72,7Exhaust Inlet 37 45 54 60 59 58 55 51 65,0Exhaust outlet 42 53 61 67 67 65 64 62 72,7Casing 38 47 52 49 49 45 39 33 56,2

Surroundings 30 39 39 37 40 34 29 23 45,2

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 2500 U

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 5,4 9,6 11,5 12,7 13,9 15,1 22,4

KK2-15-09-v1

Page 40: air Handling Units KompaKt

38

ReGo 3000 UH6 7 51

1

REGO 3000 UV 31

C

D

B

a

a

B

D

CD

B

C

a

a

B

C

D

1150

1150

323

323

400

500

597

303

D

a

323

400

500

597

303

C

B

B

C D

a

650 700 750

750 700 650

328,5

400x500 (x4)

504

1150

43

3231150

3231150

6

2

274

5 3

9

8

9 8

10

10

10

KompaKt ReGo 3000 U

panel thickness 50 mmUnit weight 440 (140/160/140) kg nominal air fl ow 3000 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 16,8 amaximal operating current (W) 4,2 apaint color RaL 7035Control panel KomfovEnt C5.1

Design 1. Rotary heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. Drop eliminator 8. fluid connection tubes 9. Condensate drain 10. Connection of main cable

Shown as left

Shown as right

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 41: air Handling Units KompaKt

39

XLL

m

2000 2200 2400 2600 2800 3000 3200 3400 3600

90

85

80

75

70

65

XL

L

m

0

40

- 40

- 80

80

2000 2200 2400 2600 2800 3000 3200 3400 3600

Sfp 0,5

Sfp 0,75

Sfp 1

Sfp 1,25

m – option, L – standard, XL – option

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 525x510x46 mmQuantity 2 pcs.

eC fans Input power at point 100 pa / 3000 m3/h 650 WRotation speed 2200 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 9 kWair temperature, Δt 9,2°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 13,6 13,6 13,6 13,6 17,4 15,0flow rate, dm3/h 600 600 600 1179 2988 2592pressure drop, kpa 1 1 1 1,2 8,5 6,5Connection, ” 1temperature in/RH–out/RH, °C/% 8,5-22 30/50-

18/8926/70-18/95

performance ReGo 3000 U

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2100 m3/h (583 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 3000 UH(v)eSupply Inlet 25 32 47 54 53 56 54 47 60,8Supply outlet 29 37 53 59 67 67 64 59 71,6Exhaust Inlet 25 32 47 54 53 57 54 47 61,2Exhaust outlet 29 37 53 59 67 67 64 59 71,6Casing 27 34 46 44 48 46 38 32 52,5

Surroundings 19 26 33 32 39 35 28 22 41,7

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater. temperature efficiency

Winter Summeroutside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 8,5 12 13,5 14,4 15,3 16,3 21,9

KK2-15-09-v1

Page 42: air Handling Units KompaKt

40

KompaKt ReGo 4000 U

ReGo 4000 UH 6 7 51

1

REGO 4000 UV 31

C

D

B

a

a

B

D

CD

B

C

a

a

B

C

D

1150

1150

323

323

400

500

597

303

D

a

323

400

500

597

303

C

B

B

C D

a

650 700 750

750 700 650

328,5

400x500 (x4)

504

1150

43

3231150

3231150

6

2

274

5 3

9

8

9 8

10

10

10

panel thickness 50 mmUnit weight 450 (145/160/145) kgnominal air fl ow 4000 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 25,5 amaximal operating current (W) 4,2 apaint color RaL 7035Control panel KomfovEnt C5.1

Design 1. Rotary heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. Drop eliminator 8. fluid connection tubes 9. Condensate drain 10. Connection of main cable

Shown as left

Shown as right

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 43: air Handling Units KompaKt

41

XLL

m

90

85

80

75

70

65

602000 2500 3000 3500 4000 4500

XL

L

m0

40

- 40

- 80

80

2000 2500 3000 3500 4000 4500

Sfp 0,5

Sfp 0,75

Sfp 1

Sfp 1,25

m – option, L – standard, XL – option

additional pressure drop

air fl ow rate (m3/h)

pres

sure

dro

p (p

a)

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 525x510x46 mmQuantity 2 pcs.

eC fans Input power at point 100 pa / 4000 m3/h 1080 WRotation speed 2000 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 15 kWair temperature, Δt 11,4°C* option

temperature effi ciency

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 22 22 22 22 23,3 20,1flow rate, dm3/h 900 900 900 1750 3996 3456pressure drop, kpa 1 1 1 2 14 11Connection, ” 1temperature in/RH–out/RH, °C/% 6,4-22 30/50-

18/8926/70-18/88

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2800 m3/h (778 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 4000 UH(v)eSupply Inlet 38 44 57 62 60 62 58 48 67,3Supply outlet 43 50 62 69 75 72 67 60 78,0Exhaust Inlet 38 44 57 62 60 63 58 48 67,6Exhaust outlet 43 50 62 69 75 72 67 60 78,0Casing 39 45 54 50 53 49 40 32 58,3

Surroundings 31 37 41 38 44 38 30 22 47,3

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 4000 U

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air fl ow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air fl ow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: fi lter M5, rotary heat exchanger L and electric air heater.

temperature effi ciencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 6,4 10,5 12,3 13,4 14,5 15,6 22,3

KK2-15-09-v1

Page 44: air Handling Units KompaKt

42

ReGo 4500 UH6 7 51

1

REGO 4500 UV 31

C

D

B

a

a

B

D

CD

B

C

a

a

B

C

D

1150

1150

323

323

400

500

597

303

D

a

323

400

500

597

303

C

B

B

C D

a

650 700 750

750 700 650

328,5

400x500 (x4)

504

1150

43

3231150

3231150

6

2

274

5 3

9

8

9 8

10

10

10

KompaKt ReGo 4500 U

panel thickness 50 mmUnit weight 450 (145/160/145) kgnominal air fl ow 4500 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 27,3 amaximal operating current (W) 6,0 apaint color RaL 7035Control panel KomfovEnt C5.1

Design 1. Rotary heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. Drop eliminator 8. fluid connection tubes 9. Condensate drain 10. Connection of main cable

Shown as left

Shown as right

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 45: air Handling Units KompaKt

43

90

85

80

75

70

65

602200 2600 3000 3400 3800 4200 4600 5000 5400

XL

L

m

0

40

- 40

- 80

80

2200 2600 3000 3400 3800 4200 4600 5000 5400

XLL

m

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

m – option, L – standard, XL – option

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 525x510x46 mmQuantity 2 pcs.

eC fans Input power at point 100 pa / 4500 m3/h 1280 WRotation speed 2280 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 15 kWair temperature, Δt 9,8°C* option

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

Changeover water heating/cooling exchanger (CHW)Winter Summer

Water temperature in/out, °C 90/70 80/60 60/40 45/35 7/12

Capacity, kW 25 25 25 25 24,5 22,7flow rate, dm3/h 1100 1100 1100 2187 4212 3888pressure drop, kpa 1 1 1 3 16 14Connection, ” 1temperature in/RH–out/RH, °C/% 5,3-22 30/50-

18,5/8826/70-18/95

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 3150 m3/h (875 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 4500 UH(v)eSupply Inlet 40 37 58 61 59 62 57 51 66,9Supply outlet 43 42 60 67 73 73 67 63 77,2Exhaust Inlet 40 37 58 61 59 62 57 51 66,9Exhaust outlet 43 42 60 67 73 73 67 63 77,2Casing 40 39 54 49 52 50 40 34 57,9

Surroundings 32 31 41 37 43 39 30 24 46,6

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 4500 U

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger L and electric air heater.

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 5,3 9,8 11,7 12,9 14,0 15,2 22,5

KK2-15-09-v1

Page 46: air Handling Units KompaKt

44

D C

a B

B a

C D

ReGo 7000 H

1200750

600

1520

600

125 430 750

1500

6 3 45 2 8

D

a

С

B

7 71

KompaKt ReGo 7000

panel thickness 45 mmUnit weight 780 (270/230/280) kgnominal air fl ow 7000 m3/hSupply voltage 3~ 400 vmaximal operating current 9,9 apaint color RaL 7035Control panel KomfovEnt C5.1

Design1. Rotary heat exchanger2. Water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. fluid connection tube

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as right

a outdoor intake B Supply airC Extract indoor D Exhaust air

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89

KK2-15-09-v1

Page 47: air Handling Units KompaKt

45

XL

L

m

90

85

80

75

70

65

602000 3000 4000 5000 6000 7000 8000 9000

2000 3000 4000 5000 6000 7000 8000 9000

XL

L

m0

40

- 40

- 80

80

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x592-12x500 mmQuantity 2 pcs.

eC fans Input power at point 100 pa / 7000 m3/h 1350 WRotation speed 1680 rpmprotection level, IEC 34-5 Ip 54* option

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: filter M5, rotary heat exchanger – L.

temperature efficiency

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

Hot water air heater (HW)Winter

Water temperature in/out, °C 90/70 80/60 60/40 45/35Capacity, kW 34,7 34,7 34,7 34,7flow rate, dm3/h 1533 1526 1513 3016pressure drop, kpa 8,8 8,9 9,5 34Connection, ” 1temperature in–out, °C 7,2-22

additional pressure drop

air flow rate (m3/h)

pres

sure

dro

p (p

a)

m – option, L – standard, XL – option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 4900 m3/h (1361 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReGo 7000 HWSupply Inlet 29 38 56 59 56 55 52 49 63,3Supply outlet 35 45 61 70 73 69 65 59 76,3Exhaust Inlet 29 38 56 59 56 55 52 49 63,3Exhaust outlet 36 46 63 72 75 71 68 64 78,5Casing 32 41 54 52 53 49 41 35 58,6

Surroundings 24 33 41 40 44 38 31 25 47,3

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReGo 7000

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

temperature efficiencyWinter Summer

outside temperature, °C -40 -23 -15 -10 -5 0 30after regeneration, °C(indoors +20°C) 7,2 10,9 12,6 13,6 14,7 15,7 22,1

KK2-15-09-v1

Page 48: air Handling Units KompaKt

46

+20°C

+1°C (+4°C*) +20°C

-23°C

D

Ca

B

Komfovent KompaKt ReCU UnitsKomfovEnt KompaKt RECU air handling units with plate heat exchanger.Capacity range from 220 to 8 000 m3/h.

Heat energy SavingIn the process of ventilation the heat of the exhaust air is reco-vered to the supplied air – the unit allows up to 65% heat re-covery with standard plate heat exchanger and up to 92% with highly effi cient polystyrene plate heat exchanger.

totally separated airfl owsthe supply and exhaust airfl ows are separated, thus ma king possible utilization of the heat of the extracted foul air.

Long term effi cient operationthe absence of the conditions of movable parts eff ective heat exchange and long run.

Low noise levelKomfovEnt KompaKt air handling units are equipped with silently operating fans and sound insulation, which ensures low noise level.

advantages of Komfovent KompaKt ReCU Units

* temperature after the heat exchanger

a outdoor intake C Extract indoorB Supply air D Exhaust air

92%

ther

mal efficiency and

energy saving up to

65%

ther

mal efficiency and

energy saving up to

KK2-15-09-v1

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Page 49: air Handling Units KompaKt

47

20 % 120 %

7000

4000

3000

2000

1600

1200

900

700

400

4500

0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4600 5000 5400 8000 m3/h

0 0.11 0.22 0.33 0.44 0.55 0.67 0.78 0.89 1 1.11 1.22 1.28 1.38 1.5 2,2 m3/s

20 % 120 %

Standard plate heat exchanger

Design:• A packet of thin aluminum plates with spacing left bet ween

them.• Exhaust warm air fl ows through every second channel be-

tween the plates warming up fresh air fl owing through the remaining channels.

