Air handling unit
The FLOWAY dual-flow air handling unit is a PLUG & PLAY ventilation unit equipped with a highly efficient heat recovery unit with plug fans and high performance EC motors, designed to meet all the requirements of recent ecodesign regulations. Unit supplied ready to use, prewired, preprogrammed in the factory and supplied with a remote control.It draws clean, fresh air indoors using, on average, 80% less energy than that needed for air conditioning (cooling and heating).These units are designed for use in the following applications:• Administrative buildings, Offices • Shopping Centres• Education facilities, Libraries, • Nursing homes,
Community centres Healthcare facilities• Cafés, Hotels, Restaurants • Collective housing
é All facilities where ventilation is required.
Classic RHE model: 9 sizes, air flow from 300 to 18,000 m3/h.
Access RHE model: 5 sizes, air flow from 350 to 8500m³/h.
Classic model: 5 sizes, air flow from 300 to 6600 m3/h. Ground installation, horizontal position, horizontal air flow, air circuits on the sides.
Vertical model: 3 sizes, air flow from 300 to 2600 m3/h. Ground installation, vertical position, vertical air flow, air circuits on the top.
Ceiling-mounted model: 3 sizes, air flow from 300 to 1900 m3/h. Ceiling-mounted horizontal unit with vertical air flows and air connections on the sides.
Plug & Play AHU with onboard control, Energy class A+ across the entire range, High efficiency heat recovery unit, EC fan motor assembly, high performance
Use
Air flow: 500 to 18 000 m3/h
* These values are provided for guidance only and are based on a standard dual-flow unit without electric heater option.
MODELS Nominal flow rate (m3/h) Max. power* (kW) Max current* (A) Voltage (V)700 700 1,43 6,2 1-Ph 2301200 1200 1,43 6,2
1600 1600 2,50 3,6 3-Ph 400
MODELS Nominal flow rate (m3/h) Max. power* (kW) Max current* (A) Voltage (V)700 1000 1,43 6,2 1-Ph 230
1500 1500 2,50 3,6 3-Ph 4002000 2000 2,50 3,6
MODELS Nominal flow rate (m3/h) Max. power* (kW) Max current* (A) Voltage (V)1000 1000 1,2 5,4 1-Ph 2302000 2000 2,5 2,9
3-Ph 4003000 3000 4,2 6,15000 5000 6,1 8,87500 7500 7,1 10,3
MODELS Nominal flow rate (m3/h) Max. power* (kW) Max current* (A) Voltage (V)1000 1000 1,43 6,2 1-Ph 2302000 2000 2,50 3,6
3-Ph 400
3000 3000 3,82 5,54000 4000 4,23 6,15000 5000 4,23 6,16000 6000 6,03 8,77500 7500 6,03 8,7
10000 10000 12,06 17,415000 15000 15,45 22,3
RangeFLOWAY Classic & Classic RHE
FLOWAY Vertical
FLOWAY Access RHE
FLOWAY Ceiling-mounted
Specifications ClassMechanical strength D2
Airtightness L2Filter bypass leak F9
Thermal transmission T3Thermal bridge TB2
High energy-efficiency heat recovery unitDepending on its layout, the Floway offers two different high-efficiency heat recovery systems:
"CONTRA FLOW" plate heat exchangerequipped with a bypass (Classic, Vertical, Ceiling-mounted models)
Rotary heat exchanger (Classic and Access RHE models)Year-round optimal heat recovery unit
NA16674A_ floway.indd 1 29/08/2017 09:25:09
-
2 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAY
Casingn Double-skin panels made from sheet steel, galvanised on both
sides, thickness 8/10 mm. n RAL 7035 grey precoated external panels.n Class M0/A1.n Mineral wool, thickness 50 mm.
Filtrationn M5, F7 HEE, F9 HEE filters.n Filter cells kept compressed by a special system to ensure a
leaktight seal.n Classic, Vertical, Ceiling-mounted models: fouling value
monitored by analogue sensor and displayed by controller.n Access model: pressure switch control on each air flow.
