air-cooled type screw chiller - clkkorea.com › products › download.asp?filedown=clk...
TRANSCRIPT
- 1 -
Prepared date ; 03 .Dec.’14 (rev.0) SWL
Air-Cooled Type Screw Chiller (35℃)
Technical Date Sheet
- 1 -
Prepared date ; 03 .Dec.’14 (rev.0) SWL
Air-Cooled Type Screw Chiller (50℃)
Technical Date Sheet
CLK Corporation
· Model : 12S004UR3
· Dimension(Length x Width x Height)
2300 x 1900 x 2400
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
kW
7
Chilled Water Flow Rate
Lubricating Oil ℓ
Power
16 1
403.2
40
78.28
HANBELL, TAIWANRC2-310B
Y - △
171.2
3Ph x AC 220 / 380 / 440V x 50Hz
Semi Hermetic Screw Type
1Ph x AC 220 / 24V x 50HzControl Supply -
Starting Method -
Air-Cooled Type Screw Chiller-40RT
Specification
Outdoor Air Condition ℃ DB
Cooling Capacitykcal/h
usRT
50
120,960
2590 kg
-
Compressor
Type -
Model / Maker -
Nominal Output x Q'ty kW
Main Supply
Total Input(Comp + Fan)
Condenser Type - Cross Fin Tube Type
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃
1
4.0Pressure Drop mAq
ℓ/min
Controller - Micro Process Controller
Refrigerant - R-134a
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min 1320
Condensing
Pressure Control
Type
Motor Nom. Output x Q'ty kW
- Controlling the Number of Operation Fans
Air Flow % 100-50-0
1.12 4
Refrigerant Control - Thermostatic Expansion Valve
Connection Chilled Water Pipe mm
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
65 1
CLK Corporation
· Model : 12S005UR3
· Dimension(Length x Width x Height)
2300 x 1900 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 80 1
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 4
Controller - Micro Process Controller
1320
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 504 1
Pressure Drop mAq 4.0
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 15 1
- RC2-410B HANBELL, TAIWAN
Nominal Output x Q'ty kW 94.7 1
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 101.78
Air-Cooled Type Screw Chiller-50RT
2710 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 151,200
usRT 50
CLK Corporation
· Model : 12S006UR3
· Dimension(Length x Width x Height)
2300 x 1900 x 2600
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 80 1
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 4
Controller - Micro Process Controller
1320
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 604.8 1
Pressure Drop mAq 4.0
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 18 1
- RC2-470B HANBELL, TAIWAN
Nominal Output x Q'ty kW 106 1
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 113.08
Air-Cooled Type Screw Chiller-60RT
2930 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 181,440
usRT 60
CLK Corporation
· Model : 12S008UR3
· Dimension(Length x Width x Height)
2300 x 2850 x 2400
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 1
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 6
Controller - Micro Process Controller
1980
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 806.4 1
Pressure Drop mAq 4.0
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 1
- RC2-710B HANBELL, TAIWAN
Nominal Output x Q'ty kW 156 1
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 166.12
Air-Cooled Type Screw Chiller-80RT
3390 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 241,920
usRT 80
CLK Corporation
· Model : 12S010UR3
· Dimension(Length x Width x Height)
4600 x 1900 x 2400
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 1
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 8
Controller - Micro Process Controller
2640
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 1008 1
Pressure Drop mAq 4.0
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 1
- RC2-790B HANBELL, TAIWAN
Nominal Output x Q'ty kW 172.2 1
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 185.36
Air-Cooled Type Screw Chiller-100RT
4320 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 302,400
usRT 100
CLK Corporation
· Model : 12S016UR3
· Dimension(Length x Width x Height)
4600 x 2850 x 2400
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 2
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 12
Controller - Micro Process Controller
3960
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 806.4 2
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 2
- RC2-710B HANBELL, TAIWAN
Nominal Output x Q'ty kW 156 2
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 331.24
Air-Cooled Type Screw Chiller-160RT
6840 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 483,840
usRT 160