• To prevent the plates from bending under the impact of diff erential pressure of the air fl ows, strengthening gaskets are inserted between the plates.

• Rough surface of the aluminum plates generates the turbu-lent air stream thus intensifying heat exchange.

anti-frosting protectionDecreasing of the outdoor air temperature below -10°C (it is an approximate value depending on the relative humidity of the air fl ows and temperature) the exhaust air enhances the danger of the heat exchanger freezing. Defrosting of the heat exchanger is controlled automa tically in response to sensor signals. temperature sensors are supplied with the unit.

note: the water trap must be installed for condensate drain!

Counterfl ow polystyrene plate heat exchanger

this type of exchanger is available for size RECU 700Cf (page 52). the exchanger is constructed completely from polystyrene – from the foils to the casing. only solvent-free elastic adhesives are used.

• The triangular ducts in the recuperator are arranged so that each one is surrounded by parallel ducts in which the air is in counter fl ow.

• Each fresh-air duct is surrounded by three ducts fi lled with warmer exhaust air. Likewise, each duct with exhaust air is sur-rounded by three fresh-air ducts. this maximizes the surface area over which energy can effi ciently be transferred, recap-tured and reused.

• This design principle is what makes this exchanger‘s outstan-ding performance possible.

anti-frosting protectionIf the temperature of the exhaust air drops below 0oC, freezing may occur at the exhaust air corner of the heat exchanger. to avoid free zing the temperature sensor is installed in this zone to give a signal to the automatic control. If for some period of time temperature will not rise up, by-pass damper is opened to redirect outdoor air through by-pass channel and only warm exhaust air fl ows through exchanger to defrost risky zone. for the conditions when outdoor temperatures may be lower than -4oC , duct mounted preheater is recommended.

performance range

Standard sizes of Komfovent KompaKt ReCU units

Uni

t siz

e

Effi ciency of aHU

65%

ther

mal efficiency and

energy saving up t

o

92%

ther

mal efficiency and

energy saving up t

o

KK2-15-09-v1

Page 50: air Handling Units KompaKt

48

ReCU 400 H

ReCU 400 v

7

15

6

7

2

3 4

5

6 1 82 8

1000

900

780

920

390

145 145

150

90

200 200

195

200 (4x)

600

145

145

3901150

4 3 8

C

D

a

B

D

B

160 (4x)

D

B

a

C

C

a

B

D

B

D

C

a C

a

B

D

KompaKt ReCU 400

panel thickness 45 mmUnit weight v/H 62/55 kgnominal air fl ow 400 m3/hSupply voltage 1~ 230 vmaximal operating current 10,7 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left

Shown as right

Design1. plate heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Condensate drain (the water trap must be installed D=15 mm)8. Connection of main cable

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92p. 88

KK2-15-09-v1

Page 51: air Handling Units KompaKt

49

100 150 200 250 300 350 400 450 500 550 600

70

68

66

64

62

60

58

56

54

52

50

0oC

-23oC

+5oC

-10oC

0 100 200 300 400 500 600

0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 400

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 7,6 9,1 10,9

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 300x195x46 mm

eC fansInput power at point 100 pa / 400 m3/h 60 WRotation speed 3570 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e)Capacity 2 kWair temperature, Δt 14,4°C* option

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 280 m3/h (78 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 400 H(v)eSupply Inlet 18 28 36 41 44 42 39 34 48,4Supply outlet 24 35 44 49 52 52 50 44 57,4Exhaust Inlet 18 28 36 41 44 42 39 34 48,4Exhaust outlet 24 35 44 49 52 53 50 45 57,8Casing 22 31 38 37 39 38 31 25 44,6

Surroundings 14 23 25 25 30 27 21 15 33,7

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 52: air Handling Units KompaKt

50

3 4 56 1 82 8

71170 245

250 (4x)

600

145

160

4951325

4 3

15

6

7

2

1000

950

1090

490

150 170

156

156

220 210

200 (4x)

KompaKt ReCU 700

ReCU 700 H

ReCU 700 v

D

B

C

D

a

B

D

B

a

C

C

a

B

D

B

D

C

a C

a

B

D

panel thickness 45 mmUnit weight v/H 85/75 kgnominal air fl ow 700 m3/hSupply voltage 1~ 230 vmaximal operating current EC/aC 13,7/12,9 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Design1. plate heat exchanger2. Electric air Heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Condensate drain (the water trap must be installed D=15 mm)8. Connection of main cable

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

Shown as left

Shown as right

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 53: air Handling Units KompaKt

51

100 200 300 400 500 600 700 800 900

75

70

65

60

55

50

45

3

2

1

0oC

-23oC

+5oC

-10oC

0 200 400 600 800 1000

0 0,05 0,1 0,15 0,2 0,25500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

0 200 400 600 800 1000

0 0,05 0,1 0,15 0,2 0,25500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

temperature effi ciency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 7,3 9,9 11,4

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 400x235x46 mm

eC/aC fansInput power EC at point 100 pa / 700 m3/h 125 WInput power aC at point 100 pa / 550 m3/h 150 WRotation speed 2570/2800 rpmprotection level, IEC 34-5 Ip 44

electric air heater (e)Capacity 2,5 kWair temperature, Δt 10,7°C* option

a-weighted sound power levels Lwa, dB(a). operation point: 685 m3/h (190 l/s), 196 pa.

ReCU 700 H(v)e-aCSupply Inlet 31 46 53 58 56 48 42 37 61,3Supply outlet 34 49 57 63 63 57 52 45 67,1Exhaust Inlet 31 46 53 58 56 48 42 37 61,3Exhaust outlet 34 49 57 63 63 57 53 46 67,1Casing 28 42 49 46 45 39 32 25 52,5

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 490 m3/h (136 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 700 H(v)e-eCSupply Inlet 29 34 44 48 49 44 40 34 53,2Supply outlet 36 41 52 56 58 55 51 44 62,2Exhaust Inlet 29 34 44 48 49 44 40 34 53,2Exhaust outlet 36 41 52 56 58 55 52 46 62,4Casing 33 37 45 42 43 39 32 25 49,3

Surroundings 25 29 32 30 34 28 22 15 38,2

Surroundings 20 34 36 34 36 28 22 15 41,3

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReCU 700-aC

performance ReCU 700-eC

fan

pow

er*

(W)

1, 2, 3 – speed; * – fan power is shown for one fan motor. Performance data: fi lter M5. Correction factor for H/vW approximately 20 pa at 700 m3/h. Correction factor for f7 class fi lter approximately – 70 pa.

air fl ow rate (m3/s)

air fl ow rate (m3/h)

Stat

ic p

ress

ure

(pa)

temperature effi ciency wet

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

application: 21°C, RH 45% indoor

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air fl ow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air fl ow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: fi lter m5 and electric air heater.

KK2-15-09-v1

Page 54: air Handling Units KompaKt

52

3 4 56 1 92 7

8

1500

250 (4x)

245

200

300

490

1540

ReCU 700 veCf

D

a

С

B

490

49 6 73

1

8

5

2

700

1040

1145

90

370

155

160

1020

155 455

455410

200 (4x)

700

ReCU 700 HeCfC

D

a

B

D

B

a

C

C

a

B

DB

D

C

a C

a

B

D

KompaKt ReCU 700

panel thickness 45 mmUnit weight 95 kgnominal air fl ow 700 m3/hSupply voltage 1~ 230 vmaximal operating current 11,5 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left

Shown as right

Design1. Counterfl ow polystyrene plate heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Connection of main cable8. Condensate drain (D=15 mm)9. By-pass damper

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 55: air Handling Units KompaKt

53

100

95

90

85

80

75

0oC

-23oC

+5oC

-10oC

100 200 300 400 500 600 700 800 900

0 200 400 600 800 1000

0 0,05 0,1 0,15 0,2 0,25500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

air fl ow rate (m3/h)

performance ReCU 700HeCf

performance ReCU 700veCf

temperature effi ciency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 15,8 17 17,5

air filters. Supply / exhaust filter class En779:2011 m5/f7*type CompactDimensions bxhxl 390x300x46 mm

eC fans Input power at point 100 pa / 700 m3/h 140 WRotation speed 2570 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e) Capacity 2 kWair temperature, Δt 8,2°C* option

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. Performance data: fi lter M5. Correction factor for H/vW approximately 20 pa at 700 m3/h. Correction factor for f7 class fi lter approximately – 70 pa.

air fl ow rate (m3/s)acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 490 m3/h (136 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 700 v(H)eCfSupply Inlet 33 37 48 54 53 47 42 36 57,7Supply outlet 40 45 57 63 62 58 54 48 67,0Exhaust Inlet 33 37 48 54 53 47 42 37 57,7Exhaust outlet 40 45 57 63 62 58 54 48 67,0Casing 36 40 49 46 45 41 34 27 52,6

Surroundings 28 32 36 34 36 30 24 17 41,2

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature effi ciency wet

air fl ow rate (m3/h)

tem

p. e

ffi ci

ency

(%)

application: 21°C, RH 45% indoor

outdoor

Stat

ic p

ress

ure

(pa)

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air fl ow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air fl ow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: fi lter m5 and electric air heater.

KK2-15-09-v1

Page 56: air Handling Units KompaKt

54

3 4 56 1 82 8

71170 245

250 (4x)

600

145

160

4951325

4 3 8

15

6

7

2

1000

950

1090

490

150 170

156

156

220 210

200 (4x)

D

B

C

D

a

B

D

B

a

C

C

a

B

D

B

D

C

a C

a

B

D

ReCU 900 H

ReCU 900 v

KompaKt ReCU 900

panel thickness 45 mmUnit weight v/H 90/78 kgnominal air fl ow 900 m3/hSupply voltage 3~ 400 vmaximal operating current EC/aC 9,3/10,3 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left

Shown as right

Design1. plate heat exchanger2. Electric air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Condensate drain (the water trap must be installed D=15 mm)8. Connection of main cable

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92p. 88

KK2-15-09-v1

Page 57: air Handling Units KompaKt

55

3

2

1

200 300 400 500 600 700 800 900 1000 1100

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 900-aC

performance ReCU 900-eC

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 7 9,7 11,2

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 400x235x46 mm

eC/aC fansInput power EC at point 100 pa / 870 m3/h 160 WInput power aC at point 100 pa / 850 m3/h 225 WRotation speed 2900/2780 rpmprotection level, IEC 34-5 Ip 44

electric air Heater (e)Capacity 4,5 kWair temperature, Δt 15°C* option

fan

pow

er*

(W)

1, 2, 3 – speed; * – fan power is shown for one fan motor. Performance data: filter M5. Correction factor for H/vW approximately 30 pa at 900 m3/h. Correction factor for f7 class filter approximately – 70 pa.

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

a-weighted sound power levels Lwa, dB(a). operation point: 833 m3/h (231 l/s), 290 pa.

