GEA Heat Exchangers | GEA Rainey Solutions Reliability Powered by Experience. AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS Fans Number of Fans 2 - Fan Size 6 ft Power per Fan 4.2 kW Overall size Bundle Face Area 8.7 m2 Total Plot Area 14 m2 GEA Aircooled Systems (Pty) Ltd., July 2004 - 2007 All rights reserved Design Requirements Inlet Temperature 120 deg C Required Outlet Temperature 60 deg C Duty 0.4 MW Ambient Temperature 25 deg C Barometric Pressure 101.3 kPa Description Viscous Fluid Cooling Operating Point Exhaust Air Temperature 34.93 deg C Inlet Face Velocity 3.88 m/s Airside Pressure Drop 160 Pa Geometry Number of Bays 1 - Number of Bundles 2 - Tube Length 4.18 m Number of Tubes per Bundle 66 - Air Cooled Heat Exchanger http://www.gearainey.com/opencms/opencms/grc/en/Air_Cooled_Heat_E... 1 of 1 2/12/2013 1:48 PM

Upload: honey-tiwari

Post on 01-Jan-2016

54 views

Category:

Documents


6 download

DESCRIPTION

SUMMARY Air Cooled Heat Exchanger

TRANSCRIPT

Page 1: Air Cooled Heat Exchanger SUMMARY

GEA Heat Exchangers | GEA Rainey Solutions

Reliability

Powered by Experience.

AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS

Fans

Number of Fans 2 -

Fan Size 6 ft

Power per Fan 4.2 kW

Overall size

Bundle Face Area 8.7 m2

Total Plot Area 14 m2

GEA Aircooled Systems (Pty) Ltd., July 2004 - 2007

All rights reserved

Design Requirements

Inlet Temperature 120 deg C

Required Outlet Temperature 60 deg C

Duty 0.4 MW

Ambient Temperature 25 deg C

Barometric Pressure 101.3 kPa

DescriptionViscous Fluid

Cooling

Operating Point

Exhaust Air Temperature 34.93 deg C

Inlet Face Velocity 3.88 m/s

Airside Pressure Drop 160 Pa

Geometry

Number of Bays 1 -

Number of Bundles 2 -

Tube Length 4.18 m

Number of Tubes per Bundle 66 -