CLK Corporation
· Model : 12S020UR3
· Dimension(Length x Width x Height)
4600 x 3800 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 2
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 16
Controller - Micro Process Controller
5280
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 1008 2
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 2
- RC2-790B HANBELL, TAIWAN
Nominal Output x Q'ty kW 172.2 2
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 369.72
Air-Cooled Type Screw Chiller-200RT
10810 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 604,800
usRT 200
CLK Corporation
· Model : 12S025UR3
· Dimension(Length x Width x Height)
6900 x 2850 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 3
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 18
Controller - Micro Process Controller
5940
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 840 3
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 3
- RC2-710B HANBELL, TAIWAN
Nominal Output x Q'ty kW 156 3
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 496.36
Air-Cooled Type Screw Chiller-250RT
10850 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 756,000
usRT 250 RT
CLK Corporation
· Model : 12S030UR3
· Dimension(Length x Width x Height)
4600 x 5700 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 3
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 24
Controller - Micro Process Controller
7920
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 1008 3
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 3
- RC2-790B HANBELL, TAIWAN
Nominal Output x Q'ty kW 172.2 3
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 554.08
Air-Cooled Type Screw Chiller-300RT
12970 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 907,200
usRT 300
CLK Corporation
· Model : 12S032UR3
· Dimension(Length x Width x Height)
4600 x 5700 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 4
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 24
Controller - Micro Process Controller
7920
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 806.4 4
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 4
- RC2-710B HANBELL, TAIWAN
Nominal Output x Q'ty kW 156 4
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 661.48
Air-Cooled Type Screw Chiller-320RT
13570 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 967,680
usRT 320
CLK Corporation
· Model : 12S040UR3
· Dimension(Length x Width x Height)
4600 x 7600 x 2500
· Net Weight
· Features
- Application of globally recognized high performance/high
efficiency comperssor and heat exchanger
· 'ZERO' ozone depletion by the environment friendly
refrigerants
· Efficient operation enabled by Straight Stepless Capacity
Control System
· Product safety/stability guaranteed by the reliable comperssor and perfect protection devices
· High performance Micro Process Controller
· Easy management/maintenance by a simple stucture without pump oil.
/
x
x
x
x
x
Note) 1. Fouling factor of water side : 0.0001m2h℃/kcal(Based on KS B 6275)
2. Electric power input is bassed on standard operation condition. If the operation condition is changed then the power consumption will be changed. The
capacity of transformer and other electric equipment must be 130% higher than the standard power consumption.
3. Specifications are subject to change.
Connection Chilled Water Pipe mm 100 4
Capacity Control Range % 0-33~100%(Stepless)
Protection Device -
High/low Pressure Switch, Anti-Freezing Device,
Over Current Relay, Internal Thermostat,
Dischange Temp. Sensor, Safety Valve, Fusible Plug
Refrigerant - R-134a
Refrigerant Control - Thermostatic Expansion Valve
Motor Nom. Output x Q'ty kW 1.12 32
Controller - Micro Process Controller
10560
Condensing
Pressure Control
Type - Controlling the Number of Operation Fans
Air Flow % 100-50-0
Condenser Type - Cross Fin Tube Type
Fan
Type - Propeller Fan
Air Flow Rate ㎥/min
Chilled Water Flow Rate ℓ/min 1008 4
Pressure Drop mAq 6.2
Evaporator
Type - Shell & Tube Type
Chilled Water Inlet Temp. ℃ 12
Chilled Water Outlet Temp. ℃ 7
Compressor
Type - Semi Hermetic Screw Type
Model / Maker
Starting Method - Y - △
Lubricating Oil ℓ 28 4
- RC2-790B HANBELL, TAIWAN
Nominal Output x Q'ty kW 172.2 4
Power
Main Supply - 3Ph x AC 220 / 380 / 440V x 50Hz
Control Supply - 1Ph x AC 220 / 24V x 50Hz
Total Input(Comp + Fan) kW 738.44
Air-Cooled Type Screw Chiller-400RT
17290 kg
Specification
Outdoor Air Condition ℃ DB 50
Cooling Capacitykcal/h 1,209,600
usRT 400