ReCU 900 H(v)e-aCSupply Inlet 37 45 52 55 60 54 51 45 62,8Supply outlet 44 53 61 65 69 66 64 57 72,9Exhaust Inlet 37 45 52 55 60 54 51 45 62,8Exhaust outlet 44 53 61 65 69 67 65 59 73,3Casing 40 47 52 48 50 47 39 32 56,4

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 630 m3/h (175 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 900 H(v)e-eCSupply Inlet 24 36 46 52 52 48 42 35 56,5Supply outlet 31 44 55 61 61 59 54 46 66,0Exhaust Inlet 24 36 46 52 52 48 42 35 56,5Exhaust outlet 31 44 55 61 61 59 55 47 66,0Casing 28 39 47 45 45 42 34 26 51,5

Surroundings 20 31 34 33 36 31 24 16 40,3

Surroundings 32 39 39 36 41 36 29 22 45,6

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 58: air Handling Units KompaKt

56

29

9

2

3 34 4

1 1

5 56 6

7 7

8 8

1360 1360

210 210

700

700

1300

130015

35

1535

210 210

70 70

250 (4x) 250 (4x)

200

200

200

200

250

250

300 300300 300

ReCU 1200 ve ReCU 1200 vW

Da C

BBC a

D

D D

a aС С

B B

KompaKt ReCU 1200

panel thickness 45 mmUnit weight 225 kgnominal air fl ow 1200 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 14,3 amaximal operating current (W) 5,6 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left Shown as rightDesign1. plate heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Condensate drain (the water trap must be installed D=15 mm)8. Connection of main cable9. fluid connection tube only for W

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 88 p. 92

KK2-15-09-v1

Page 59: air Handling Units KompaKt

57

75

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

300 450 600 750 900 1050 1200 1350 1500

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 1200

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 5,7 8 9,9

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 11,94 9,33 8,43flow rate, dm3/h 530 409 370pressure drop, kpa 6,7 4 3,6Connection, ” 1/2temperature in–out, °C 5,9/35 5,9/29 5,9/27

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x287x360 mm

eC fans Input power at point 100 pa / 1200 m3/h 175 WRotation speed 2700 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 6 kWair temperature, Δt 14,8°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 840 m3/h (233 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 1200 veSupply Inlet 30 36 41 44 44 40 36 30 49,2Supply outlet 37 45 51 54 55 52 50 42 60,0Exhaust Inlet 30 36 41 44 44 40 36 30 49,2Exhaust outlet 37 45 51 54 55 53 51 43 60,3Casing 34 40 44 40 41 38 32 24 48,3

Surroundings 26 32 31 28 32 27 22 14 37,6

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency wette

mp.

effi

cien

cy (%

)

application: 21°C, RH 45% indoor

air flow rate (m3/h)

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 60: air Handling Units KompaKt

58

KompaKt ReCU 1200

250

315 (4x)

315 (4x)

1670

1670

350

350

700

700

1820

1820

200

200

860

860

220

220

80

6

6

7

7

3

3

1

1

4

4

5

2

5 9

8

8

25080

2

ReCU 1200 He

ReCU 1200 HW

C

C

D

D

a

a

B

B

BD

C a C a

B D

panel thickness 45 mmUnit weight 200 kgnominal air fl ow 1200 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 14,3 amaximal operating current (W) 5,6 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as rightDesign1. plate heat exchanger2. Electric or water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan

7. Condensate drain (the water trap must be installed D=15 mm)

8. Connection of main cable9. fluid connection tube only for W

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92p. 88

KK2-15-09-v1

Page 61: air Handling Units KompaKt

59

300 450 600 750 900 1050 1200 1350 1500

75

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 5,7 8 9,9

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 11 9,3 7,7flow rate, dm3/h 482 409 336pressure drop, kpa 5 4 3Connection, ” 1/2temperature in–out, °C 4,2/31 4,2/27 4,2/23

performance ReCU 1200air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x287x360 mm

eC fansInput power at point 100 pa / 1200 m3/h 175 WRotation speed 2700 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 6 kWair temperature, Δt 14,8°C* option

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 840 m3/h (233 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 1200 HeSupply Inlet 30 36 41 44 44 40 36 30 49,2Supply outlet 37 45 51 54 55 52 50 42 60,0Exhaust Inlet 30 36 41 44 44 40 36 30 49,2Exhaust outlet 37 45 51 54 55 53 51 43 60,3Casing 34 40 44 40 41 38 32 24 48,3

Surroundings 26 32 31 28 32 27 22 14 37,6

temperature efficiency wet

air flow rate (m3/h)

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 62: air Handling Units KompaKt

60

KompaKt ReCU 1600

22

11

5

10

5

88

9 9

1470 1470

195 195195 195

700

700

1310

1310

1460

1460

80 80

315 (4x) 315 (4x)

200

200

220

220

240

240

355 355355 355

33 66 77 44 10 10ReCU 1600 ve ReCU 1600 vW

D D

a a

С СB B

Da

CBB

Ca

D

panel thickness 45 mmUnit weight E/W 300/290 kgnominal air fl ow 1600 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 23,2 amaximal operating current (W) 6,3 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left Shown as right Design 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. By-pass damper 8. Condensate drain

(the water trap must be installed D=15 mm) 9. Connection of main cable10. fluid connection tube only for W

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 63: air Handling Units KompaKt

61

400 600 800 1000 1200 1400 1600 1800 2000

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

61

performance ReCU 1600

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 6,6 9,4 11

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 25,4 21,6 19,5flow rate, dm3/h 1121 946 851pressure drop, kpa 5 4 2Connection, ” 1temperature in–out, °C -20/27,1 -20/20 -20/16,2

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x287x360 mm

eC fansInput power at point 100 pa / 1600 m3/h 370 WRotation speed 2760 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 12 kWair temperature, Δt 17,2°C* option

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1120 m3/h (311 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

ReCU 1600 veSupply Inlet 36 43 48 51 50 46 42 35 55,7Supply outlet 45 53 59 62 62 59 57 49 67,5Exhaust Inlet 36 43 48 51 50 46 42 35 55,7Exhaust outlet 45 53 59 62 62 60 58 50 67,7Casing 40 47 51 46 46 42 35 27 54,6

Surroundings 32 39 38 34 37 31 25 17 43,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 64: air Handling Units KompaKt

62

KompaKt ReCU 1600

200

200

355 (4x)

355 (4x)

1900

1900

350

350

700

700

2050

2050

200

200

900

900

240

240

80

80

6

6

9

9

8

8

3

3

1

1

7

7

4

4

5

5

10

10

11

11

2

2

C

C

D

D

a

a

B

B

ReCU 1600 He

ReCU 1600 HW

BD

C a C a

B D

panel thickness 45 mmUnit weight E/W 320/330 kgnominal air fl ow 1600 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 23,2 amaximal operating current (W) 6,3 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as rightDesign 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan

7. By-pass damper 8. Condensate drain (the water trap

must be installed D=28 mm) 9. Drop eliminator10. Connection of main cable11. fluid connection tube only for W a outdoor intake C Extract indoor

B Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 65: air Handling Units KompaKt

63

400 600 800 1000 1200 1400 1600 1800 2000

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 6,6 9,4 11

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 25 23,2 18,3flow rate, dm3/h 1140 1015 798pressure drop, kpa 5 4 2Connection, ” 1temperature in–out, °C -23/25 -23/20 -14/20

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 610x350x96 mm

eC fansInput power at point 100 pa / 1600 m3/h 370 WRotation speed 2600 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 12 kWair temperature, Δt 22,1°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1120 m3/h (311 l/s), 100 paoctave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 1600 HeSupply Inlet 37 45 50 53 53 48 45 38 58,0Supply outlet 45 53 59 62 62 59 57 49 67,5Exhaust Inlet 37 45 50 53 53 48 44 37 58,0Exhaust outlet 45 53 59 62 62 60 58 50 67,7Casing 40 47 51 46 46 42 35 27 54,6

Surroundings 32 39 38 34 37 31 25 17 43,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

performance ReCU 1600

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 66: air Handling Units KompaKt

64

KompaKt ReCU 1600 p

ReCU 1600 pe

a

a

D

D

B

B

C

C

C

C

D

D

a

a

B

B

110

600

600

1350 14

60

375

375

315 (4x)

a

DB

C

264528

1560

1705

72,5 264

8 1 65 2

4 5 9 10 3

7

Design 1. plate heat exchanger 2. Electric air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. Connection of main cable 8. Control system 9. Condensate drain (the water trap must be

installed D=28 mm)10. By-pass damper

Shown as left

Shown as right

panel thickness 50 mmUnit weight 190 kgnominal air fl ow 1600 m3/hSupply voltage 3~ 400 vmaximal operating current 14,1 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

a outdoor intake B Supply airC Extract indoor D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

KK2-15-09-v1

Page 67: air Handling Units KompaKt

65

0 400 800 1200 1600 2000

0 0,1 0,2 0,3 0,4 0,5500

400

300

200

100

0

Sfp 0,5

Sfp 0,75

Sfp 1

Sfp 1,25

400 600 800 1000 1200 1400 1600 1800 2000

85

80

75

70

65

60

0oC

-23oC

+5oC

-10oC

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 11,4 14 14,6

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 600x420x96 mm

eC fansInput power at point 100 pa / 1600 m3/h 330 WRotation speed 2540 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 7,5 kWair temperature, Δt 13,8°C* option

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

outdoor

temperature efficiency wet

performance ReCU 1600 p

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1120 m3/h (311 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 1600 peSupply Inlet 35 42 47 50 51 47 43 36 55,7Supply outlet 43 50 55 59 60 57 55 47 64,9Exhaust Inlet 35 42 47 50 51 47 43 36 55,7Exhaust outlet 43 50 55 59 60 58 56 48 65,2Casing 39 45 48 44 44 41 34 27 52,3

Surroundings 31 37 35 32 35 30 24 17 41,7

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 68: air Handling Units KompaKt

66

KompaKt ReCU 2000

200

200

355 (4x)

355 (4x)

1900

1900

350

350

700

700

2050

2050

200

200

900

900

240

240

80

80

6

6

9

9

8

8

3

3

1

1

7

7

4

4

5

5

10

10

11

11

2

2

C

C

D

D

a

a

B

B

ReCU 2000 He

ReCU 2000 HW

BD

C a C a

B D

panel thickness 45 mmUnit weight E/W 325/330 kgnominal air fl ow 2000 m3/hSupply voltage (E) 3~ 400 vSupply voltage (W) 1~ 230 vmaximal operating current (E) 32,1 amaximal operating current (W) 6,4 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as right Shown as leftDesign 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan

7. By-pass damper 8. Condensate drain (the water trap

must be installed D=28 mm) 9. Drop eliminator10. Connection of main cable11. fluid connection tube only for W

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 69: air Handling Units KompaKt

67

500 750 1000 1250 1500 1750 2000 2250

60

58

56

54

52

50

48

46

44

42

40

0oC

-23oC

+5oC

-10oC

0 500 1000 1500 2000 2500

0 0,1 0,2 0,3 0,4 0,5 0,6500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 2000

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 4,1 7,3 9,5

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 29,7 25,2 18,9flow rate, dm3/h 1308 1094 825pressure drop, kpa 6 4 3Connection, ” 1temperature in–out, °C -23/21 -17/20 -8/20

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 610x350x96 mm

eC fansInput power at point 100 pa / 2000 m3/h 410 WRotation speed 2170 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e) Capacity 18 kWair temperature, Δt 26,6°C* option

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1400 m3/h (389 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 2000 HeSupply Inlet 34 47 53 55 55 54 48 42 60,8Supply outlet 41 56 61 64 64 65 62 53 70,7Exhaust Inlet 34 47 53 55 55 54 48 41 60,8Exhaust outlet 41 56 61 64 64 66 62 54 71,0Casing 37 50 53 47 47 46 38 30 56,6

Surroundings 29 42 40 35 38 35 28 20 45,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 70: air Handling Units KompaKt

68

KompaKt ReCU 2000 p

ReCU 2000 pe

a

a

D

D

B

B

C

C

C

C

D

D

a

a

B

B

110

600

600

1350 14

60

375

375

315 (4x)

a

DB

C

264528

1560

1705

72,5 264

8 1 65 2

4 5 9 10 3

7

panel thickness 50 mmUnit weight 190 kgnominal air fl ow 2000 m3/hSupply voltage 3~ 400 vmaximal operating current 16,3 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as left