Pressure switch status displayed by controller.
Ventilationn "Plug Fan" type direct drive FMA. n Plug fan driven by an electronically commutated motor (EC
motor, built-in variable speed control).
Heat recovery unitsn "Contra Flow" plate heat exchanger equipped with a
motorised bypass (Ceiling-mounted, Vertical and Classic models). é Efficiency greater than 80% across the range of air flows.
n Rotary heat exchanger equipped with rotation speed control (Classic RHE model).é Efficiency greater than 80% at nominal flow rate.
n Constant speed rotary heat exchanger (Access RHE model).é 80% efficiency at nominal flow rate.
Hydraulic coiln Copper pipes, aluminium fins.n Coil can be integrated or additional (cased).n With the accessory fitted, 2- or 3-way control valve and
0-10 V actuator controlled by FLOWAY Control for setpoint accuracy.
n Stainless steel condensate drain pan (cooling coil or mixed coil only).
Electrics box
n Electrics box for power, control and internal regulation of the unit, comprising as standard:
- Power supply (3-Ph/400 V/Earth or 1-Ph/230 V/Earth).- Main disconnect switch.- Protected transformer.- Protection and control of all electrical components by a
circuit breaker and contact switch.- Peripheral options and power terminal block.- Factory-programmed PLC control.- Hand-held cabled micro-terminal.- Fault summary contact.- 3 temperature sensors.- 4 pressure sensors (2 pressure sensors and 2 pressure
switches on the Access model).
AccessoriesDamper formed of airfoil blades, powered by a servomotorOn/off with return spring.Flexible sleeve.Adjustable feet.CO2 air quality sensor.Roof.Canopy.Mixing section.Indoor environment switch.ModBus RTU, LON, KNX, ModBus communicationTCP, Bacnet IP, web interface.
DescRiption
Electric heatersn High-limit safety thermostat with automatic and manual reset.n Control by 2-stage on/off operation fully controlled by FLOWAY
Control.
MODELS & SIZES Power (kW) Current (A) Voltage (V)
Classic & Classic RHE 1000 Vertical 700
Ceiling-mounted 700 & 12004,5 20 1-Ph 230
Vertical 1500 (additional casing)Ceiling-mounted 1600 (additional casing) 7,20 11
3-Ph 400
Vertical 1500 8,1 12Classic & Classic RHE 2000 10,8 16Classic & Classic RHE 3000 12,6 19Classic & Classic RHE 4000 16,8 25
Classic RHE 5000 19,8 29Classic & Classic RHE 6000 22,8 34
Classic RHE 7500 31,2 46Classic RHE 10000 N/A N/AClassic RHE 15000 N/A N/A
NA16674A_ floway.indd 2 29/08/2017 09:25:09
-
3
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAY Control function (software V2.2) Included Options*
Fan time schedule Built-in timer: management in series 4 events per year, per week and per day X
Safety
Frost protectionBy fresh air temperature control XBy exhaust air flow pressure on heat recovery unit delta control (pressure sensor) X
Monitoring of sensor status XMonitoring operation values (thresholds) XOperating control of EC fan motor assemblies XFilter fouling control (via analogue sensor or pressure switch, depending on the model) X
Fault summary XFire monitoring (potential free (dry) contact available (normally closed)) X
Alarms Management of alarms and log (100) X
Control mode
Control of return air or supply air temperature X
Regulated temperature control based on outdoor temperature X
Control of room temperature with a room terminal X
Hot air and/or cold air production
Gradual action on the 2- or 3-way control valve on the hydraulic coil XGradual action on the electric heater TRIAC XOn/Off action on the various stages of the electric heater X
Free coolingRotary heat exchanger shut down (Classic and Access RHE models) XOpen bypass on contra-flow plate recovery unit (Vertical, Ceiling-mounted & Classic models) X
