air cooled heat exchanger summary
DESCRIPTION
SUMMARY Air Cooled Heat ExchangerTRANSCRIPT
![Page 1: Air Cooled Heat Exchanger SUMMARY](https://reader030.vdocuments.mx/reader030/viewer/2022020208/55cf9ac0550346d033a33d51/html5/thumbnails/1.jpg)
GEA Heat Exchangers | GEA Rainey Solutions
Reliability
Powered by Experience.
AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS
Fans
Number of Fans 2 -
Fan Size 6 ft
Power per Fan 4.2 kW
Overall size
Bundle Face Area 8.7 m2
Total Plot Area 14 m2
GEA Aircooled Systems (Pty) Ltd., July 2004 - 2007
All rights reserved
Design Requirements
Inlet Temperature 120 deg C
Required Outlet Temperature 60 deg C
Duty 0.4 MW
Ambient Temperature 25 deg C
Barometric Pressure 101.3 kPa
DescriptionViscous Fluid
Cooling
Operating Point
Exhaust Air Temperature 34.93 deg C
Inlet Face Velocity 3.88 m/s
Airside Pressure Drop 160 Pa
Geometry
Number of Bays 1 -
Number of Bundles 2 -
Tube Length 4.18 m
Number of Tubes per Bundle 66 -
Air Cooled Heat Exchanger http://www.gearainey.com/opencms/opencms/grc/en/Air_Cooled_Heat_E...