Shown as right

a outdoor intake C Extract indoorB Supply air D Exhaust air

Design 1. plate heat exchanger 2. Electric air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan 7. Connection of main cable 8. Control system 9. Condensate drain (the water trap

must be installed D=28 mm)10. By-pass damper

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 84 p. 85 p. 88 p. 90 p. 86

KK2-15-09-v1

Page 71: air Handling Units KompaKt

69

0 500 1000 1500 2000 2500

0 0,1 0,2 0,3 0,4 0,5 0,6500

400

300

200

100

0

Sfp 0,5

Sfp 0,75

Sfp 1

Sfp 1,25

400 600 800 1000 1200 1400 1600 1800 2000

85

80

75

70

65

60

0oC

-23oC

+5oC

-10oC

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 11,4 14 14,6

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type CompactDimensions bxhxl 600x420x96 mm

eC fansInput power at point 100 pa / 2000 m3/h 600 WRotation speed 2900 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 9,0 kWair temperature, Δt 13,3°C* option

temperature efficiency wet

performance ReCU 2000 p

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1400 m3/h (389 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 2000 peSupply Inlet 36 47 53 57 56 51 47 43 61,3Supply outlet 44 55 62 66 65 63 60 55 70,9Exhaust Inlet 36 47 53 57 56 51 47 43 61,3Exhaust outlet 44 55 62 66 65 63 61 56 71,0Casing 40 49 53 49 48 44 37 30 56,7

Surroundings 32 41 40 37 39 33 27 20 45,8

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

outdoor

KK2-15-09-v1

Page 72: air Handling Units KompaKt

70

KompaKt ReCU 3000

1770

1770

885

885

600

600

790

790

1800

1800

915

915

350

350

500

500

500

500

350

350

1365

1365

100

100

130

130

395

395

6

6

9

9

8

8 11

11

3

3

1

1

7

7

4

4

2

2

5 10

10

10

105

a

a

D

D

С

С

B

B

ReCU 3000 He

ReCU 3000 HW

BD

C a C a

B D

panel thickness 45 mmUnit weight 540 (390/150) kgnominal air fl ow 3000 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 29,7 amaximal operating current (W) 4,1 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as rightDesign 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan

7. By-pass damper 8. Condensate drain (the water trap

must be installed D=28 mm) 9. Drop eliminator10. Connection of main cable11. fluid connection tube only for W a outdoor intake C Extract indoor

B Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 73: air Handling Units KompaKt

71

900 1200 1500 1800 2100 2400 2700 3000 3300 3600 3900

75

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

0 500 1000 1500 2000 2500 3000 3500 4000 4500

0 0,2 0,4 0,6 0,8 1 1,2500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 3000

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 6,6 8,9 10,9

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 25,4 21,76 18,2flow rate, dm3/h 1117 953 792pressure drop, kpa 4 3 2Connection, ” 1temperature in–out, °C 0/25,1 0/21,5 0/18

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x592x300 mm

eC fansInput power at point 100 pa / 3000 m3/h 480 WRotation speed 2580 rpmprotection level, IEC 34-5 Ip 55

electric air Heater (e)Capacity 18 kWair temperature, Δt 17,8°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2100 m3/h (583 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 3000 HeSupply Inlet 22 31 44 51 52 50 48 44 57,0Supply outlet 28 36 52 59 66 67 63 59 71,1Exhaust Inlet 22 31 44 51 52 51 48 44 57,2Exhaust outlet 28 36 52 59 66 67 63 59 71,1Casing 26 34 45 44 47 46 38 31 52,0

Surroundings 18 26 32 32 38 35 28 21 41,1

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 74: air Handling Units KompaKt

72

KompaKt ReCU 4000

1770

1770

885

885

600

600

790

790

1800

1800

915

915

350

350

500

500

500

500

350

350

1365

1365

100

100

130

130

395

395

6

6

9

9

8

8 11

11

3

3

1

1

7

7

4

4

2

2

5 10

10

10

105

a

a

D

D

С

С

B

B

ReCU 4000 He

ReCU 4000 HW

BD

C a C a

B D

panel thickness 45 mmUnit weight 620 (440/180) kgnominal air fl ow 4000 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 38,4 amaximal operating current (W) 4,1 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as rightDesign 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan

7. By-pass damper 8. Condensate drain (the water trap

must be installed D=28 mm) 9. Drop eliminator10. Connection of main cable11. fluid connection tube only for W a outdoor intake C Extract indoor

B Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 75: air Handling Units KompaKt

73

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

800 1200 1600 2000 2400 2800 3200 3600 4000

75

70

65

60

55

50

45

0oC

-23oC

+5oC

-10oC

performance ReCU 4000

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 5,9 7,5 10

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 48 41,8 35,7flow rate, dm3/h 2114 1833 1555pressure drop, kpa 23 18 13Connection, ” 1temperature in–out, °C -5/30,6 -5/26,1 -5/21,5

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x592x300 mm

eC fansInput power at point 100 pa / 4000 m3/h 800 WRotation speed 2140 rpmprotection level, IEC 34-5 Ip 55

electric air Heater (e)Capacity 24 kWair temperature, Δt 17,8°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2800 m3/h (778 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 4000 HeSupply Inlet 33 42 52 58 58 55 51 46 62,8Supply outlet 40 49 60 67 73 71 65 60 76,3Exhaust Inlet 33 42 52 58 58 56 51 46 63,0Exhaust outlet 40 49 60 67 73 71 65 60 76,3Casing 37 44 52 49 52 48 39 32 57,0

Surroundings 29 36 39 37 43 37 29 22 46,1

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 76: air Handling Units KompaKt

74

1770

1770

885

885

600

600

790

790

1800

1800

915

915

350

350

500

500

500

500

350

350

1365

1365

100

100

130

130

395

395

6

6

9

9

8

8 11

11

3

3

1

1

7

7

4

4

2

2

5 10

10

10

105

a

a

D

D

С

С

B

B

KompaKt ReCU 4500

ReCU 4500 He

ReCU 4500 HW

BD

C a C a

B D

panel thickness 45 mmUnit weight 625 (440/185) kgnominal air fl ow 4500 m3/hSupply voltage 3~ 400 vmaximal operating current (E) 40,2 amaximal operating current (W) 5,9 a paint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as rightDesign 1. plate heat exchanger 2. Electric or water air heater 3. Supply air fi lter 4. Exhaust air fi lter 5. Supply fan 6. Exhaust fan

7. By-pass damper 8. Condensate drain (the water trap

must be installed D=28 mm) 9. Drop eliminator10. Connection of main cable11. fluid connection tube only for W a outdoor intake C Extract indoor

B Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 77: air Handling Units KompaKt

75

70

65

60

55

50

451000 1500 2000 2500 3000 3500 4000 4500 5000

0oC

-23oC

+5oC

-10oC

0 1000 2000 3000 4000 5000 6000

0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6500

400

300

200

100

0

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

performance ReCU 4500

temperature efficiency wetSupply exhaust

Intake temperature, °C -10 -5 0 20Supply temperature, °C 5,7 7,5 10

Hot water air heater (HW)

Water temperature in/out, °C 90/70 80/60 70/50Capacity, kW 46 40 34flow rate, dm3/h 2021 1751 1484pressure drop, kpa 26 21 15Connection, ” 1temperature in–out, °C -5/25 -5/21 -5/17

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x592x300 mm

eC fansInput power at point 100 pa / 4500 m3/h 1150 WRotation speed 2600 rpmprotection level, IEC 34-5 Ip 54

electric air Heater (e)Capacity 24 kWair temperature, Δt 15,8°C* option

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 3150 m3/h (875 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 4500 HeSupply Inlet 38 37 57 58 58 57 51 48 63,9Supply outlet 43 43 61 68 74 74 68 63 78,2Exhaust Inlet 38 37 57 58 58 57 51 48 63,9Exhaust outlet 43 43 61 68 74 74 68 63 78,2Casing 40 39 55 50 52 50 40 34 58,5

Surroundings 32 31 42 38 43 39 30 24 47,0

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

temperature efficiency wette

mp.

effi

cien

cy (%

)

application: 21°C, RH 45% indoor

outdoor

air flow rate (m3/h)

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5 and electric air heater.

KK2-15-09-v1

Page 78: air Handling Units KompaKt

76

KompaKt ReCU 7000

ReCU 7000 HW

12001500

750

600

600

1520

125

1140 750

6 3 17 4 2 85

a

D

С

B

9

BD

C a C a

B D

panel thickness 45 mmUnit weight 800 (260/260/280) kgnominal air fl ow 7000 m3/hSupply voltage 3~ 400 vmaximal operating current 9,6 apaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Shown as leftShown as right

Design1. plate heat exchanger2. Water air heater3. Supply air fi lter4. Exhaust air fi lter5. Supply fan6. Exhaust fan7. Condensate drain8. fluid connection tube9. Connection of main cable

a outdoor intake C Extract indoorB Supply air D Exhaust air

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

accessories

the

phot

o is

inte

nded

for i

nfor

mat

iona

l pur

pose

s on

ly,

exac

t det

ails

may

var

y.

p. 83 p. 85 p. 88 p. 90 p. 86 p. 89 p. 92

KK2-15-09-v1

Page 79: air Handling Units KompaKt

77

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

2000 3000 4000 5000 6000 7000 8000 9000 10 000

80

75

70

65

60

55

50

0oC

-23oC

+5oC

-10oC

performance ReCU 7000

temperature efficiency wetSupply exhaust

Intake temperature, °C -15 -10 -5 0 20Supply temperature, °C 7,7 9,2 10,4 11,9

Hot water air heater (HW)

Water temperature in/out, °C 80/60Capacity, kW 35,4flow rate, dm3/h 1560pressure drop, kpa 7,6Connection, ” 3/4temperature in–out, °C 6/21

air filters. Supply / exhaustfilter class En779:2011 m5/f7*type Bag filterDimensions bxhxl 592x592-12x500 mmQuantity 2 pcs.

eC fansInput power at point 100 pa / 7000 m3/h 1400 WRotation speed 2040 rpmprotection level, IEC 34-5 Ip 54* option

temperature efficiency wet

air flow rate (m3/h)

tem

p. e

ffici

ency

(%)

application: 21°C, RH 45% indoor

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 4900 m3/h (1361 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

ReCU 7000 HWSupply Inlet 27 38 53 56 54 49 46 46 60,1Supply outlet 35 45 61 70 73 69 65 59 76,3Exhaust Inlet 27 38 53 56 54 49 46 45 60,0Exhaust outlet 36 46 63 72 75 71 68 64 78,5Casing 32 41 54 52 53 48 41 35 58,5

Surroundings 24 33 41 40 44 37 31 25 47,2

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

outdoor

all data can be calculated in KompaKt selection software. If data of performance do not correspond to data in selection software, please refer to data shown in software.

air flow rate (m3/s)

Stat

ic p

ress

ure

(pa)

air flow rate (m3/h)

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5.

KK2-15-09-v1

Page 80: air Handling Units KompaKt

78

L

BxH

3

2

1

KompaKt otK 700

performance otK 700pe-aC

type of supply air handling units

Dimensions BxHxL, mm

thermal and sound

insulation, mm

Ducts connection,

mmSupply

voltage, vfan input

power aC, W

air heater capacity,

kW

maximal operating current, a

Δt, °C filter m5

With electric heaterotK 700p-e3 440x350x850 45 ø 200 1~230 165 3,0 13,8 13 345x287x46otK 700p-e6 440x350x850 45 ø 200 3~400 165 6,0 9,4 25 345x287x46otK 700p-e9 440x350x850 45 ø 200 3~400 165 9,0 13,8 38 345x287x46

• Height is only 350 mm (for OTK 3000 and OTK 4000 – 545 mm) – easy to choose the place for installation.

• Units are complemented with fastening profiles and vib ration absorbing holders.