Night cooling functionRotary heat exchanger shut down (Classic and Access RHE models) XOpen bypass on contra-flow plate recovery unit (Vertical, Ceiling-mounted & Classic models) X
Morning heating function Opening level control of mixing bypass (CLASSIC RHE model) X
Eco-recycling function Opening level control of mixing bypass (CLASSIC RHE model) X
Efficiency optimisation Variation of the rotation speed of the rotary recovery unit (CLASSIC RHE model) X
Configuration of the air flow rate
2 air flow rate setpoints per air flow XDisplay of the air flow rate X
Constant flow rate oper-ation Keeps the air flow rate constant regardless of how fouled the filters are X
Modulation of flow rates operation
Single zoneSignal 0-10V CO2 sensor X
ContactPresence contact XExternal contact X
Multi zone Air supply duct constant pressure operation X
Communicating mode Management by CMS
ModBus RS485 protocol XLON protocol XKNX protocol XModBus TCP/BACNET IP protocol XWeb interface
Miscellaneous
Languages supported (French/English/German/Dutch/Spanish/Italian) XIntegrated temperature sensors (*3: fresh air supply and extraction, exhaust air extraction) XIntegrated pressure checks (*4: fresh air and exhaust air filter fouling level, fresh air and exhaust air fan) X
Damper control XInformation provided to the user via the hand-held micro terminal XContact for controlling the pumps for the hydraulic coils (with operating control)** XContact for controlling an external outdoor heat production system (boiler, etc.)** XContact for controlling a humidifier** XElectric heater load shedding input** X
contRolFLOWAY ControlFLOWAY features, as standard, an electrics box equipped with a factory-programmed PLC and a hand-held micro-terminal.
Option*: Requires the component to be selected as an option: damper, coil, CO2 sensor, etc.** Except Access RHE model
NA16674A_ floway.indd 3 29/08/2017 09:25:11
-
4 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAYaiR flow Dimensions anD oRientation
AIR FLOW ORIENTATIONAccess and Classic RHE models
Classic models
FLOWAY CLASSIC, CLASSIC RHE, ACCESS RHE
SIZES
FLOWAY Classic, Classic RHE, Access RHE
Height (C)(mm)
Width (B)(mm)
Length (A) (mm) Weight (kg)*
Classic Classic RHEAccess
RHE ClassicClassic
RHE Access RHE
1000 958 810 1580** 1266** 1266 200 201 1802000 1158 1010 1150 + 800** 510 + 800** 1310 350 309 2503000 1359 1210 1264 + 800 800 + 800 1600 465 432 3304000 1659 1510 1264 + 800 800 + 800 - 580 558 -5000 1659 1510 - 800 + 800 1600 - 604 4456000 1959 1810 1407 + 800 800 + 800 - 765 702 -7500 1959 1810 - 800 + 800 1600 - 751 580
10000 2090 1920 - 1100 + 1100 - - 955 -15000 2340 2192 - 1100 + 1200 - - 1250 -
AD
B
E
C
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
* Without internal option.** Circular coupling; protrudes 47 mm on either side.
ROTS 2.1
PLAS01
ROTS 2.2
PLAS02
NA16674A_ floway.indd 4 29/08/2017 09:25:13
-
5
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAY Vertical
Ø 16 mm condensate drain pipe.
MODELS Dimensions Weight (kg)* Height Length Width
700 1385 1313 730 2021500 1758 1593 832 3302000 1901 1735 832 389
Size 1000
* Without internal option
Size 1500
n
n
n
n
n
WHITE ARROW = FRESH AIR
BLACK ARROW = EXHAUST AIR
Size 2000
n
n
n
n
n
WHITE ARROW = FRESH AIR
BLACK ARROW = EXHAUST AIR
1313
1550
1735
730
805
832
805
492.5
572
620 824 248
584.5
730
193
248
702
832
124
124
124
250
355 355
355
355
355
355
355
355
250
250 250
584.5
730
824
193
248
248
492.5
572
620
46
46
46
4747
47
100
100
100
272
349
385
231
253
253
253
295
295
253
239
231
7070
70
1385
1758
1901
1711
1854
1754
1611
1338
1238
1270
1593
1692
NA16674A_ floway.indd 5 29/08/2017 09:25:16
-
6 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAY
Ø 16 mm condensate drain pipe.
