air cooled heat exchanger

1
Reliability Powered by Experience. GEA Heat Exchangers | GEA Rainey Solutions AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS Fans Number of Fans 2 - Fan Size 11 ft Power per Fan 15 kW Overall size Bundle Face Area 30.5 m2 Total Plot Area 40 m2 Back Print GEA A ircooled Syst ems (Pt y) Lt d., July 2004 - 2007 A ll right s reserved Design Requirements Inlet Temperature 90 deg C Required Outlet Temperature 48 deg C Duty 0.6 MW Ambient Temperature 38 deg C Barometric Pressure 101.3 kPa Description Viscous Fluid Cooling Operating Point Exhaust Air Temperature 42.33 deg C Inlet Face Velocity 3.98 m/s Airside Pressure Drop 160 Pa Geometry Number of Bays 1 - Number of Bundles 2 - Tube Length 7.82 m Number of Tubes per Bundle 123 -

Upload: muhammadtayyab87

Post on 20-Sep-2015

79 views

Category:

Documents


1 download

DESCRIPTION

GE Air Cooled Heat Exchanger

TRANSCRIPT

  • 5/15/2015 Air Cooled Heat Exchanger

    http://www.gearainey.com/opencms/opencms/grc/en/Air_Cooled_Heat_Exchangers/calculators/AFC_Calculator.html 1/1

    ReliabilityPowered by Experience.

    GEA Heat Exchangers | GEA Rainey Solutions

    AIRCOOLED HEAT EXCHANGER - CALCULATION RESULTS

    Fans

    Number of Fans 2 -

    Fan Size 11 ft

    Power per Fan 15 kW

    Overall size

    Bundle Face Area 30.5 m2

    Total Plot Area 40 m2

    Back Print

    GEA Aircooled Systems (Pty) Ltd., July 2004 - 2007

    All rights reserved

    Design Requirements

    Inlet Temperature 90 deg C

    Required Outlet Temperature 48 deg C

    Duty 0.6 MW

    Ambient Temperature 38 deg C

    Barometric Pressure 101.3 kPa

    DescriptionViscous Fluid

    Cooling

    Operating Point

    Exhaust Air Temperature 42.33 deg C

    Inlet Face Velocity 3.98 m/s

    Airside Pressure Drop 160 Pa

    Geometry

    Number of Bays 1 -

    Number of Bundles 2 -

    Tube Length 7.82 m

    Number of Tubes per Bundle 123 -