• Safe and handy design of removable cover ensures easy fi xing of cover at different opening levels for performing mainte-nance and service inspection.

panel thickness 45 mmUnit weight 32,5 kgnominal air flow 700 m3/hpaint color RaL 7035Control panel KomfovEnt C3 / C3.1

• KOMPAKT OTK air handling units have integrated control sys-tem C3.

• Control panel may be installed in any user-convenient place.• Control panel display enables to set the operation para meters

of the unit and monitor them.• There is a possibility to complement and control the duct

mounted cooling section.

Komfovent KompaKt otK unitsfalse ceiling supply air handling units. Capacity range from 170 to 4 200 m3/h.

fan

pow

er*

(W)

1, 2, 3 – speed; * – fan power is shown for one fan motor. Performance data: filter M5. Correction factor for f7 class filter approximately – 70 pa at 700 m3/h.

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

the photo is intended for informational purposes only, exact details may vary.

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 633 m3/h (176 l/s), 168 pa.octave band mid-frequency, Hz 63 125 250 500 1 000 2 000 4 000 8 000 total

otK 700 peSupply Inlet 32 45 54 58 61 59 54 46 65,1Supply outlet 35 48 57 62 64 63 59 51 68,8Casing 29 40 46 43 44 41 33 25 50,4

Surroundings 21 32 33 31 35 30 23 15 39,4

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 81: air Handling Units KompaKt

79

L

BxH

L

BxH

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35

3

2

1

KompaKt otK 1200

performance otK 1200pe-aC

type of supply air handling units

Dimensions BxHxL, mm

thermal and sound

insulation, mm

Ducts connection,

mm

Supply voltage,

vfan input

power aC, Wair heater

capacity, kW

maximal operating current, a

Δt, °C filter m5

With electric heaterotK 1200p-e9 690x350x850 45 ø 250 3~400 290 9,0 14,3 22 558x287x46otK 1200p-e15 690x350x850 45 ø 250 3~400 290 15,0 23,0 37 558x287x46With hot water heaterotK 1200pW 690x350x850 45 ø 250 1~230 290 – 1,8 558x287x46

panel thickness 45 mmUnit weight 46 kgnominal air flow 1200 m3/hpaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Hot water air heater (HW)

Water temperature in/out, °C 70/50 80/60 90/70Capacity, kW 16,2 18,5 20,55flow rate, dm3/h 707 812 907pressure drop, kpa 2,9 3,6 4,28Connection, ” 1/2temperature in–out, °C -30/9,32 -30/15 -30/20

fan

pow

er*

(W)

1, 2, 3 – speed; * – fan power is shown for one fan motor. Performance data: filter M5. Correction factor for pW approximately 30 pa at 1200 m3/h. Correction factor for f7 class filter approximately – 30 pa at 1200 m3/h.

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

the photo is intended for informational purposes only, exact details may vary.

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 1103 m3/h (306 l/s), 173 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

otK 1200 peSupply Inlet 39 50 58 60 65 63 60 56 69,2Supply outlet 42 53 61 64 69 67 66 62 73,5Casing 35 44 49 44 47 44 37 30 53,3

Surroundings 27 36 36 32 38 33 27 20 42,5

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

KK2-15-09-v1

Page 82: air Handling Units KompaKt

80

L

BxH

L

BxH

3

2

1

KompaKt otK 2000

performance otK 2000pe-aC

panel thickness 45 mmUnit weight 73 kgnominal air flow 2000 m3/hpaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Hot water air heater (HW)

Water temperature in/out, °C 70/50 80/60 90/70Capacity, kW 28,6 32,4 34,2flow rate, dm3/h 1253 1423 1511pressure drop, kpa 9,82 12,03 13,07Connection, ” 1/2temperature in–out, °C -30/12 -30/17 -30/20

type of supply air handling units

Dimensions BxHxL, mm

thermal and sound

insulation, mm

Ducts connection,

mmSupply

voltage, v

fan input power,

Wair heater

capacity, kW

maximal operating current, a

Δt, °C filter m5

With electric heaterotK 2000p-e15 1000x350x865 45 700x250 3~400 2x290 15,0 24,2 22 858x287x46otK 2000p-e22.5 1000x350x865 45 700x250 3~400 2x290 22,5 35,1 33 858x287x46With hot water heaterotK 2000pW 1000x350x865 45 700x250 1~230 2x290 – 12,5 858x287x46

fan

pow

er*

(W)

1, 2, 3 – speed; * – fan power is shown for one fan motor. Performance data: filter M5. Correction factor for pW approximately 30 pa at 2000 m3/h. Correction factor for f7 class filter approximately – 70 pa at 2000 m3/h.

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

the photo is intended for informational purposes only, exact details may vary.

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2000 m3/h (556 l/s), 232 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

otK 2000 pe-aCSupply Inlet 43 52 59 63 68 65 63 58 71,8Supply outlet 46 55 62 66 71 70 68 63 75,7Casing 38 46 50 46 49 45 38 31 54,9

Surroundings 30 38 37 34 40 34 28 21 44,2

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 83: air Handling Units KompaKt

81

L

BxH

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

KompaKt otK 3000

performance otK 3000pW-eC

panel thickness 45 mmUnit weight 120 kgnominal air flow 3000 m3/hpaint color RaL 7035Control panel KomfovEnt C3 / C3.1

type of supply air handling units

Dimensions BxHxL, mm

thermal and sound insulation, mm

Ducts connection, mm

Supply voltage, v

fan input power eC, W

maximal operating current, a filter m5

With hot water heaterotK 3000pW 1005x545x1217 45 600 x 400 3~400 990 2,2 450 x 480 x 96(x2)

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

the photo is intended for informational purposes only, exact details may vary.

Hot water air heater (HW)

Water temperature in/out, °C 60/40 70/50 80/60 90/70Capacity, kW 51,4 51,4 51,4 51,4flow rate, dm3/h 2239 2248 2257 2267pressure drop, kpa 4,8 5,4 4,5 4,5Connection, ” 1temperature in–out, °C -30/20 -30/20 -30/20 -30/20Safety on capacity, % 13 26 36 45

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2100 m3/h (583 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

otK 3000 pWSupply Inlet 29 40 54 58 58 61 58 51 65,5Supply outlet 33 42 58 63 70 71 68 62 75,2Casing 27 35 47 43 47 45 37 30 52,1

Surroundings 19 27 34 31 38 34 27 20 41,0

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5.

KK2-15-09-v1

Page 84: air Handling Units KompaKt

82

L

BxH

Sfp 1,25

Sfp 0,75

Sfp 0,5

Sfp 1

KompaKt otK 4000

performance otK 4000pW-eC

panel thickness 45 mmUnit weight 125 kgnominal air flow 4000 m3/hpaint color RaL 7035Control panel KomfovEnt C3 / C3.1

Hot water air heater (HW)

Water temperature in/out, °C 60/40 70/50 80/60 90/70Capacity, kW 68,5 68,5 68,5 68,5flow rate, dm3/h 2985 2997 3009 3023pressure drop, kpa 8,0 7,9 7,7 7,5Connection, ” 1temperature in–out, °C -30/20 -30/20 -30/20 -30/20Safety on capacity, % 5 18 30 40

type of supply air handling units

Dimensions BxHxL, mm

thermal and sound

insulation, mm

Ducts connection,

mmSupply

voltage, vfan input power

eC, W

maximal operating current, a

Δp Water,

kpa filter m5With hot water heaterotK 4000pW 1005x545x1217 45 600 x 400 3~400 1000 2,3 5,1 450 x 480 x 96(x2)

air flow rate (m3/s)

air flow rate (m3/h)

Stat

ic p

ress

ure

(pa)

the photo is intended for informational purposes only, exact details may vary.

acoustic Dataa-weighted sound power levels Lwa, dB(a). operation point: 2800 m3/h (778 l/s), 100 pa.octave band mid-frequency, Hz 63 125 250 500 1000 2000 4000 8000 total

otK 4000 pWSupply Inlet 37 46 57 62 62 62 57 50 67,7Supply outlet 41 49 60 68 74 71 66 60 77,0Casing 34 41 49 47 49 46 36 29 54,3

Surroundings 26 33 36 35 40 35 26 19 43,3

a-weighted sound pressure levels Lpa, dB(a), 10 m2 normally isolated room, distance from casing – 3 m.

the sound data table indicates the sound power level Lwa which should not be confused with the sound pressure level Lpa.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

p[kW]= Sfp[kW/(m3/s)] · v[m3/s]; SFP is shown for one fan. performance data: filter m5.

KK2-15-09-v1

Page 85: air Handling Units KompaKt

83

LB

H

accessories

Supply and exhaust filters99,9% (in amount) of particulates in the outdoor air are smaller than 1 µm. By mass the mentioned particulates account for only 30% of all airborne dust. thus, if the outdoor air is supplied to the public and dwelling houses, to ensure air purity required by hygienic standards, fi lters of EU5-EU7 class are enough. EU4 and EU5 class fi lters are used for fi ltering the exhaust air in air han-dling units. air fi ltering protects air handling equipment against pollution, extends its service life. therefore dirty fi lters should be replaced on a timely basis to assure comfortable conditions in the premises and protection of air handling units against breaka ge. a light on the control panel indicates the fi lter clog-ging. Usually air fi lters should be replaced not less than twice per year: after the end of the heating season and in autumn.

filter classifi cation and standardsfilters applied in the air handling units are classifi ed according to EURovEnt 4/9 (CEn En 779 and CEn En 1882) system.

types of fi lters1. m5 (standard fi lter) or f7 (optional) class fi lters for supply air

fi lter. very compact, but are distinguished by extra large fi lte-ring surface. Large fi ltering surface provides long-life perfor-mance and low pressure losses (low pressure losses reduce power consumption). the fi lters from glass fi ber material and a paper fi lter case. Ecologically clean materials allow just bur-ning clogged air fi lters.

2. Bag fi lters are used in bigger size units: m5 (or f7) classes for supply and for exhaust air.

Unit size filter m5, f7 dimensions BxHxL, mm

REGo 400 410x200x46REGo 500 540x260x46REGo 500 U 545x300x46REGo 600 U RHp 500x280x46REGo 700 540x260x46REGo 700 p 320x360x46REGo 900 U 800x400x46 REGo 1200 U 800x400x46 REGo 1200 p 410x420x46REGo 1400 U 800x400x46REGo 1600 U 800x450x46REGo 2000 U 800x450x46REGo 2000 p 560x420x96REGo 2500 U 800x450x46REGo 3000 U 525x510x46 (x2)REGo 4000 U 525x510x46 (x2)REGo 4500 U 525x510x46 (x2)REGo 7000 592x592-12x500 (x2)

RECU 400 300x195x46RECU 700 400x235x46RECU 700 Cf 390x300x46RECU 900 400x235x46RECU 1200 592x287-6x360RECU 1600 v 592x287-6x360RECU 1600 H 610x350x96RECU 1600 p 600x420x96RECU 2000 610x350x96RECU 2000 p 600x420x96RECU 3000 592x592-6x300RECU 4000 592x592-6x300RECU 4500 592x592-6x300RECU 7000 592x592-12x500 (x2)

Unit size filter dimensions BxHxL, mm m5 f7

otK 700 345x287x46 + –otK 1200 558x287x46 + –otK 2000 858x287x46 + –otK 3000 450x480x92 (x2) + +otK 4000 450x480x92 (x2) + +

Page 86: air Handling Units KompaKt

84

B

H D

L

DD

Hot water duct air heatersHot water duct air heaters are off ered for KompaKt REGo and RECU units. Heaters are mounted on the outside of the unit in any user-convenient place. there is heater control possibility in automatic control system.

Design:• Galvanized sheet steel casing.• Copper pipes for heat transfer fl uid (water).• Pacing between profi led aluminum plates is 3 mm (standard

spacing). optional threaded connection for freezing protection alarm sensor (to be specifi ed in the order form).