Size 1200
FLOWAY Ceiling-mounted
MODELS Dimensions Weight (kg)Height Length Width
700 585 1453 896 161 1200 585 1592 1174 2061600 585 1850 1456 279
Size 700
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
n
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
Size 1600
n
n
MODELSAir flow dimensions (MM)
A B C D
700 306 306 Ø160 Ø315
1200 398 398 Ø250 Ø355
1600 499.5 499.5 Ø250 Ø400
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
13.5
13.5
13.5
924
1202
1484
1456
1506
253
896
1174
946
1224
280
280
280
4745
280
47 1762
1856
280
280
47
47 47
47
471359
1498
1592
1453
799
938
601
A
C C
D16
71
B
601
NA16674A_ floway.indd 6 29/08/2017 09:25:17
-
7
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
405 405
221
321
810
505 505
1010
271
371
1210
759
1069
1810
Additional casing (MUST ONLY BE POSITIONED IN A HORIZONTAL AIR FLOW)
Size 1
Size 3
Size 5
Size 2
Size 4
FLOWAY MODELS Additional casing sizes (mm) Weight (kg)
Classic RHE, Classic 1000Vertical 700Ceiling-mounted 700
Size1542 x 496 x 810 49 kg
Classic RHE, Classic 2000Vertical 1500 & 2000Ceiling-mounted 1200 & 1600
Size 2 642 x 496 x 1010 62 kg
Classic RHE & Classic 3000 Size 3 759 x 400 x 1210 68 kg
Classic RHE & Classic 4000 & 5000 Size 4 909 x 400 x 1510 88 kg
Classic RHE & Classic 6000 & 7500 Size 5 1059 x 400 x 1810 112 kg
1510
906793
NA16674A_ floway.indd 7 29/08/2017 09:25:20
-
8 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAYclassic RHe moDel peRfoRmance
sfpv aHU = f (flow Rate)
Heat RecoveRy Unit efficiency = f (flow Rate)
opeRating pRessURe = f(flow)
200 Pa
400 Pa
800 Pa
500 m3/h 2500 m3/h 4500 m3/h 6500 m3/h 8500 m3/h 10500 m3/h 12500 m3/h 14500 m3/h 16500 m3/h
1000 2000
3000
4000
5000
6000
7500 10000
15000
70,0%
80,0%
90,0%
500 m3/h 2500 m3/h 4500 m3/h 6500 m3/h 8500 m3/h 10500 m3/h 12500 m3/h 14500 m3/h 16500 m3/h
1000 2000 3000
4000
5000
6000
7500
1000015000
0,30W/(m3/h)
0,40W/(m3/h)
0,50W/(m3/h)
0,60W/(m3/h)
500 m3/h 2500 m3/h 4500 m3/h 6500 m3/h 8500 m3/h 10500 m3/h 12500 m3/h 14500 m3/h 16500 m3/h
10002000
3000
4000
5000
6000
7500
10000
15000
SFPv = 0.6 W/(m3/h)RT reference output
Efficiency
SFPv
Pressure
Flow rate
Flow rate
Flow rate
F5 exhaust filter, F7 intake filter, duct pressure: 200 Pa, heat recovery unit conditions: 0°C/90% - 20°C/50%
NA16674A_ floway.indd 8 29/08/2017 09:25:22
-
9
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
access RHe moDel peRfoRmance
20001500700
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h75,0%
85,0%
70.00%
72.00%
74.00%
76.00%
78.00%
80.00%
82.00%
84.00%
86.00%
88.00%
90.00%
500 1500 2500 3500 4500 5500 6500 7500 8500
1000
2000
3000
50007500
20001500
700
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h0,30W/(m3/h)
0,40W/(m3/h)
0,50W/(m3/h)
0,60W/(m3/h)
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.55
0.6
500 1500 2500 3500 4500 5500 6500 7500 8500
1000
2000
3000 5000
7500
2000
1500
700
1000
2000 3000
500
7500
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h400 Pa
800 Pa
200
300
400
500
600
700
800
900
1000
1100
500 1500 2500 3500 4500 5500 6500 7500 8500