Capacitive Constraints• Maximum operating pressure – 10 bar.• Maximum water temperature +100°C.• Maximum airfl ow velocity in the heater 3 m/s.

Inlet air temperature, °C

Water temperature in/out ºC60/40 70/50 80/60 90/70

-25 1.19 1.42 1.61 1.82-20 1.15 1.34 1.52 1.50-15 1.06 1.24 1.44 1.63-10 0.98 1.16 1.35 1.53

-5 0.89 1.08 1.27 1.450 0.81 0.98 1.18 1.37

+5 0.71 0.90 1.10 1.29+10 0.63 0.82 1.00 1.19+15 0.53 0.73 0.92 1.11+20 0.44 0.63 0.82 1.02

note: such calculation is approximate.

* In case a duct water heater with diff erent water parameters is needed, a temperature from the table has to be chosen and heater‘s capacity has to be multiplied by an appropriate coeffi cient (see right).

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Hot water duct heater type

Dimensions, mm tubes connectionD B H L

DH-160 160 330 290 270 ½"DH-200 200 360 320 270 ½"DH-250 250 420 380 270 ½"DH-315 315 (315m) 510 470 270 ½"DH-355 355 600 526 270 ½"

air handling unit size

Water temperature in/out 80/60°C*

Duct heater Capacity, kW

air temperature in/out, °C

air pressure drop, pa

flow rate, dm3/h

Water pressure drop, kpa

REGo 700 DH-250 4.5 8 / 26 14 196 7.0REGo 1200 p DH-315 7.3 7 / 25 34 321 10.0REGo 2000 p DH-355 12.3 7 / 25 55 540 3.2RECU 400 v DH-160 2.7 8 / 27 11 117 2.2RECU 400 H DH-200 2.7 8 / 27 11 117 2.2RECU 700 v DH-200 3.1 7 / 20 25 144 2.8RECU 700 H DH-250 3.1 7 / 20 14 144 3.6RECU 900 v DH-200 4.0 7 / 20 40 180 4.5RECU 900 H DH-250 4.0 7 / 20 21 180 5.6RECU 1600 p DH-315m 9.7 7 / 25 38 432 2.1RECU 2000 p DH-315m 12.3 7 / 25 55 540 3.2

KK2-15-09-v1

Page 87: air Handling Units KompaKt

85

8

8

7

7

6 5 4 1

1

2

3

9

note: for more detailed description and selection, pipework package selection program may be used. It can be downloaded from www.komfovent.com

pipework packagepipework package Unit ppU is used for the adjustment of thermal power of water heaters, i.e. for the adjustment of thermal media debit via the heater and respectfully, the temperature of supplied air. fully assembled pipework package is available to each size of the air handing unit where hot water heater is used.

air fl ow Design:1. Stop valve2. Return valve3. throttling valve4. filter5. Control valve6. Circulation pump7. manometer8. thermometer9. actuator

air handling unit size

Water temperature in/out ºCHeater type 60/40 °C 70/50 °C 80/60 °C 90/70 °C

REGo 400 Duct heater DH-160 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20REGo 500 v Duct heater DH-250 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20REGo 500 H Duct heater DH-200 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20REGo 700 Duct heater DH-250 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20REGo 900 U Integrated heater ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20REGo 1200 p Duct heater DH-315 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20REGo 1200 U Integrated heater ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20REGo 1400 U Integrated heater ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20REGo 1600 U Integrated heater ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20REGo 2000 U Integrated heater ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40REGo 2000 p Duct heater DH-355 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40REGo 2500 U Integrated heater ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40REGo 3000 U Integrated heater ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 REGo 4000 U Integrated heater ppU-2.5-25_40 ppU-2.5-25_40 ppU-4.0-25_60 ppU-4.0-25_60REGo 4500 U Integrated heater ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60REGo 7000 Integrated heater ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60RECU 400 v Duct heater DH-160 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20RECU 400 H Duct heater DH-200 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20RECU 700 v Duct heater DH-200 ppU-1.0-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20RECU 700 H Duct heater DH-250 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-0.63-25_20RECU 900 v Duct heater DH-200 ppU-1.0-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-1.0-25_20RECU 900 H Duct heater DH-250 ppU-1.0-25_20 ppU-0.63-25_20 ppU-0.63-25_20 ppU-1.0-25_20RECU 1200 Integrated heater ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.0-25_20 ppU-1.6-25_40RECU 1600 Integrated heater ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40RECU 1600 p Duct heater DH-315 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40 ppU-1.6-25_40RECU 2000 Integrated heater ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40RECU 2000 p Duct heater DH-315 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40RECU 3000 Integrated heater ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60RECU 4000 Integrated heater ppU-6.3-25_60 ppU-6.3-25_60 ppU-6.3-25_60 ppU-4.0-25_60RECU 4500 Integrated heater ppU-10-25_80 ppU-6.3-25_60 ppU-6.3-25_60 ppU-6.3-25_60RECU 7000 Integrated heater ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60otK 1200 Integrated heater ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40 ppU-2.5-25_40otK 2000 Integrated heater ppU-6.3-25_60 ppU-4.0-25_60 ppU-4.0-25_60 ppU-4.0-25_60otK 3000 Integrated heater ppU-10-25_80 ppU-6.3-25_60 ppU-6.3-25_60 ppU-6.3-25_60otK 4000 Integrated heater ppU-10-25_80 ppU-10-25_80 ppU-10-25_80 ppU-10-25_80

KK2-15-09-v1

Page 88: air Handling Units KompaKt

86

Silencersto ensure the normal noise level in the system and pre mises, si-lencers are used. there are circular and rectangular silencers of standard dimensions. appropriate silencer can be selected using the online selection program, which can be found on www.komfovent.com.

StS-C-B-H-LC – baffler’s codeB – silencer’s widthH – silencer’s heightL – silencer’s length

aGS-d-h-Ld – connecting diameterh – insulation’s thicknessL – silencer’s length

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Silencers for ReGo air handling units

Unit size Silencer type

REGo 400

a aGS-160-50-600-mB aGS-160-50-900-mC aGS-160-50-900-mD aGS-160-50-600-m

REGo 500 v

a aGS-250-50-600-mB aGS-250-50-900-mC aGS-250-50-900-mD aGS-250-50-600-m

REGo 500 HREGo 500 U

a aGS-200-50-600-mB aGS-200-50-900-mC aGS-200-50-900-mD aGS-200-50-600-m

REGo 600 U RHp

a aGS-200-50-600-mB aGS-200-50-900-mC aGS-200-50-900-mD aGS-200-50-600-m

REGo 700

a aGS-250-50-600-mB aGS-250-50-900-mC aGS-250-50-900-mD aGS-250-50-600-m

REGo 900 UREGo 1200 U / 1200 p REGo 1400 UREGo 2000 p

a aGS-315-100-900-mB aGS-315-100-1200-mC aGS-315-100-1200-mD avSGS-355-1200-S

REGo 1600 Uv

a StS-IvR3Ba-600-300-700-SB StS-IvR3Ba-600-300-1250-SC StS-IvR3Ba-600-300-1250-SD StS-IvR3Ba-600-300-700-S

REGo 1600 UH

a StS-IvR3Ba-400-400-700-SB StS-IvR3Ba-400-400-1250-SC StS-IvR3Ba-400-400-1250-SD StS-IvR3Ba-400-400-700-S

REGo 2000 Uv

a StS-IvR3Ba-600-300-700-SB StS-IvR3Ba-600-300-1250-SC StS-IvR3Ba-600-300-1250-SD StS-IvR3Ba-600-300-700-S

REGo 2000 UH

a StS-IvR3Ba-400-400-700-SB StS-IvR3Ba-400-400-1250-SC StS-IvR3Ba-400-400-1250-SD StS-IvR3Ba-400-400-700-S

Unit size Silencer type

REGo 2500 Uv

a StS-IvR3Ba-800-300-700-SB StS-IvR3Ba-800-300-1250-SC StS-IvR3Ba-800-300-1250-SD StS-IvR3Ba-800-300-700-S

REGo 2500 UH

a StS-IvR3Ba-600-400-700-SB StS-IvR3Ba-600-400-1250-SC StS-IvR3Ba-600-400-1250-SD StS-IvR3Ba-600-400-700-S

REGo 3000 Uv

a StS-IvR3Ba-600-400-700-SB StS-IvR3Ba-600-400-1250-SC StS-IvR3Ba-600-400-1250-SD StS-IvR3Ba-600-400-700-S

REGo 3000 UH

a StS-IvR3Ba-600-500-700-SB StS-IvR3Ba-600-500-1250-SC StS-IvR3Ba-600-500-1250-SD StS-IvR3Ba-600-500-700-S

REGo 4000 Uv

a StS-IvR3Ba-800-400-700-SB StS-IvR3Ba-800-400-1250-SC StS-IvR3Ba-800-400-1250-SD StS-IvR3Ba-800-400-700-S

REGo 4000 UH

a StS-IvR3Ba-800-500-700-SB StS-IvR3Ba-800-500-1250-SC StS-IvR3Ba-800-500-1250-SD StS-IvR3Ba-800-500-700-S

REGo 4500 Uv

a StS-IvR3Ba-1000-400-700-SB StS-IvR3Ba-1000-400-1250-SC StS-IvR3Ba-1000-400-1250-SD StS-IvR3Ba-1000-400-700-S

REGo 4500 UH

a StS-IvR3Ba-800-500-700-SB StS-IvR3Ba-800-500-1250-SC StS-IvR3Ba-800-500-1250-SD StS-IvR3Ba-800-500-700-S

REGo 7000

a StS-IvR3Ba-1200-600-700-SB StS-IvR3Ba-1200-600-1250-SC StS-IvR3Ba-1200-600-1250-SD StS-IvR3Ba-1200-600-700-S

KK2-15-09-v1

Page 89: air Handling Units KompaKt

87

Unit size Silencer type

otK 700pa aGS-200-50-600-mB aGS-200-50-900-m

otK 1200pa aGS-250-50-900-mB aGS-250-50-1200-m

otK 2000pa StS-IvR3Ba-800-250-700-SB StS-IvR3Ba-800-250-1250-S

otK 3000pa StS-IvR3Ba-600-400-700-SB StS-IvR3Ba-600-400-1250-S

otK 4000pa StS-IvR3Ba-800-400-700-SB StS-IvR3Ba-800-400-1250-S

Silencers for otK air handling units

Silencers for ReCU air handling units

a outdoor intake B Supply air C Extract indoor D Exhaust air

note: acoustic countable data is: 50 dB(a) for exhaust outlet and 40 dB(a) for supply outlet. for other parameters use our selection program from www.komfovent.com.

Unit size Silencer type

RECU 400v

a aGS-160-50-600-mB aGS-160-50-900-mC aGS-160-50-900-mD aGS-160-50-600-m

RECU 400H

a aGS-200-50-600-mB aGS-200-50-900-mC aGS-200-50-900-mD aGS-200-50-600-m

RECU 700v

a aGS-200-50-600-mB aGS-200-50-900-mC aGS-200-50-900-mD aGS-200-50-600-m

RECU 700H

a aGS-250-50-600-mB aGS-250-50-900-mC aGS-250-50-900-mD aGS-250-50-600-m

RECU 900v

a aGS-200-50-600-mB aGS-200-50-900-mC aGS-200-50-900-mD aGS-200-50-600-m

RECU 900H

a aGS-250-50-900-mB aGS-250-50-1200-mC aGS-250-50-1200-mD aGS-250-50-900-m

RECU 1200v

a aGS-250-50-900-mB aGS-250-50-1200-mC aGS-250-50-1200-mD aGS-250-50-900-m

RECU 1200H

a aGS-315-100-900-mB aGS-315-100-1200-mC aGS-315-100-1200-mD aGS-315-100-900-m

RECU 1600vRECU 1600p

a aGS-315-100-900-mB aGS-315-100-1200-mC aGS-315-100-1200-mD aGS-315-100-900-m

RECU 1600H

a aGS-355-100-900-mB aGS-355-100-1200-mC aGS-355-100-1200-mD aGS-355-100-900-m

Unit size Silencer type

RECU 2000

a aGS-355-100-900-mB aGS-355-100-1200-mC aGS-355-100-1200-mD aGS-355-100-900-m

RECU 2000 p

a aGS-315-100-900-mB aGS-315-100-1200-mC aGS-315-100-1200-mD aGS-315-100-900-m

RECU 3000

a StS-IvR3Ba-600-500-700-SB StS-IvR3Ba-600-500-1250-SC StS-IvR3Ba-600-500-1250-SD StS-IvR3Ba-600-500-700-S

RECU 4000

a StS-IvR3Ba-800-500-700-SB StS-IvR3Ba-800-500-1250-SC StS-IvR3Ba-800-500-1250-SD StS-IvR3Ba-800-500-700-S

RECU 4500

a StS-IvR3Ba-800-500-700-SB StS-IvR3Ba-800-500-1250-SC StS-IvR3Ba-800-500-1250-SD StS-IvR3Ba-800-500-700-S

RECU 7000

a StS-IvR3Ba-1200-600-700-SB StS-IvR3Ba-1200-600-1250-SC StS-IvR3Ba-1200-600-1250-SD StS-IvR3Ba-1200-600-700-S

KK2-15-09-v1

Page 90: air Handling Units KompaKt

88

motorized closing dampers

to protect air handling units from freezing or other external factors motorized closing dampers must be used. they are mounted on sup-ply and exhaust vents. there is dampers control possibility in auto-matic control system.

Control system actuator

Lf24 Lm24aKomfovEnt C3, C5 + +

note:Lf damper actuator is with spring-return Lm damper actuator is without spring-return

Summer Cassette for plate Heat exchangerCassette is used in summer if air is not conditioned by other equip-ment. It can be used in units without air by-pass damper: KompaKt RECU 400, RECU 700, RECU 900, RECU 1200. Unusable for counterfl ow plate heat exchangers.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

Unit size DamperREGo 400 aGUJ-m-160REGo 500 v aGUJ-m-250REGo 500 H aGUJ-m-200REGo 500 U aGUJ-m-200REGo 600 U RHp aGUJ-m-200REGo 700 aGUJ-m-250REGo 900 U aGUJ-m-315REGo 1200 U aGUJ-m-315REGo 1200 p aGUJ-m-315REGo 1400 U aGUJ-m-315REGo 1600 UH SRU-m-300x400REGo 1600 Uv SRU-m-400x300REGo 2000 UH SRU-m-300x400REGo 2000 Uv SRU-m-400x300REGo 2000 p aGUJ-m-355REGo 2500 UH SRU-m-300x400REGo 2500 Uv SRU-m-400x300REGo 3000 UH SRU-m-400x500REGo 3000 Uv SRU-m-500x400REGo 4000 UH SRU-m-400x500REGo 4000 Uv SRU-m-500x400REGo 4500 UH SRU-m-400x500REGo 4500 Uv SRU-m-500x400REGo 7000 SRU-m-1200x600

Unit size DamperRECU 400 v aGUJ-m-160RECU 400 H aGUJ-m-200RECU 700 v aGUJ-m-200RECU 700 H aGUJ-m-250RECU 900 v aGUJ-m-200RECU 900 H aGUJ-m-250RECU 1200 v aGUJ-m-250RECU 1200 H aGUJ-m-315RECU 1600 v aGUJ-m-315RECU 1600 H aGUJ-m-355RECU 1600 p aGUJ-m-315RECU 2000 aGUJ-m-355RECU 2000 p aGUJ-m-315RECU 3000 SRU-m-600x500RECU 4000 SRU-m-600x500RECU 4500 SRU-m-600x500RECU 7000 SRU-m-1200x600otK 700 p aGUJ-m-200otK 1200 p aGUJ-m-250otK 2000 p SRU-m-700x250otK 3000 p SRU-m-600x400otK 4000 p SRU-m-600x400

KK2-15-09-v1

Page 91: air Handling Units KompaKt

89

B L

H

accessories for unit outside installationKomfovEnt KompaKt air handling units can be installed out-side due to thick casing insulation and easy mounting. protective optional accessories should be used if unit is for out-side installation: roof, base frame, legs, grills, supply and exhaust hoods.

Standard base frame for air handling units

note: Standard frame is 100 mm height, without feet, painted RaL 7035.

air handling unit size Roof code Dimensions BxLREGo (500-700) H 712200023 910x1210REGo (900-1200-1400) U 712200264 1180x1555REGo (1600-2000-2500) UH 712232873 1165x1700REGo (3000-4000-4500) UH 712200271 1345x2400REGo 7000 H 712200252 1790x2050RECU 400 H 712232869 505x1300RECU (700-900) H 712237971 605x1470RECU 700 HCf 712200247 590x1700RECU 1200 H 712232870 855x1870RECU (1600-2000) H 712232868 1000x2110RECU (3000-4000-4500) H 712232875 1260x2700RECU 7000 H 712200253 1790x2800

air handling unit size type of hood for supply air

type of hood for exhaust air

REGo 500 H G-350x350 aHIa-200REGo 700 H G-350x350 aHIa-250REGo (900-1200-1400) U G-600x430 aHIa-315REGo (1600-2000-2500) U G-600x430 G-600x430REGo (3000-4000-4500) U G-540x1115 G-540-1115_10REGo 7000 H v-40-34-00.000.2 v-40-34-00.000RECU 400 H G-270x270 aHIa-200RECU (700-900) H G-350x350 aHIa-250RECU 700 HCf G-350x350 aHIa-250RECU 1200 H G-600x430 aHIa-315RECU (1600-2000) H G-600x430 aHIa-355RECU (3000-4000-4500) H G-700x600 G-700x600RECU 7000 H v-40-34-00.000.2 v-40-34-00.000

air handling unit size frame type Dimensions BxHxLREGo 400 H SSK-07.001a 460x100x640REGo (500-700) v SSK-08.001a 585x100x1060REGo (500-700) H SSK-09.001a 585x100x930REGo 500 U SSK-10.001a 590x100x1115REGo (900-1200-1400) U SSK-15.001a 840x100x1340REGo (1600-2000-2500) U SSK-12.001a 850x100x1500REGo (3000-4500) U SSK-13.001a 1100x100x2100RECU 400 H SSK-00.001a 340x100x1000RECU (700-900) H SSK-01.001a 440x100x1170RECU 700 HCf SSK-14.001a 390x100x1500RECU 1200 H SSK-02.001a 650x100x1670RECU (1600-2000) H SSK-03.001a 650x100x1900RECU (3000-4000-4500) SSK-04.001a 1100x100x2400

KK2-15-09-v1

Page 92: air Handling Units KompaKt

90

BxH

B1xH

1

L

* With drop eliminator.

Water and direct evaporation air coolersair cooler is mounted on the outside of the unit.Casing of the cooler section corresponds to the unit’s ca sing: galvanized steel sheets with internal mineral wool insulation of 45 mm thickness. Cooler section is assembled with a drop sepa-rator and a drain tray. Cooler control function is provided in the automatic control system of the unit.Internal fl uid – R410a, water 7/12.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

air handling unit size

Cooler’s type

Supply air volume,

m³/h

air temper.

in/out, ºCCapacity,

kW

air pressure

drop, pa*

fluid pressure loss, kpa

BxHxL, mm

B1xH1, mm

tubes connections

Weight, kg

REGo/RECU400DCf-0,4-2 400 30/18 2,38 48 5,47 605x550x390 300x400 ½“ /22 mm 37DCW-0,4-3 400 30/18 2,7 34 15,8 505x550x390 300x400 ½“ 32

REGo 500DCf-0,5-3 500 30/18 2,97 43 4,91 600x550x390 400x300 ½“ /22 mm 38DCW-0,5-3 500 30/18 3,4 30 29,5 600x550x390 400x300 ½“ 35

REGo/RECU 700DCf-0,7-4 700 30/18 4,16 53 2,57 705x610x390 500x400 ½“ /22 mm 46DCW-0,7-5 700 30/18 4,7 29 11,2 705x610x390 500x400 ½“ 41

REGo/RECU 900DCf-0,9-5 900 30/18 5,3 64 3,89 705x610x390 500x400 ½“ /22 mm 46DCW-0,9-6 900 30/18 6,0 36 3,7 705x610x390 500x400 ¾“ 45

REGo/RECU 1200DCf-1,2-7 1200 30/18 7,13 93 6,11 705x610x390 500x400 ½“ /22 mm 46DCW-1,2-8 1200 30/18 8,1 60 6,3 705x610x390 500x400 3/4“ 45

REGo 1400DCf-1,4-8 1400 30/18 8,3 40 8,3 705x610x390 500x400 ½“ /22 mm 46DCW-1,4-9 1400 30/18 9,4 78 8,3 705x610x390 500x400 ¾“ 45

REGo/RECU 1600DCf-1,6-10 1600 30/18 9,51 118 11,17 755x610x420 500x400 ½“ /22 mm 49DCW-1,6-11 1600 30/18 10,7 83 11,2 755x610x420 500x400 ¾“ 46

REGo/RECU 2000DCf-2,0-12 2000 30/18 11,89 106 2,95 920x610x420 700x400 ½“ /22 mm 56DCW-2,0-13 2000 30/18 13,4 78 20,6 920x610x420 700x400 ¾“ 56

REGo 2500DCf-2,5-15 2500 30/18 14,86 92 3,81 1080x670x420 800x400 ½“ /28 mm 68DCW-2,5-17 2500 30/18 16,9 55 28,3 1080x670x420 800x400 1“ 65

REGo/RECU 3000DCf-3,0-18 3000 30/18 17,83 112 5,3 1080x670x420 800x400 ½“ /28 mm 68DCW-3,0-20 3000 30/18 20,2 102 11 1080x670x420 800x400 1“ 69

REGo/RECU 4000DCf-4,0-24 4000 30/18 23,77 101 8,24 1220x730x420 900x500 ₇⁄₈”/28 mm 80DCW-4,0-27 4000 30/18 27 106 17,1 1220x730x420 900x500 1“ 82

REGo/RECU 4500DCf-4,5-27 4500 30/18 26,74 115 8,16 1220x790x420 900x600 ₇⁄₈”/28 mm 84DCW-4,5-30 4500 30/18 30,3 108 31,8 1220x790x420 900x600 1“ 86

REGo/RECU 7000DCf-7,0-42 7000 30/21 2x20,8 141 3,17 1500x790x480 1200x600 2x₅⁄₈”/2x28 mm 107DCW-7,0-47 7000 30/18 46,5 138 23,4 1500x790x420 1200x600 1 ½“ 105

otK 700pDCf-0,7-4 700 30/18 4,16 53 2,57 705x610x390 500x400 ½“ /22 mm 46DCW-0,7-5 700 30/18 4,7 29 11,2 705x610x390 500x400 ½“ 41

otK 1200pDCf-1,2-7 1200 30/18 7,13 93 6,11 705x610x390 500x400 ½“ /22 mm 46DCW-1,2-8 1200 30/18 8,1 60 6,3 705x610x420 500x400 ¾“ 45

otK 2000pDCf-2,0-12 2000 30/18 11,89 106 2,95 920x610x420 700x400 ½“ /22 mm 56DCW-2,0-13 2000 30/18 13,4 78 20,6 920x610x420 700x400 ¾“ 56

otK 3000pDCf-3,0-18 3000 30/18 17,83 112 5,3 1080x670x420 800x400 ½“ /28 mm 68DCW-3,0-20 3000 30/18 20,2 102 11 1080x670x420 800x400 1“ 69

otK 4000pDCf-4,0-24 4000 30/18 23,77 101 8,24 1220x730x420 900x500 ₇⁄₈”/28 mm 80DCW-4,0-27 4000 30/18 27 106 17,1 1220x730x420 900x500 1“ 82

KK2-15-09-v1

Page 93: air Handling Units KompaKt

91

outdoor unitsInverter outdoor units are supplied with control modules.