Efficiency
SFPv W/(m3/h)
Pressure Pa
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
SFPv = 0.6 W/(m3/h)RT reference output
sfpv aHU = f (flow Rate)
Heat RecoveRy Unit efficiency = f (flow Rate)
opeRating pRessURe = f(flow)F5 exhaust filter, F7 intake filter, duct pressure: 200 Pa, heat recovery unit conditions: 0°C/90% - 20°C/50%
NA16674A_ floway.indd 9 29/08/2017 09:25:23
-
10 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAYclassic moDel peRfoRmance
sfpv aHU = f (flow Rate)
opeRating pRessURe = f(flow)
200 Pa
400 Pa
800 Pa
500 m3/h 1500 m3/h 2500 m3/h 3500 m3/h 4000 m3/h 5500 m3/h 6500 m3/h
2000
1000
3000
4000
6000
75,0%
85,0%
500 m3/h 1500 m3/h 2500 m3/h 3500 m3/h 4500 m3/h 5500 m3/h 6500 m3/h
1000 2000 3000 40006000
0,30W/(m3/h)
0,40W/(m3/h)
0,50W/(m3/h)
0,60W/(m3/h)
500 m3/h 1500 m3/h 2500 m3/h 3500 m3/h 4500 m3/h 5500 m3/h 6500 m3/h
1000
20003000 4000 6000
SFPv=0.6 W/(m3/h)RT reference output
Efficiency
SFPv
Pressure
Flow rate
Flow rate
Flow rate
Heat RecoveRy Unit efficiency = f (flow Rate)
F5 exhaust filter, F7 intake filter, duct pressure: 200 Pa, heat recovery unit conditions: 0°C/90% - 20°C/50%
NA16674A_ floway.indd 10 29/08/2017 09:25:25
-
11
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
veRtical moDel peRfoRmance
20001500700
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h75,0%
85,0%
20001500
700
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h0,30W/(m3/h)
0,40W/(m3/h)
0,50W/(m3/h)
0,60W/(m3/h)
2000
1500
700
2500 m3/h2000 m3/h1500 m3/h1000 m3/h500 m3/h400 Pa
800 Pa
Efficiency
SFPv
Pressure
Flow rate
Flow rate
Flow rate
SFPv = 0.6 W/(m3/h)RT reference output
sfpv aHU = f (flow Rate)
Heat RecoveRy Unit efficiency = f (flow Rate)
opeRating pRessURe = f(flow)F5 exhaust filter, F7 intake filter, duct pressure: 200 Pa, heat recovery unit conditions: 0°C/90% - 20°C/50%
NA16674A_ floway.indd 11 29/08/2017 09:25:26
-
12 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
FLOWAYceiling-moUnteD moDel peRfoRmance
sfpv aHU = f (flow Rate)
0,30W/(m3/h)
0,40W/(m3/h)
0,50W/(m3/h)
0,60W/(m3/h)
700 1200
1600
500 m3/h 700 m3/h 900 m3/h 1100 m3/h 1300 m3/h 1500 m3/h 1700 m3/h 1900 m3/h
Heat RecoveRy Unit efficiency = f (flow Rate)
opeRating pRessURe = f(flow)
400 Pa
800 Pa
700
1200
1600
500 m3/h 700 m3/h 900 m3/h 1100 m3/h 1300 m3/h 1500 m3/h 1700 m3/h 1900 m3/h
75,0 %
85,0 %
700
12001600
500 m3/h 700 m3/h 900 m3/h 1100 m3/h 1300 m3/h 1500 m3/h 1700 m3/h 1900 m3/h
Efficiency
SFPv
Pressure
Flow rate
Flow rate
Flow rate
SFPv = 0.6 W/(m3/h)RT reference output
F5 exhaust filter, F7 intake filter, duct pressure: 200 Pa, heat recovery unit conditions: 0°C/90% - 20°C/50%
NA16674A_ floway.indd 12 29/08/2017 09:25:27
-
13
FLO
WAY
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 16.674 A
Air handling unit
TàP FRANCAIS ou plusieurs langues
TàP ANGLAIS
TàP ALLEMAND
TàP ESPAGNOL
TàP ITALIEN
Document non contractuel. Dans le souci constant d’améliorer son matériel, CIAT se réserve le droit de procéder sans préavis à toutes modifications techniques.