Water and direct evaporation air coolersDuct direct expansion coil suitable for condenser unit moU.Internal fluid – R410a.

* With drop eliminator.

typeCapacity,

kW

maximal operating current, А

Supply voltage, v

Refrigerant type

Sound level, dB (a)

Diameter of tubes for fluid/gas, mm

maximal length

of tubes, mInverter moU-18Hfn1 5,3 10 230 R410a 60 ∅6,35/∅12,7 (¼”/½”) 30Inverter moU-24Hfn1 7,3 13 230 R410a 60 ∅9,52/∅15,9 (₃⁄₈”/₅⁄₈”) 50Inverter moU-30Hfn1 8,8 18 230 R410a 61 ∅9,52/∅15,9 (₃⁄₈”/₅⁄₈”) 50Inverter moU-36Hfn1 10,5 11 400 R410a 63 ∅9,52/∅15,9 (₃⁄₈”/₅⁄₈”) 65Inverter moU-48HDn1 14,0 13 400 R410a 63 ∅9,52/∅15,9 (₃⁄₈”/₅⁄₈”) 65Inverter moU-60HDn1 16,0 15 400 R410a 64 ∅9,52/∅15,9 (₃⁄₈”/₅⁄₈”) 65on/offmoU-48Hn1 14,1 10,5 400 R410a 59 ∅12,7/∅19,0 (½”/¾”) 50on/off moU-60Hn1 17,6 12,8 400 R410a 60 ∅12,7/∅19,0 (½”/¾”) 50

air handling unit size

Cooler’s type

Supply air volume,

m³/h

air temper.

in/out, ºCCapacity,

kW

air pressure

drop, pa*

fluid pressure loss, kpa

BxHxL, mm

B1xH1, mm

tubes connections

Weight, kg

REGo/RECU 400 DCf-0,4-2 400 30/18 2,38 48 5,47 605x550x390 300x400 ½“ /22 mm 37REGo 500 DCf-0,5-3 500 30/18 2,97 43 4,91 600x550x390 400x300 ½“ /22 mm 38REGo/RECU 700 DCf-0,7-4 700 30/18 4,16 53 2,57 705x610x390 500x400 ½“ /22 mm 46REGo/RECU 900 DCf-0,9-5 900 30/18 5,3 64 3,89 705x610x390 500x400 ½“ /22 mm 46REGo/RECU 1200 DCf-1,2-7 1200 30/18 7,13 93 6,11 705x610x390 500x400 ½“ /22 mm 46REGo 1400 DCf-1,4-8 1400 30/18 8,3 100 8,3 705x610x390 500x400 ½“ /22 mm 46REGo/RECU 1600 DCf-1,6-10 1600 30/18 9,51 118 11,17 755x610x420 500x400 ½“ /22 mm 49REGo/RECU 2000 DCf-2,0-12 2000 30/18 11,89 106 2,95 920x610x420 700x400 ½“ /22 mm 56REGo 2500 DCf-2,5-15 2500 30/18 14,86 92 3,81 1080x670x420 800x400 ½“ /28 mm 68REGo/RECU 3000 DCf-3,0-18 3000 30/18 17,83 112 5,3 1080x670x420 800x400 ½“ /28 mm 68REGo/RECU 4000 DCf-4,0-24 4000 30/18 23,77 101 8,24 1220x730x420 900x500 ₇⁄₈”/28 mm 80REGo/RECU 4500 DCf-4,5-27 4500 30/18 26,74 115 8,16 1220x790x420 900x600 ₇⁄₈”/28 mm 84REGo/RECU 7000 DCf-7,0-42 7000 30/21 2x20,8 141 3,17 1500x790x480 1200x600 2x₅⁄₈”/2x28 mm 107otK 700p DCf-0,7-4 700 30/18 4,16 53 2,57 705x610x390 500x400 ½“ /22 mm 46otK 1200p DCf-1,2-7 1200 30/18 7,13 93 6,11 705x610x390 500x400 ½“ /22 mm 46otK 2000p DCf-2,0-12 2000 30/18 11,89 106 2,95 920x610x420 700x400 ½“ /22 mm 56otK 3000p DCf-3,0-18 3000 30/18 17,83 112 5,3 1080x670x420 800x400 ½“ /28 mm 68otK 4000p DCf-4,0-24 4000 30/18 23,77 101 8,24 1220x730x420 900x500 ₇⁄₈”/28 mm 80

KK2-15-09-v1

Page 94: air Handling Units KompaKt

92

Control System accessories

pressure sensorpressure sensor for vav function. Supply voltage 24v aC output signal 0-10v DC. 8 selected diapasons: 0...100/200/300/500/1000/1500/2000/2500 pa.

pressure switchpressure range 0-500 pa. Safety class Ip54. 1 change-over contact (no+nC).

movement detector (pIR)movement detector (pIR) for ovR function. Detection angle 180o. max. distance 12 m. Safety class Ip44.

HumidistatHumidity range 35-95%. 1 change-over contact (no+nC). Safety class Ip30.

Co2 switchRelay output. measured range 450-1800 ppm. Supply voltage 18-32v DC/12-18v aC.

air quality sensorSupply voltage 24v aC/DC. output signal 0-10v DC. Detected gas: Co, H2S, solvent steam, alcohol steam, cigarette smoke, exhaust steam, expiratory air.

Humidity sensorSupply voltage 24v aC/DC. output signal 0-10v DC. measured humidity range 0-100%.

Co2 sensorSupply voltage 24v aC/DC. output signal 0-10v DC. Co2 measured range 0-2000 ppm.

network module "ping2"network module "ping2" is intended for connection of KomfovEnt air handling units with C3 controller to the computer network (Ethernet) or another network (RS-485).

air damper actuatorair damper actuator is intended for additionally mounted duct air dampers. Supply voltage 24v aC/DC. Control: open-close or 3 point. Selection of rotation direction.

aQ function

“pC control” function vav function

ovR function

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 95: air Handling Units KompaKt

93

electric Wiring of air Handling UnitsWhen the air handling unit is installed, the user should just connect it to the mains power supply and install one temperature sensor in the supply air duct, and in case of need extend the connecting cable of the control panel. the units with a hot water air heater are provided with extra connecting cables for a heating damper drive, a pump, and an air damper drive. If the air handling unit voltage is ~230V; 50 Hz it is necessary to install the socket with grounding of corresponding capacity. If the voltage is ~400V; 50 Hz, the cable of electrical power supply is con-nected to the main switch, which is located on the unit’s outside wall.

the air handling units power supply cable types are specified in the table:

note: control panel connecting cable type: 4x0,22 mm2

type of the air handling unit

electric power supply connecting

cable, mm2

REGo 400 HE 3 x 1,5

REGo 500 H(v)E 3 x 1,5 REGo 500 U 3 x 1,5REGo 600 U RHp 3 x 1,5 REGo 700 H(v)E 3 x 1,5 REGo 700 p 3 x 1,5REGo 900 UH(v)E 5 x 1,5 REGo 900 UHW 3 x 1,5 REGo 1200 UH(v)E 5 x 1,5 REGo 1200 UHW 3 x 1,5 REGo 1200 pE 5 x 1,5 REGo 1400 UH(v)E 5 x 1,5REGo 1600 UH(v)E 5 x 1,5 REGo 1600 UH(v)W 3 x 1,5 REGo 2000 UH(v)E 5 x 2,5 REGo 2000 UH(v)W 3 x 1,5 REGo 2000 pE 5 x 2,5REGo 2500 UH(v)E 5 x 2,5 REGo 2500 UH(v)W 3 x 1,5 REGo 3000 UH(v)E 5 x 2,5 REGo 3000 UH(v)W 5 x 1,5 REGo 4000 UH(v)E 5 x 6,0 REGo 4000 UH(v)W 5 x 1,5 REGo 4500 UH(v)E 5 x 6,0 REGo 4500 UH(v)W 5 x 1,5

REGo 7000 HW 5 x 1,5

type of the air handling unit

electric power supply connecting

cable, mm2

RECU 400 H(v)E 3 x 1,5 RECU 700 H(v)E 3 x 1,5 RECU 700 H(v)ECf-EC 3 x 1,5 RECU 900 H(v)E 5 x 1,5 RECU 1200 H(v)E-EC 5 x 2,5 RECU 1200 H(v)W-EC 3 x 1,5 RECU 1600 H(v)E-EC 5 x 4,0 RECU 1600 H(v)W-EC 3 x 1,5 RECU 1600 pE 5 x 2,5RECU 2000 HE-EC 5 x 10,0 RECU 2000 HW-EC 3 x 1,5 RECU 2000 pE 5 x 2,5RECU 3000 HE-EC 5 x 6,0 RECU 3000 HW-EC 5 x 1,5 RECU 4000 HE-EC 5 x 10,0 RECU 4000 HW-EC 5 x 1,5 RECU 4500 HE-EC 5 x 10,0 RECU 4500 HW-EC 5 x 1,5

type of the air handling unit

electric power supply connecting

cable, mm2

RECU 7000 HW-EC 5 x 1,5 otK 700 p-E3 3 x 2,5 otK 700 p-E6 5 x 1,5 otK 700 p-E9 5 x 2,5 otK 1200 p-E9 5 x 2,5 otK 1200 p-E15 5 x 4,0 otK 1200 pW 3 x 1,5 otK 2000 p-E15 5 x 4,0 otK 2000 p-E22,5 5 x 10,0 otK 2000 pW 3 x 1,5 otK 3000 pW-EC 5 x 1,5 otK 4000 pW-EC 5 x 1,5

KK2-15-09-v1

Page 96: air Handling Units KompaKt

94

ReGo 3000 U H W - L - eC - C5.1-m5

X X X X X - X - X - X - X

otK 700 p e9 C3

ordering Key

aHU type: REGo – units with rotary heat exchangerRECU – units with plate heat exchangerotK – flat supply air units Unit sizeUniversal connection (REGo 900-4500 only)version: H – horizontal, v – vertical, p – flatair heater: W – water, E – electric, Cf – counter cross-flow plate heat exchangerRHp – heat pumpInspection side: R – right, L – leftmotor type: EC, aCController type: C3, C5filter class

aHU type: REGo – units with rotary heat exchangerUnit size 3000Universal connection (REGo 900-4500 only)Horizontal versionWater air heaterLeft inspection sidemotor type ECController С5filter class m5

Supply air unit otKUnit size 700flat model Electric air heater 9 kWController C3

оrdering key

ordering example nr.1

ordering example nr.2

the determination of inspection side:Right side – looking to the air handling unit from the inspection door side, the supply air fan is on the right side. Left side – looking to the air handling unit from the inspection door side, the supply air fan is on the left side.

UaB amaLva reserves the right to introduce the changes of parameters and sizes in the process of improvement of the air handling units.

KK2-15-09-v1

Page 97: air Handling Units KompaKt

KK2-15-09-v1

Page 98: air Handling Units KompaKt
Page 99: air Handling Units KompaKt
Page 100: air Handling Units KompaKt

www.komfovent.com

UaB amaLvaLithuania, 08200 Lt vilnius,tel. +370 5 2051579E-mail: [email protected]

2015