Siège social 700 Avenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel. : +33(0)4 79 42 42 42Fax : +33(0)4 79 42 42 10www.ciat.com
Compagnie Industrielle d’Applications Thermiques - S.A. au capital de 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114
CIAT ServiceAssistance technique : 0 892 05 93 93 (0,34 € / mn)Pièces de rechange : 0 826 96 95 94 (0,15 € / mn)
[email protected] - [email protected]
Système de Management certifié
This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.
Head office 700 Avenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel.: +33 (0)4 79 42 42 42Fax: +33 (0)4 79 42 42 10www.ciat.com
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114
Certified Management System
Documento non contrattuale. Nella preoccupazione costante di migliorare il suo materiale, CIAT si riserva il diritto di procedere senza preavviso ad ogni modifica tecnica.
Sede sociale 700 Avenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel. : +33 (0)4 79 42 42 42Fax : +33 (0)4 79 42 42 10www.ciat.com
Compagnie Industrielle d’Applications Thermiques - S.A. al capitale di 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114
I T A L I A
CIAT ITALIA S.R.L.Via Nassar, 46 - 37026 Pescantina (VR) Italia
Tel. : 045 6750065 - Fax : 045 [email protected] - www.ciat-italia.it
Sistema di Gestione certificato
Documento no contractual. Con el fin de mejorar su material, CIAT se reserva el derecho de realizar modificaciones técnicas sin previo aviso.
Sede social 700 Avenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel.: +33 (0)4 79 42 42 42Fax: +33 (0)4 79 42 42 10www.ciat.com
Compagnie Industrielle d’Applications Thermiques - S.A. con un capital de 26 728 480 € - Reg. Mercantil Bourg-en-Bresse B 545 620 114
CIAT ESPAÑA Polígono Industrial Llanos de Jarata14550 - Montilla (Córdoba) - España
Tel.: +34 957 652 311Fax: +34 957 652 212
[email protected] - www.grupociat.esSistema de
gestión certificado
Compagnie Industrielle d’Applications Thermiques AG nach franz. Recht mit einem Kapital von 26 728 480 € - Handelsregister Bourg-en-Bresse Nr. B545 620 114
Dieses Dokument ist keine Vertragsunterlage. Da wir ständig bemüht sind, unser Material noch weiter zu verbessern, behält sich CIAT das Recht vor, technische Änderungen ohne vorherige Ankündigung vorzunehmen.
Firmensitz 700 Avenue Jean Falconnier - BP1401350 Culoz - FrankreichTel.: +33 (0)4 79 42 42 42Fax: +33 (0)4 79 42 42 10www.ciat.com
Luxemburg CIAT Luxembourg2 route de Remich
L5650 Mondorf les BainsTel. : +352(49) 28 49
Deutschland CIAT Kälte- und Klimatechnik GmbHWendenweg 19, D-44149 Dortmund
Tel. : +49 (0) 231 96 97 55 0Fax : +49 (0) 231 96 97 55 15
www.ciat.de
Schweiz KalithermRoute de Denges 28 G, CH-1027 LonayTel : +41 (21) 863 60 60Fax : +41 (21) 862 12 [email protected] - www.kalitherm.ch
ZertifiziertesManagementsystem
CIAT [email protected]
NA16674A_ floway.indd 13 29/08/2017 09:25:28